Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.4 LAccepted-AOC | L1 | Accepted-AOC work awarded being L1 firm | |
| 2 | L2₹7.3 L+₹74,776 (11.5%)Rejected-Finance | L2 | Rejected-Finance Rejected being L2 firm | |
| 3 | Rejected-Technical | - | Rejected-Technical Bid non responsive and disqualified | |
| 4 | Rejected-Technical HOUSE NO 2246 SECTOR 15 C CHANDIGARH | NA | NA | 160001 | - | Rejected-Technical Bid non responsive and disqualified |
Tender Value
₹10.0 L
EMD Value
₹20,000
Closing Date
19 Jul 2019, 10:00 amClosed
Executive Engineer Electrical Division HPPWD Mand
Executive Engineer Electrical Division HPPWD Mandi
Construction of 50 Bedded Hospital at Bagsaid, District- Mandi HP SH Providing, Installation, testing and commissioning of addressable fire alarm and PA System therein
2019_PWD_30067_1
PW/MED/TA/NIT/ e-notice/19-20-1810-16 dt 25.06.19
Open Tender
Electrical Works
Item Rate
365 days
Sunder Nagar
Please refer to NIT and bid document
11 documents required · 11 mandatory
₹350
Executive Engineer Electrical Division HPPWD Mand
₹20,000
20 Feb 2020
10 Jul 2019
19 Jul 2019
10 Jul 2019
19 Jul 2019
10 Jul 2019
Amount
Supplying, installation, testing and commissioning of Microprocessor based multi- loop, True Peer-to- Peer net workable Addressable Fire Alarm control Panel with LCD display, QWERTY key pad for programming. The panel should be equipped with sufficient numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 300 alnalog addressable devices. The panel shall work in degrade mode in case of CPU failure. Four access levels, flash EPROM, 240 bolts AC power supply , automatic battery charger , 24 bolts sealed led acid batteries sufficient for 24 hours normal working and 30 mins in alarm conditions as required complete in all respect Make:- Bosch , Honeywell, Siemens.
Supplying, installation, testing and commissioning of Addressable Photoelectric Smoke Detector with sensitivity range of 0.5 to 4.0% obs/ft. The detector shall have multy co-operative sensing technology for faster rseponse and avoide false alarms. The detector shall have twin bi- colour LED for 360 degree viewing. Addressing shall be with user friendly rotary decimal switches. Designed to meet UL 268, 7th Edition. as required complete in all respect Make:- Bosch , Honeywell , Siemens.
Supplying, installation, testing and commissioning of Addressable Manual call Point (Pull down/ Brake Glass Type) . The device shall have an LED which shall blink in normal state & steady on activation to monitor the heath status of the device.as required complete in all respect Make:- Bosch , Honeywell, Siemens.
Supplying, installation, testing and commissioning of Addressable Isolator Module for Isolating short/ dewired / loose circuits with automatic resetting arrangement. Isolator Base can also be proposed , however in that case needs to be consideraed with each detcetor and moudule. The device shall have an LED which shall blink in normal state & steady on activation to monitor the heath status of the device. Addressing shall be with user friendly rotary decimal switches. Module shall be supplied with mounting plate form OEM for ease of installation & maintenance as required complete in all respect.Make:-Bosch , Honeywell, Siemens.
Supplying, installation, testing and commissioning of 8 zone IP based, digital Voice Alarm Controller expandable up to 128 zones. The voice alarm controller should be able to connect directly over Ethernet. It should have functions like the audio playing , zone control , fault monitoring log recording volume control and amplifire switchover. The voice alarm controller should also have the following functions.255 priorities, time schedule broadcasts. capableof amplifier redundency. 8 trigger inputs / outputs as required complete in all respect.Make:- Bosch , Honeywell, Siemens.
Supplying, installation, testing and commissioning of 6W Wall mount with max SPL1M/1W 96dB. Frequency response of 160 Hz-20KHz. The speaker should have tappings at 6W/3W as required complete in all respect.Make:-Bosch , Honeywell , Siemens.
Supplying and fixing of following sizes of PVC conduit along with the accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required compltre in all respect.
Supplying and drawing following size of PVC insulated, heat resistant, flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in existing surface / recessed, Steel/PVC conduit as required.complete in all respect PLAZA / UNITECH / BONTON /KEI / BIYANI / CMI cable make.
2x1.5 Sq. mm.
3x1.5 Sq. mm.
4x1.5 Sq. mm.
5x1.5 Sq. mm.
TARUN FIRE SYSTEM
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .