Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.5 LAccepted-AOC | L1 | Accepted-AOC BEING LOWEST AND ACCEPTABLE | |
| 2 | L2₹16.8 L+₹1.4 L (9.25%)Rejected-Finance 224 OFFICERS ENCLAVE BEHIND PLV MEMORIAL COLLEGE SHIKARGARH ARMY AREA JODHPUR RAJ 342001 | JODHPUR | RAJASTHAN | 342001 | L2 | Rejected-Finance BEING NOT LOWEST | |
| 3 | L3₹17.9 L+₹2.5 L (16.1%)Rejected-Finance 00 BEHIND COURT PHALODI NAI SARAK PHALODI JODHPUR RAJASTHAN 342301 UDYAM RJ 22 0048153 | JODHPUR | RAJASTHAN | 342301 | L3 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹14.8 L
EMD Value
₹29,500
Closing Date
15 Nov 2024, 6:00 pmClosed
CWE AF JODHPUR
HQ CWE AF JODHPUR Opp Mosam Vibhag Airforce Chauraha , Ratanada Jodhpur (Raj) 342011
SPECIAL REPAIR/ REPALCEMENT OF CONVENTIONAL LIGHT FITTING TO LED AT AF STN PHALODI
2024_MES_675755_2
88095/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE AF PHALODI
As per NIT
8 documents required · 8 mandatory
₹500
GE AF PHALODI
₹29,500
Yes
26 Nov 2024
25 Oct 2024
18 Nov 2024
25 Oct 2024
15 Nov 2024
1 Nov 2024
Amount
M&L for point wiring with three layer PVC Insulated 1.5 Sqmm multi-strand copper conductor FRLSH cable 1100 Volts grade drawn into concealed PVC conduits medium grade not less than 20mm( ISI marked) including all fitting and fixing accessories including 1.25 mm thick sunken pressed steel terminal boxes/Modular metal flush box duly painted with two coats of anti-corrosive paint outside and two coats of aluminium paint inside with and including 3mm thick hylam brand laminated white bakelite sheet cover for mounting switches, sockets, fan regulators fixed with CP screws with cup wahsers and PVC insulated 1.5 Sqmm multi-strand copper conductor cable as earth wire and making good the disturbed surfaces with cement sand mortar 1:3 to match with the existing surfaces for One light point controlled by one switch complete all as specified & as directed by Engineer-in-charge
M&L for point wiring with three layer PVC Insulated 1.5 Sqmm multi-strand copper conductor FRLSH cable 1100 Volts grade drawn into PVC casing caping size 20mm as and incl all fitting and fixing accessories suitabale size PVC box with cover plate for fixing /mounting switches, sockets, fan regulators flush to surface for one light , fan , bell point controlled by one switch on the same board with other switch or independant including PVC insulated sheathed 1.5 Sqmm multi-strand copper conductor FRLSH cable as earth wire and making good the disturbed surfaces with cement sand mortar 1:3 to match with the existing surfaces complete all as specified & as directed by Engineer-in-charge
S&F in replacement of switch piano flush type, 6 Amp 240 Volt, AC one way etc complete all as specified and directed by Engineer-in-Charge.
S&F in replacement of ceiling rose surface PVC/ Polycarbonate, 3 terminals with back plate etc complete all as specified and directed by Engineer-in-Charge.
M & L for XLPE screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty)with stranded aluminum conductor, 1100 volts grade, earth type cross sectional area 16 Sqmm 4 core LT UG cable laid in trenches/through pipe/fixed along pole or in duct with necessary angle iron support,clamp,nut bolts etc. complete all as specified and as directed
All as per item No 5.01 but of size 10 Sqmm x 4 core
All as per item No 5.01 but of size 10 Sqmm x 2 core
All as per item No 5.01 but of size 25 Sqmm x 4 core
Disconnecting and Taking out of old LT armored PVC cables from trenches of any size/core/any voltage grade from trenches for replacement all as directed by Engr in charge
M & L replacement for PVC insulated and sheathed weather proof two core 2.5 sqmm single stranded aluminium conductor service cable for connection incl taking down UNSV cable all complete as specified and directed .
M & L replacement for PVC insulated and sheathed weather proof two core 4 sqmm single stranded aluminium conductor service cable for connection all incl taking down UNSV cable complete as specified and directed .
M & L replacement for PVC insulated and sheathed weather proof two core 6 sqmm single stranded aluminium conductor service cable for connection all incl taking down UNSV cable complete as specified and directed
Taking down unserviceable LED garden lights / LED bollard 10/30/40 Watts completer all as specified and as directed by Engr-In-Charge.
S & F Adjustable thermal & magnetic release MCCB 4 pole 100 Amps, 25 KA rating,Ics = 100% Icu (Icu = 25 kA), 415 volts AC complete incl removing of existing U/S one.
Taking down unserviceable LED flood light fitting 200/150/120 Watt complete all as specified and directed.
Disconnection of street light fittings and refixing,Material and labour in replacement for circuit /sub main wiring from junction box to street light fitting complete with 1.5 sqmm 3 core PVC insulated and PVC round sheathed multistranded copper conductor flexible industrial cable 1100 V grade drawn through PVC conduit in street light poles complete all as specified and directed.
Supply and fix in replacement LT Cable junction box outdoor shall be made out of Polycarbonate reinforced and size should be not less than 205mm x 255mm x 112 mm(upto Cable Size 35/25 sq.mm). The Polycarbonate Junction Box shall be environment friendly, recyclable, halogen & silicon free, anti acid & anti corrosive. The Junction Box shall be rated for Degree of ingress Protection IP 66/69 in accordance with IEC 60695.Weatherproof, UV-resistant, rainwater-proof, temperature-resistant. The gasket material of junction box shall be Polyurethane and the gasket shall be internally embedded. The Junction Box shall be complies with requirements of the standards IEC 60695 - . The Junction Box with Connectors or Terminal Trip or Bus Bar. The manufacturer of Junction Box / Enclosure shall submit a copy of IEC Certificate . For better safety the Polycarbonate enclosure and shall be fire retardant & self - extinguishing in accordance with IEC 60695 - The impact strength of Polycarbonate enclosure / boards i.e. the Degree of protection against mechanical load shall be in accordance with EN 50298 - 98 for IK 08 including one No. 4 pole connector and one no. MCB SP 'B' curved 6-32 Amp and chromium plated clamps and nut bolts, Glands complete all as per manufacturer’s instructions.
Disconnecting the electric supply from existing high mast panel, dismantling, and taking down laltern carriage of high mast assembly and open up for examination of Engr-in-charge of high mast, dismantling and servicing complete lifting and lowering system,and check the all mechanism assembly is housed in a chasis,pulley, flexible marine grade stainless steel wire rope,trailing cable,lubricating in bearings, cable connection,power tools,fidder pillar box, and reassembling the all mechanism complete and testing on completion all as specified and directed.
Supply and fixing in replacement of flexible marine grade stainless steel wire rope without any intermediate joints and shall consists of only non corrodible as per existing size/grade (304 or 316) in flexible 7/19 breaking capacity of rope is 2350 kg x 2 all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of double drum winch complete mechanism system including 140/90 SAE lubricant as per existing make and capacity,and safe working load 750 Kg complete all as specified and directed.
Supply and fixing in replacement of trailing cable flexible EPR insulated PCP sheathed round copper conductor power cable 5 core x 4 sqmm copper.
Taking out from high mast winch/power tool and repairs,servicing and rewinding with super enameled copper conductor of existing size , testing on completion to electric motor 1/1.5 HP all as specified and directed by Engr-in- Charge.
Taking down old unserviceable LED street light fitting of 25/35/45/60 Watt Complete all as specified and directed by Engr-In-Charge.
Supply and fixing of 45 watt Inverter LED Street Light with IR Sensor for automatic On-Off of street light and shall have inbuilt Li-on battery for 90mins power backup in case of power failure. Housing of fixture shall be presurre die cast and system efficacy >100LPW, CRI >70, CCT 5700K, PF>0.9, THD<15%. Complete all as specified and as directed
Supply and fixing of 60 watt Inverter LED Street Light with IR Sensor for automatic On-Off of street light and shall have inbuilt Li-on battery for 90mins power backup in case of power failure. Housing of fixture shall be presurre die cast and system efficacy >100LPW, CRI >70, CCT 5700K, PF>0.9, THD<15%.Complete all as specified and as directed
S&F in renewal for earthing with galvanized steel plate electrode 600 x 600 mm x 6 mm size directly burred in ground vertically earth pit not less than 2.25 meter deep below normal ground level with top edge of the earth plate not less than 1.5 m below normal ground level surrounded with coal dust and common salt filling in alternative layers of 15 cm thick each connected to and including GI earth wire 4 mm dia by means of GI nuts, bolts, check nuts & washers etc connecting to earthing test point, main switch board and including 15 mm dia GI pipe light grade for protection of earth lead from earth plate upto 5 mtr and 20 mm dia GI pipe medium grade connected with funnel having wire mess for watering purpose including necessary excavation and earth work, PCC (1:2:4) type B-1 (using stone aggregates) for earthing pit, 10mm thick cast iron cover with angle iron frame all as specified and shown in electrical plate No 3 of SSR Part-I and testing on completion.
Supply and laying/ fixing GI tube, light grade, 50mm dia for encasing cables for mechanical protection, laid under plinth/ floors/ path/ culverts or fixed on wall or concealed in wall/ floor or along poles or as street light polesor as mounting bracket, bent to shape with complete accessories such as bends/ sockets/ reducers/ saddles including necessary threading/ drilling works complete all as specified and as directed.
S&F in repairs for rigid non-metallic PVC conduit of 20 mm dia heavy duty alongwith street light poles for wire from junction box to light fittings including fixing arrangement complete all as directed by Engr-in-Charge. .
Dismantling of existing unserviceable/cracks PCC poles of any size and type from its position from the site and taking away from site including necessary excavation and earth work in any type of strata,demolition of concrete, disconnecting of street light fitting etc all as specified and as directed.
Supply and fix in replacement of steel tubular swaged poles type 410 SP-31 (9.0 meter long) complete all as specified and as directed
S&F in replacement of MCB SP 6 to 32 Amp B curves MCB repturing capacity 10 KA etc complete all as specified and directed by Engineer-in-Charge
S&F in replacement of LED batten fitting 18/20/22/10 Watt complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of decorative wall light fitting WITH LAMPS 9/10 WATT made up of Polycarbonate , City-1 , Cylindrical shape , with LED lamp 9 Watt complete with fixing arrangements on wall all as specified and directed. Make:City 1 of havells or equivalent in bajaj ,philips
Taking down old unserviceable LED recees/ surface/ bulkhead light fitting any wattage complete all as specified and directed by Engr-in-Charge.
Taking down old unserviceable LED flameproof light flame proof 1X16/20 Watt complete all as specified and directed.
Supply and Fixing in replacement of LED decorative designer pole light 1X45 Watt, 3.5Mtr Long Double bracket long with die cast MS poles , fixture driver, holder, connector etc prewired including connecting up with 3 core copper cable in steel flexible pipe complete all as specified and directed.
Supply & fix in replacement of Inverter LED lamp 9/10 watt IP 20 and inbuilt btry back up with light dependent sensor, IP65 protected. Complete all as specified and as directed
Supply & fixing in renewal LED Inverter batten fitting 18/20 Watt, 220 V decorative box type with driver 4" complete fitting connection with 3 core flexible copper cable 23/0.00076 from ceiling rose to tube fitting connection etc complete all as specified and directed by Engineer-in-charge.
Supply & fix in replacement of LED Aviation obstruction light 6 watt with light dependent sensor, IP65 protected.
Excavation in trenches, n.exc 1.5m wide & n.exc 1.5m in depth for foundation & getting out in Soft/ loose soil etc for laying of cable complete as specified.
Removal of surplus soil to a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cms thick in soils complete all as specified
Material and labour for dry tibba sand in trenches cushioning to under ground cable spreading, levelling hand punning complete all as specified and directed.Note- Punned down thickness will be measured for payment purpose.
Supply and lay un reinforced precast concrete cable covers Class LV,Type 1, flat, size 250mm x 150mmx 40mm complete all as specified and directed.
Material and labour for Cement Concrete 1:2:4 type B0 using 20mm graded stone aggregate for pole base foundation and coping complete all as specified and as directed
M&L in repair cement concrete PCC 1:4:8 type D-2 using 40mm graded stone aggregate as in pole foundation all as specified
Supply and laying/ fixing GI tube, light grade, 40mm dia for encasing cables for mechanical protection, laid under plinth/ floors/ path/ culverts or fixed on wall or concealed in wall/ floor or along poles or as street light polesor as mounting bracket, bent to shape with complete accessories such as bends/ sockets/ reducers/ saddles including necessary threading/ drilling works complete all as specified and as directed.
M/S HARIOM CONSTRUCTION COMPANY (BID ID -3166299)
Mahaveer Traders (BID ID -3166306)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .