Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
Tender Value
₹2.0 L
EMD Value
₹3,937
Closing Date
1 Mar 2024, 3:00 pmClosed
Executive Engineer (Elect)
Room No 25, T.E. Building Kidwai Bhawan MTNL, New Delhi
Replacement/Repairing of Siemens make smoke detectors of existing addressable Fire detection system and other associated works at TE Bldg JLN Marg, MTNL,ND
2024_MTNL_796234_1
EE(E)KBN/2023-24/19-02-24/153
Open Tender
Miscellaneous Services
Item Rate
15 days
Kidwai Bhawan
Please refer Tender documents.
8 documents required · 8 mandatory
₹590
Yes
MTNL Delhi
₹3,937
Yes
4 Mar 2024
19 Feb 2024
2 Mar 2024
19 Feb 2024
1 Mar 2024
19 Feb 2024
Amount
Replacement of following Siemens make faulty equipment , by removing the faulty equipment and programming the new device with the Siemens programmer and install the same and configuring the same in Fire panel to make the Addressable fire alarm panel fully functional a) Addressable Smoke cum heat detector
Supply & installation of single headed external hydrant valve with 1 no 63 mm dia instantaneous SS cooling & cast iron wheel ISI marked conforming to IS 5290 with blank cap & chain as required
Replacement of wear out hose reel pipe of dai 20 mm with new water Hose thermoplastic pipe as per IS 12585 complete as required
Wrapping & coating of 150 mm dia MS pipe with 1 coat of bitumen paint and wrapping the pipe with 4 mm thick coating sheet complete as required
Excavation of the ground for laying 150 mm dia MS pipe, the job include cutting the RCC and digging the earth and of suitable depth for laying the pipe and refilling the soil after laying of pipe.
Replacement of rusted and broken 25 mm dia Ball valve with new ball valve complte as required .
Replacement of wear out mechanical seal ( 2 nos seal) in the Main electric pump, by removing the pump from the location with the help of chain pulley block taking it to workshop for replacement of seal and taking it back to site and refixing the same
Repairing of the leakage of existing sluice & Non return valve by opening the same, removing the ols stem packing cleaning and it inside, fixing the new stem packing, placing the packing gland and tighten the same to stop leakage as required.
Replacement of the broken cable with new cu conductor 2x1.5 sq mm Armd FRLS cable on wall or cable tray complete with connection as required
Supply & fixing of 80 mm dia Butterfly valve PN 1.6, with nut & bolts etc complete as required
Replacement faulty battery of fire panel with new 2x 12V 7 Ah battery complete with thimble etc as required
Less credit for old dismantled material shall be property of contractor.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .