Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.2 LAccepted-AOC 66 102 ARUN JYOTHI MULLASSERY CANAL ROAD ERNAKULAM KOCHI 682 011 | KOCHI | ERNAKULAM | KERALA | 682011 | L1 | Accepted-AOC Lowest bidder with reasonable rates | |
| 2 | L2₹12.4 L+₹12,200 (1.00%)Rejected-Finance CHEMBISSERY PUTHIYAKAVU TRIPUNITHURA P O KOCHI 682301 | ERNAKULAM | KERALA | 682301 | L2 | Rejected-Finance Other than lowest tenderer | |
| 3 | L3₹12.4 L+₹15,100 (1.23%)Rejected-Finance | L3 | Rejected-Finance Other than lowest tenderer |
Tender Value
Refer Docs
EMD Value
₹26,000
Closing Date
11 Jan 2021, 6:00 pmClosed
CWE (NW) KOCHI
CWE (NW) KOCHI NAVAL BASE PO KATARIBAGH KOCHI - 682004
ADDN/ALTN FOR HT INTERCONNECTION BETWEEN NSRY AND SNC (O) MESS SUBSTATIONS AT NAVAL BASE KOCHI
2020_MES_396772_1
CWE(NW)KOCHI/81175
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KOCHI
AS PER NIT
6 documents required · 6 mandatory
₹500
GE (NS) KOCHI
₹26,000
Yes
4 Feb 2021
20 Nov 2020
14 Jan 2021
20 Nov 2020
11 Jan 2021
28 Dec 2020
20 Nov 2020 - 4 Jan 2021
Amount
Supply, install, extension to and connecting up to existing ABB make outdoor RMU, testing and commissioning of outdoor, both side extendable HT 12 KV rated voltage and 11 KV operating voltage, 3 phase 50 Hz, one way Ring Main Unit (+C+) Type : one load break motorised isolator, totally enclosed metal clad switch gear, having rated current of Ring Switch is 630 Amp, copper bus bar with danger notice board, with factory made 2mm thick ,weather proof enclosure by the switchgear manufacturer. The unit shall be painted in RAL7012/7035 paint shade with folowing specifications and all as per the IEC 62271 –200 and Type test report of RMU should include Internal Arc with AFLR classification and as per the specification of the manufacturer.
(a) Ring Switch/Isolator (i) Capacity 11 KV, HT, 630 Amps. Triple pole, single break, having three position ('ON', 'OFF' and 'EARTH') Ring Main Switches, each with independent motor charged spring mechanism and fully rated earth switch. (ii) Air insulated cable boxes with gland plate suitable for bottom entry of single run of three core cable up to 300 sqmm. (iii) Cable Bushings (iv) Capacitive Voltage Indicator with LED Display. (v) Mimic diagram on front panel, complete with status indicators (ON-OFF-EARTH). (vi) Motorised assembly (vii) One set of Potential Free contacts for SCADA Compatibility. (viii) Fault Passage Indicators with remote contact. (ix) Angle Boots-NON TOUCH PROOF
(b) General spacifications : (i) One set of positive standard mechanical interlocks to avoid unsafe operations. (ii) Provision of pad locking for open, close, earth position in correct sequence. (iii) Mano meter for indicating SF6 gas pressure with green and red zone. (iv) Three mm thick stainless steel SF6 tank with robotically welded construction with IP67 protection. (v) External stud for earthing connections. (vi) SF6 Gas re filling provision. (vii) Extendable bushings future for future extension with metallic end cap cover.
Supply, install, connecting up, testing and commissioning of indoor, both side extendable HT 12 KV rated voltage and 11 KV operating voltage, 3 phase 50 Hz, four way Ring Main Unit (+CCCV+) Type :one fixed vacuum circuit breaker duly interlocked, and three load break motorised isolator, battery charger, totally enclosed metal clad switch gear with motorized 24 volt DC battery bank and charger, protection relays, having rated current of Ring Switch and Breaker is 630 Amp, copper bus bar with danger notice board, with factory made ,2 mm thick weather proof enclosure by the switchgear manufacturer. The unit shall be painted in RAL7012/7035 paint shade with folowing specifications and all as per the IEC 62271 –200 and Type test report of RMU should include Internal Arc with AFLR classification and as per the specification of the manufacturer.
(a) Ring Switch/Isolator (i) Capacity 11 KV, HT, 630 Amps. Triple pole, single break, having three position ('ON', 'OFF' and 'EARTH') Ring Main Switches, each with independent motor charged spring mechanism and fully rated earth switch. (ii) Air insulated cable boxes with gland plate suitable for bottom entry of single run of three core cable up to 300 sqmm. (iii) Cable Bushings (iv) Capacitive Voltage Indicator with LED Display. (v) Mimic diagram on front panel, complete with status indicators (ON-OFF-EARTH). (vi) Motorised assembly (vii) One set of Potential Free contacts for SCADA Compatibility. (viii) Fault Passage Indicators with remote contact. (ix) Angle Boots-NON TOUCH PROOF
(b) Vacuum Circuit Breaker : (i) Capacity 630 Amps, Triple pole, Vacuum Circuit Breaker, with independent motor charged spring mechanism and fully rated earth switch, with provision for earth of the cable. (ii) Air insulated cable box with gland plate suitable for bottom entry of single run of 3-core cable up to 300 sqmm. (iii) multi powered Over current & Earth Fault Relay with digital display(iv) Resin cast current transformers for protection circuit mounted on Cable bushings / cable box of ratio 100-50/1A, 5P10, 2.5VA. (v) Capacitive Voltage Indicators with LED Display. (vi) Mimic diagram on front panel, complete with status indicators (ON-OFF-EARTH). (vi) Motorised assembly. (vii) Epoxy Moulded low energy Tripping Coil for tripping the circuit breaker in fault condition. (viii) One set of Potential Free contacts for SCADA Compatibility. (ix) Right Angle Boots-NON TOUCH PROOF.
(c) General spacifications : (i) One set of positive standard mechanical interlocks to avoid unsafe operations. (ii) Provision of pad locking for open, close, earth position in correct sequence. (iii) Mano meter for indicating SF6 gas pressure with green and red zone. (iv) Three mm thick stainless steel SF6 tank with robotically welded construction with IP67 protection. (v) External stud for earthing connections. (vi) SF6 Gas re filling provision. (vii) Extendable bushings future for future extension with metallic end cap cover. (viii)Battery with charger. (ix) One set of key interlock for operation between two 'C' modules. (x) One set of key interlock for operation between one 'C' module and one module in another existing RMU including installation of key interlock in another existing RMU module. (xi) Cost for disconnecting existing HT cable from existing HT panel and connecting to RMU is deemed to be included in the quoted rate.
Supply and laying cables in trenches, or fixing on walls or passing through cable duct / pipe XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor, 11000 volts,(earthed ) grade having cross sectional area 3 core 185 sqmm all as specified and as directed.
Supply and fixing of cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm all as specified and as directed.
Supply and laying cables in trenches, or fixing on walls or passing through cable duct / pipe XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor, 1100 volts, grade having cross sectional area 2 core 4 sqmm all as specified and as directed.
Materials and labour for earthing complete with galvanised iron earth plate electrode of size 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with and including galvanised earth strip of size 32 x 6mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe 40 mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion all as specified and as directed by the Engr-in-Charge.
M/s.Rejoy Constructions
PHEJAYS AGENCIES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .