Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.4 LAccepted-AOC | L1 | Accepted-AOC Due to lowest accepted | |
| 2 | L2₹8.0 L+₹2,309.90 (0.29%)Rejected-Finance | L2 | Rejected-Finance Other than lowest |
Tender Value
₹7.3 L
EMD Value
₹14,628
Closing Date
27 Jun 2022, 6:00 pmClosed
Garrison Engineer Ludhiana
Garrison Engineer Military Engineer services Near Jagraon Bridge Ludhiana-141001
SPECIAL REPAIR / REPLACEMENT OF LT PANEL AND OVER HEAD LINE TO UNDER GROUND CABLE AT VAJRA ARMY SCHOOL AND PROVN OF SEPTIC TANK FOR 100 PERS AND SOAK WELL SIZE 2.4M DIA 3.0 DEPTH WITH SEWAGE LINE NEAR BLDG NO T-310 AT DHOLEWAL UNDER GE LUDHIANA
2022_MES_516311_3
GE/LDH-64/2021-22
Open Tender
Civil Works
Item Rate
180 days
Dholewal Cantt under GE Ludhiana
As per NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE Ludhiana
₹14,628
Yes
11 Jul 2022
6 Jun 2022
28 Jun 2022
6 Jun 2022
27 Jun 2022
13 Jun 2022
6 Jun 2022 - 12 Jun 2022
Amount
Sch 'A' sec-I
Excavation in trenches any type of soil not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of pipes/cables etc getting out complete all as directed & specified
Returning filling in including spreading leveling watering and well ramming in layers each not exceeding 25 cm thickness complete all as specified and as directed
Removal of surplus spoil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed
Supplying, filling in trenches, spreading, leveling sand cushioning 8 cm below cable and 15 cm above the cable for under ground cable complete all as specified & directed. (Note:- 18 cm punned down thick shall be considerd for mesurement)
M & L for old size sub class 'B' bricks,laid flat in trenches over the cable with length of brick perpendicular to the direction of the cable , adjacent/abutting each other complete all as specified
Dismantling & taking down of existing worn out/unserviceable aluminium conductor, steel reinforces (ACSR) of any description / size and in any position from from existing LT poles/lines all as specified and directed.
Supply, laying and testing cable XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core complete all as specified and directed.
Supply, laying and testing cable XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sqmm 4.0 core complete all as specified and directed.
Supply and fixing for bldg security light fitting LED 60 W LED made up of pressure die cast aluminium housing with potted isolated driver and high power LED and indl lenses,, IP66 with high power LED lamp incl with suitable size of bracket compete all as specified and directed.
S& F for polycarbonate thermoplastic outdoor junction box for steet lights with flap cover operate with IEC 61439-3 which should be shock proof, protection class-II, earthed , IP 65 weather proof , corrision free , acid and chemical resistant , impact resistant, , ultra voilet resistant made of halogen & silicone free recyclable mtrl, internally embedded gasket with provision for cable entry through integrated flanges top and bottom,The gasket should be internally embedded made of polycarbonate incl with bus bar & fixing arrangement ( clamps, nuts and Bolts etc.) complete all as specified.
M& L for earthing including necessary excavation/earth work in any type of soil complete for LT Panels with galvanised steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25 metres below normal ground level with top edge of the plate at a depth not less than 1.5 metres below normal ground level, connected with and including GI strip 32mm x 6mm and including GI pipe 50mm bore light grade as protection pipe (from top of earth plate up to the test point) by means of GI bolts, nuts, check nuts and washers of GI and thimbles, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick, all around including top and bottom and watering pipe 20mm bore of GI pipe medium grade with funnel and wire mesh, PCC chamber of size 300x300x300mm(top of chamber minimum 15 cm above the normal ground level (1:3:6) using 20mm graded stone aggregate and RCC cover (1:2:4) type B-I using 20mm graded crushed stone aggregate of 25mm thick with 2 nos MS handles of 12mm dia including necessary excavation/ earth work in any type of soil and as shown in Electrical plate No. 3 of SSR Part-I (2009) testing on completion complete all as specified.
M&L for cement concrete 1:3:6 type C-2 using 40mm graded stone agg as in bed to drain pipe, incl packing under and haunching against the sides of pipe 150mm bore after they are laid and tested.
M&L for 150mm internal dia Sail-glazed stoneware drain pipes, laid ingradient completed with collars and jointed as specified.
M&L for PCC (1:3:6) type C-2 using 40 mm graded stone aggregate as in foundation, filling and mass concrete.
M&L for brick work with sub class B brick straight or curved on plan exc 6 mtr mean radius built in cement mortar 1:4.
M&L for PCC 1:2:4 type B-1 using 20mm graded stone aggregate as in bed plates, coping, kerbs, water trough and like incl. rounded or chamfered on edges.
M&L for 15mm thick rendering on brick work or concrete surfaces in cement mortar 1:4 finished even and smooth with using extra cement (with water proofing compound).
M&L for rendering 15mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 finished surface even and smooth, without using extra cement.
M&L for preparation of new plastered wall surfaces and applying three coats of whitewash
M & L for PCC (1:3:6) type C2 using 40mm geaded stone aggregate as in surface channel and drains.
M&L for cutting into existing manhole for connecting new drains not exc150mm dia, making good to pipe and rendering, cutting out existing benching for and forming branch channel (1/2 round or 3/4 section) in cement concrete (1:2:4) type B-1 smooth finished, and reforming benching as required complete all as specified & directed by Engineer-in-charge.
S&F for Mild steel TMT bar 6mm to 8mmdia and above cut to length, bent to shape rquired including cranling , bending spirally for hooping for column , hooking ends and binding with mild steel wire not less than 0.9mm dia as specified.
M&L for providing reinforced cement concrete type B-l, 1:2:4 (20 mm graded aggregate) in precast cover slab over for menholes , average sectional area n exc 100 sq. cm, with or without chamfered angles and flat, splayed, rounded or mitred tops as directed
Supply only integral water proofing compound
M&L for extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using ex- tra cement, including forms, moulds, mi- tred/stopped ends etc.
Excavation over areas in any type of soil, n exc 1.5 m deep and getting out complete all as specified and directed by Engineer in Charge.
Excavation over areas in any type of soil, exc 1.5 m deep and n.exc 3.0 getting out complete all as specified and directed by Engineer in Charge.
Excavation over areas in any type of soil, exc 3.0 m deep and n.exc 4.5 getting out complete all as specified and directed by Engineer in Charge.
M&L for 100 mm thick Hardcore of broken stone or boulders gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface complete all as specified.
M&L for PCC 1:4:8 type D-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete etc complete all as specified and directed.
M&L for RCC 1:1.5:3 using 20mm graded aggregates on slabs supported on walls beams and columns in floors roofs landings balconies etc complete all as specified and directed.
S&F for 100mm bore cast iron soil waste and vent pipes in any length with or without ears with cement joints laid in trenches or in floor complete all as specified and directed
M&L for RCC 1:2:4 type B1 (using 20mm stone aggregate)Beams, cantilevers, bressummers, lintels over 1.5m span complete all as specified and directed.
Formwork to edges of concrete flats, treads, breaks in floors,window cills, concrete railings,openings in concretewalls, floorand roofs n exc 20cm wide and sides of RCC/PCC bands in walls,horizontal or sloping and similar work exc 10cm but n exc 20cm wide complete all as specified and directed.
M&L for RCC 1:2:4 type B1 (using 20mm stone aggregate) Slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed.
M&L for formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200mm thick (Horizontal or sloping) complete all as specified and directed.
M&L for Broken brick coarse (63 mm)aggregate complete all as specified and directed.
M&L for Cast Iron Manhole cover with frame of heavy duty (HD) casting and confirming to IS: 1726:1991 for clear opening 560x560mm and chequer of cover shall not be less than 4mm .Manhole cover and frame coated with material having base- with black bitumen composition. Frame shall be embaded in concrete firmly and complete all as specified and as directed.
S&F for Mild steel square bar 20mm dia (For Rungs) and above cut to length, bent to shape rquired including cranling , bending spirally for hooping for column , hooking ends and binding with mild steel wire not less than 0.9mm dia as specified(Fe-410-W(Gde.E-250) Qulaty A.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .