Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
₹14.0 L
EMD Value
₹27,960
Closing Date
22 Apr 2023, 2:00 pmClosed
XEN ED JPDLC RAJOURI
OFFICE OF XEN ED JPDLC RAJOURI
SUPPLY, INSTALLATION, TESTING AND COMMISSIONING FOR CREATION OF 3x100 KVA SUB STATION ALONG WITH HT LT NETWORK AT PHE WSS AT KALSIAN, DABBAR AND TALLAN TAIN NOWSHERA UNDER LANGUISHING SCHEME FOR PHE DIVISION NOWSHERA ON TURNKEY BASIS.
2023_PDD_209083_1
EDR/01 of 2023-24 Dated 01-04-2023
Open Tender
Electrical Works
Turn-key
60 days
RAJOURI
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
XEN ED JPDCL RAJOURI
₹27,960
18 Jul 2023
1 Apr 2023
24 Apr 2023
1 Apr 2023
22 Apr 2023
1 Apr 2023
Amount
11 KV (HT) Line (Note: For detailed specifications please refer attached SBD which forms a part of the tender)
Supply, Loading, Transportation, Insurance, Unloading, Carriage, Delivery at Site including handling, preservation and proper storage at site.
8 Mtr. Long PCC Poles (WL-250KG) (As per recommended IS/REC Standard)
30 mm2 ACSR (Weasel) Conductor with PG clamps of required size (as per site requirement) (As per recommended IS/REC Standard)
GI Channel Cross-arm (75x40x6mm) with GI Angle Braces, GI Pole Top Bracket (50x50x6 mm) including GI Back Clamps of 50X8 mm for fixing Cross arm and pole top bracket without making holes in the ST pole as per REC standard. (As per recommended IS/REC Standard)
11 kV Pin Insulators (polymer) with Pins (10 KN) (As per recommended IS/REC Standard)
11 kV Disc Insulators (polymer) Complete with fittings (45KN) depending upon conductor size. (As per recommended IS/REC Standard)
Galvanised Stay Set with 50*8mm stay clamp, guy insulator (02 Nos), Anchor Plate(200*200*6mm) nut & bolts, 02 No turn buckles 1.8mtr long 16mm diameter solid GS stay rod & 7/3.15 mm dia GI Stranded wire complete.
Galvanized Nuts and Bolts of sizes.
Erection/Installation, Testing and commisioning of material supplied at Sl. No-1.01
Erection of 8 Mtr. Long PCC Poles (WL-250KG) with pit excavation and refilling of pit complete work. (As per recommended IS/REC Standard)
Laying, stringing and binding of 30 mm2 ACSR (Weasel) Conductor with PG clamps of required size (as per site requirement) (As per recommended IS/REC Standard)
Fixing / Erection of GI Channel Cross-arm (75x40x6mm) with GI Angle Braces, GI Pole Top Bracket (50x50x6 mm) including GI Back Clamps of 50X8 mm for fixing Cross arm and pole top bracket without making holes in the ST pole as per REC standard. NOTE: Please refer Pole drawings for details (As per recommended IS/REC Standard)
Fixing of 11 kV Pin Insulators (polymer) with Pins (10 KN) (As per recommended IS/REC Standard)
Fixing of 11 kV Disc Insulator with fitting (polymer) with Pins (45 KN) (As per recommended IS/REC Standard)
Fixing of Galvanised Stay Set with 50*8mm stay clamp, guy insulator ( 02Nos), Anchor Plate(200*200*6mm) nut & bolts, 02 No turn buckles 1.8mtr long 16mm diameter solid GS stay rod & 7/3.15 mm dia GI Stranded wire complete. (As per recommended IS/REC Standard)
Fixing of Galvanized Nuts and Bolts of sizes.
11/0.433 kV Distribution Transformer (Note: For detailed specifications please refer attached SBD which forms a part of the tender)
Supply, Loading, Transportation, Insurance, Unloading, Carriage, Delivery at Site including handling, preservation and proper storage at site of 11/0.433 kV Distribution Transformer.
100 kVA, 11/0.433 kV Distribution Transformer, Energy Efficiency Level-II, Al Wound, oil filled, with LT cable termination box with detachable Aluminium Gland Plate.(As per recommended IS/REC Standard)
8 Mtr. Long PCC Poles (WL-250KG) (As per recommended IS/REC Standard) (2 Poles for Stn Structure & 1 Pole for LT outgoing for each S/Stn)
Gapless Surge Arrestor,9 kV,10 kA, LA with (polymer) housing, Station Type (As per recommended IS/REC Standard)
11 kV, G.O AB Switch , 3-phase, 200A (As per recommended IS/REC Standard)
11 kV, Horn Gap Switch , 3-phase, 200A (As per recommended IS/REC Standard)
GI Channel, GI Cross Arms (100x50x6mm) / (75x40x6 mm) / GI Angles (50x50x6 mm) with 50X8 mm GI Back clamps without drilling/punching holes in the ST poles. (As per recommended IS/REC Standard)
Galvanised Stay Set with 50*8mm stay clamp, guy insulator ( 02Nos), Anchor Plate(200*200*6mm) nut & bolts, 02 No turn buckles 1.8mtr long 16mm diameter solid GS stay rod & 7/3.15 mm dia GI Stranded wire complete. (As per recommended IS/REC Standard).
185mm sq Cable PVC FRLS with Al Thimbles
11 kV Pin Insulators (polymer) with Pins (10 KN) (As per recommended IS/REC Standard)
11 kV Disc Insulators (polymer) Complete with fitting (45 KN) (As per recommended IS/REC Standard)
Galvanized Nuts and Bolts of sizes.
Sub station earthing by GI Pipe 40 mm dia 4 mm wall thickness or GI Rod 20mm, 2.5 mtr long through GI Strip of 50X6 mm for 1 No. Neutral Earthing and through GI Strip of 25X3 mm for 1 No. Strip for LA Earth and 1 No. strip for connecting 2 Nos transformer body Earth, 2 Nos Pole Earth, and 1 No. GO handle Earth (Note: For LA Earth 1 pipe/rod shall be kept separate) with Earthing Insulators, GI Nuts, Bolts and GI Clamps. (As per recommended IS/REC Standard)
Sundry Items/LT Fuse Set with busbar (As per recommended IS/REC Standard)
Erection/Installation, Testing and commisioning of material supplied at Sl. No-3.01
Installation of 100 kVA, 11/0.433 kV Distribution Transformer, Energy Efficiency Level-II, Al Wound, oil filled, with LT cable termination box with detachable Aluminium Gland Plate.(As per recommended IS/REC Standard)
Erection of 8 Mtr. Long PCC Poles (WL-250KG) with pit excavation and refilling of pit complete work. (As per recommended IS/REC Standard)
Installation of Gapless Surge Arrestor,9 kV,10 kA, LA with (polymer) housing, Station Type (As per recommended IS/REC Standard)
Installation of 11 kV, Horn Gap Switch , 3-phase, 200A (As per recommended IS/REC Standard)
Installation of 11 kV, G.O AB Switch , 3-phase, 200A (As per recommended IS/REC Standard)
Fixing / Erection of GI Channel, GI Cross Arms (100x50x6mm) / (75x40x6 mm) / GI Angles (50x50x6 mm) with 50X8 mm GI Back clamps without drilling/punching holes in the ST poles. (As per recommended IS/REC Standard)
Fixing of Galvanised Stay Set with 50*mm stay clamp, guy insulator ( 02Nos), Anchor Plate(200*200*6mm) nut & bolts, 02 No turn buckles 1.8mtr long 16mm diameter solid GS stay rod & 7/3.15 mm dia GI Stranded wire complete. (As per recommended IS/REC Standard).
Fixing / Crimping of 185 mm sq Cable PVC FRLS with Al Thimbles
Fixing of 11 kV Pin Insulators (polymer) with Pins (10 KN) (As per recommended IS/REC Standard)
Installation of 11 kV Disc Insulators (polymer) Complete with fitting( 45 KN) (As per recommended IS/REC Standard)
Fixing of Galvanized Nuts and Bolts of sizes.
Excavation of Earthing Pits of dia = 650 mm and depth= 3000 mm, Installation and fixing of Sub station earthing as per REC approved arrangement/spacing (delta 6.5 m apart ) by GI Pipe 40 mm dia 4 mm wall thickness or GI Rod 20mm, 2.5 mtr long through GI Strip of 50X6 mm 1 no for neutral earthing and 25X3 mm for 1 No. Strip for LA Earth and 1 No. strip for connecting 2 Nos transformer body Earth, 2 Nos Pole Earth, and 1 No. GO handle Earth. (Note: For LA Earth 1 pipe shall be kept separate) with Earthing Insulators, GI Nuts, Bolts and Clamps. Refilled with earth enhancement materials and earthing chamber made of brick masonary with RCC Slab Cover (Proper Earthing Value must be insured) (As per recommended IS/REC Standard)
Fixing of Sundry Items/LT Fuse Set (As per recommended IS/REC Standard)
LT Line (Note: For detailed specifications please refer attached SBD which forms a part of the tender)
Supply, Loading, Transportation, Insurance, Unloading, Carriage, Delivery at Site including handling, preservation and proper storage at site.
8 Mtr. Long PCC Poles (WL-250KG) (As per recommended IS/REC Standard)
30 mm2 ACSR (Weasel) Conductor with PG clamps of required size (as per site requirement) (As per recommended IS/REC Standard)
GI U clamps with LT Shackle insulators (polymer)16KN with GI back clamps to be fixed without drilling/punching of holes on ST poles. (As per recommended IS/REC Standard)
Galvanized Nuts and Bolts of sizes.
Erection/Installation, Testing and commisioning of material supplied at Sl. No 5.01
Erection of 8 Mtr. Long PCC Poles (WL-250KG) with pit excavation and refilling of pit complete work. (As per recommended IS/REC Standard)
Laying, stringing and binding of 30 mm2 ACSR (Weasel) Conductor with PG clamps of required size (as per site requirement) (As per recommended IS/REC Standard)
Fixing of GI U clamps with LT Shackle insulators(polymer)16KN with GI back clamps to be fixed without drilling/punching of holes on ST poles. (As per recommended IS/REC Standard)
Fixing of Galvanized Nuts and Bolts of sizes.
M/S M Y Electrical Constructions
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .