| Sl No | Description | Qty | Unit | RAHUL TRADERS L1 | M/s Bharat Construction and Trading Company L2 | M/S KUNDAN SINGH SAINI CONTRACTOR L3 |
|---|---|---|---|---|---|---|
| 1.00Supply | ||||||
| 1.01 | Enabling and Integration of Auto-Reclose (AR) Function in Existing Distance Protection Relay (132 kV Line)
• Verification of the existing 132 kV line distance protection relay hardware and firmware to confirm Auto-Reclose functionality.
• Enabling AR logic and relevant settings in the relay configuration software (e.g., MiCOM S1 Studio, DIGSI 5, or EnerVista, as applicable).
• Integration of AR logic with the existing protection scheme and coordination with breaker-failure (BFR) relay logic.
• Ensuring AR sequence and timing comply with approved protection philosophy (e.g., single-shot, 1-phase or 3-phase reclose logic). | 14 | Nos. | 9,990 ₹1,39,860 Lowest | 12,990 ₹1,81,860 | 14,995 ₹2,09,930 |
| 1.02 | Provision of Auto-Reclose Control Circuitry with Breaker Status to Relay (Including Wiring, Terminals, and Mounting)
• Development of inter-connection circuitry between the circuit breaker auxiliary contacts and relay I/O terminals for AR enable, dead-time, and reclaim-time logic.
• Provision of additional terminals, ferrules, and labels inside the relay/control panel for identification and future maintenance.
• Routing and termination of control wiring from breaker marshalling kiosk to relay panel as per approved drawings.
• Verification of correct logic and status indication through continuity and simulation tests. | 14 | Nos. | 14,990 ₹2,09,860 Lowest | 17,990 ₹2,51,860 | 19,995 ₹2,79,930 |
| 1.03 | Configuration, Mapping, and Testing of Auto-Reclose Function (Including Secondary Injection and Commissioning)
• Configuration and mapping of AR logic with trip, reclose, and lockout functions within the 132 kV relay.
• Setting appropriate dead-time, reclaim-time, and shot count parameters as per system requirements and relay capabilities.
• Testing of AR function using a secondary injection kit, verifying correct operation for single-phase and three-phase trip sequences.
• Final commissioning of the AR scheme in coordination with the protection and operations teams.
• Preparation and submission of complete test results, configuration files, and commissioning records. | 14 | Nos. | 39,985 ₹5,59,790 Lowest | 44,990 ₹6,29,860 | 46,995 ₹6,57,930 |
Tender Value
Refer Docs
EMD Value
₹33,000
Closing Date
11 Feb 2026, 5:00 pmClosed
Superintending Engineer (t and c) Haldwani
Office of Superintending Engineer, Test and Commissioning Kumaon zone,132 KV Sub Station Campus, Haldwani-263126
Work of Configuration and Testing Autoreclose function of various Distance Relays at various substations under TandC Circle Haldwani
2025_PTC21_90313_1
SE/TandC/PTCUL/HLD/01/2025-26
Open Tender
Electrical Works
Item Rate
270 days
haldwani
Please refer Tender documents.
3 documents required · 3 mandatory
₹590
Yes
Executive Engineer, T and C Division Kashipur
₹33,000
Yes
haldwani
31 Mar 2026
24 Dec 2025
12 Feb 2026
24 Dec 2025
11 Feb 2026
24 Dec 2025
2 Jan 2026
Supply
Enabling and Integration of Auto-Reclose (AR) Function in Existing Distance Protection Relay (132 kV Line) • Verification of the existing 132 kV line distance protection relay hardware and firmware to confirm Auto-Reclose functionality. • Enabling AR logic and relevant settings in the relay configuration software (e.g., MiCOM S1 Studio, DIGSI 5, or EnerVista, as applicable). • Integration of AR logic with the existing protection scheme and coordination with breaker-failure (BFR) relay logic. • Ensuring AR sequence and timing comply with approved protection philosophy (e.g., single-shot, 1-phase or 3-phase reclose logic).
Provision of Auto-Reclose Control Circuitry with Breaker Status to Relay (Including Wiring, Terminals, and Mounting) • Development of inter-connection circuitry between the circuit breaker auxiliary contacts and relay I/O terminals for AR enable, dead-time, and reclaim-time logic. • Provision of additional terminals, ferrules, and labels inside the relay/control panel for identification and future maintenance. • Routing and termination of control wiring from breaker marshalling kiosk to relay panel as per approved drawings. • Verification of correct logic and status indication through continuity and simulation tests.
Configuration, Mapping, and Testing of Auto-Reclose Function (Including Secondary Injection and Commissioning) • Configuration and mapping of AR logic with trip, reclose, and lockout functions within the 132 kV relay. • Setting appropriate dead-time, reclaim-time, and shot count parameters as per system requirements and relay capabilities. • Testing of AR function using a secondary injection kit, verifying correct operation for single-phase and three-phase trip sequences. • Final commissioning of the AR scheme in coordination with the protection and operations teams. • Preparation and submission of complete test results, configuration files, and commissioning records.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.55 MB
BOQ_107010.xls
BOQ • 0.28 MB
TD.pdf
Tender Documents • 1.64 MB
PQR.xls
Other Document • 0.17 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .