Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.4 LAccepted-AOC | ₹1.4 L | L1 | Accepted-AOC L1 |
| Sl No | Description | Qty | Unit | Vinod Kumar M L1 |
|---|---|---|---|---|
| 1.00UPS Installation | ||||
| 1.00 | OD145751/2025-2026:Supply Installation and testing and commissioning of 3 kVA online UPS pure sinewave with 120 min backup with tubular C10 battery with minimum VAH of 9600. a) 1 ph to1 ph with by pass arrangement, b) Input pf > 0.95 @ full load, c) Output pf : >.95 d) Input voltage range : 160V -280V with cut off e) THD < 10% f) Overall Efficiency >.9 % g) Ambient Temperature : 0-40°C h) Generator Compatibility available. i) Pure sine wave. j) Battery over charge & under charge cut off. k) Bypass arrangement. i) EN/IEC620401 for General Safety compatibility j) LED/LCD Display with digital indications of Input V & A, output V & A, Battery charge, Temperature, frequency q) Approved UPS make : APC/Delta/Numeric) Approved C10 rated tubular battery make:-Exide/Quanta/Amaron, s) Architecture Tower type only (rack mountable not acceptable. t)Marking CE, BIS, ROHS u) All certificates copy to be submitted. v)Three year warranty. Battery rack : Painted MS angle iron rack Suitable for the battery supplied. | 1 | each | 1,27,500 ₹1.3 L |
| 1.00 | 2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature
circuit breaker suitable for inductive load of following poles in the existing MCB
DB complete with connections, testing and commissioning etc. as required.
Single pole | 4 | each | 250 ₹1,000 |
| 1.00 | 1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm | 40 | metre | 124 ₹4,960 |
| 1.00 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm | 30 | metre | 98 ₹2,940 |
| 1.00 | 1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm | 8 | metre | 215 ₹1,720 |
| 1.01 | 1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm) | 2 | each | 390 ₹780 |
| 1.01 | 1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm) | 1 | each | 440 ₹440 |
| 1.01 | 1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch | 4 | each | 100 ₹400 |
| 1.01 | 1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet | 4 | each | 119 ₹476 |
Tender Value
₹1.4 L
EMD Value
₹3,623
Closing Date
25 Oct 2025, 6:00 pmClosed
Assisstant Executive Engineer
Office of the Assisstant Executive Engineer PWD Electrical Subdivision Thalassery
DEPOSIT-SITC of UPS at Revenue Offices Anthoor village office- SITC of UPS and Allied Electrical Works-General Electrical Work-1
2025_PWD_789945_2
PWD/BLDG/TR/4757/2024_6_7_6/1
Open Tender
Electrical Works
90 days
KANNUR
Please refer Tender documents.
7 documents required · 7 mandatory
₹555
₹3,623
30 Apr 2026
18 Oct 2025
28 Oct 2025
18 Oct 2025
25 Oct 2025
18 Oct 2025
Amount
UPS Installation
OD145751/2025-2026:Supply Installation and testing and commissioning of 3 kVA online UPS pure sinewave with 120 min backup with tubular C10 battery with minimum VAH of 9600. a) 1 ph to1 ph with by pass arrangement, b) Input pf > 0.95 @ full load, c) Output pf : >.95 d) Input voltage range : 160V -280V with cut off e) THD < 10% f) Overall Efficiency >.9 % g) Ambient Temperature : 0-40°C h) Generator Compatibility available. i) Pure sine wave. j) Battery over charge & under charge cut off. k) Bypass arrangement. i) EN/IEC620401 for General Safety compatibility j) LED/LCD Display with digital indications of Input V & A, output V & A, Battery charge, Temperature, frequency q) Approved UPS make : APC/Delta/Numeric) Approved C10 rated tubular battery make:-Exide/Quanta/Amaron, s) Architecture Tower type only (rack mountable not acceptable. t)Marking CE, BIS, ROHS u) All certificates copy to be submitted. v)Three year warranty. Battery rack : Painted MS angle iron rack Suitable for the battery supplied.
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.27.4:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.6 Module (200mmX75mm)
1.27.3:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.4 Module (125mmX75mm)
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
90.10.3.32:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
Bidder Name
Vinod Kumar M
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1356155.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
specificconditionNEW.pdf
Tender Documents • 0.34 MB
MOM.pdf
Tender Documents • 0.19 MB
BOQ_1356155.xls
BOQ • 0.31 MB
viewnit.pdf
Tender Documents • 0.02 MB
viewsbd.pdf
Tender Documents • 1.63 MB
Download all tender documents and submit your bid