COL SUNIL PILLAI
HQ CWE TENGA PIN-900194 C/o 99 APO
PROVISION OF 315 KVA TRANSFORMER FOR SMQs AT AF STATION MISSAMARI UNDER GE MISSAMARI
2023_MES_616042_1
8384/E8
Open Tender
Civil Works
Item Rate
180 days
GE MISSAMARI
D (b) (ii)
8 documents required · 8 mandatory
₹500
GE MISSAMARI
₹68,000
Yes
25 Nov 2023
28 Aug 2023
7 Oct 2023
28 Aug 2023
30 Sept 2023
11 Sept 2023
Amount
Supply, install, test and commission step down transformer, outdoor type, plinth mounted HT 11 KV, 3 phase 433 volts, 4 wire, 50 Hz, delta/star connected, vector group DYN -11 double copper wound, ONAN, manual type off load tap changing facility on HT side to vary secondary voltage from minus 7.5% to plus 7.5% in steps of 2.5 %, continuous rating of capacity 315 KVA and of Level - 2 energy efficiency incl bushing on HT end cable box on LT side. The transformer shall be complete with all standard fittings and accessories, gauges, first fill of transformer oil, etc, and conforming to IS 1180 Part-1:2014 duly mounted on plinth and all as specified and as directed. Make :- ABB / SCHNEIDER / CROMPTON GREAVES / VOLTAMP / ITE GURGAON (a) Oil conservator with filling hole, cap and drain plug (b) Silica gel breather with oil seal and first fills of dehydrating agent (c) Adequate Nos of thermometer pockets incl one No for accomodating bulb type thermometer (d) Drain cum bottom filter valve (e) Top filter valve (f) Prisomatic oil level gauge (g) Inspection cover (h) Cover fitting lugs (j) Jacking and fitting lugs (k) Separate neutral bushing brought out for earthing on LV side (l) Earthing terminal Note :- Construction of platform for must be suitable to the actual size of the Transformer and to be executed after approval of Engr-in- Charge. Cost of Platform deemed to be included in the Quoted rates.
Supply laying & testing cable XLPE insulated, earthed, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 6.35/11KV volts, grade cross sectional area 95 sq. mm 3 core conforming to IS 7098 complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 95 sq mm complete all as specified and directed. Make :- DENSON/RAYCHEM/YAMUNA
Supply & Fix Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11 metres long) and applying two coats of aluminum paint over a coat of red oxide primer, the embedded portion shall be applied with two coats bituminous paint complete all as specified and directed.
M&L Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint as specified and directed.
M&L for Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed.
M&L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT11000V, of size 20cmx15cm complete all as specified and directed .
Supply and fixing lightning arrestor complete with all fittings discharge capacity 65kA suitable for 11000V complete all as specified and directed. Make ALSTOM/OBLUM/BHEL/JAIPURIA BROTHERS
Supply and install HT 11 KV outdoor type gang operated air-break switch , mechanically operated mounted on insulator and steel frame ,with operating mechanism worked from ground level suitable for horizontal or vertical mounting including drop out fuse having 12 insulators of rating upto 200 Amps complete all as specified and directed .
M & L for earthing complete with copper Earth Plate Electrode 600mm x 600mm x3.15mm, thick buried directly in ground vertically to a depth not less than 2.25 Metre below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 Metre below Normal Ground Level, connected to Copper earth strip 20x3 mm drawn through and including Galvanized Iron protection Pipe 40 mm bore (dia) Light grade up to height of the transformer foundation where transformer is situated by means of Bolts, Nuts, Check Nuts and Washers etc Earth plate surrounded by a packed thickness of charcoal or coke dust mixed with common salt in alternate layers of not exc 150mm thick PCC Pit in cement concrete 1:3:6 (20 mm graded aggregate ), Precast RCC 1:2:4 (20mm graded aggregate ) cover slab 350 x350 x 50mm thick reinforced with and including 8mm dia TMT Bars @ 10 cm Centre to Centre both ways GI Wire Mesh , Funnel, with GI Watering Pipe 20mm bore dia Medium grade necessary excavation in soft loose soil returning filling in and removal of surplus soil upto a distance of 50 METRE and all as shown in Electrical Plate No. 3 of MES schedule Part- I and testing on completion complete all as specified and as directed.( Two each for transformer neutral ).
M & L for earthing complete with Galvanized iron Earth Plate Electrode 600mm x 600mm x3.15mm, thick buried directly in ground vertically to a depth not less than 2.25 Metre below Ground Level with Top Edge of Earth Plate at depth not less than 1.50 Metre below Normal Ground Level, connected to Galvanized Iron earth strip 32x6 mm drawn through and including galvanized Iron protection Pipe 50 mm bore (dia) Light grade up to height of the transformer foundation where transformer is situated by means of Bolts, Nuts, Check Nuts and Washers etc Earth plate surrounded by a packed thickness of charcoal or coke dust mixed with common salt in alternate layers of not exc 150mm thick PCC Pit in cement concrete 1:3:6 (20 mm graded aggregate ), Precast RCC 1:2:4 (20mm graded aggregate ) cover slab 350 x350 x 50mm thick reinforced with and including 8mm dia TMT Bars @ 10 cm Centre to Centre both ways GI Wire Mesh , Funnel, with GI Watering Pipe 20mm bore dia Medium grade necessary excavation in soft loose soil returning filling in and removal of surplus soil upto a distance of 50 METRE and all as shown in Electrical Plate No. 3 of MES schedule Part- I and testing on completion complete all as specified and as directed. (Two each for transformer body, LT panel , Two pole structure & LA)
Supplying and laying un-reinforced precast concrete cable cover class HV, type - I, flat, size 300 x 180 x 40 mm all as specified and directed.
Supply, lay, & testing cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following size: - (a) 400 sq mm 3½ core (Transformer to LT Panel)
(b) 240 sq mm 3½ core ( LT Panel to FPB 1 & 2)
(c) 185 sq mm 3½ core (LT Panel to FPB 3)
(d) 25 sq mm 3½ core (For Security Lights)
Supply & Fix chain link fencing 75 mm x 75 mm mesh, of height minimum 2 meters length with 3.14 mm dia galvanized steel wire, made up into mattresses or cages, lapped, straining fixed to RCC/angle iron post including securing or tying with GI MS wire, staples etc. complete all as specified and directed.
Supply & Fix Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-31 (09 metres long) and applying two coats of aluminum paint over a coat of red oxide primer, the embedded portion shall be applied with two coats bituminous paint complete all as specified and directed.
Supply & Fixing street light bracket made of 32mm dia GI Pipe light grade upto 1.2mtr including two pairs of clamps made out of flat iron 40mm X6mm of suitable length complete all as specified and directed.
S& F energy saving new generation environmental friendly long life versatile pressure die cast aluminum IP 66 security light fittings luminaire with high power LEDs as light source & electronic drivers of capacity 60 watts with pre wired and necessary mounting arrangement & provision of 6 Sqmm three core Copper conductor cable multi stranded from fitting to Junction Box duly crimped by copper lugs and testing complete all as specified and directed.
Supply & Fix thermoplastic cable junction box for street lights of size 200x160x98 mm including terminals for cable connection with IP 66 protection duly fixed in poles with the help of clamps nut bolts arrangement complete all as specified and directed. Make: Hensel /Syntex /Taparia
M & L for cement concrete type C2 1:3:6 40mm graded aggregate for foundation to poles complete all as specified and directed.
M & L for PCC in flooring ,filling and mass concrete type C2, 40mm graded aggregate 1:3:6 for flooring of size 9m X 9m X 0.05m complete all as specified ( for Sub station yard)
M & L for filling of flooring of 40 mm graded coarse stone gravel for flooring of size 9m X 9m X 0.1m complete all as specified (For sub station yard)
Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for foundations etc, or for shafts, wells, cesspits, man holes, pier holes etc not exc 10 sq m on plan and getting out in soft / loose soil complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft / loose soil complete all as specified and directed.
Removing excavated materials (soil) not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Material and labour for sand cushioning for cable protection using clean dry sand complete all as specified and directed.
Supply & Laying well burnt brick , locally available best quality (sub class "B" bricks ) laid in trenches perpendicular to UG Cable protection complete all as specified.
Supply laying & fixing GI Pipe light 80mm dia , ISI marked ,of required length for protection of cables in wall/pole/under road complete including necessary MS clamps , nuts , bolts & washers etc complete all as specified and directed.
S & F GI Tubing light grade of size 50mm dia in protection of cable at road crossing /hard standing/pole protection fixed with clam as per site requirement etc complete all as specified and directed.
S & F Mild steel bars 10mm dia Fe-410-W (Gde.E-250) Part- I quality-A or Fe 290 (Gde - E-165) and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed
HUMERS INFRATECH
MONA GENERATOR SEVICES PVT. LTD.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .