Loading…
Loading…
Tender Value
₹10.9 Cr
EMD Value
₹10.9 L
Closing Date
27 Apr 2026, 6:00 pmClosed
Similar tender results from the same govt authority in the past 3 years.
Dy.City Engineer
CONSTRUCTION OF COMMUNITY HEALTH CENTER BUILDING AT F.P. NO :- 37, T.P.NO :- 14(SHAHIBAUG) IN SHAHIBAUG WARD, CENTRAL ZONE, AHMEDABAD
296475
18/ 2025-26 , Tender No.624
Open
Miscellaneous Works
Ahmedabad
₹18,000
Municipal Commissioner, Ahmedabad
₹10.9 L
13 Apr 2026
13 Apr 2026
13 Apr 2026
27 Apr 2026
13 Apr 2026
Name of Work:- CONSTRUCTION OF COMMUNITY HEALTH CENTER BUILDING AT F.P.NO :- 37 , T.P.NO
:- 14(SHAHIBAUG) IN SHAHIBAUG WARD, CENTRAL ZONE, AHMEDABAD
Bill of Quantities
I. No. Qty Items Unit Rate Per Amount
Civil Work Estimate
1 Demolition & Dismantling work
Demolition of RCC work using Hydra
Breacker including stacking of servicable
materials and disposal of unservicable
materials with all lead and lift.Removal Of
Existing Building Foundation and Super
Structure If Any.
Demolition of Brick work and stone
masonry including stacking of serviceable
materials and disposal of unserviceable
materials with all lead and lift.(ii) In Cement
Mortar.Removal Of Existing Building
Foundation and Super Structure If Any.
Dismentaling of sheet roofing including
ridges, Hips, Valleys, Gutters etc. stacking
c of serviceable materials and disposal of
unserviceable materials with all lead and
i 10 (i) G.I.sheet roofing. 47.25 Sq.mt
ii 5 (ii) A.C. sheet roofing. 53.55 sq.mt
Dismentling steel work including
d 2000 distempering and stacking the materials 3.63 Kg.
with all lead and lift.
Dismentling doors, windows, ventilators
etc. (wood or steel) shutters including
chowkhats architraves, hold fasts and other
e 2 185.85 Each
attachment etc. complete and stacking
them with in all lead and lift.
(i)Notexceeding 3 Sq.M. in area.
Removing & Scrapping of Old deteriorated
Plaster of any thickness from Masonary /
R.C.C. member including stacking of
serviceable material & disposal of un
serviceable from site of work with all lead &
Dismentaling any type tiled of stone floors
laid in mortar including stacking of
g 50 serviceable materilas and disposal of 47.25 Sq.M.
unserviceable materials with all lead and
Excavation for foundation including sorting
out stacking of useful material & disposing
2 of excavated stuff upto 50 mt. lead. Loose
& Soft soil.Excexuted With Mechanical
a 2125 up to 1.5 mt. depth 115.92 Cu.M.
b 1822 1.5 to 3.0 mt. depth. 128.52 Cu.M.
c 1714 3.0 to 5.0 mt. depth 141.11 Cu.M.
Add extra for Disposing off the excavated
d 100 stuff of above items for lead of (A) 50 m to 17.28 Cu.M.
Add extra for Disposing off the excavated
e 100 stuff of above items for lead of (B) 100 m to 34.56 Cu.M.
Providing and installing cast in situ single
under reamed piles of specified diameter
and length below pile cap, excluding the
cost of Concrete, steel reinforcement but
f including the cost of boring with bentonite
solution and the length of the pile to be
embedded in pile cap etc. all complete.
(Length of pile for payment shall be
measured upto to the bottom of pile cap) :
i 20 400 mm dia. Piles 638.83 Rmt.
ii 20 450 mm dia. Piles 705.03 Rmt.
Extra over single under ream for providing
additional bulbs in under reamed piles,
g under specified diameter excluding the cost
of Concrete, steel reinforcement (only the
nos. of extra bulbs are to be paid).
t 2 400 mm dia. Piles 813.05 Each
ii 2 450 mm dia. Piles 1103.43 Each
Provdg. & laying cement concrete 1:5:10 (1
cement : 5 course sand : 10 hand broken
3a 1 aggregates 40 mm nominal size) and 2492.52 Cu.M.
curing complete, excluding cost of form
work in foundation & Plinth.
Provdg. & laying cement concrete 1:3:6 (1
cement : 3 coarse sand : 6 hand broken
3b stone aggregates 40 mm nominal size) and
curing complete excluding cost of form
554 (A) Foundation and plinth 2976.00 Cu.M.
Supplying of graded hand brocken stone
3c 201 size of 90 mm to 127 mm at site (Rubble or 609.82 Cu.M.
Labour charges for spreading the spouls
mm to 127 mm thick layer good earth filling
in voids correcting the grade & camber
comp. with rolling, watering, incl. preparing
thesurface by brushing for removing all
loose or dirts ect.comp.
Provdg. & laying cement concrete 1:4:8 (1
cement : 4 coarse sand : 8 hand broken
4 5 stone aggregates 40 mm nominal size) and 2653.67 Cu.M.
curing complete excluding cost of form
work in foundation& plinth.
Filling available excavated earth (excluding
rock) in trenches, plinth, sides of
5 4750 foundations etc. in layers not exceeding 20 129.10 Cu.M.
cm. in depth consolidation each deposited
layer by ramming and watering.
Conveyance charges of earth lime,
murrum, building rubbish, manure,
garbage, sludge, excavated rock, fly ash,
aggregate of any kind etc. comp.
a 100 Conveyance charges 0 km to 1 km 46.63 Cmt
b 100 Conveyance charges 0 km to 2 km 60.69 Cmt
c 8000 Conveyance charges 0 km to 5 km 100.44 Cmt
d 8000 Extra For Lead on Above Item Above 5 km 9.26 Cmt
e 8000 Extra For Lead on Above Item Above 6 km 9.26 Cmt
f 8000 Extra For Lead on Above Item Above 7 km 9.26 Cmt
g 8000 Extra For Lead on Above Item Above 8 km 9.26 Cmt
h 8000 Extra For Lead on Above Item Above 9 km 9.26 Cmt
Filling in plinth with sand under floors
7a 15 including watering, ramming, consolidating, 455.63 Cu.M.
compacting and dressing etc. completed.
Filling in foundation and plinth with murrum
7b 225 or selected soil in layers of 20 cm. 286.20 Cmt
thickness including watering, ramming and
consolidating etc. Complete.
Brick work using common burnt clay
building bricks having crushing strength
8 not less than 35 kg/Sq. cm. in cement
mortar 1:6 (1 cement : 6 fine sand)
conventional brick
a 85 (a) in foundation & Plinth 3981.21 Cu.M.
b 526 Super structure Upto Floor Two Level 4253.46 Cu.M.
c 455 Super structure Above Floor Two Level 4293.55 Cu.M.
I.Half brick masonry in common burnt clay
building bricks having crushing strength
note less than 35 Kg/Sq. Cm. in cement
mortar 1:4 (1 cement : 4 coarse sand)
using conventional brick in Super structure
upto floor Four level
a 515 All Floor Level 646.70 Sq.M.
Providing and laying controlled cement
concrete of M-25 Grade and curing
complete, Excluding the cost of form work,
Scaffolding, cost of reinforcement for
reinforced concrete work For any Height up
to any FloorLevel.
a 48 Foundations,Raft,Footings,Mass concrete 4238.04 Cu.M.
b1 2 RCC Retaining wall at All Floor 4519.88 Cu.M.
Tie-Beam, Lintel , Beam- Bracket, Stair
Case & Landing, Coping ,Slab, balcony,
weather shed, loft , any cantilever etc All
Columns,Pillars, posts and struts at All
Providing and laying controlled cement
concrete of M-20 Grade and curing
complete, Excluding the cost of form work,
Scaffolding, cost of reinforcement for
reinforced concrete work For any Height up
to Floor Four Level.
a 10 Foundations,Raft,Footings,Mass concrete 3977.88 Cu.M.
Tie Beam , Lintel , Beam- Bracket , Coping
b1 153 ,landing, Slab, balcony, weather shed, loft , 4460.36 Cu.M.
any cantilever etc at All Floor
c1 3 Column at All Floor 4558.20 Cu.M.
d1 1 Stair Case All Floor 5418.91 Cu.M.
Providing and laying in position Ready
Mixed M250 grade concrete for reinforced
cement conctere work , using cement
content as per approved Design Mix
manufactured in fully automatic batching
plant and transported to site of work in
transit mixer for all lead having continuous
agitated mixer, manufactured as per mix
design of specified grade for reinforced
cement concrete work including pumping of
R.M.C. from transit mixer to site of laying
with all lead and lift, excluding the cost of
centering shuttering finishing and
reinforcement including cost of admixtures
in recommended proportions as per IS:
9103 to accelerate/ retard setting of
concrete, improve workability without
impairing strength and durability as per
direction of the Engineer - in charge.
Without Fly Ash (Min cement level as per
latest IS 456 shall be maintained) (Cement
Providing and laying in position Ready
Mixed M200 grade concrete for reinforced
cement conctere work , using cement
content as per approved Design Mix
manufactured in fully automatic batching
plant and transported to site of work in
transit mixer for all lead having continuous
agitated mixer, manufactured as per mix
design of specified grade for reinforced
cement concrete work including pumping of
R.M.C. from transit mixer to site of laying
with all lead and lift, excluding the cost of
centering shuttering finishing and
reinforcement including cost of admixtures
in recommended proportions as per IS:
9103 to accelerate/ retard setting of
concrete, improve workability without
impairing strength and durability as per
direction of the Engineer - in charge.
Without Fly Ash (Min cement level as per
latest IS 456 shall be maintained) (Cement
Drilling suitable holes in reinforced or plain
cement concrete with power driven drill
machine to a minimum depth of 80mm upto
250mm in RCC beams, lintels, columns
and slabs to introduce steel bars for
sunshades/balconies including fixing the
steel bars in position using Hilti Chemical
HY200-R but excluding the cost of
reinforcement, all complete as per direction
of Engineer-In-Charge.
8 mm Dia in 80 mm Deep & 12 mm Dia
10 mm Dia in 100 mm Deep & 14 mm Dia
12 mm Dia in 120 mm Deep & 16 mm Dia
16 mm Dia in 160 mm Deep & 20 mm Dia
d 90 608.63 Each
20 mm Dia in 200 mm Deep & 25 mm Dia
25 mm Dia in 250 mm Deep & 32 mm Dia
Providing and laying controlled cement
concrete 1:2:4( 1cement : 2 coarse sand :
Graded stone aggregate 20 mm nominal
size ) and curing complete, Excluding the
cost of form work and reinforcement for
reinforced concrete work in:
a 4 Foundations, footings, base of 3923.53 Cu.M.
columns,grade slab and mass concrete.
slab, landing shelves, Balconies, lintels,
b 1 beams, girders, and cantilever, up to aany 4012.47 Cu.M.
P/A Trimix with dewatering machine and
floater machine on constructed R.C.C. work
c 1635 54.00 Sqmtr
incl. cost of machine and labour etc. comp.
Making 15 mm Groove in R.C.C work on
road and filling it with poly sulfied selant
and finished it good incl. all labour charges
etc. comp. as directed
Providing and laying and fixing 25 mm thick
expansion joint by hydrocell semi rigid UV
e 14 resistance with high performance laminated 738.13 Sqmt
closed cell polythene foam joint filler in
sheet foam as directed, etc. complete.
Providing form work in ordinary timber
planking so as to give a rough finish
including centering, shuttering, strutting and
propping etc. height of propping and
centering below supporting floor to celling
not exceeding 4 M & removal of the same
for in situ reinforced or plain concrete work
a 891 (A) Foundation, footings, bases of columns 171.68 Smt
etc. and mass concrete.
b 3119 (B) Flat surface such as soffits of slabs, 252.00 Smt
landing and the like
c 1443 (C) Vertical surfaces such as walls (any 229.95 Smt
thickness) partitions.
(D) Columns, pillars, posts & struts.
d 2228 (1) Square, rectangular, polygonal in plan 297.68 Smt
e 20 (2) Circular or curved in plan. 422.10 Smt
(H) (1) Sides and soffits of beam,
haunchings cantilevers, girders,
bressumers, Coping and lintels not
exceeding 1 M in depth.
(2) Sides and soffits of beam, haunchings
g 10 cantilevers, girders, bressumers and lintels 259.88 Smt
exceeding 1 M in depth.
h 130 (L) chullah hoops, weather sheds, chhajas, 155.78 Smt
carbels etc including edges.
(M) Staircase with-sloping or stepped
i 400 soffits incl. risers & strings excluding 242.55 Smt
Extra for additional height of propping and
centering where the height of propping and
centering exceeds 4 .O M between
j 100 supporting floor to ceiling including 386.48 Smt
temporary brick or stone pillars for
supporting as required. (i)Height more than
4.0 M.and upto 5.0 M.
Providing T.M.T Fe 500D bar reinforcement
for R.C.C. work including bending, binding
and placing in position complete up to any
a 262735 All Floor Level 75.46 Kg.
Providing and laying polished Kota stone
slab (Polished / River Finish, Green colour )
flooring over 20 mm. (average) thick base
14 60 of cement mortar 1:6 (1 cement : 6 coarse 982.83 Sq.M.
sand) or lime mortar 1:1.5 laid over and
joined with grey cement slurry including
rubbing and polishing complete.25 mm th.
Providing and laying polished Kota stone
slab 25 mm. thick in Platform ,Riser of Stair
, Skirting, Tread , dado and pillars laid on
10 mm. thick cement mortar 1:3 (1 cement :
3 coarse sand) jointed with grey cement
slurry including rubbing and polishing and
MAking groove where it is Required etc.
Providing and laying white/Colur glazed
tiles 6 mm thick in flooring treads of steps
and landing laid on a bed of 12 mm thick
cement mortar 1:3 (1 cement : 3 coarse
sand) finished with flush pointing in white
Providing and layingWhite / Colour glazed
tiles of size 600 mmx300mm x 8 mm /
mmx 450mm x 8 mm in skirting, risers of
steps, Floor and dedo on 10 mm. thick
cement plaster 1:3 (1 cement : 3 coarse
sand) and jointed with white cement slurry.
Providing and laying marble stone slab
flooring over 20 mm. (Average) base of
cement mortar 1:6 (1 cement: 6 coarse
18 2 sand) or L.M. 1:1.5 laid and jointed with 2194.63 Sq. M.
grey cement slurry including rubbing and
polishing complete: (A) Marble slab 25 mm.
Providing and laying Vitrified tiles 8 to
mm thick , 24'' x 24'' in flooring treads of
steps and landing laid on a bed of 12mm
thick cement mortar 1:3 (1-cement : 3-
coarse sand) finishing with flush pointing in
Providing and laying Vitrified tiles 8 to
mm thick , 24'' x 24'' in skrting risers of
19b 4100 steps and dedo on 10mm thick cement 1130.15 Sq. M.
plaster 1:3 (1cement : 3-coarse sand) and
jointed with white cement slurry
P & L 24" x 24" vitrified 8 mm thick tile
20 mm (average) base of cement mortar
1:6 ( 1cement: 6 coarse sand) on new
surface or fixing on existing flooring by
adhesive material including dismentaling of
existing flooring and jointed with color
cement slurry including finised with flush
pointing & cleaning the surface etc.
complete for Antiskid
Providing and Fixing 18 mm thick concrete
base exposed brick cladding including
19d 68 surface waterproffing, polymer modified tile 3574.35 Sq.M.
adhesive and polymer modifies tile grout (
grey / white) with neccesary scafolding etc
compl. As per direction of engg. Incharge.
Providing and Laying Tactile Tile (For
Vision Impaired Persons as per
Strandards) of Size 300x300x9.8 mm
Having with Water Absorption less than
0.5% and Confirming to is:15622 of
Approved Make in all Colours and Shades
in for Outdoor floors such as footpath,
Courtyard, Multi models Location etc., laid
in 20 mm Thick Base of Cement Mortar 1:4
( 1 Cement : 4 Course Sand) in all Shapes
& pattern including Grouting the Joints with
White Cement mixed with Matching
pigment etc. Complete as per Direction of
Engineer-in-charge.
Providing and laying Ceramics tiles 6 to
mm thick in flooring, treads of steps,
20 10 landing and dedo on 12 mm. thick cement 960.47 Sq. M.
plaster 1:3 (1 cement : 3 coarse sand) and
jointed with white cement slurry.
Providing & Laying 18 mm thick Mirror
polish granite For flooring , counter , stair -
riser , tread , skirting , dedo , Jambs etc.
machine cut or chiselled on bed of cement
mortar 1:1 pointing with neat cement slurry
incl. moulding, Making grooves where it is
required etc. comp. as per instruction of
engineer in charge.
Provdg. 20 mm. thick Finish / Mala cement
plaster in single coat on fair side of brick /
22a concrete walls for interior plastering upto
any Floor level and finished even and
smooth in C.M.1:4.
i 3835 All Floor Level 190.58 Sq.M.
Provdg. 20 mm. thick Finish / Mala cement
plaster in single coat plastering on ceilings,
b Beam side and sofits of stairs upto any
Floor level and finished even and smooth in
i 3699 All Floor Level 215.15 Sq.M.
Providing & fixing 23 cm wide chicken
c 1288 mesh jali with nails & then application of 15 292.59 Sq.mt
mm plaster on R.C.C. & masonary joints as
per dir. of engg. In charge.
Providing and mixing water proofing
materials in cement mortar in proportion
d 250 recommended by the manufacturer. etc. 48.77
comp. as per instruction of engineer in
Providing 20 mm th. Double coat Sand face
/ Mala Cement Plaster on Walls upto any
Height Above Ground level consisting of
23a 2902 mm th. Backing coat of C.M. 1:3 ( 1 cement 297.68 Sq.M.
: 3 Ssand ) & 8 mm th. Finishing coat of
C.M. 1:1 ( 1 cement : 1 sand ) ets.
White / Color washing with lime on
undecorated wall surfaces (two coats) to
24a 100 give an even shade including thoroughly 12.29 Sq.M.
brooming the surface to remove all dirt,
dust mortar drops and other foreign matter.
Providing & Applying 3 mm thick External
Wall Rustic Type Texture as per Design &
Make as Approved by Consultants /
Engineer in Charge. Work Includes All
Necessary Scaffolding Work upto Any
Finishing walls with Acrylic Smooth exterior
paint of required shade :New work (Two or
24 c 2850 more coat applied @ 1.67 ltr/10 sqm over 174.97 Sq.M.
and including priming coat of exterior
primer applied @ 2.20 kg/10 sqm)
P./L. METALIC HERITAGE SURFACE
Providing and fixing of HERITAGE textured
homogeneous wall finishing system from
BAKELITE HYLAM LTD or equivalent
make consisting of a two component
system of (25 kgs per Pack) made of 92%
silica particles coated with fade resistant
pigments, 100% acrylic polymer bonding
agent (5kgs per pack) with the applied
thickness of the coating being between
0.8mm-1.2mm to be applied on acured,
smooth level plaster without keying, as per
the shades/combinations approved, as per
the manufacturer directions, for usages,
tobe applied by an approved applicator of
the manufacturer, as per the directions /
supervision of the engineers in charge, all
complete. Includes All Necessary
Scaffolding Work upto Any Height.
Wall Painting (two coats) with plastic
emulsion / Oil paint of approved brand and
manufacture and of shade required on
undecorated wall surfaces to give an even
shade, over and including a priming coat
25a 5800 with alkali resistance primer of approved 78.44 Sq.M.
brand and manufacture after thoroughly
brushing the surface free from mortar
droppings, and other foreign matter and
also including preparing the surface even
and sand -papered smooth
Extra over above item for every subsequent
b 5800 coat of of wall painting with plastic emulsion 33.39 Sq.mt.
/ Oil paint of approved brand.
Applying two coats of Birla (white cement
based) or Asian (acrylic lapy-putty) or
equivalent & two coats of primer of
approved brand and manufacture on new
wall surface to give an even shade
including thoroughly brushing the surface
free from mortar dropping and other foreign
matter and sand papered smooth.
Providing & Laying & Jointing glazed
stoneware pipes incl. excavation up to
mt.,refilling, trasporting the pipe to work
site, unloading, lowering in trenches, laying
and jointing the pipes in c.m. 1:1 incl. all
26 jointing materials such as cement, sand,
hemp, bitumen as dire. testing the pipe line
to a head of 1.5 mt. and hydraulic test as
dire incl. watering trenches, spreading , and
carting away of surplus earth within
mt.lead as dire. etc. comp.
a 150 23 cm dia. 344.64 Rmt
Providing & Laying & Jointing glazed
stoneware pipes incl. excavation up to
mt.,refilling, trasporting the pipe to work
site, unloading, lowering in trenches, laying
and jointing the pipes in c.m. 1:1 incl. all
jointing materials such as cement, sand,
hemp, bitumen as dire. testing the pipe line
to a head of 1.5 mt. and hydraulic test as
dire incl. watering trenches, spreading , and
carting away of surplus earth within
mt.lead as dire. etc. comp.
b 25 15 cm dia 211.05 Rmt
c 15 10 cm dia. 288.23 Rmt
Constructing brick masonry chamber for
under ground C.I. Inspection chamber and
bends with bricks having croshing strength
not less than 35 Kg. Cm2 in C.M. 1:5 C.I.
cover with frame (Lightduty) 455mm x
mm intenal dimensions total weight of
cover with frame to be not less than 38 Kg.
(Wt. of cover 23Kg.) and Wt. of frame
27 18 15Kg.) (R.C.C.top slab with 1:2:4 mix (1- 3863.85 No.
cement:2-coarse sand:4-graded stone
aggregate 20mm size) foundation concrete
1:5:10 inside plaster 15 mm thick with
cement mortar 1:3 finished smooth with a
floating coat of neat cement on walls and
bed concrete etc. complete.(i) Inside
dimensions 455 mm x 610 mm and up to
Constructing Manhole with R.C.C. top slab
in 1:2:4mix (1-cement: 2-coarse sand:4-
graded stone aggregate 20 mm nominal
size) foundation concrete 1:3:6 mix (1-
cement:3-coarse sand:6-Brick bats
40+50mm size) inside plastering 15mm
thick with Cement Mortar 1:5 (1-Cement:5-
coarse sand) finished with a floating coat of
neat cement and making channels in
cement concrete 1:2:4 mix (1-Cement:2 -
Coarse sand:4-stone aggregate 20 mm
28 a 4 nominal size) finished smooth complete 19139.07 No.
including curing and festing (i) Inside size
900mm x 1200mm and up to 1.5M. deep
including C.I. cover with frame size 560 mm
diameter total weight of cover and frame to
be not less than 128kgs. (Wt. of cover
64Kg. and Wt. of frame 64Kg.) (A) With
mm thick walls of brick masonry using brick
having crushing strength not less than
35Kg./Sq.cm. in Cement Mortar 1:5 (1-
Cement: 5-Coarse sand) (2)B type depth
up to 1.50 Metre
Providing and fixing white vitreous china
flat back or wall corner type lipped front
urinal basin of 340x280x470 mm sizes
respectively with standard flush pipe,
Waster Pipe, Waste Coupling, PVc
Connection and G.I clamps complete,
including painting of fittings and brackets,
cutting and making good the walls and
floors wherever required : Cera Model No.
S4020103 or Equivalent
Providing and Fixing of C.P. Brass BIB
Cock of 15 mm Dia of Jaquar make
b 60 florentine series model no. 5047n or 1564.17 No.
equivalent make with all necessary fittings.
as approved by Engineer - in - charge.,
Providing and fixing brass screw down
Angle stop tap.(A) 15mm dia. Of Jaquar
c 60 make florentine series modelno. 5053n or 1160.57 No.
equivalent make with all necessary fittings.
as approved by Engineer - in - charge.,
Providing and fixing C.P. brass shower
d 10 rose with 15mm or 20mm inlet Shower 279.37 No.
Arm.(A) 100mm dia. Each
Provding and Fixing of autoclosing
pressmatic pillar cock / bib cock with all
necessary fittings of Polished Bright
e 10 Chrome Finish of Jaquar make model no. 3280.52 No.
031L65 or equivalent make as approved by
Engineer in Charge. Rate including of cost
of labour, material etc. in complete manner.
Providing and Fixing of C.P. Brass Two
Way Bib Cock of 15 mm Dia of Jaquar
f 32 make model no. 041kn or equivalent make 1411.58 No.
approved make with all necessary fittings.
as approved by Engineer - in - charge.,
Providing and Fixing of C.P. Brass urinal
Valve Auto Closing System With Full Built
in Control Cock & Wall Flange of 15 mm
g 20 Dia of Jaquar make model no. 077 or 2568.08 No.
equivalent make approved make with all
necessary fittings. as approved by
Engineer - in - charge.,
Providing and Fixing of C.P. Brass Pillar
Cock Auto Closing System with Elbow
Operated Extended Lever of 15 mm Dia of
h 30 Jaquar Make Model No,031 MED or 3723.48 No.
Equvalent Approved Make & Model with all
necessary fittings. as approved by
Engineer - in - charge.,
Provdg. & laying S.W. Gully trap with C.I.
garting brick masonry chamber & water
30 15 tight C.I. cover with frame of 300 mm x 300 1234.57 No.
mm size ( inside) with standard weight.
sqare mouth trap size 150 x100 mm P trap
Providing erecting and fixing double coated
31 2000 ISI water tank of required capacity each 3.91 Litre
with all necessary fittings and connection
etc. complete on terrace
Extra rate over item of excavation of earth
for excavation of asphalt pavement/RCC of
thickness up to 0.20 meter including
32 20 demolishing the asphalt carpet, metal, 71.43 Sq.M.
soiling / cutting Reinforcement etc.comp.
with stacking the material as directed.-up to
0.20 meter thickness
Providing and fixing PVC SWR Nahni trap
IS 14735 for drain - 100 mm diameter with
33 55 following nominal diameter of self cleansing 565.43 No.
design with C.I scread down or hinged
grating including the cost of cutting and
making good the walls.
Provdg. And fixing Concealed / Open to
wall, ceiling & floor in true line and level
UPVC pipe Schedule- 40 of make as
approved by engg. incharge. pipe shall be
fix on wall with the help of clamp at every
34a twi meter center to center of shall be
concealed as directed in cluding
neccesarry fitting etc. in cluding testing of
pipe and jointd and fixing the same with
adhesive solvent , including cost of all
materials of following nominal bore
ii 650 25 mm 90.93 Rmt
iii 15 32 mm 117.97 Rmt
iv 240 40 mm 146.65 Rmt
Providing and fixing concealed center point
to wall ceiling & floor CPVC (SDR 13.5)
PIPE having National Sanitation
34b Foundation (NSF) seal for potable water of
following dia. nominal bore tube fittings and
clamps including making good the wall,
ceiling and floor etc. complete
i 5 15 mm 165.21 Rmt
ii 5 20 mm 202.97 Rmt
iii 5 25 mm 247.25 Rmt
iv 5 32 mm 330.36 Rmt
v 5 40 mm 437.66 Rmt
vi 5 50 mm 647.30 Rmt
Provdg. And fixing to wall ,ceiling and floor
10.00 kg. F/Sq.Cm2 working pressure
polythelene pipes of the following outside
35 diameter, low, density, complete with
special flange compression type fittings,
wall clips etc. making good wall ceiling and
b 130 (A) 75mm dia 274.68 Rmt
c 400 © 110 mm dia 332.91 Rmt
Providing and fixing water closet squatting
36 8 Pan ( Indian type W.C. Pan) size 580mm 1351.15 No.
(A)VitreousChina. (I)Long pattern = White
colour with Trap and Pair of Foot Rest
Providing and fixing white vitreous china
extended wall mounting water closet of
Cera Make S1043101 Carat Model Or
Equivalent Model With EWC Soft Close
Seat Cover, Chair Bracket, nuts, bolts and
gasket etc complete.
Providing and fixing chromium plated brass
b half trun flush cock of approved quality
including fixing in pipe line etc. complete.
Providing and fixing Health Faucet of
Jaquar make model no. 573 oe equivalent
c 30 make as approved by engg. In charge with 1543.36 No.
flexible tube upto 1 metre long etc.
Providing and fixing 24"x18"x8" Carysil
Elegance or Equivalent Make of Single
38a 2 Bowl Sink S.S. Matt Finish With Waste 7960.60 No.
Coupling, Waste Pipe,etc. cutting and
making good the walls wherever required.
Providing and fixing Under counter Wash
basine including 15 mm C.P. Brass Pillar
tap, 32 mm C.P. Brass Waste of Standard
make, Include All Accessaries, Cutting &
Making good the wall / granite Wherever
Required in White Color : Model S2030101
of Cera Clair Series or Equivalent make
Waash basine of size : 520x450 mm
Providing and fixing Wall Hung wash basin
Including 32 mm C.P. brass waste of
standard pattern, Include All Accessaries,
c 15 cutting and making good the walls / granite 3825.20 No.
wherever require:In White Color : Cera
Cadal Or Equivalent Make Wash basin of
size 515 x 410 mm
Providing and Fixing White Vitreous China
Laboratory Sink with C.I. Brackets, C.P.
Brass Chain with Rubber Plug, 40 mm C.P.
Brass Waste and 40 mm C.P. Brass Trap
d 4 with Necessary C.P. Brass Unions 5581.19 No.
Complete, Including Painting of Fittings and
Brackets, Cutting and Making Good to Wall
/ Granite Wherever Required: Size 600 x
Provdg. & fixing 600mm x 450 mm
Bevelled edge mirror of superior glass
39a 35 mounted of .6 mm th. A.C. sheet or 825.48 No.
plywood sheet and fixed to wooden pluge
with C.P. brass screws and washers.
Provdg. & fixing C.P..Brass towal rail
complete with C.P. brass brackets fixed to
wooden plugs with C.P. Brass screws.(600
mmx 20 mm size)
Providing and fixing ball valve (brass) of
41 approved quality, High or low pressure,
with plastic floats complete :
i 14 15 mm dia 886.22 No.
ii 1 20 mm dia 1099.94 No.
iii 40 25 mm dia 1552.93 No.
iv 20 40 mm dia 3312.60 No.
v 5 50 mm dia 4613.48 No.
42a Providing and fixing Full Way valve (HEX)
with wheel of approved quality :
i 6 15 mm Full Way valve (HEX) 1461.17 No.
ii 1 20 mm Full Way valve (HEX) 1924.61 No.
iii 12 25 mm Full Way valve (HEX) 2535.55 No.
iv 1 32 mm Full Way valve (HEX) 3377.64 No.
v 10 40 mm Full Way valve (HEX) 4661.10 No.
vi 5 50 mm Full Way valve (HEX) 6675.14 No.
Providing and Fixing of C.P.Brass Pillar
Cock of 15 mm Dia of approved make with
all necessary fittings. as approved by
Engineer - in - charge.,
b 10 Providing fixing of SS grab bar with all 1937.24 No.
hardwares for Physically Handicap toilet.
Providing and laying integral cement based
water proofing treatment including
44a 800 preparation of surface as required for 1150.48 Sq.M.
treatment of roofs, balconies, terraces etc
consisting of following operations:
(a) Applying a slurry coat of neat cement
using 2.75 kg/sqm of cement admixed with
water proofing compound conforming to IS.
2645 and approved by Engineer-in-charge
over the RCC slab including adjoining walls
upto 300 mm height including cleaning the
surface before treatment.
(b) Laying brick bats with mortar using
broken bricks/brick bats 25 mm to 115 mm
size with 50% of cement mortar 1:5 (1
cement : 5 coarse sand) admixed with
water proofing compound conforming to IS
: 2645 and approved by Engineer-in-charge
over 20 mm thick layer of cement mortar of
mix 1:5 (1 cement :5 coarse sand )
admixed with water proofing compound
conforming to IS : 2645 and approved by
Engineer-in-charge to required slope and
treating similarly the adjoining walls upto
300 mm height including rounding of
junctions of walls and slabs.
(c) After two days of proper curing applying
a second coat of cement slurry using
kg/ sqm of cement admixed with water
proofing compound conforming to IS :
and approved by Engineerin- charge.
(d) Finishing the surface with 20 mm thick
jointless cement mortar of mix 1:4 (1
cement :4 coarse sand) admixed with water
proofing compound conforming to IS :
and approved by Engineerin- charge
(e) The whole terrace so finished shall be
flooded with water for a minimum period of
two weeks for curing and for final test.“All
above operations to be done in order and
as directed and specified by the Engineer-
in-Charge :and shall be guaranteed for
minimum period of 10 years after handing
over the completed building by the main
contractor to be finished as directed.
Stamp paper guarantee 10 years to be
furnished before receiving any payment
from the client.
With average thickness of 120 mm and
minimum thickness at khurra as 65 mm.
Providing and laying broken chine mosaic
flooring for terrace using 12 mm to 20 mm
broken pieces of glazed tiles to be laid over
cement mortar 1:3 to plain or slope and to
b 800 be tempered to bring mortar creme out upto 739.89 Sq. M.
surface using white cement including
rounding off junctions and extending them
upto 15 cm along the wall,clearing with
water and oxalic acid etc. as directed.
Providing and applying fibre reinforced
elastomeric liquid water proofing
membrane with resilient acrylic polymers
having Sun Reflectivity Index (SRI) of
on top of concrete roof in three coats
@10.76 litre/ 10 sqm. One coat of self-
priming of elastomeric waterproofing liquid
(dilution with water in the ratio of 3:1) and
c 490 two coats of undiluted elastomeric 562.40 Sq. M.
waterproofing liquid (dry film thickness of
complete application/system not less than
500 microns). The operation shall be
carried out after scrapping and properly
cleaning the surface to remove loose
particles with wire brushes, complete in all
respect as per the direction of Engineer-in-
Filling in Sunken Portion with good Quality
Aerated light weight concrete block having
crushing strength not less than 35 kg/sqcm
and where directed by the Architect /
Engineer-in-charge, in sunk in layer.
including watering, ramming where it is
required etc. complete, as directed by the
Architect / Engineer-in-charge .
Providing and laying cement concrete
flooring ( I.P.S.) 1:2:4 (1-cement : 2-coarse
sand : 4-graded stone aggregate 20mm
nominal size) laid in one layer and finished
with a floating coat of neat cement. (B)
Providing and fixing M.S. grills/ Gate of
required pattern to wooden/ Granite frames
of windows etc. with M.S. flats at required
spacings and frame alround, square or
round bars with round headed bolts and
nuts or by screws all complete as per the
structural designs and directions of
Engineer in charge
Providing & Fixing Structural steel work (
Confirming to IS 4923-1997) riveted, bolted
or welded in builtup for all type sections, in
framed work, including cutting, hoisting,
fixing in position and applying a priming
coat of approved steel primer all complete
as per the structural designs and directions
of Engineer in charge
Applying priming coat over new steel and
other metel surface after and including
preparing the surface by throughly
c 600 cleaning, oil, grease, dirt and other foreign 34.34 Sqmt
matter and scoured with brushes fine steel
wood, scrapers and sand paper with ready
mixed priming paint brushing red lead.
Painting two coats (excluding priming coat)
on new steel and other metal surface with
enamel paint, brushing, interior to give an
d 600 even shade including cleaning the surface 86.94 Sqmt
an even shade including cleaning the
surface of all dirt, dust and other foreign
Providing & Fixing 1.2 mm Thick S.S.-304
Grade 900 mm to 1150 mm High S.S.
Railing having Hand Rail Member of 50 mm
Dia., 4 No. of Horizontal Pipe of 16 mm
e 120 Dia. & Baluster Suppprt of 40 mm Dia. At 2270.21 R.Mtr.
Every Third Step as per Detail Given. Rate
Includes All Work Complete as per
Description & as per Direction of Engg. in
Providing and fixing in position collapsible
steel shutters with vertical channels
20x10x2 mm braced with flat iron diagonals
20x5 mm size with top & bottom rails of T-
iron 40x40x6 mm with 38 mm dia. Steel
pulleys complete with bolts , nuts , locking
arrangement , stoppers , handles including
applying a priming coat of red lead paint.
Providing corrugated 0.80 mm (22 gauge)
thick G.I. sheets roofing fixed with
galvanized iron ‘J’ or ‘L’ hook bolts, and
b 5 nuts 8 mm. dia with bitumen and G.I. limpet 719.93 Sq.M.
washers filled with white lead complete
excluding the cost of purlines, rafters and
Providing valleys 900 mm. overall in plain
1.6 mm. thick G.I. sheet Class – 3 fixed
c 2 with ‘J’ or ‘L’ hook bolts and nuts 1042.78 Sq.mt.
galvanized from ‘J’ or ‘L’ hook bolts and
bitumen washers complete.
Providing and fixing rolling shutters of
approved make made of 80 mm wide M.S.
laths inter-locked together through their
entire length and jointed together at the
ends by end locks mounted on specially
48a 9 designed pipe shaft with bracket plates, 3468.72 Sq.M.
guide channels and arragements for inside
and outside locking with push-pull
operation including the cost of hood cover
and spring etc. complete.(A) Shutters
having width below 3.5 M.
Providing and fixing rolling shutters of
approved make made of 80 mm wide M.S.
laths inter-locked together through their
entire length and jointed together at the
ends by end locks mounted on specially
b 12 designed pipe shaft with bracket plates, 4450.51 Sq.M.
guide channels and arragements for inside
and outside locking with push-pull
operation including the cost of hood cover
and spring etc. complete. (B) Shutters
having width 3.5 M. and above
Providing and fixing 27mm domal Series -
1.2 mm Th. Alluminium Section Three track
Sliding window With Metalic Powder
49a 194 Coating and 4 MM Clear Glaas(Non Tuffen) 6373.85 Sq. M.
Include All Accessaries and Fixture etc.
complete as per the direction of Engineer-
Providing and fixing 27mm domal Series -
1.2 mm Th. Alluminium Section Two track
Sliding window With Metalic Powder
b 12 Coating and 4 MM Clear Glaas(Non Tuffen) 4999.10 Sq. M.
Include All Accessaries and Fixture etc.
complete as per the direction of Engineer-
ALUMINIUM DOOR WORK
Providing and fixing Aluminium Door work
(Single Shutter OR Double Shutter with or
without fix glass) made from Jindal or
equivalent make Powder Coated (50
micron pure polyester coating ) ,aluminium
section frame built up standard tubular and
other section of approved make confirming
to IS 733 and IS 1285 , member size with
shutters of horizontal member , vertical
member Confirming to IS733 and IS
fixed with rawl plug abd screws or fixing
clips or with expansion hold fasteners
including necessary filling up of gaps at
junctions at top bottom and sides with
required PVC/ Neoprene felt, 8/12 mm
toughened glass of approved make etc.
Aluminum sections shall be smooth, rust
free, straight.mitred and jointed
mechanically wherever required including
Door Hardware such as cleat angles
aluminum snap beading for glazing
/paneling, CP Brass/ Stainless steel
screws, Stoppers, heavy duty floor hing,
S.S. Hinges, aldrop , Locking system,
heavy duty Floor Springs, Pivot and fixtures
and transparent silicon sealant glass fixing
to frame as per details all complete as per
architectural drawings and the direction of
Engineer in Charge. rate incl. all type of
alumnium sections for doors as per the
detail Architectural dwg.
Providing and fixing standared extruded of
alluminium section of size 63 mm x
mm x 1.2mm (Section:2434, @
50 a 20 Wt.0.643Kg/mt ) with colour anodized 1163.92 Sq. M.
alluminium frame for ventilation with 5 mm
thick frosted glass as details etc complete
for Ventilation
Providing and fixing standared extruded of
alluminium section of size 63.50 x 38.10 x
1.95 mm ( Section no: 4605, @Wt
50 b 27 Kg / Rmt with colour anodized alluminium 1509.90 Sq. M.
frame with 5 mm thick transparent bronze
colour tinted float glass as details etc
complete for Fix window.
Providing Fixing 1.2 mm thick Alluminium
Section Partition -Fully Glazed / Partly
Panelled Partly Glazed / Fully Panelled
Having Size of Section of 2.1/2 x 1.1/2 with
4 mm Compact Sheet / 5 mm thick Glass
Fixing with 4 mm thick EPDM Rubber etc.
Complete as per Direction of Consultant /
Providing Fixing 1.2 mm thick Alluminium
Section Partition Door -Fully Glazed / Partly
Panelled Partly Glazed / Fully Panelled
frame Having Size of Section of 2 .1/2 x
.1/2 and Door Section Having Size of Tips
Vertical 1 .3/4 x 1 .3/4, Top Rail 4 x
50d 4 .3/4, Middle Rail 1 .3/4 x 1 .3/4, Bottom 4061.77 Sq.mtr.
rail 4 x 1 .3/4 with 4 mm Compact Sheet /
5 mm thick Glass Fixing with 4 mm thick
EPDM Rubber Including Lock, Handle,
Door Closer, Door Stoper, Stopper etc
Complete as per Direction of Consultant /
Providing and fixing Structural Glazing with
using the 17 Micron anodised of approved
colour alluminium section as transium,
mullium of size 63mm x 38mm x 2 mm with
using 6 mm thick reflective structural glass
of approved make, colour / Tinted,
toughned and shade and fixed with silicone
sealant and spacer tap and at corner
sealed neoprene foam dust and Air sealed
gasket mirred including scaffolding,
cleaning of glass etc.complete at all heights
anf lifts with all necessary fitting and
fixtures, anchore fasteners, necessary M.S.
or Aluminium brackets, suitable design for
openable or sliding window as per
Architectural drawing and as directed by
Engineer-in-charge. Grooves between the
glasses to be filled with sealant of Dow
corning - structural sealant 995, weather
sealant 789. The entire facade should be
water proof. The mullions are to be
connected to bracket by SS-304 nut bolts.
Measurement shall be given as per actual
execution of the work. (Rate are included
providing & fixing of MS structure steel
work wherever Required)
Providing and fixing ISI marked 35 mm
thick flush door shutters conforming to IS :
2202 (Part I) decorative type, core of block
board construction with frame of 1st class
hard wood and well matched teak 3 ply
veneering with vertical grains or cross
bands and face veneers on both faces of
shutters with 1.00 mm thick Decorative
Laminated Sheet on both faces of shutters
including ISI marked Stainless Steel butt
hinges, bright /matt finished 125 mm
Stainless Steel handles of approved quality
& make, ISI marked oxidised M.S. door
latches / Aldrop Conforming to IS:5930 with
necessary screws etc. complete as per
direction of Engg. incharge.
Providing wood work in frames of Doors,
windows cleare story windows and
othersimilar works wrought, framede and Cu.Decim
fixed in position. (A) Indian Teak Wood
Providing & Fixing Fluted Glass Partition
and Door Using 16 x 45 mm Powder
Coated Alluminium Section with 8 mm
Thick Fluted Toughened Glass Including
Lock, Handle, Floor Spring, Connector,
Silicon and All Other Accessaries including
Making Pit etc Complete as per Direction
of Consultant / Engg.incharge.
Providing & Fixing Profile Shutter Using
x 45 mm Powder Coated Alluminium
Section with 5 mm Thick Fluted Toughened
d 220 Glass, Concealed Handle Section and 14838.39 Sq.mt.
Hinges Including All Accessaries etc
Complete as per Direction of Consultant /
Providing and fixing of approved make
Clean room doors. Doors should be
finished in Powder Coating with thickness
of 60 microns approx. in desired Shades.
The manufacturer company must be ISO
9001-2015 certified. The door frame is a
Single rebate profile of minimum size
105mm X 57 mm made out of 1.2 mm
minimum thick galvanized steel sheet. The
frame is finished with Powder Coating in
desired Shade. Frame having provisions
e 75 and necessary Arrangement for receiving 10705.16 Sq.mt.
appropriate hardware like lock and hinges.
The door leaf shall be a minimum 46mm
thick fully flush double skin door with vision
lite of DGU Glass of Size 300 x 300 mm x
mm . The door leaf shall be manufactured
from 1.0 mm thick galvanised steel sheet.
Door Includes SS 304 Hinges, D type Pull
Handle-SS 304, Mortise Deadlock with
cylinder - 70mm both side key , Flush type
tower bolt, Door Seal , Door Closer etc.
Complete as per Standard Requirement.
Providing and fixing of approved make
radiation-proof lead line door with
galvanised steel. Recommended lead door
design should be a sandwich-type panel
with both sides GI Sheet with a minimum
2mm Lead infill. Doors should be finished in
Powder Coating with thickness of
microns approx. in desired Shades. The
manufacturer company must be ISO 9001-
2015 certified. The door frame is a Single
rebate profile of minimum size 105mm X
mm made out of 1.2 mm minimum thick
galvanized steel sheet & with 2mm lead
f 19 infill. The frame is finished with Powder 27488.83 Sq.mt.
Coating in desired Shade. Frame having
provisions and necessary Arrangement for
receiving appropriate hardware like lock
and hinges. The door leaf shall be a
minimum 46mm thick fully flush double skin
door without vision lite. The door leaf shall
be manufactured from 1.0 mm thick
galvanised steel sheet. Door Includes SS
304 Hinges, D type Pull Handle-SS
Mortise Deadlock with cylinder - 70mm
both side key , Flush type tower bolt, Door
Seal , Door Closer etc. Complete as per
Standard Requirement.
Providing and fixing 35 mm th. Shutters
for doors windows & clearstory windows
incl. wood frames as specified 12 cm. x
53 7cm. size incl. anodised alluminium fixtures
and fastenings including primer coat of
approved quality and two coats of oil paint
a 3 Fully glazed 4788.50 Sq. M.
b 3 Fully panelled 5478.89 Sq. M.
c 3 Partly panelled and partly glazed 5133.69 Sq. M.
Providing and Fixing FRP FRAME size
x 65 mm and 35 mm thick FRP shutter with
wood grain raised pannel design finish
shutter having extra reinforcement on sides
and edges and in polish finish The core of
the shutter is to be filled up with injected
fire extingushing grade.polyurethane foam
54 65 done in situ along with embedded wooden 1999.98 Sq.M.
pieces for stiffering and also for tacking
hinges and fixtures. The whole FRP frame
and shutter is to be water proof.weather
proof,tennite proof and resistance to mild
acid/ Alkali, Rates are to be inclusive of
S.S. hinges with necessary screws and
brass fixtures and fasening.
Making connection to the ex.M.H.in running
sewer incl. Dewatering and other required
machinery etc. of following dia pipes at any
convenient time. All damaged work shall be
well repaired as per instructions.
a 1 For Pipe 150 mm to 300 mm diameter 1339.29 No.
b 1 For Pipe 400 mm to 600 mm diameter 2232.14 No.
Making connection of galvanised Mild steel
distribution branch with galvanised mild
56 1 steel main 50mm to 80mm nominal bore by 600.08 No.
providing and fixing tee including cutting
and threading the pipes complete
Providing throating or plaster drip, grooves
57a 2000 and moulding to Wall , R.C.C. chajja and 41.25 Rmt
Providing & Laying cement vatta 10 cm x
10 cm in size quarter round in c.m. 1:1 (
57b 180 cement, 1 coarse sand) laid in one layers 23.45 Rmt
finishing with a floating of neat cement
watering etc complete as dire.
Carring out plinth treat ment to post
construction/ existing structure by spraying
chemical solution for termite control
treatment including labour and material
consist ment withI.S.I specification. Using
Chlordene and Chiorpur files 20EC. As Per
58 800 6131_ paret- II Consentration Weight one 104.09 Sq.mt
percent is recommended i.e one litre 20EC
chemical emulsion with19 liter give1%
concrentration inclusive of one litre
chemical emulsion appication at the rate of
5 Litre chemical/ Sqm of surface is
recommended as per I.S
Carring out timber treatment to all wood
work including drilling holes and spraying
oil based chemical solution on surface of
timber work for termite control including
labour and material etc. complete. Using
Chlordene 20EC. As Per 6113_part III
Consentration Weight 1.00 percent is
recommended one litre chemical emulsion
dillute with 9 liter of kerosene precent
concentration. Total dillute concrentration
will be10litre inclusive of the litre chemical
emulsion application 0.75/Litre chemical
per one Sqmt printed two coat wood
Paver Block Providing and laying shot
blasted Non - interlocking, Paver blocks of
specified thickness, size, grade of concrete
and colour machine made and blasting by
automatic shot blasting machine and high
density of as per approved sample of
approved make for footpath, parking areas,
service lanes,cross over and other areas as
mentioned in the drawing. Including
providing and laying 50 mm thick averave
bedding layer of coarse sand below paver
block as per required grading and
specification. Laid paver block shall be
mechanically compacted. The work of the
paving blocks shall be executed in line and
60 200 level by skilled mason of flooring work only. 758.93 Sq.mt.
Small size of paver block with same
specification shall be used at residue or at
end. It should be laid in such a way that the
no cutting of the paver block to be
necessary. If cutting of paver block shall be
required , than cut by machine only and
laying to be done by skilled flooring mason.
The finished surface of the paver block
shall have coarse sand Texture Finish.
Pave blocks shall be compacted and shall
be re-laid if necessary. Actual laid area
shall be measured and paid without any
wastage. (A) 80 mm thick M-35 grade Grey
Paver block of size 200mm x 200mm. As
per approved rate
SProviding and fixing pre-cast concrete
kerb stone of gray cement based concrete
block 30cm length,30cm height and 15cm
thick of M250 grade concret as per
approved design and including excavation
for fixing in proper line and level,filling the
joint with C:M 1:3 (1cement:3fine sand) etc
Providing and fixing double action hydraulic
floor spring of approved brand and
manufacture conforming to IS :
having brand logo embossed on the body /
plate with double spring mechanism and
door weight upto 125 kg, for doors,
including cost of cutting floors, embedding
62a 36 in floors as required and making good the 4558.89 No.
same matching to the existing floor
finishing and cover plates with brass pivot
and single piece M.S. sheet outer box with
slide plate etc. complete as per the
direction of Engineer-in-charge. With
stainless steel cover plate minimum
Providing and fixing aluminium extruded
section body tubular type universal
hydraulic door closer (having brand logo
with ISi, IS : 3564, embossed on the body,
door weight upto 36 kg to 80 kg and door
width from 701 mm to 1200 mm), with
double speed adjustment with necessary
accessories and screws etc. complete.
Designing, fabricating, testing, installing
and fixing in position Curtain Wall with
Aluminium Composite Panel Cladding, with
open grooves for linear as well as
curvilinear portions of the building , for all
heights and all levels etc. including:
(a) Structural analysis & design and
preparation of shop drawings for pressure
equalisation or rain screen principle as
required, proper drainage of water to make
it watertight including checking of all the
structural and functional design.
(b) Providing, fabricating and supplying and
fixing panels of aluminium composite panel
cladding in pan shape in metalic colour of
approved shades made out of 4mm thick
aluminium composite panel material
consisting of 3mm thick FR grade mineral
core sandwiched between two Aluminium
sheets (each 0.5mm thick). The aluminium
composite panel cladding sheet shall be
coil coated, with Kynar 500 based PVDF /
Lumiflon based fluoropolymer resin coating
of approved colour andshade on face #
and polymer (Service) coating on face #
as specified using stainless steel screws,
nuts, bolts, washers, cleats, weather
silicone sealant, backer rods etc.
(c) The fastening brackets of Aluminium
alloy 6005 T5 / MS with Hot Dip Galvanised
with serrations and serrated washers to
arrest the wind load movement, fasteners,
SS 316 Pins and anchor bolts of approved
make in SS 316, Nylon separators to
prevent bi-metallic contacts all complete
required to perform as per specification and
drawing The item includes cost of all
material & labour component, the cost of all
mock ups at site, cost of all samples of the
individual components for testing in an
approved laboratory, field tests on the
assembled working curtain wall with
aluminium composite panel cladding,
cleaning and protection of the curtain wall
with aluminium composite panel cladding
till the handing over of the building for
occupation. Base frame work cost for ACP
cladding is included in this item rate. The
Contractor shall provide curtain wall with
aluminium composite panel cladding,
having all the performance characteristics
all complete , as per the Architectural
drawings, as per item description, as
specified, as per the approved shop
drawings and as directed by the Engineer-
in-Charge. However, for the purpose of
payment, only the actual area on the
external face of the curtain wall with
Aluminum Composite Panel Cladding
(including width of groove) shall be
measured in sqm. up to two decimal
Providing and Fixing Box type metal letters
forming composite box made from 1mm
thick stainless steel plate of grade
having brush finish of following font size to
64 be fixed at Main Gate in english and or
Gujrati and including fixing charges. etc.
complete as per direction of Engg.
incharge. for Payment Purpose Height of
Letter will be measured.
a 960 Upto 300 mm Height 93.85 R. Inch
Providing and Fixing MURAL made out of
2mm thick s.s. plate grade 304, including
making necessary design as per Architect
dwg. Through laser cutting including
connection to the R.C.C./Masonary with
necessary frame,anchor fastnuts,M.S.Plate
etc. complete as per direction of Engg.
Providing and Fixing Sinage - internal and
external signage boards with Vinyle Text on
65b 20000 ACP sheet / 2 mm th. S.S. Plate etc. 9.38 Sq.Inch
complete as per direction of Engg.
Providing and fixing retro Reflective Hi
Intensity Micro Prismatic Grade Board
using 2mm Aluminum / 4mm ACP, angle
iron 75 x 75 x 6mm. Descaling and
degreasing the board as per requirement
using epoxy reflactive process by screen
painting as directed etc. complete including
transporting and fixing in C.C. 1:2:4 with
65c 5 necessary excavation curing etc. complete 7535.31 Sq.mtr.
as per I.R.C. 67-2012 design. A warranty
for 7 years for the Retro reflective sheeting
from original manufacturer & a certified
copy of 3 year outdoor exposure test report
from third party test lab for the product
offered shall be submitted by contractor.
(B)Class B Type-4(MDR/ODR) retro
reflective sheeting
Road marking with hot applied
thermoplastic paints with reflectorising
glass beads on bitumin surface providing
and laying a hot applied thermoplastic
compound 2.5 mm thick including
reflectorising glass beads @ 250gms per
sqm area, thickness of 2.5mm is excluding
of surface applied glass beds as per
IRC:35-2015. The finished surface to be
level, uniform and free from streaks and
holes. zebra patta /bump patta lane/center
line/ edge line/cut patta. The white color
marking should provide liminance
coefficinet on cemend road shalll be min
130 mcd/m2/lux and Asphalt road shall be
min 100 mcd/m2/lux during the service life
during the day time. The marking should
meet the performance criteria for night time
reflectivity, wet reflectivity and skid
resistance as mentioned in the section-15
of IRC 352015. Warranty for the Retro
reflectivity should be two years.
CAT EYE/Pavement Marker(MNC two nail)
made out of acrylic StreneAcrylonitrile or hi-
impact poly Steren fitted with moulded of
metheacrylate(MNC)reflector cube corner
reflector design,filled with tightly adhering
pooting compound as per ASTMD-788 size
11.5x7x1.60 cms or 10x10x1.75 cms
provided with bituminous adhesive in
sufficient quantity with each unit fixing with
two shrank .Reflector on both side.Co
efficient of lumination as per specification
and compressive strenth 13 tones at
degree centigrade etc.B) Double side
Providing and fixing eco-friendly light
weight calcium silicate false ceiling tiles
having T egular edge & 15mm Thick
Densified edges on the Tile Periphery for
Extra Strength The Light weight calcium
silicate ceiling tiles shall have, light
reflection 85% non-combustible as per
B.S.476 part IV, 100% humidity resistance
and also having thermal conductivity 0.043°
w/m KC. for the best thermal Insulation.
The Light weight calcium Silicate tile shall
be of approved texture Fine fissured/
Spintone/ Cosmos having NRC value of
& Globe having NRC value of 0.75 NRC or
equivalent of size 595X595 mm to be laid
on true horizontal level suspended inter
locking metal grid of hot dipped galvanized
steel sections (galvanizing @ 120 grams
per sqm including bothside) consisting of
main ‘T’ runner suitably spaced at joints to
get required length and size of 24X38 mm
made from 0.30 mm thick (minimum) sheet,
1200 mm centre to centre, and cross ‘T’ of
size 24X28 mm made out of 0.33 mm
(Minimum) sheet spaced 1200 mm along
spaced between main ‘T’ at 600 mm
centre to centre to form a grid of
1200X600mm and secondary cross ’T’ of
length 600mm and size 24x28mm made of
0.30 mm thick (Minimum) sheet to be
interlocked at middle of the 1200X600mm
panel to form grid of size 600X600mm
resting on periphery walls / partitions on a
perimeter wall angle pre-coated steel of
size (24X24X3000mm made of 0.40mm
thick (minimum)
sheet with the help of rawl plugs at 450mm
centre to centre with 25mm long dry wall
screws @ 230mm interval and laying
15mm thick Densified edges light weight
calcium silicate ceiling tiles of approved
texture (Fine Fissured/ Cosmos/Spintone)
in the grid including, cutting /making
opening for services like diffusers, grills,
light fittings, fixtures, smoke detectors etc.,
wherever required, Main ‘T’ runners to be
suspended from ceiling using G.I. slotted
cleats of size 25X35X1.6mm fixed to ceiling
with 12.5mm dia and 50mm long dash
fasteners, 4mm G.I. adjustable rods with
galvanized steel level clips of size
85X30X0.8mm, spaced at 1200mm centre
to centre long main ‘T’ bottom exposed with
24mm of all T-sections shall be pre-painted
with polyester baked paint, for all heights,
, as per specifications, drawings and as
directed by engineer-incharge.Note:- Only
calcium silicate false ceiling area will be
measured from wall to wall. No deduction
shall be made for exposed frames/ opening
(cut outs) having area less than 0.30 sqm.
The calcium silicate ceiling tiles shall have
NRC. Value of 0.50 (Minimum) for Fine
fissured/ Spintone/ Cosmos and 0.75 NRC
for Globe, light reflection 85%
noncombustible as per B.S. 476 part IV,
100% humidity resistance and also having
thermal conductivity. 0.043° w/m KC.for the
best thermal Insulation
Providing and fixing single layer water proof
gypusm board 12.5 mm thick of the make
New good Group Co.Ltd. or equivalent &
New good Group Co.Ltd. company sections
using water proof board of size 1220 mm x
1830 mm x 8.0 mm suspended by G.I
suspender of size 25 mm x 3 mm with
intermediate channel of size 18mm x40mm
x0.80mm at 1220 mm center to center
66b 810 ceiling section of size 40mmx 35mmx 600.94 Sq.mt.
0.55mm at 457 mm center to center and
perimetre chanel A of size 20mm x 27mm x
30mm x 0.50mm at edges & drops
including paper taps and sofit cleat, anchor
fastener, scoch bolt connecting cleat joining
compound top coat on ceiling including
making necessary opening for light fitting,
diffuser etc. complete as per detail drawing
Providing and Fixing 6 mm thick Lexan
Polycarbonate multi wall roofing sheet fixed
67 10 with hilti screw and rubber silicon sealer 1427.62 sq.mt.
and alluminium strip of size 50 x 3 mm etc
complete as directed by Engineer in charge
Manufacturing,testing ,supplying
loading,,transporting to work site,loading
unloading lowering in trenches,laying and
jointing RCC NP3 class pipes in C:M 1:1
including all jointing materials such as
cement,sand,hemp bitumen as directed
testing the pipe line to a head of 1.5 mt and
hydraulic test as directed etc comp.
a 175 300 mm Diameter 616.07 Rmt
b 10 450 mm Diameter 806.25 Rmt
Constructing Bombay Pattern Type Catch
x 0.60 depth up to 1 mt including
excavation, B.B.C.C.
(1:5:10), 23 cms thick brick maso. wall in
the prop. of CM
(1:6) with 40 mm thick IPS flooring in the
bottom and 15 mm thick cement plaster
inside the catch pit in the proportion of CM
(1:3) with out jali etc. comp. as
CatchPit Jali Fixing P/F FRC catch pit jali
with frame 600mm x 600mm clear opening
etc. comp.. As directed by engineer in
PERCOLATION WELL
71 120 Drilling of pilot bore hole in Alluvial Strata 694.64 Rmt
by direct Rotary Rig of 250 mm.
72 120 Reaming 400 mm 212.50 Rmt
73 1 Electro Logging charges with carting 16071.43 Job
Providing and Installing 200 mm dia
74 60 IS:12818 upvc Casing Pipe "CM" class 1193.75 Rmt
75 1 Providing and Installing 200 mm dia 669.64 Set
IS:12818 upvc End Cap, with Air Vent cowl
200 mm dia Regular with 1.5 mm sloted
size cage type trapezoidal shape wire
wound little carbon galvanized screen
confirming to IS:8110
77 10 Supply of Pea sized Gravel 2029.46 Cmt
78 1 Air Vent of 50 mm Bend 401.79 Unit
79 120 Lowering and Removing of Dropline up to 147.32 Rmt
80 1 Air Compressor 60 CFM/150 PSI 22205.36 Ls
Estimate For Civil Work With
Percolation Well
I. No. Qty Items Unit Rate Per Amount
Electrical Work Estimate
1 INTERNAL WIRING
Point wiring for Light / Bell with 2-1.5
sq.mm & earth wire of 1.5 sq.mm (Green)
both are of ISI marked 1.1 KV grade
ZHFR/HRFR PVC insulated multi strand
copper wires up to 10 mtr length , in below
type of pipe erected with 6A Modular type
switch / bell push & accessories and earth
1.1 continuity of following type, erected on
PVC / Metallic/Wooden box, single
mounting base frame covered with
textured/metallic/white front plate modules
erected on / in wall / ceiling as per pipe
erected, with necessary Lamp
holder/ceiling rose / H.D.Connector as
(f) with medium class Rigid PVC pipe and
395 accessories erected concealed in 505.05 Pt
wall/ceiling complete
Point wiring for FAN with 2-1.5 sq.mm &
earth wire of 1.5 sq.mm (Green) both are of
.ISI marked 1.1 KV Grade ZHFR/HRFR
PVC insulated multi strand copper wires up
to 10 mtr length, in below type of pipe
erected with 6A Modular type switch and
hum free EME four or more step type
electronic fan regulator with separately
mounted and accessories with earth
continuity of following type erected on PVC
/ Metallic/Wooden box, single mounting
base frame covered with
textured/metallic/white front plate modules
erected on / in wall / ceiling as per pipe
erected. with necessary ceiling rose /
H.D.Connector as directed.
(f) with medium class Rigid PVC pipe and
200 accessories erected concealed in 701.40 Pt
wall/ceiling complete
Point wiring for secondary light point with 2-
1.5 sq.mm & earth wire of 1.5 sq.mm
(green) both are of ISI marked 1.1 KV
grade ZHFR/HRFR PVC insulated multi
strand copper wires, in below type of pipe
to be erected complete with earth
continuity and necessary connection with
1.3 primary light with accessories erected on
Metal / PVC / wooden box covered
covered with appropriate front plate
modules erected on / in wall / ceiling for
open / concealed wiring. with necessary
Lamp holder / ceiling rose / H.D.Connector
as directed.as per pipe erected with
following type of accessories.
Note:- Maximum up to 6 mtrs length,
excess will be considered as Mains for
Secondary Point.
(f) with medium class Rigid PVC pipe and
275 accessories erected concealed in 174.30 Pt
wall/ceiling complete
Point wiring for Individual Plug with & earth
wire of 1.5 sq.mm (Green) both are of ISI
marked 1.1 KV grade ZHFR/HRFR PVC
insulated multi strand copper wires up to
mtr length, in below type of pipe erected
1.4 complete with Modular type switch & 5 pin
Plug erected on PVC / Metallic/Wooden
box covered with appropriate front plate
modules erected on / in wall / ceiling as per
pipe erected with following type of
[I] For 6A Plug and 6 a switch with 2-1.5
1.4.1 120 sq.mm Cu. Wire from nearby 530.25 Pt
switchboard/mcb db board
(f) with medium class Rigid PVC pipe and
accessories erected concealed in
wall/ceiling complete
1.4.2 50 [II] For 16A Plug and 16 amp switch with 2- 774.90 Pt
2.5 sq.mm Cu. Wire from mcb db board.
(f) with medium class Rigid PVC pipe and
accessories erected concealed in
wall/ceiling complete
[III] For 16A Plug and 16 amp switch with
1.4.3 15 2-4 sq.mm Cu. Wire with 2.5 sq.mm ( 906.15 Pt
green) earthing wire from mcb d b board.
(f) with medium class Rigid PVC pipe and
accessories erected concealed in
wall/ceiling complete
Point wiring for on board Looped Plug with
6A Modular type switch & 5 pin socket
erected on PVC / Metallic/Wooden box,
1.5 265 single mounting base frame covered with 255.00 Pt
textured / metallic/white front plate
modules erected on / in wall / ceiling with
following type accessories
Point wiring for Two Way Controlled Light
Point with 2-1.5 sq.mm & earth wire of
sq.mm (green) both are of .ISI marked
KV grade ZHFR/HRFR PVC insulated
multi strand copper wires erected in below
type of pipe with 6A Modular type switches
1.6 and following type of accessories erected
on PVC / Metallic/Wooden box, single
mounting base frame covered with textured
/ metallic/white front plate modules erected
on / in wall / ceiling as per pipe erected.
with necessary batten/angle holder or
ceiling rose or H.D.Connector as directed.
(f) with medium class Rigid PVC pipe and
16 accessories erected concealed in 627.90 Pt
wall/ceiling complete
Providing following type of Modular Type
Accessories mounted with PVC /
metallic/Wooden box, single mounting base
1.7 frame covered with textured / metallic/white
front plate , modules erected with
necessary connections as per site situation
directed by Engineer In charge.
1.7.2 40 (2) One No 5 pin plug 150.00 E.a.
1.7.3 90 (7) Blank Plate Single 25.00 E.a.
1.7.4 22 (8) Computer RJ-45 socket 159.00 E.a.
1.7.5 35 (9) 16 Amp. SP one way switch 179.00 E.a.
1.7.6 35 (10) 6/16Amp. Universal socket 198.00 E.a.
1.7.7 5 (13) 6A/10A/16A/20A/25A/32A Single pole 307.00 E.a.
Modular MCB Switch
Pole Modular MCB Switch
Supplying and erecting approved make
suitable panel indicator LED type lamp,
lens cover, complete erected with
necessary connections.
Providing and erecting ISI mark Medium
class RIGID PVC PIPES of following size
complete to be erected on/in wall or ceiling
1.8 erected with necessary PVC fittings &
Junction boxes fixed with adhesive solution
& Clamps with following dia of pipes, in
approved manner as directed
Providing & erecting PVC Corrugated
1.9 Flexible Conduit with required nos. of
coupling, PVC bushes, Check-nuts etc.
complete of following sizes.
providing and erecting Mains with ISI
marked electrolyte stranded copper
conductor, Non PVC Zero Halogen free fire
retardant insulated copper conductor,
insulated wire (HRFR) conforms to IS-694,
erected in existing pipe with 1.5sq. mm
copper conductor of same specifications for
earth continuity of following size.
In Existing medium class Rigid PVC pipe
and accessories
providing and erecting Mains with 1.1 KV
grade FRLS PVC insulated ISI marked
stranded Copper conductor wire in
following type of pipe to be erected in / on
wall / ceiling with 2.5 sq. mm copper
conductor FRLS PVC insulated stranded
wire of green colour for earth continuity of
(A) with medium class Rigid PVC pipe and
(c) 2 wire 10 sq. mm (use earth wire of
1.11.2 20 (h) 4 wire 6 sq. mm 258.00 Mtr
(i) 4 wire 10 sq. mm (use earth wire of
providing and erecting Mains with ISI
marked, 1.5KV grade electrolyte multi
stranded, annealed copper conductor with
heat resistant PVC insulated conforms to IS
1.12 694, IEC - 227 erected in existing pipe of
following size (Specifically for control panel,
relays, power switchgears, motor starters &
control wiring) with required size of copper
lugs, nuts and bolts if required.
1.12.1 25 (e) One wire 6.00 sq. mm 56.00 Mtr
1.12.2 40 (f) One wire 10.00 sq. mm 91.00 Mtr
1.12.3 10 (g) One wire 16.00 sq. mm 141.00 Mtr
1.12.4 10 (h) One wire 25.00 sq. mm 234.00 Mtr
1.12.5 20 (i) One wire 35.00 sq. mm 298.00 Mtr
1.12.6 20 (j) One wire 50.00 sq. mm 466.00 Mtr
1.12.7 40 (k) One wire 70.00 sq. mm 663.00 Mtr
1.12.8 40 (l) One wire 95.00 sq. mm 910.00 Mtr
Supplying and erecting Flexible PVC
1.13 insulated multi strand multi core 1.1 kv
grade ISI marked copper wires of following
size to be erected as directed.
1.13.1 110 e) 1.50 Sq.mm 3 core round PVC sheathed 46.00 Mtr
1.13.2 40 h) 2.50 Sq.mm 3 core round PVC sheathed 77.00 Mtr
1.13.3 55 k) 4.00Sq.mm 4 core round PVC sheathed 175.00 Mtr
Supplying & erecting M.S. Box having
Gauge painted with red oxide or Heavy
1.14 duty PVC box erected flushed on wall or
concealed in wall with necessary plastering
& finishing as directed of following size.
SUB - TOTAL OF INTERNAL WIRING
2 Switchgears , Panels , MCBDBs & MCBs
Providing and erecting Approved make
Three pole moulded case circuit breaker
having breaking capacity ICU of 25 K.A. at
415 V having normal current rating up to
2.1.1 25 A to 100A. with Fixed thermal &
magnetic release suitable to work on A.C.
supply 50 c/s. with all internal connections,
spreader tinned copper & complete erected
in existing 16 G.M.S. housing.
3 ICS=100% of ICU only 5832.20 No
Providing and erecting Approved make
Three pole moulded case circuit breaker
having breaking capacity/strength ICU of
35 K.A. at 415 V. having normal current
2.1.2 rating 125A.with Fixed thermal & magnetic
release suitable to work on A.C.supply
c/s. with all internal connections, spreader
tinned copper & complete erected in
existing 16 G.M.S. housing.
3 ICS=100% of ICU only 6510.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. at
415 V. having Normal current rating
200A.with Microprocessor
release,Adjustable Overload Settings from
0.25 to 1 In (in steps of 0.01),Conforms to
IS/IEC 60947-2, suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing
1 ICS=100% of ICU only 23288.45 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. and
above at 415 V . having normal current
rating 250A. with variable thermal &
magnetic release suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
1 ICS=100% of ICU only 22812.90 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 50 KA and
above at 415 V having Normal current
rating 400A. with variable Thermal &
magnetic release suitable to work on
A.C.supply 50 c/s. With all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
1 ICS=100% of ICU only 27476.90 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 50 K.A.
and above at 415 V having normal current
rating up to 630A. with Microprocessr
release Adjustable Overload Settings from
0.25 to 1 In (in steps of 0.01) ,Conforms to
IS/IEC 60947-2, suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
1 ICS=100% of ICU only 40447.75 No
Providing and erecting Approved make
Earth fault Relay suitable to mount with
inter connection suitable to following size
of moulded case circuit breaker having CT
ratio & MCCB rating as following along
with shunt trip 220V AC. with all internal
connections & complete erected in existing
Design, fabrication, assembling, supply,
installation, testing and commissioning of
cubicle type, wall / Floor mounted LT panel
suitable for 415 V 3 phase, 4 wire 50 Hz
AC supply system fabricated in
compartmentised design from CRCA sheet
steel of 2 mm thick for frame work ,Doors
and partitions IP 42 and covers,3 mm thick
for gland plates i/c cleaning and finishing
complete 9 tank process in house facility
for powder coating in approved shade,
extendable type FP aluminium alloy
busbars of high condectivity, DMC/SMC
busbar supports, entire panel shall have a
common copper earthbar of size 25mm X
mm OR 50 x 6mm aluminium at the rear
with 2 Nos. earth studs, solid connection
from main busbar to switchgears with
require size of aluminium busbar & control
wiring with 1.5 sqmm FRLS insulated
copper conductor cable, cable alleys, cable
gland plates i/c accessrories as per
specification and providing switchgears,
metering instruments etc. for following
panel.G.A.Drawing to be approved by EIC
or consultant. ( Outgoing connectors must
be nut-bolt type. Outgoing mains for 63Amp
MCBs must be of 4 x 16sqmm cu flexible
wires).Incomers Mains for MCBs shall be
always from the busbars.
( a ) Providing cable clamps / supports
within distribution boards cable alley.
( b ) All hinged door shall be earthed
through 2.5 sq mm tinned b raided copper
( c ) Pad locking of MCCB’s handles in
“OFF” Position.
( d ) All the C.T.s should be auto short link
( e ) All the MCCB's should be with rotary
( f ) All incoming and outgoing air circuit
breakers shall be placed on middle portion
of the vertical in single tier formation.
( g ) Any descripancy found in SLD & Boq
it should be brought in the notice of the
client / consultant, and the decision will be
taken final by Client / consultant.
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. at
415 V. having normal current rating 125A.
2.2.1 with Fixed thermal & magnetic release
suitable to work on A.C.supply 50 c/s. with
all internal connections, spreader tinned
copper & complete erected in existing
G.M.S. housing.
4 ICS=100% of ICU only 7976.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. at
415 V. having Normal current rating
200A.with variable Thermal & magnetic
release suitable to work on A.C.supply
c/s. with all internal connections, spreader
tinned copper & complete erected in
existing 16 G.M.S.housing. Overload
release Range: 84 - 125Amp
1 ICS=100% of ICU only 16061.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. at
415 V. having Normal current rating
200A.with variable Thermal & magnetic
release suitable to work on A.C.supply
c/s. with all internal connections, spreader
tinned copper & complete erected in
existing 16 G.M.S.housing. Overload
release Range: 125 - 160Amp
1 ICS=100% of ICU only 16061.00 No
Providing and erecting Approved make
Three pole moulded case circuit breaker
having breaking capacity/strength ICU of
35 K.A. and above at 415 V. having Normal
current rating 200A.with variable Thermal
2.2.4 1 & magnetic release suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
housing.Overload release Range: 125 -
1 ICS=100% of ICU only 15421.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. and
above at 415 V . having normal current
rating 250A. with variable thermal &
magnetic release suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
2 ICS=100% of ICU only 20739.00 No
Providing and erecting Approved make
Three pole moulded case circuit breaker
having breaking capacity ICU of 25 K.A. at
415 V having normal current rating up to
2.2.6 25 A to 100A. with Fixed thermal &
magnetic release suitable to work on A.C.
supply 50 c/s. with all internal connections,
spreader tinned copper & complete erected
in existing 16 G.M.S. housing.
3 ICS=100% of ICU only 5302.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 50 K.A.
and above at 415 V having normal current
rating up to 630A. with Microprocessr
release Adjustable Overload Settings from
0.25 to 1 In (in steps of 0.01) ,Conforms to
IS/IEC 60947-2, suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
1 ICS=100% of ICU only 37658.25 No
providing and erecting Approved make
Earth fault Relay suitable to mount with
inter connection suitable to following size
of moulded case circuit breaker having CT
ratio & MCCB rating as following along
with shunt trip 220V AC. with all internal
connections & complete erected in existing
providing and erecting Miniature circuit
breaker single pole 0.5A to 2A system and
2.2.9 20 having breaking capacity 10 KA to be 268.00 No
erected in existing box. confirming to IS
8828/1996 with ISI Mark
providing and erecting Miniature circuit
breaker single pole 6A to 25A suitable to
operate on 240 V A.C. system and having
breaking capacity 10 KA to be erected in
existing box. confirming to IS 8828/1996
Providing & erecting 240 V MCB double
pole switch for motor & inductive load (C
2.2.11 Curve) having 10 KA breaking capacity &
confirms to IS : 8828 in existing box having
following capacity
Providing & erecting 415 V MCB Four Pole
for Motor & Inductive Load (C Curve)
2.2.12 having 10KA breaking capacity & confirms
to IS :8828 in existing box having following
2.2.13 Providing and erecting following additional
parts for panel mounting MCCBs
(A)Extended operating rotary handle with
2.2.13a 12 pad lock with three position trip,off,on 865.00 No
suitable for 25A to 250 A panel mounting
(B)Extended operating rotary handle with
2.2.13b 1 pad lock with three position trip,off,on 1298.00 No
suitable for 400A to 630 A panel mounting
Supplying and erecting approved make
panel mounting type Digital Voltmeter
having 3 digits LED display, 0 to 750 AC
Volts range erected on existing panel
board with all connection, wiring etc .with
manufacturers calibration certificate.
Supplying and erecting approved make
panel mounting type Digital Ammeter
having 3 digits LED display, external CT
operated, calibrated for 0 to 1000 Amps
suitable to operate on 500 Volt AC
erected on existing panel board with all
connection, wiring etc .with manufacturers
calibration certificate.
Supplying and erecting Ammeter /
Voltmeter selector switch for 3 phase AC
Supply 500 V on existing panel board with
necessary connections.
Providing & erecting L.T. Current
Transformer with bar primary 50/5 to
2.2.17 15 1000/5 ratio 15 VA burden erected in 272.00 No
existing CRCA box duly secured with
insulating materials connected to the meter
Supplying & erecting approved make
Power Factor Meter 150mm dia
flush/projection type/ balanced &
unbalanced load to work with appropriately
provided CT’s 100/5A to 400/5A ratio &
other accessories complete erected in M.S.
box & connected to the circuit by means of
PVC copper Core leads.
Supplying and erecting approved make
suitable panel indicator LED type lamp,
lens cover, complete erected with
necessary connections.
Providing and erecting metallic vitrified
danger notice board as per language
2.2.20 4 suggested by engineer incharge for 69.00 No
MEDIUM VOLTAGE installation to be
erected as per IS-2551.
Providing and erecting required size
Aluminium strip for earthing of H.T. , OCB /
ACB / Transformer, LT panel board, Motors
etc. using copper clamp.
Providing and erecting required size
Copper strip for earthing of H.T. OCB /
ACB/ Transformer, LT panel board, Motors
etc. using copper clamp.
providng and erecting Approved make
2.2.23 3 energy meter 3 phase 4 wire unbalanced 2179.00 No
load 500 V. 5 to 10A complete erected as
directed with necessary earth wire.Class-1
Providing , erecting , fabricating the M.S.
structure as per requirement on site
incorporating proper size of M.S.
angles,square,round, flats, bars, channels,
sections complete with cutting, welding,
grinding & finishing duly painted with one
coat of red oxide with erection on site as
per direction of engineer in charge with
necessary grouting, cementing, plastering
& finishing complete.
Supplying and erecting triple pole & neutral
440V/ 500V panel mounting Aluminium
Busbars with four equal Nos. of bus having
current density not more than 0.8 Amp. /
sq.mm (Rated current / cross section area)
2.2.25 duly wrapped with colour insulating tape for
phase sequence of following current
carrying capacity, erected with necessary
bus bar supports /insulators, main cable
socket to each busbar,erected in existing
cubical panel with necessary connections.
2.2.25a 10 (A) Suitable for 100 Amp. Capacity 654.00 RnMtr
2.2.25b 18 (B) Suitable for 200 Amp. Capacity 1027.00 RnMtr
2.2.25c 18 (C) Suitable for 300 Amp. Capacity 1455.00 RnMtr
2.2.25d 30 (E) Suitable for 630 Amp. capacity 3031.00 RnMtr
Providing & erecting weather proof, dust &
vermin proof, floor mounted front operated
indoor type cubical panel board necessary
IP-42 and above protection as per
approval from engineer incharge made
from 14 SWG thick CRC M.S. sheet for
outer body & doors, 16 SWG thick CRC
M.S.sheet for internal partitions with
necessary accesories , supporting angles/
flats channel including cutting, bending,
drilling, welding, riveting with internal
partitions & cable alley as per requirements
& instruction of engineer-in-charge with
supplied switch gears, BUSBARS, suitable
size of inter connecting PVC copper wire /
copper-aluminium strips, rubber grommets,
rib, bakelite control fuses/MCB for
measuring instruments, earth bus & earth
bolts, foundation flange - bolts-base Plates,
sufficient nos. of hinged doors, handles
with locking arrangement and rubber
gasket,heavy duty end terminal
connection,danger notice board,necessary
ventilation,earthing strip complete. The
Panel shall be painted with epoxy powder
(The rates excludes the cost of
switchgears, bus bars, inter connecting
mains & Copper Aluminium strips, meters,
Fuses etc. The dimension shall be
measured excluding base beams) The
panel shall be supplied with following
approved manufacturers with following
(B) The standard companies switch gear
shall be used and only manufacturers at
CPRI approved factory
12 (i) with 350mm depth 14755.00 Sqmtr
Supplying & erecting XLPE(IS:7098)(I)-88
2.2.27 ISI unarmoured copper cable 1.1 KV grade
to be erected as directed of following size.
2.2.27a 40 (N) 4 core 16 Sq. mm 721.00 Mtr
2.2.27b 50 (M) 4 core 10 Sq. mm 568.00 Mtr
2.2.27c 12 (L) 4 core 6 Sq. mm 361.00 Mtr
2.2.27d 90 (C) 2 core 6 Sq. mm 202.00 Mtr
2.2.27e 20 (B) 2 core 4 sq.mm 130.00 Mtr
providing and erecting Mains with ISI
marked, 1.5KV grade electrolyte multi
stranded, annealed copper conductor with
heat resistant PVC insulated conforms to IS
2.2.28 694, IEC - 227 erected in existing pipe of
following size (Specifically for control panel,
relays, power switchgears, motor starters &
control wiring) with required size of copper
lugs, nuts and bolts if required.
2.2.28a 300 (a) One wire 1.00 sq. mm 12.00 Mtr
2.2.28b 120 (b) One wire 1.50 sq. mm 17.00 Mtr
2.2.28c 100 (c) One wire 2.50 sq. mm 27.00 Mtr
Design, Supplying, installing, testing of
factory fabricated ready made Three phase
APFC Panel Cubical Panel fabrication
should be type tested as per IEC
61439:1&2 Capacitor Duty Contactor for
switching as per following Steps Incomer
Switch of MCCB type Icu=Ics=50KA at
400/440 Volts, with OC, SC, internal earth
fault protection Incomer Switch of MCCB
type Icu=Ics=50KA at 400/440 Volts, with
OC, SC, internal earth fault
protection,Copper tinned insulated
Busbar,Cubical panel should be indoor type
with IP 43 and IK 10,Metalized
2.3 polypropylene film tye3-phase 528-550Volt
Capacitor,De tuning Reactor for each
capacitor,Panel having Short Circuit and
Overload protection,Each step Capacitor
having suitable MCB with Sc, OL, internal
earth fault relay,Each stage having Stage
Contactor (Capacitor load rating),PF
regulator master controller having suitable
steps with LCD display, Rs
Communication port, Indication LED Lamps
for main incomer and ON-OFF for each
capacitor bank,MS Chanel for Floor
mounting, Cable entry as per site
situation,Cooling fans for panel, ( STEPS-
Supplying & erecting approved make IP
grade Company fabricated Timer Panel of
following capacity for switch On-Off street
lights on time scheduling basis made from
16G CRCA sheet duly epoxy power painted
inside and outside with hinged doors and
2.4 locking arrangement consisting of suitable
size of 4 Pole MCB and 4 pole contactor
(cat-III)with analog time switch, auto
manual switch of same make and suitable
input and output Bakelite terminals and with
door earthing approved by Engineer in
MCBDBs and MCBs
providing and erecting Miniature circuit
breaker single pole 6A to 25A suitable to
operate on 240 V A.C. system and having
breaking capacity 10 KA to be erected in
existing box. confirming to IS 8828/1996
Providing & erecting 240 V MCB double
pole switch for motor & inductive load (C
2.6 Curve) having 10 KA breaking capacity &
confirms to IS : 8828 in existing box having
following capacity
Providing & erecting 415 V MCB Four Pole
for Motor & Inductive Load (C Curve)
2.7 having 10KA breaking capacity & confirms
to IS :8828 in existing box having following
Sheets steel powder coated enclosure
2.8 4 suitable for incorporating One/Two nos. 175.00 E.a.
Providing and erecting Sheet Steel powder
coated MCB distribution board - flush /
surface mounted fitted with busbar, neutral
link, earth bar and DIN rail, Conforms to IS
8623-1 & 3, IEC 61439-1 & 3 without MCB
to house appropriate nos. of MCBs.(The
DBs should be used of same company of
MCB to be used) suitable for
(A) single phase incoming and horizontal
single phase outgoing
(b) sheet steel double door (IP-43)
2.9.1 4 (i)4 way ( concealed manner ) 747.60 E.a.
2.9.3 5 (iii)8 way ( concealed manner ) 1369.20 E.a.
2.9.5 18 (iv)12 way ( concealed manner ) 1773.60 E.a.
(B) three phase incoming and single phase
2.10. horizontal type outgoing Per phase
isolation type (PPI)
(b) sheet steel double door
2.10.1 10 (i)4 way ( concealed manner ) 2779.20 E.a.
2.10.3 2 (ii)6 way ( concealed manner ) 3462.00 E.a.
2.10.5 9 (iii)8 way ( concealed manner ) 4054.80 E.a.
Supplying & erecting Sheet Steel powder
coated Cable end termination Box to be
mounted on Top or Bottom of the MCB
Distribution Box for housing/covering Extra
wires & Cables, suitable for following size
(G) Three Phase 8 Way ( concealed
2.11.2 2 (G) Three Phase 8 Way 683.00 E.a.
Providing and erecting Sheet Steel powder
coated Vertical MCB distribution board
(VTPN) - flush / surface mounted double
door (IP54) fitted with copper insulated
busbar, isolated neutral bar, earth bar and
2.12 DIN rail, Conforms to IS 8623-1 & 3, IEC
61439-1 & 3, suitable for 250 AMP TPN
MCCB + RCCB as incomer and three
phase outgoing as per following .(The DBs
should be used of same company of MCB
2.12.1 1 (A)4 way outgoing 13315.00 E.a.
2.12.2 1 (B)6 way outgoing 15450.00 E.a.
2.12.3 1 (C)8 way outgoing 17078.00 E.a.
Providing & erecting 415 V MCB three Pole
for Motor & Inductive Load (C Curve)
2.13 having 10KA breaking capacity & confirms
to IS :8828 in existing box having following
providing and erecting Approved make
ELCBs / RCCBs conforming to IS:
and having sensitivity of 30 mA and Short
Circuit withstand capacity of 10 KA and
suitable for operation on single phase
V,50Hz. having characteristic of quick
action & tripping with all advance feature &
do not incorporate any electronic
component. for following Max. rating
erected as directed
Providing and erecting metallic vitrified
danger notice board as per language
2.15 45 suggested by engineer incharge for 69.00 E.a.
MEDIUM VOLTAGE installation to be
erected as per IS-2551.
Providing & erecting Medium Voltage
Danger Notice Board sticker as per
language suggested by engineer incharge
of standard size as per IS-2551
SUB - TOTAL OF Switchgears , Panel
Follow IS code :3043 is the guideline for
Providing and erecting required size HOT
3.1 350 deep Galvanised iron strip for earthing of 77.00 KG
H.T. , OCB/ ACB/ Transformer LT panel
board, Motors etc. using proper clamp.
Providing and erecting required size
Copper strip for earthing of H.T. OCB /
ACB/ Transformer, LT panel board, Motors
etc. using copper clamp.
3.3 15 Providing and erecting Annealed bare 787.00 KG
Copper wire 8 to 16 SWG.
3.4 80 Providing and erecting HOT deep 77.00 KG
Galvanised iron strip wire 8 to 16 SWG.
Supplying & erecting earth pit of minimum
bore dia.150mm size approved make
Earthing Electrode consisting Pipe-in-Pipe
Technology as per IS 3043-1987 made of
corrosion free hot dipped G.I.Pipes having
Outer pipe dia of 50mm having 80-200
Micron galvanising, Inner pipe dia of 25 mm
having 200-250 Micron galvanising,
connection terminal dia of 12mm with
constant ohmic value surrounded by highly
conductive compound with high charge
3.5 dissipation suitable for following type of
applications with chamber and heavy duty
cover.(approved make OEM has to submit
test certificate) & having back filling
compound of (B) Inner chemical (CCM
Compound)- Resistivity:- 0.2 W/ meter
testing as per IEC 62561-2017, Voltage
drop:- < 1 volt at no load & dry form,
Sulphar content:- <2%(C) Back fill
Compound :- Earthing compound should
be capable to retain moisture for long time
Necessary test report must be submitted.
(a) For Electrical Installation up to 440V in
3.5.1 4 Length of pipe - 1 Mtr 4546.00 E.a.
Back filling compound - 1 Nos Bag of
(c) For Electrical Installation covering
Transformer Neutrals, Lightning arrester
Earthing, A.C.Plant & Sensitive Computer
System(like Automation, SCADA) i.e
independent Earthing in normal soil.
Length of Pipe : 3.00 mtrs
Back filling Compound :2 nos Bags of
Supply, installation,testing and
commissioning of Chemical Earthing with
UL Certified 17.2mm Dia. X 3000mm Long
254 Micron-Copper bonded M.S. Rod
manufactured as per IEC 62561-2 with
25Kg Bentonite powder plus " U " bolt rod
clamp complete with Lockable high
performence chamber suitable & tested for
5000T capacity with SS Hardware.or
Supplying & erecting funnel type earthing
having earth plate of following size burred
in specifically prepared earth pit 3 mtr.
below ground with 40 kg. charcoal and salt
with alternate layers of charcoal & salt,
20mm.dia. G.I. pipe with Funnel with a
wire mesh for watering & bricks masonry
block, C.I. Cover complete as per para
3.7 of IS 3043 with necessary length of double
Galvanised Iron / copper earth wire No
SWG bolted with lug to the plate and
covered in 12 mm dia. G.I. pipe 2.5 mtr
long complete connected to the nearest
switch gear with end socket as per direction
& duly tested by earth tester confirming to
IS (As per drawing) with following
(C) with 60 x 60x 0.315 cms. Copper earth
SUB - TOTAL OF Earthing
4 CABLES, Cable Termination and cable
Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Aluminium
4.1 conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench
/ pipe of following size of cables
(B) 3 1/2 core 50 Sq. mm ( 25 Sq.1/2 mm
(D) 3 1/2 core 70 Sq. mm ( 35 Sq. mm
(E) 3 1/2 core 95 Sq. mm ( 50 Sq. mm
(F) 3 1/2 core 120 Sq. mm ( 70 Sq. mm
Providing and erecting XLPE (IS:7098)(I)-
88 ISI armoured cable multistrand / Solid
4.2 Aluminium conductor for 1.1 KV. to be laid
on wall with necessary clamps or in existing
trench / pipe of following size of cables
4.2.1 65 (a) 4 core 4 Sq. mm 116.00 Mtr
4.2.2 360 (b) 4 core 6 Sq. mm 125.00 Mtr
Providing and erecting XLPE (IS:7098)(I)-
88 ISI armoured cable multistrand
4.3 Aluminium conductor for 1.1 KV. to be laid
on wall with necessary clamps or in existing
trench / pipe of following size of cables
4.3.1 85 (d) 4 core 16 Sq. mm 152.00 Mtr
Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench
/ pipe at road crossing or floor of following
4.4.1 30 (C) 3 core 6 Sq. mm 392.00 Mtr
4.4.2 70 (D) 3 core 10 Sq. mm 495.00 Mtr
Supplying & erecting XLPE(IS:7098)(I)-88
4.4.3 ISI unarmoured copper cable 1.1 KV grade
to be erected as directed of following size.
35 (I) 3 core 16 Sq. mm 557.00 Mtr
Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand / Solid
Copper conductor for 1.1 KV. to be laid
on wall with necessary clamps or in existing
trench / pipe at road crossing or floor of
following size of cables.
4.5.2 35 (B) 4 core 4 Sq. mm 361.00 Mtr
4.5.3 50 (C) 4 core 6 Sq. mm 505.00 Mtr
Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench
/ pipe at road crossing or floor of following
size of cables.
4.6.1 80 (D) 8 core 2.5 sq.mm 315.00 mtr
Making trench in soft soil of suitable width
of 90 cm deep for laying cable or locating
4.7 240 the fault all over the run and back filling the 55.00 Mtr
same and making the surface as normal
Covering of cable with second class bricks
or cement tiles laid cover the cable
4.8 40 crosswise & also on both sides with 139.00 Mtr
covering of 7. 5 Cm. layer of sand above &
below cable (16 bricks per meter)
( A )Making trench in Hard Murrum / Tar
Road of suitable width of 90 cm or required
depth for laying any size of cable or
locating the fault all over the run and back
filling the same and making the surface as
4.10. 5 (B) If additional machinery like hammer 354.00 Mtr
driller or JCB use [Add]
Drilling the road without breaking the road
surface (Asphalt) for laying of cable for
4.11 feeding power supply by making up to
following size of holes at both ends
4.11.1 5 (A) Up to 100 mm bore dia 488.00 Mtr
4.11.2 5 (B) Up to 150 mm bore dia 610.00 Mtr
Supplying following size of Light duty “A”
4.12 Class G.I . Pipe & erecting as directed by
Engineer-in-charge.
10 (A) 25 mm dia 171.00 Mtr
Providing & laying. R.C.C. Hume pipe for
cable to be laid 90 cm. below ground
4.13 across the road crossing or on floor with
necessary material in an approved manner
and making the ground as per original.
Providing & laying approved make Double
walled corrugated pipes (DWC) of
polyethylene(conforming to IS 14930 II
4.14 )with necessary connecting accessories of
same material at required depth in existing
trench for laying of cable. below ground /
road surface for enclosing cable
4.14.1 100 (A)50 mm outer dia 62.00 Mtr
4.14.2 285 (B)63mm outer dia 73.00 Mtr
4.14.3 50 (C))90 mm outer dia 95.00 Mtr
4.14.4 40 (D)120 mm outer dia. 136.00 Mtr
Providing & laying approved make ISI
marked Rigid PVC pipe having 6Kg / cm2
(Class-3) to be erected at road crossing on
or floor as directed for laying of cable. The
pipes as following size of dia & weight per
4.15.1 5 (D) 75 mm inner Dia. (5.5 Kg/6RMT) 124.00 Mtr
4.15.2 5 (F) 110 mm inner Dia. (11.63 Kg/6 RMT) 234.00 Mtr
Providing and, fixing heavy duty flange type
brass cable gland with rubber ring for PVC
4.16 insulated armoured cable complete with out
going tails, insulating tape etc for following
size of cables.
Providing and, fixing heavy duty flange type
brass double compression type cable
gland with rubber ring for PVC insulated
armoured cable complete with out going
tails, insulating tape etc for following size of
Solder less crimping type Aluminium lugs
conforming to IS suitable for cable of
following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut
bolts in an approved manner.
Solder less crimping type Copper lugs
conforming to IS suitable for cable of
following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut
bolts in an approved manner.
Providing and fixing approved make
Perforated C type cable tray. Made from
sheet steel. The cable tray should be single
or double bended as per required and as
per IS 2062/1079 and shall be coated with
hot dip galvanizing as per IS 2629/4759.
with max 17.5% perforation with coupler
plate / Fish plate and GI hardware like nut -
bolt and washers etc. erection with
necessary support( included) as per
Specification and as per instruction of
engineer in charge..
SUB - TOTAL OF Cables,Cable
Terminations & Cable Trenches
5 Light Fixtures & Fans
Supply , Installation, testing and
commissioning of pre-wired, LED
fitting/post top luminaries etc of all types,
complete with all accessories and tube etc.
directly on ceiling/ wall, including
connection with 1.5 sq. mm FRLS PVC
insulated, flexible, copper conductor, single
core cable with flexible conduits and
coupler and earthing etc. as required.
Note:- The LED Light fixtures should
comply all international standards third
party ( LM 79 for complete fixture, LM
for individual LED ). The Manufacturer /
Channel Partner of the Manufacturer has
to submit 4- Years unconditional free
Replacement Guarantee for complete
Supplying and erecting LED indoor fittings
with LEDs of wattage 0.2 Watt to 0.5 Watt
assembled on single MCPCB, with
housing used as a heat sink shall be made
of thick sheet Steel conforming to IS:
513/CRCA/ aluminium die cast powder
coated and high U.V. & corrosion
resistance with diffuser with company
mark/name 160V to 270V, Power Factor
more than 0.95, THD < 15%,CCT 3000 K
to 6500K, Luminaire efficacy>
lumens/watt , LED driver efficiency > 85 %(
fitting required LM-79 & LM-80
Certificates)(NOTE: Below description have
shown ranges of Wattage capacity of LED
fittings.The Engineer incharge may select
any wattage capacity between the ranges
( A ) Tube Light with integral / non integral
5.1.1a 10 (iii) 18-20 Watts, Surge - 2KV,IP-20, 293.00 No
conventional 2/ 4 feet
5.1.1b 25 (v) 36-40 Watts, Surge-2 KV, IP-20, 530.00 No
conventional 4 feet
(B) LED Panel Light with provision for
5.1.2 Plane front frame with translucent cover
fixed to housing complete.IP20
5.1.2a 42 (i)up to 8 Watts,4" x 4", Surge-2 KV 271.00 No
5.1.2b 290 (iii) 12-15 watts, 6" x 6", Surge-2 KV 462.00 No
5.1.2c 100 (iv) 18 to 20 watts, 8" x 8", Surge- 2 KV 607.00 No
5.1.2d 95 (vi) 36 watts, 24" x 24", Surge- 2KV 1777.00 No
5.1.3 (G) Spot Light 425 Lumens, Surge-2KV
5.1.3a 5 (a) 3 to 7 Watts 805.00 No
5.1.4 18 (H) Mirror Light 9 Watts, wall mounted 309.00 No
minimum 1 feet long
(I) Adjustable spot light with COB led
5.1.5 having aluminium reflector of following
5.1.5a 4 (ii) 12 Watts 957.00 No
5.1.5b 6 (iii) 15 Watts 1087.00 No
Providing & erecting Approved make Power
Saving 50 Watt Ceiling Fan with double ball
bearing ISI mark with Condenser 230 volt
A.C. 50 Hz 1200 mm sweep complete
having 3blades with aluminium blades with
, canopy & 30 cm. down rod erected with
earthing.(Make shall be approved by
Engineer in charge))
Providing & erecting Approved make
Ceiling Fan with double ball bearing ISI
mark with condenser A.C.230V 50c/s.
5.3 50 mm. sweep complete, canopy erected on 1721.00 No
existing hook or clamp with earthing [
Make shall be approved by Engineer in
Providing & erecting Approved make
Ceiling Fan with double ball bearing with
Condenser 230 volt A.C.50 Hz. 900 mm
sweep complete having 3 Aluminium
blades, canopy erected complete. [ Make
shall be approved by Engineer in Charge]
Supplying and erecting approved make
oscillating type medium duty bracket fan
with Aluminium Blades A.C. 23OV. 50cy/s
wall mounted with height adjustment and
5.5 4 rotary tilting device complete with guard, 2329.00 No
mounting accessories kit, pull cord for
speed and oscillation flexible Core plug top
complete erected with lead wires as
directed. 400MM.
Supplying & erecting approved make low
noise decorative exhaust fan having size
5.6 50 200mm with 1350 RPM with square frame 1687.00 No
ABS body with inbuilt lowers & square
Supplying & erecting fan hook box of
mm M.S. round bar bounded to the RCC
bars up to 50mm length each side and
5.7 175 pierced through a 16 Gauge M.S. box / 107.00 No
Heavy Duty PVC box complete erected
concealed in Ceiling with necessary
5.8 175 Providing 2.5mm.thick laminated acrylic 18.00 No
sheet to cover the fan hook or Fan box.
Supplying and erecting 19 / 20 mm.
nominal bore Medium Class M.S. Pipe
5.9 175 down rod erected duly painted for fan 107.00 Mtr
complete with proper insulation without
leakage and earthing.
Supplying & erecting single phase
approved make industrial exhaust fan
suitable for medium duty ring mounted low
noise operation suitable for medium duty
having following dia size and maximum
1 [D] 450 mm dia 900 RPM 3306.00 No
5.11 1 Providing suitable M.S. louver shutter of the 365.00 No
Supplying & erecting electro galvanised
G.I. wire micro mesh jali cover of grade
5.12 1 required size with suitable wooden frame 628.00 Sqmtr
duly fitted in wall outside of exhaust fan for
insect protection.
Providing and erecting PVC body surface
or pendent mounting LED Bulk type 9 watt
Lighting Fitting with electronic driver. And
lumen output from luminaire 720lm , input
voltage range 90-300VAC , 50Hz cool
white(3000 to 6500k), inbuilt driver, -
20degC to +60degC working temperature,
AL frame with Beam Angle 120deg
SUB - TOTAL OF Light Fixtures & Fans
6 External lighting
Supply , Installation, testing and
commissioning of pre-wired, LED fitting
/post top luminaries etc of all typesof
external lights, complete with all
accessories and tube etc. directly on pole /
pole bracket , including connection with
/ 2.5 sq. mm FRLS PVC insulated,3 core
flexible, copper conductor, with flexible
conduits and coupler and earthing etc. as
Supplying and erecting LED street light /
Flood light fittings with High power White
LEDs wattage of 3 Watt and above
assembled on single MCPCB, efficiency
more than 130 lm/w and corrosion free
High pressure die cast aluminum housing
with smooth finish powder coated and heat
sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses, with
toughened glass with company mark/name
engraved or embossed 160 to 270 V,Power
Factor more than 0.95, THD < 10 %, CCT
3000 K to 5700K,Uniformity ratio >0.45,
Luminaire efficacy> 100 lumens/watt . LED
driver efficiency > 85 %.( fittings required
LM-79 & LM-80 certificates)(NOTE: Below
description have shown ranges of Wattage
capacity of LED fittings.The Engineer
incharge may select any wattage capacity
between the ranges shown.)
(A) Street Light (IP-65), Surge protection -
4KV /5000K integral and 10 kv non integral
6.1.1 ,Light must have 440VAC line supply
protection. It should withstand 48 hours for
440VAC line supply.
(f) Above 60 watts to 90 watts ( Required
(B) Flood Light (IP-65), Surge -4KV/5000K
,Light must have 440VAC line supply
protection. It should withstand 48 hours for
440VAC line supply
6.1.2.a 12 (c) Above 60 watts to 90 watts 6028.00 No
6.1.2.b 4 (v) above 120 to 160 watts 8370.00 No
Supply of approved make frp/grp pole
having followiing specifications :
FRP/GRP pole made by centrifugal
moulding process using thermoset resin
polyester/epoxy resin system having
minimum glass content 45.0%.The pole
should be in one pieceand tapered round in
shape,having smooth outside surface finish
and should be totally fre from corrosion as
well as non conductive and shock proof.
Pole should be provided with FRP/GRP
base bracket dully fabricated from
6.2 metal(M.S) and dully claded with FRP/GRP
material to avoid any metal exposer and
painted with PU paint.
Pole should mechanical properties i.e
Specfic gravity (ASTM D 792) 1.3‐1.8
Kg/m3, 2. Glass Content % by weight
absorption (ASTM D 570) <0.5%,
Tensile Strength(ASTM D 638) 200+/‐
50Mpa, 5. Flexural strength (ASTM D 790)
250+/‐50Mpa, 6. Compressive Strength
(ASTM D 695) 200+/‐50MPa, 7. Yeild
Strength(ASTM D638) 250 +/‐50MPa.
Pole should be flame retardant as per IS
6746.Resin used shall be UV resistance
and pigmented. Pole should be painted
with first coat of epoxy primer and then two
coat of highly weather resistance
polyurethen paint to ensure proper
addhesion of the paint.Minimum thickness
shall be 80 to 100 micron.Defelection of the
pole shall not exceed more than 10.0 % of
the length of the pole for the given
load.Pole should be generally made as per
the dimensional data,performance criteria
and some interchagebility features of poles
as per the standard ANSI C123.20 latest
version of ASTM D 923/01 including cable
termination box with necessory
accessories.The size of pole and type of
installation with foundation , Anchor Base &
Internal junction box as per the
manufacturer details and site requirement .
The cost of 6 Mtr & 10 Mtr pole's Flood light
mounting ring is included.
(3) 'B' class (Heavy Duty) frp/grp pole
suitable for base plate mounting
[D] Overall Length of 6.0 meter, Average
thickness : 7mm, Top/Bottom Outside Dia.
76/176mm +/‐2.Weight of Pole 25.0 Kg
14 approx. (Without base) Metal Anchor Base 16815.00 E.a.
dully frp claded (Size : 340 Ø * 12mmthk
Mounting hole PCD 285mm * 6 nos. of
Providing FRP/GRP arm bracket of having
6.3 15˚ arm with 50 mm OD pipe *5 mm
thk,1000mm long from pole centre
6.3.1 12 (a) Single arm bracket 1882.00 No
6.3.2 1 (b) Double arm bracket 2390.00 No
Supplying & erecting sintex make SMC
press moulded composite FRP. loop-in,
loop-out approx. 2mm thick box complete
with bakelite connector strip 4way & hinged
doors having locking arrangements with
mounting clamp with nuts, bolts & washers
suitable for erection on wall ( c)150mm x
125mm x 100mm [deep].
Providing cement concrete.for foundation
or for concrete filling in 1:2:4 ratio with 20 to
6.5 7 25 mm stone metal duly plastered with 5077.00 CU Mtr
necessary curing for pole muffing or any
B' class galvanised iron pipe 32 mm
outside dia 45 cms long duly welded on
cms x 20 cms x 3 mm thick M.S. base
plate, erected on wall or corner for
mounting street light luminaire with
necessary hardware materials duly painted.
SUB - TOTAL OF External Lighting
Supplying & erecting approved make
Automatic liquid level controller 6A. with
sensor testing as per instruction of
7.1 1 Engineer in charge on site complete with 2332.00 Job
wiring connection with existing wires , with
copper conductor from pump to upper and
Supplying and erecting Flexible PVC
7.2 insulated multistrand multicore 1.1 kv grade
ISI marked copper wires of following size to
be erected as directed.
90 e) 1.50 Sq.mm 3 core round PVC sheathed 46.00 Mtr
Providing and erecting ISI mark Medium
class RIGID PVC PIPES of following size
complete to be erected on/in wall or ceiling
7.3 erected with necessary PVC fittings &
Junction boxes fixed with adhesive solution
& Clamps with following dia of pipes, in
approved manner as directed .
Providing & erecting water cooler having
storage capacity 150 Ltr. & cooling capacity
150 Ltr.per hour @ an ambient temp of 45˚
C. The outlet temp. of the water should
drop by 15˚C within a hour, The water
cooler should be comprising of hermetically
sealed compressor, fan motor, condensing
unit, water tank surrounded by evaporating,
coil, thermostats, relay etc.complete with
necessary inlet & outlet connection. The
body of water cooler will be made from
Stainless Steel.
Supplying and erecting water filter cum
7.5 4 purifier with ultra violate technology. 5371.00 No
(Aquaguard / waterdoc model or equivalent
symphony/ crystal/videocon model)
Providing & erecting open well horizontal
mono block pump set with cast iron body,
complete for three phase submersible
[D] For 5 HP 3 phase open well horizontal
7.6.1 2 mono block pump set suitable for 1350 18561.00 No
LPM to 310 LPM @ 10 to 42 Mtr head
suitable for 50/65 mm dia delivery pipe
[C] For 3 HP 3 phase open well horizontal
7.6.2 1 mono block pump set suitable for 85 LPM 15552.00 No
to 270 LPM @ 11 mtr to 33 mtr head
suitable for 50/65 mm dia delivery pipe
Supplying & erecting approved make
motor control cubical panel (Direct - on -
line) made from 16 G. CRCA sheet duly
epoxy powder painted inside and outside
with hinged doors and locking,
arrangement consisting of suitable size of
ON- OFF isolator (AC - 3/23duty) main
fuses, single phasing preventer, indicating
7.7 lamps for R- Y - B phases, overload relay,
Automatic water level controller, Ammeter,
Voltmeter each with two way selector
switch incoming, wires duly socket crimped,
main contactor & overload relay, start - stop
push buttons, to be erected on angle iron
frame grouted on wall as directed. The
isolator, overload relay & contactors will be
of L & T, Siemens or BCH make only.
2 (a) DOL up to 5.0 H.P. 7646.00 No
Charges for doing liasioning work for
obtaining the necessary clearances from
the Electrical inspector / competent
Authorities for the total Electrical
installation,co-ordinating with various
agencies including getting highrise
permission. All necessary drawings,
calculations, test certificates, etc. as
7.8 1 required by these authorities shall be 10000.00 No
prepared and furnished by the EPC
Vendor. Any modification/rectification as
required by these authorities shall be
carried out by theEPC Vendor at free of
cost. The fees required to be paid to these
authorities for inspection shall be borne by
Owner on production of documentary
online Un-interruptible Power Supply
Supplying and erecting approved make
online Un-interruptible Power Supply
system comprising flat cum-boost charger
with IGBT base rectifier & Inverter &
sealed maintenance free SMF batteries.
The charger having operating capacity for
input 160-270V AC & inverter having
output 230V,50 Hz Ac with 0.8 load power
factor with battery, over/under voltage
output with over load & short circuit
protection equipment. The system housed
in CRC sheet duly powder coated paint
with following power backup.with MS
painted batteries stand, 10% Overload
capacity for momentary load.
3 [H} 10 KVA with 1Hr Backup 265597.00 No
Supplying and erecting horizontal / vertical
mounting type storage water heater with
copper container housed in M.S./S.S. body
insulated with glass wool / puff complete
7.10. with heating elements,adjustable
thermostats 300C to 850C, indicating
lamp, safety valve, fusible plug,
etc.complete erected with coach bolts,
nuts. washers & cementation
6 (C)25 Ltr. with 2 KW. heating element 11342.00 No
Premium category
Providing & erecting fibre reinforced PVC
flexible pipe with brass locking nuts &
washers & clips at both ends complete
erected without leakage
SUB - TOTAL OF MISC. Work
8 PASSENGERS ELEVATOR
Supply ,installing , commissioning and
testing of Stretcher Lift ( Hospital lift )
15/16 passengers (MRL LIFT) as per R &
B S.O.R ( Category - Premium ) having
following specifications:- G+3 Floor
Supplying, Erecting, Testing &
Commissioning the passenger lift having
following main features:
[1] GEAR LESS LIFT DRIVE comprising of
High Starting torque Lift 3 phase 440 V A.
C. Permanent Magnet Synchronous motor
of proper rating with high efficiency shall be
[2] Micro processor based / PLC, ACVVVF,
vector control drive with encoder feedback
closed loop system shall be used for lift car
and door operation which shall be full
collective selective operation hall call
demand response, UP/DOWN hall stops,
Main, Up/ Down Contactor with overload
and phase reversal relay and safety
[3] Car with M S platform with bracings of
adequate size and to sustain the impact
load cabin + passenger with safety factor of
fire for steel and side panels of Stainless
steel of sheet of grade 304 duty. Car ceiling
will be S.S. finishes with aesthetic
appearance with LED ceiling lights. Car
flooring shall be of anti skid PVC with
choice of colour of engineer in charge. Car
doors shall be of stainless steel grade
hairline finish with centre opening /
telescopic automatic doors. Car panel will
also be S.S. 304 finished with emergency
stop device, mechanical door safety device,
facility of auto/ attended mode. All car
panel buttons and all floor switches must
be with brail language as per lift act.
[4] All landing doors must be fire rated for
hour shall be fully automatic centre
opening/ telescopic opening made of
hairline finish steel grade of 304 with key
holes and infrared curtains with Unlocking
facility from outside
[5] Appropriate battery operated emergency
light in the car along with alarm switch shall
be provided. Also, Emergency Light & Fan
should start immediately without any Time
Delay as soon as power fails.
[6] Digital scrolling indicator system for up-
down arrow along with floor position
indicator shall be provided inside the car
and at all floors.
[7] Full height infra red curtain with multiple
cross / crossing light beams shall be
[8] Automatic Rescue Device (ARD) shall
be provided accordingly of passenger
capacity with Manual Rescue Operation (
Manual Cranking Facility).
[9] Audio visual indication in the lift car
showing over loading shall be provided
such that doors kept open till excess load is
[10] Spring buffers/PU Buffers shall be
[11] Car fan as per passenger capacity with
automatic sleep timer shall be provided.
[12] Voice annunciator with suitable music
shall be provided in lift car.
[13] Self diagnostics system for operational
and safety parameters shall be provided in
[14] Mechanical over speed governor with
governor calibration as per actual site
parameters and submission of calibration
certificate submission, door key holes in the
floor doors, fireman switch shall be
[15] Lift machine hoisting arrangement in
the lift machine room and monkey ladder
for lift pit should be provided by the lift
agency, along with the other steel structure
works, foundations for the machine etc…
[16] In the hoist way fascia plate shall be
provided without any extra cost, where ever
required as / if directed by engineer in
[17] Permanent wiring with necessary
safety devices like RCCB in all circuit, Over
Voltage Under Voltage protection and THD
eliminator in circuit for lift machine room
and lift well with proper numbers of light
points, with fixtures, exhaust fan and plug
points shall be provided by the agency.
Only 3 phase Power Supply shall be made
available by department in lift machine
room. Necessary Earthing as per Lift
Act/Rules shall be arranged by Lift Agency.
[18] Any civil/ electrical works for additional
and alteration in lift shaft and machine
room related to erection of lift shall be
made by lift agency without any extra cost.
(granite/marble fixing around all landing
door openings are not in lift agency’s
[19] Agency has to provide all working
drawings and documents and liaison
services for obtaining all necessary
permission from lift inspector and other
[20] acrylic transparent licence/display A4
size holder in lift car
[20A] As per statutory requirement of Govt.
Of Gujarat lift & escalator act 2000, lift
agency has to provide
1. Car top safety barricade
2. Push & talk communication system.
3. Fireman's switch operation at Ground
4.carrying out third party lift inspection
during/after lift erection and provide report
by third party authorized by concern
licensing authority 5.agency has to
provide third party insurance upto
completion of free maintenance period and
submit the document for the same.
[21] Car Panel Operating Buttons with floor
position indicator/buttons must be of Auto
Glow type clearly visible when view from
[22] For Physically Handicapped person
Full Length Handrails of hairline finish steel
grade of 304 should be provided at
appropriate height on the Rear & Side Wall
Panels in Lift Car.
[23] With Necessary KVA rating voltage
controlled Stabilizer suitable for your
controller, drive and all equipments of lift.
[24] Necessary rating of DP Elcb and FP
Elcb required for lift is in scope of work
which rating is sugested by CEICED
Department (electrical Inspector)
(B) SPECIAL FEATURES DESCRIPTION
OF LIFTS for PREMIUM category
1. Advanced control system dual 64 bit
embedded microprocessor with CANBUS
Serial Communication mode including
Regenerative power efficient operation,on
site programming facility, Anti nuisance,
Pte-opening, BMS/RMS with necessary
online real time monitoring system having
necessary connectivity for remote
monitoring & other suitable supporting
hardware & software devices to fulfil the
2. Floor Indication LCD Display with call
registration & brail mark with arrival gong
and hall lantern & TFT Screen in the car
with MP3 Voice Announcer.
3. CAR Panel should be Scratch resistive
SS Moonrock finish / Hair Line /
Honeycomb for car and all Doors, All
landing doors must have fire rating up to
hours and car door must have multi-level
crisscross beam door protection.
4. To & fro communication system & wiring
(i.e. car , control room & guard room ) and
Each elevator are equipped with remote
monitoring system.agency has to provide
mobile app and user id and password for
15/16 Passengers, Stretcher Lift Ground
plus 3 upper floor with Rated Speed of
AMC LOGO design as per given by
department to be embossed inside the lift
car wall opp. To door.
(C) With General PLUS ADDITIONAL
2 SPECIAL FEATURES attached herewith. 2003064.00 No
SUB TOTAL of Passengers Elevator
Providing and erecting approved make split
air-conditioning unit consisting of copper
condensing unit with fan motor,
hermetically sealed rotary compressor with
accessories etc. duly connected separately
erected evaporating unit and blower motor
9.1 with its accessories by means of extra
supplied proper insulated copper
tubing,drain PVC pipes suitable for ( cost
includes powder coated Stand, Eco
Friendly green gas charging, 15A plug top
& Remote Control) with necessary core
(1)For ISEER Range (KWH/KWH)(3.1 to
3.99) Premium Category
9.1.1 3 [a] For 0.8 to 1.0 Ton Capacity 38986.00 No
9.1.2 17 (b) for 1.5 ton capacity 51923.00 No
9.1.3 5 (c) for 1.7 to 2.0 ton capacity 58706.00 No
Supplying and installing MS angle
powder coated / Painted standard type of
9.2 wall/floor stand mount for outdoor unit of
split AC of following capacity, erected with
necessary hardware materials as directed.
(A) 25mm*25mm*3mm thick M.S angle
9.2.1 20 suitable for upto 2 TR. Capacity of ac 1305.00 No
(B) 35mm*35mm*5mm thick M.S angle
9.2.2 5 suitable for above 2 TR to 4 TR Capacity of 1496.00 No
Supplying and erecting insulated pair of
9.3 470 soft copper tubing including power and 956.00 RMT
control cable,necessary PVC drain pipes
for Split AC machine up to 4 TR capacity
9.4 Rigid UPVC drain pipe of 10 Kg/cm2. rating
with 9 mm thick.nitrile rubber insulation.
Supplying & fixing 50mm thick TF quality
9.5 105 expanded polystyrene for underdeck 409.00 Sqmtr
insulation on slab/wall /shaft exposed to
sun/atmosphere as per specifications.
SUB TOTAL of HVAC WORK
10 D.G.SET AND ATS PANEL
Supplying and erecting, commissioning and
testing of Diesel Generating set confirming
to IS: 4722:1968 & BS:5514 having
continuous rating, 3 phase, 415 volts,
cycles A.C. supply comprising of a totally
enclosed air/water cooled diesel engine
with multi-cylinders developing suitable
BHP not less than following capacity at
1500 RPM with 10% overload for one hour
in 24 hours with standard accessories like
fly wheel, lubricating oil cooler, "A" class
governor, heavy duty fuel wheel and
lubricating oil filter, oil bath air filler,
lubricating oil pressure gauge, end exhaust
manifold, standard set of tools with
adjustable spanners, screw drivers,
cylinder head to cover, joint cylinder head
to exhaust, element lube oil filter, 12 /
volts electric starting equipment complete
with standard heavy duty battery, dynamo,
cut-outs, ammeter, necessary wiring,
pressure gauge, starter etc and heavy duty
Residential type exhaust silencer (With
DEF System) and vertical hot air duct both
logged with asbestos rope, save oil trays,
exhaust piping of required length, standard
wall/floor mounted fuel with level indicator
and piping and drip proof alternator, self
excited, self regulated, screen protected,
with excitation system, capable of
delivering the rated system output at
volts, 3 phase, 0.8 PF, 50 Hz, 4 wire,
running at 1500 RPM, conforming to IS-
4722- 1968 with voltage regulation +/-
5% of rated voltage from no load to full
load. Both the engine and alternator fitted
on a common fabricated steel base plate
with antivibration mounting engine and
alternator both connected to each other by
flexible flange coupling and with floor/wall
mounted control panel box comprising of
voltmeter ammeter, selector switches,
ACB / MCCB / MCB of adequate capacity,
indicator lamps duly wired with HRC fuses.
The alternator & control panel shall be
connected with provided suitable capacity
armoured cable and complete with Acoustic
enclosure (canopy) made out of 16 SWG
CRCA Sheet, sound absorbing material
Rockwool of 64 density & 100 mm thick
conforming to IS:8183 / PU Foam of
Density - at least 40 mm. The resin bonded
rockwool covered from inside the canopy
by perforated sheet with 3/4 mm holes,
sound level not more than 75 dB at a
distance of 1 mtr, as per PVCT norms.DG
set should have in built fuel tank capacity of
minimum 8 hrs of continous running
capacity on full load . Erection,
commissioning and satisfactory testing as
per requirement with first filling of fuel
(minimum up to the 80% of fuel tank
capacity), oil, etc. with guarantee /
Warrantee of complete system for Two
years. & with obtaining all necessary
certificate from Electrical Inspector. The
Capacity and Ratings of DG sets are as
below. (As per new CPCB4+ Emission
norms Engine With - Turbo Charger, EGR
(Exhaust Gas Recirculation), CRS
(Common Rail Fuel System), DOC (Diesel
Oxidation Catalyst), SCR (Selective
Catalytic Reduction), Integrated wiring
harness connected to ECU .)
1 (O) Continuous rating of 160 KVA ,BHP not 1382776.00 Each
less than 197 BHP
Providing & erecting approved make ATS
panel suitable for following size of 3 phase,
415 V., 50 cycles, A.C. diesel generating
set complete of scope as detailed below:
1) Power module: Motorised Changeover
switch with ATS controller, Auxiliary
contactor with NO & NC contacts with
Automatic Battery Charger, indicating
lamps for Generator ON, Mains ON, Load
and suitable control terminals and power
terminals with neutral earthing studs.
(F) ATS Panel for 160 KVA 3 phase DG
SUB TOTAL of D.G.SET & ATS Panel
I. No. Qty Items Unit Rate Per Amount
CCTV System & ELV Work Estimate
Final specification and block diagram
shall be submitted by CCTV camera
SITC of 1/2.8" CMOS 3MP IP Fixed Lens
IR rugged DOME Camera having
progressive scanning system , Pixels 3MP
(2304 x 1296),Lens 2.8 mm, Fixed, F1.4,
Minimum Illumination color / BW: Color:
0.002 Lux @ F1.6, BW 0 Lux IR ON,IR
Distance 40 Mtrs,Wide Dynamic Range
130 Db,Privacy Masking Off/On (5
Areas),Local Storage Micro
SD/SDHC/SDXC card slot (2TB),Gain
Control 0 ~ 100%,Angle of View (H x V)
H:87.2° V:49.1°,Ethernet 10 Base-T/100
Base-TX Ethernet (RJ-45),Protocols:IPv4,
1.1 34 IPv6, TCP/IP, HTTP, HTTPS, 13222.00 No
RTSP/RTP/RTCP, IGMP/Multicast, SMTP,
SNMP, DHCP, NTP, DNS, DDNS, CoS,
QoS,802.1X, UPnP, mDNS(Bonjour), UDP,
ICMP, ARP, TLS, SFTP,Body Material
Aluminium + Polycarbonate,Number of
Video Streams 4,Ingress Protection IP66,
IP67, Event Notifi cation HTTPS, HTTP,
SMTP, ONVIF, Bit Rate 100 K ~ 6 Mbps
Certificates: FCC PART 15, CE (EN
55032), ICES-003,CE (EN 55035),UL listed
to UL/CSA 62368-1, BIS IS 13252 (Part
1)/IEC 69050-1,RoHS, REACH, WEEE,BIS
SITC of 1/2.8" CMOS 3MP IP Fixed Lens
IR rugged Bullet Camera having
progressive scanning system , Pixels 3MP
(2304 x 1296),Lens 3.6 mm, Fixed, F1.4,
Minimum Illumination color / BW: Color:
0.002 Lux @ F1.6, BW 0 Lux IR ON,IR
Distance 50 Mtrs,Wide Dynamic Range
130 Db,Privacy Masking Off/On (5
Areas),Local Storage Micro
SD/SDHC/SDXC card slot (2TB),Gain
Control 0 ~ 100%,Angle of View (H x V)
H:87.2° V:49.1°,Ethernet 10 Base-T/100
Base-TX Ethernet (RJ-45),Protocols:IPv4,
1.2 6 IPv6, TCP/IP, HTTP, HTTPS, 13222.00 No
RTSP/RTP/RTCP, IGMP/Multicast, SMTP,
SNMP, DHCP, NTP, DNS, DDNS, CoS,
QoS,802.1X, UPnP, mDNS(Bonjour), UDP,
ICMP, ARP, TLS, SFTP,Body Material
Aluminium + Polycarbonate,Number of
Video Streams 4,Ingress Protection IP66,
IP67, Event Notifi cation HTTPS, HTTP,
SMTP, ONVIF, Bit Rate 100 K ~ 6 Mbps,
Certificates: FCC PART 15, CE (EN
55032), ICES-003,CE (EN 55035),UL listed
to UL/CSA 62368-1, BIS IS 13252 (Part
1)/IEC 69050-1,RoHS, REACH, WEEE,BIS
Supply , Installation , Testing and
commissioning of 32 Channel NVR
(Network Video Recorder) Embedded Linux
based for recording upto 32CH at 1080P,
960fps with 04 nos. SATA HDDs minimum
40TB storage or more (recording
requirement all cameras recording at 2MP,
25fps for 30 days), H.265
HEVC/H.264/MJPEG codec decoding,
Front Panel with LEDs Indication for Power
& HDDs Status, 3 nos. USB, ONVIF S,
Time Sync with NTP, Encrypted Streaming
& Control, 2-Way Audio Line & Out, PTZ
Operation Pan, Tilt, Zoom, Support, Pre &
Post Alarm Recording Support,
Recording/Evidence Clip Export to USB,
Channel Synchronous Playback, Playback
1.3 2 control i.e Play, Pause, Stop, Fast Forward, 66202.00 No
Backward, Speed Control, Timeline &
Zoom; Snapshot, Web Client, Central
Monitoring Software, iPhone; iPad; Android
based Mobile clients, 02HDMI & 01VGA
Output, 04 On Board HDDS each up to
10TB, Alarm Input (16 nos.), Alarm Output
(04 nos.), RS232/485, eSATA, 256 Mbps
throughput, NDAA Section 889 Compliant,
Operating Temperature –10°C to 55°C,
Certification : Certifications: ONVIF
compliant, UL/CSA 62368-1, CE (EN
50130-4), FCC Part 15, EN 55032, NDAA
& RoHS (EN63000) compliant. Including
fixing accessories and cable termination
with required connectors/Jack, complete in
all respect as per instruction of engineer in-
Supply Installation Testing &
1.4 4 Commissioning of 8TB Surveillance 25150.00 No
Supply, Installation, Testing and
Commissioning of 43 inch, Professional
LED Display Cum Commercial TV with
Android 11 & Inbuilt play store, UHD
resolution, 400 nits brightness, It's 24*7
usage, 50,000 hours life, 3 years warranty,
Android 11 with inbuilt play store, Inbuilt
wifi, Landscape / Portrait mode, Inbuilt
Bluetooth, 2 GB / 16 GB Memory, Inbuilt
SOC with HDMI cable
Providing and erecting ISI mark Medium
class RIGID PVC PIPES of following size
complete to be erected on/in wall or ceiling
1.6 erected with necessary PVC fittings &
Junction boxes fixed with adhesive solution
& Clamps with following dia of pipes, in
approved manner as directed
CAT 6 UTP Cable
Supplying & erecting approved make LAN
1.7 cable of following size in existing pipe as
1.8.1 1 Supply, Installation, Testing & 12053.57 No
Commissioning of 9U wall mount rack.
1.8.2 3 3U wall mount Rack 5025.01 No
SITC of 24 x 10/100/1000BASE-T PoE
ports 4 x Gigabit RJ45/SFP Combo ports
Advanced L2 switching and security
features L2+ Static Routing Optional
“standard mode” or “surveillance mode”
management user interface 193 W PoE
budget (Including Five year free
maintenance with guarantee)
SITC of 8 x 10/100/1000BASE-T PoE ports
2 x Gigabit SFP ports Advanced L2
switching and security features L2+ Static
Routing Optional “standard mode” or
surveillance mode” management user
interface 65W PoE budget
[Approved by Competent Authority i.e. not
Below the rank of Executive Engineer ]
Supply, Installation Testing &
Commissioning 5 Mtr. HDMI Interface
1.11 2 Cable as per the detailed Specifications 820.00 No
supports transmission of 4K Signals as per
the detailed Specifications
Supply, installation, fixing, testing and
commissioning of PVC Junction box for
1.12 40 CCTV Camera, IP65, outdoor application. 440.00 No
Junction Box size will be as per vendor's
requirement and site condition.
SITC of Patch Panel Cat 6 UTP Keystone
1.13 2 Type- 24 Port-Fully Loaded (Including Five 4357.00 No
year free maintenance with guarantee)
SITC of Jack Cat 6 Keystone UTP
1.14 46 (Including Five year free maintenance with 160.00 No
SITC of CAT6 UTP 24AWG PATCH
1.15 46 CORD:1M,Plug 30U' Snag less (Including 155.00 No
Five year free maintenance with guarantee)
SUB -TOTAL OF CCTV SYSTEM
SITC of CAT6 UTP 24AWG PATCH
2.1 22 CORD:1M,Plug 30U' Snag less (Including 155.00 No
Five year free maintenance with guarantee)
SITC of CAT6 UTP 24AWG PATCH
2.2 22 CORD:2M,Plug 30U' Snag less (Including 199.00 No
Five year free maintenance with guarantee)
SITC of 24 x 10/100/1000BASE-T ports 4 x
Gigabit RJ45/SFP Combo ports Advanced
L2 switching and security features L2+
Static Routing Optional “standard mode” or
“surveillance mode” management user
SITC of Patch Panel UTP Keystone-
Port- Unloaded (Cat 5e,Cat 6 & Cat 6 A )
(Including Five year free maintenance with
Providing & erecting main Distribution
(MDF) indoor type, back mounted frame as
per DoT standard approved with krone
1 (a) Suitable for 10 pair 985.00 E.a.
Providing & Erecting Netwrok rack with
2.5 following capacity with Necessary cooling
fan,Cable manager,6A PDU,equipment
rack with necessary mounting accessories.
Supplying & erecting approved make LAN
2.6 cable of following size in existing pipe as
Providing & Erecting approved make
following size of TV Co-axial flexible cable
comprising inner conductor of solid bare
copper insulated with Foam PE &
Secondary conductor made of poly -
Aluminium film bonded Al. Braids @
suitable coverage overall sheathed with
black PVC insulation.
Supplying and laying UPVC cable trunking
system comprising unplasticised polyvinyl,
chloride rigid material with ignition free and
flame proof confirming BS with necessary
end caps Internal and external bend, flat
bends, coupler, tee etc..All necessary
accessories and measuring of following
2.8.1 5 (2) 100 mm x 50 mm trunking 424.00 Mtr
2.8.2 5 (4)100 mm x 50 mm trunking with TWIN 1309.00 Mtr
compartment With clip in divider
Supply & installation of surface mounted U
PVC snap-on adaptable trunking raceways,
fabricated out of U-PVC to Off-White or
approved shade as per IS 733 of thickness
2.0mm for the base and sides with all
accessories like removable covers, joints
,height spacer,angles complete with
necessary bends, suitable sized junction
boxes and tees etc, Complete.
(a)Size: 50x80mm PVC Raceways for
5 Power & Data with 2 compartments above 1052.00 Mtr
specifications.
Supply & installation of modular type
accessories for U PVC snap-on adaptable
2.10. trunking/Pop up Box with required items
erected with necessary connection. As
desired by Engineer In charge
2.10.1 4 i) 6 A SP 1 Way Switch 204.00 No
2.10.2 2 ii) 16A SP 1 Way Switch 351.00 No
2.10.3 4 iv) 6A universal socket shuttered 347.00 No
2.10.4 2 iv) 6/16 A universal socket shuttered 458.00 No
2.10.5 2 vi) Cat-6 LAN Socket 561.00 No
Supplying & erecting approved make
Telephone Cable electrolytic copper
conductor PE insulation twisted in two
pairs, & wrapped with FRLS PVC tape &
2.11 sheathed with FRLS PVC or HFFR outer
Jacket suitable for telephone wiring &
confirming to C-DOT erected in existing
pipe. of following size of conductors &
nos.of pairs. With necessary connections.
(b) Armoured [Jelly Filled]
40 1) Ten Pairs 124.00 Mtr
SUB - TOTAL OF LAN NETWORKING
I. No. Qty Items Unit Rate Per Amount
FIRE FIGHTING SYSTEM
Design,Drawing,
Supply,installing,testing and
commissioning of FIRE HYDRANT
1 Internal / External Hydrant
Supplying, Installation, Testing and
Commissioning of electric driven main
1.1.1 Hydrant fire pump suitable for automatic
operation and consisting of following:
complete in all respect as required.
a) Horizontal type, single stage, centrifugal,
end suction pump of cast iron body &
bronze impeller with stainless steel shaft,
mechanical seal to ensure a minimum
pressure of 3.5 kg/sq. cm. at highest and
farthest outlet at specified flow of 2280 lpm
at 65 Mtr. head conforming to IS 1520.with
suitable size of footvalve confirming to IS
4038, Pressure rating PN2 , preventing
entry of foreign body to pump through
suction pipe, perfectly flat seating surfaces
for good sealing.
b) Suitable HP Squirrel cage induction
motor, TEFC, suitable for opertion on
volts, 3 phase 50 Hz. AC with IP 55 class
protection for enclosure, horizontal foot
mounted type with Class - 'F' insulation,
conforming to IS-325.
c) M.S. fabricated Common base plate,
coupling, coupling guard, foundation bolts
etc. as required.
d) Suitable cement concrete foundation
duly plastered with anti vibration pads.
The pump shall be capable of giving not
less than 150% discharge at ahead not less
than 65% of the rated head.
Supplying, Installation, Testing and
Commissioning of electric driven
1.1.2 1 pressurisation pump suitable for automatic 61717.00 Set
operation and consisting of following:
complete in all respect as required
a) Horizontal type, single stage, centrifugal,
end suction pump of cast iron body and
bronze impeller with stainless steel shaft,
mechanical seal at specified flow of
lpm at 56/70 m. head conforming to IS:
1520.with suitable size of footvalve
confirming to IS 4038, Pressure rating PN2
, preventing entry of foreign body to pump
through suction pipe, perfectly flat seating
surfaces for good sealing.
b) Suitable HP Squirrel cage induction
motor TEFC type suitable for operation on
415 volts, 3 phase 50 Hz. AC with IP
Class of protection for enclosure, horizontal
foot mounted type with Class F' insulation,
conforming to IS :
c) M.S. fabricated Common base plate,
flexible rubber coupling, coupling guard,
foundtion bolts etc. as required.
d) Suitable cement concrete foundation
duly plastered with anti vibration pads.
1.1.3 ENGINE DRIVEN PUMP
Supplying, Installation, Testing and
Commissioning of diesel engine driven
1 main fire pump suitable for automatic 506181.00 Set
operation and consisting of following:
complete in all respect as required
a) Horizontal type, single stage, centrifugal,
end suction pump of cast iron body and
bronze impeller with stainless steel shaft,
mechanical seal to ensure a minimum
pressure of 3.5 kg/sq. cm at highest and
farthest outlet at specified flow of 2280 lpm
at 65 m. head conforming to IS
b) Suitable HP, 1500 /1800 RPM water
cooled with radiator, diesel engine
conforming to relevant BS & IS standard
complete with auto starting mechanism,
12/24 volts electric starting equipment,
AH lead acid battery with battery stand,
exhaust pipe extended upto 6 m. outside
pump house duly insulated with 50 mm
thick glass wool with 1.0 mm. thick
aluminium sheet cladding, residential
silencer, instruments and protection as per
specification, stop solenoid for auto stop in
the event of fault with audio indications,
painted with post office red colour etc. as
c) One 200 Ltr capacity day oil storage tank
fabricated from 3 mm thick M.S. plates.
Tank shall be provided with inlet, outlet,
overflow, air vent, drain connections, filling
connection & level indicator. Tank shall be
mounted on a suitable steel structure
(Painted with 2 coats of red oxide paint).
Tank shall be provided with two or more
coats of synthetic enamel paint outside
over two coats of red oxide primer.
d) M.S. Fabricated Common base plate,
coupling, coupling guard, foundation bolts
etc. as required.
e) Suitable cement concrete foundation
duly plastered with anti vibration pads.
1.2 FIRE PANELS
FIRE CONTROL PANEL FOR Main
1 Hydrant pump and Jockey pump and 341210.00 No
Diesel Engine pump.
Fabrication, Supplying, Installation, Testing
& Commissioning of electrical control panel
of cubical construction, floor mounted type,
fabricated out of 2mm thick CRCA sheet,
compartmentalised with hinged lockable
doors, dust and vermin proof, powder
coated of approved shade after 7 tank
treatement process, cable alley, inter-
connection, having switchgears and
accessories mounting and internal wiring,
earth terminals, numbering etc. complete in
all respect, suitable for main fire pump,
pressurisation pump complete as per
CPWD specification with following in
coming and Outgoings, suitable for
operation on 415V, 3 phase, 50Hz Ac
Supply with enclosure protection class IP
42 as required :suitable for operation on
415 V, 3 phase, 50 HZ, AC supply with
enclosure protection class IP 42 as
A. Incoming Feeder:-
(i) 1 No of 200 A,35KA, 415V,FP MCCB
with Thermalmagnetic Based Releases
having O/C, S/C ,E/F protection, Digital
ELR 96x96mm with CBCT, FP Spreader
Terminals 1 set= 8 Pcs, Extended Rotory
Handle for MCCB, 240V AC Shunt Trip coil
(ii) LED type indicating Lamp with suitable
rating 2 Amp SP MCB:- 1 Set (each set
comprise of R,Y,B)
(iii) Digital type 3 phase Multi function
Meter with suitable rating of MCB & 3 Nos.
of single core epoxy resin cast type CTs of
200/5 Amps, 10 VA, CL 1.0 ratings -1 Set.
415 V, 200 Amps, FP Aluminium Busbars
with Heat shrinkable color code insulation
OUTGOINGS:-( All outgoing feeders for
pumps should have digital Ammeter with
selector switches and LED type
ON,OFF,Trip indicating Lamps )
1 sets - 125 A, 25kA TPN MCCB,
Ics=100% Icu, with fully automatic
Star/Delta starter suitable for 50 HP pump
with overload protection, current sensing
type single phase preventor complete with
all acceessories and internal wiring
required for automatic operation,selector
switch for local/remote, auto/manual/OFF
1 sets - 125 A, 25kA TPN MCCB,
Ics=100% Icu, with fully automatic
Star/Delta starter suitable for 50 HP pump
with overload protection, current sensing
type single phase preventor complete with
all acceessories and internal wiring
required for automatic operation,selector
switch for local/remote, auto/manual/OFF
1 no.63A,16KA MCCB Ics=100%,Extended
Rotry handle with TM release having O/C
& S/C protection with 10 HP fully automatic
star/ delta starter , current sensing type,
Single Phase Preventer, ON/OFF Push
Button & LED type Indicating lamps
complete with all accessories and internal
wiring required for automatic operation,
selector switch, for local/remote,
auto/manual operation
Diesel Engine Control.
Control for Diesel Engine comprising:
i) Auto/Manual selector switch & 3 attempt
starting device, timers and relays as
required, push buttons, start/stop in manual
ii) LED type Indication lamp for High/Low
Lub. Oil pressure, High Water Temp and
Engine ON indication.
iii) Battery charger suitable for 12 V/24 V
DC with boost and trickle selector switch, 0-
30 V DC volt meter, 0-20 Amp DC
iv) All standard relays, accessories for
automatic operation of diesel engine, wiring
with 1.5 sq mm PVC insulated copper wire
between various sensors and system
controller / starter, suitable size cable for
battery charging etc. as required.
System Controller
Designing, Supply, Installation, Testing and
Commissioning of system controller to
control operation of Main Electric Fire
Pump, Diesel Pump, Pressurisation Pump,
Terrace Pump in sequence as per
specification consisting of relays, timers,
sensors, annunciation window for fault
indication, control wiring complete as
3 NOS. 25A DP MCB " C " Curve
1.3 PRESSURE GAUGES AND PRESSURE
Providing, fixing, testing and
1.3.1 2 commissioning of Pressure Switch with 1329.87 Set
Providing and fixing in position the
1.3.2 3 industrial type pressure gauges with gun 967.73 Set
metal / brass valves complete as required
Providing, laying, testing & commissioning
of 'C' class heavy duty MS Pipe conforming
to IS 1239 i/c fittings like elbows, tees,
flanges, tapers, nuts bolts, gaskets etc., in
ground including excavation and providing
cement concrete blocks as support,
anticorrosive treatment with coaltar/asphalt
tape as per IS 10221, refilling the trench
etc. of following sizes complete as required
.( For HYDRANT )
35 100MM Dia 2300.63 Mtr
Providing, laying, testing & commissioning
of 'C' class heavy duty MS pipe conforming
to IS 3589/IS 1239 including Welding,
fittings like elbows, tees, flanges,tapers,
1.5 nuts bolts, gaskets etc. and fixing the pipe
on the wall/ceiling with suitable
clamp/support frame and painting with two
or more coats of synthetic enamel paint of
required shade complete as required :
1.5.9 5 200mm Dia ( wall thickness 6.3mm ) 4938.01 Mtr
Supplying and fixing Single headed internal
/ External hydrant valve with 1 No. 63 mm
dia instantaneous FM Gunmetal/Stainless
1.6 Steel coupling and cast iron wheel,ISI
marked, conforming to IS 5290 (type A)
with blank Gunmetal/Stainless Steel cap
and chain as required :
16 Single headed Stainless steel 5549.04 No
Providing, fixing, testing and
commissioning of Wall mounting swing type
first aid Fire Hose Reel with drum, hanging
1.7 15 bracket, 30 M x 25 mm dia high pressure 10499.50 No
hose reel tubing as per IS:884 with shut
nozzle and ball valve and all required
Supplying, Installation, Testing and
commissioning of weather proof Fire Hose
cabinet size 900x 600x300mm to house
fire hydrant & hose, including all other
related accessories fabricated from M.S.
sheet (16 Gauge) of fully welded
construction having front door with locking
arrangement, partially glazed with 4 mm
thick glass. Cabinet shall be powder
coated & painted with post office red colour
Providing ISI marked RRL (IS : 636, type‐
A) fire hose pipe 15 meter long and 63 mm
dia with ISI marked (IS : 903) Stainless
steel male and female coupling bound and
rivetted to hose pipes with copper rivets
and copper wire complete as required.
Providing Stainless steel ISI marked
mm. dia. male Instantaneous pattern short
branch pipes with 20 mm dia. Nozzle as
1.10. 16 per IS : 903, suitable for 10 Kg/sqcm 1502.28 No
operating pressure and suitable for
interconnections to hose pipe coupling as
Supplying and fixing of fire brigade
connection of cast iron body with gun metal
male instantaneous inlet couplings
complete with cap and chain as reqd. for
suitable dia MS pipe connection conforming
1.11.1 1 2 way - 100 mm dia M.S. Pipe 6094.09 No
1.11.2 1 4 way - 150 mm dia M.S. Pipe 12631.09 No
Providing, fixing, testing and
commissioning of 25 mm dia Air Release
Valve and Ball Valve assembly on top of
each riser for Air release system.
Providing, fixing, testing and
1.13 1 commissioning Pressure Relieaf Valve 4940.68 No
25mm dia with Ball Valve.
Supplying and fixing orifice plate made out
of 6 mm thick stainless steel (Grade 304)
with orifice of required size to be fitted
1.14 12 between flange & landing valve of external 1932.76 No
and internal hydrants to reduce pressure at
the outlet to the level of 3.5 kg/cm2
complete as required.
Supplying, fixing, testing and
commissioning of butterfly valve of PN
rating with bronze/gunmetal seat duly ISI
marked complete with nuts, bolts, washers,
gaskets conforming to IS 13095 of following
sizes as required :
Providing, installation, testing and
commissioning of non-return valve of
1.16 following sizes confirming to IS:5312
complete with rubber gasket, GI bolts,
nuts,washers etc.as required :
Providing, installation, testing and
commissioning of stainless steel Y-strainer
1.17 fabricated out of 1.6 mm thick stainless
steel, Grade 304, sheet with 3 mm dia
holes with stainless steel flange.
Supply, Installation, Testing and
1.18 11 Commissioning of Brass. Ball Valves with 737.27 No
all fittings required. 25mm size
Supplying and erecting Flexible PVC
1.19 insulated multistrand multicore 1.1 kv grade
ISI marked copper wires of following size to
be erected as directed.
80 f) 1.50 Sq.mm 4 core round PVC sheathed 67.00 Mtr
SITC of fire pump start stop push buttons in
SITC of 4 Zone standalone Fire Alarm
control Panel, 16X2 Character LCD
Display, provision for zone wise contact
1.21 1 and sounder. Panel does not have 12300.00 No
provision to connect Repeater Panel.
Approval: CE Mark.(Including Five year
free maintenance with guarantee)
Providing and erecting ISI mark Medium
class RIGID PVC PIPES of following size
complete to be erected on/in wall or ceiling
1.22 erected with necessary PVC fittings &
Junction boxes fixed with adhesive solution
& Clamps with following dia of pipes, in
approved manner as directed
Supply, Installation, Testing and
Commissioning of Single action Manual
Pull Station.Shock and Vibration Resistant,
pull Down Lever Remains Down Until
1.23 8 Reset. Shall be Polarity Insensitive (with all 1201.75 No
mounting accessories , complete with
Junction Box for mooting on Surface, Cable
lugs at Ends, cable compression glands,
cable tags and ferruling.
Supply, Installation, Testing and
Commissioning of Conventional Sounder
cum strobe having tone settings with range
of 95dbA and field selectable 15/30/75/110
1.24 8 candelas.(with all mounting accessories , 1201.75 No
complete with Junction Box for mooting on
surface, cable lugs at ends, cable
compression glands, cable tags and
CABLES AND TERMINATIONS
Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench
/ pipe at road crossing or floor of following
1.25.1 36 (B) 3 core 4 Sq. mm 285.00 Mtr
1.25.2 10 (G) 3 core 6 Sq. mm 392.00 Mtr
Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench
/ pipe at road crossing or floor of following
Providing and erecting XLPE(IS:7098)(I)-88
ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing trench
/ pipe at road crossing or floor of following
size of cables.
Providing and, fixing heavy duty flange type
brass cable gland with rubber ring for PVC
1.28 insulated armoured cable complete with out
going tails, insulating tape etc for following
size of cables.
1.28.2 8 (C) 2 to 4 core 10 Sq. mm 38.00 No
1.28.3 2 (D) 2 to 4 core 16 Sq. mm 47.00 No
Solder less crimping type Copper lugs
conforming to IS suitable for cable of
following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut
bolts in an approved manner.
Providing and fixing approved make
Perforated C type cable tray. Made from
sheet steel. The cable tray should be single
or double bended as per required and as
per IS 2062/1079 and shall be coated with
hot dip galvanizing as per IS 2629/4759.
with max 17.5% perforation with coupler
plate / Fish plate and GI hardware like nut -
bolt and washers etc. erection with
necessary support( included) as per
Specification and as per instruction of
engineer in charge..
Supply, installation,testing and
commissioning of Chemical Earthing with
UL Certified 17.2mm Dia. X 3000mm Long
254 Micron-Copper bonded M.S. Rod
manufactured as per IEC 62561-2 with
25Kg Bentonite powder plus " U " bolt rod
clamp complete with Lockable high
performence chamber suitable & tested for
5000T capacity with SS Hardware.or
1.32 SEWAGE PUMPS
Supplying, Installation, Testing and
commissioning Sewage water submersible
pumping sets of CI casing & impeller, SS
shaft, including with inbuilt water level
sensors for operating the pumps
automatically and all accessories suitable
for operation on 220 V-240 V, single phase,
50 Hz. AC supply etc. as reqd.
> 10 mm solid handling capacity,Minimum
Capacity - 50 LPM,Minimum Head >
Charges of Preparing Design , Drawings
,Testing of Fire Fighting System with
necessary Approval from Local Fire
authority.( Including Pre-NOC and NOC
from Fire authority. ) The fees required to
be paid to these authorities for inspection
shall be borne by AMC ( owner ) on
production of documentary evidences.
Providing, fixing, testing and
1.34 commissioning of below Auto Glow
1.34.2 8 Fire Equipment: 4" X 12" 514.97 No
1.34.3 8 In case of Fire, do not use lift, use 650.00 No
staircase: 8" x 8"
1.34.4 8 Fire Lift 4"X12" 514.97 No
1.34.5 8 Fire Extinguishers 8"x 4" 480.00 No
1.34.6 8 Floor Sign": 4" X 12" 514.97 No
1.34.7 8 Fire Hydrant 4” X 12” 514.97 No
1.34.8 8 Fire Hose Reel.4” X 12” 514.97 No
1.34.9 8 DCP Extinguisher 8"x 4" 480.00 No
1.34.10 8 CO2 Extinguisher 8"X 4" 480.00 No
Providing, fixing, testing & commissioning
1.35 of 15mm dia quartzoid bulb type sprinklers
of rating with required accessories :
1.35.1 140 Pendent Sprinkler 57°C standard response 362.25 No
(K-80) UL Listed
1.35.2 5 Pendent Sprinkler 68°C standard response 471.50 No
(K-80) UL Listed
Supplying, installation, testing &
commissioning of sprinkler flexible pipe (UL
Listed) of stainless steel complete with
NPT on reducer thread with maximum
working pressure of 175 PSI test pressure
of 875 PSI (Burst) with branch line (Inlet)
25mm NPT male thread to sprinkler head
(Outlet) 15mm NPT female thread with
reducer, nipple, 2 side brackets,center
bracket, stockbar of following sizes
complete as required etc of following sizes
Providing fixing, testing and commissioning
of Drainning & Testing Assembly 25mm dia
with Sight Glass , Union joint , Ball Valve &
SUB-TOTAL OF FIRE HYDRANT System
2 FIRE EXTINGUISHERS AND LIGHTNING
2.1 FIRE EXTINGUISHER
FIRE EXTINGUISHER Supplying,
Installation, Testing and commissioning of
Dry Chemical Powder (DCP) 6 Kg Fire
Extinguisher Mono Ammonium Phosphate
Powder 40, Stored Pressure Type,
2.1.1 8 Pressure Gauge, Controllable discharge 2724.25 No
mechanism Class A, Rating 3A & Class B
rating 21B as per IS 15683 ISI MARK (ABC
Dry Chemical Powder - MAP 40%)fitted
with required accessories including wall
suspension brackets.
Supplying, fixing, testing and
commissioning of CO2 type Fire
Extinguisher of capacity 4.5 kg filled with
Co2 Gas as per IS 15222 with controll
discharge mechanismfitted with Hose &
Horn applicable on Class B fire rating 21B
confirms to IS 15683, bearing ISI mark.
Co2 Cylinder as per IS
Providing & fixing of ISI marked water CO2
type Portable fire extingusher,9 LTR
capacity, Hydraulic test pressure 35Kgf/
cm2, Discharge range 2 Mtr,Average
discharge time: Min. 13Sec,Fire Rating
3A,Grade: IS:15683.
Providing & fixing of ISI marked, Squeeze
Grip Cartridge Type water CO2 type
Portable fire extingusher,9 LTR capacity,
2.1.4 1 Hydraulic test pressure 35Kgf/ cm2, 4200.00 No
Discharge range 2 Mtr,Average discharge
time: Min. 13Sec,Fire Rating 3A,Grade:
Providing,fixing, testing and commissioning
of 10Kg Modular type fire extinguisher
having Nitrogen expellant ,ceiling
mounted,Sprinkler Nozzle is gas tight the
release temperature is adjusted with
sprinkler imported bulb set at 57 degree C
or 68 degree C ,coverage area 4 to
2.2 LIGHTNING ARRESTER
SITC of Vertical Air Termination Solid
aluminium with Base- 10 mm dia and
mm long. Air Termination Base tested for
conditioning, Ageing Test & Lightning
2.2.1 5 impulse current withstand test: 100 kA of 9323.00 No
10/350µs waveform in an accredited Third
party laboratory as per 6.3 & 6.4 of IEC
62561-1 2017 protocol with MAST 34mm
dia 3000 mm long- Cold Galvanized
SITC of 8 mm dia solid Aluminium
Conductor for roof top mesh grid and
tested as per IEC 62561- 2 conducted in
the Govt. accredited thirty party laboratory
to meet the requirement of IS/IEC
with Required Accessories - Aluminium
Holding clamp at every 1 mtr distance,
Aluminium/SS cross splicer at every
crossing of Alu. conductor, Expansion
piece with connectors at every 20 mtr
distance, Aluminium straight Splicer to
connect conductors. All Accessories
should be tested as per IEC 62561-1
Cl. 6.3 for conditioning & Ageing Test &
6.4 for Lightning impulse current withstand
test: 100 kA of 10/350µs waveform(Ageing
& Electrical test ) conducted in a sequence
manner & tested in the Govt. accredited
Third party laboratory to meet the
requirements of IS/IEC
SITC of Galvanized Steel Flat 25x6 mm
thickness from earth electrode directly in
ground as required. Zinc coating: 500 g/m
2.2.3 120 square (Approx:70 micron coating) tested 153.00 Mtr
and used exclusively for lightning protection
earthing system and ring equipotential
SITC of 14.2 mm dia 3 mtr long Earth
electrode of High tensile steel electrode
with 250 micron copper bonding & 1 bag of
Carbon fill Based environment friendly
backfill tested as per IEC 62561-7 in NABL
2.2.4 5 accredited Laboratory and suitable 5933.00 No
stainless Steel double sided clamp. Eco
Friendly rust proof heavy duty weather
proof Polyethylene Earth Pit Chamber with
following dimensions :254 mm dia (top),
330 mm dia (bottom) & 260 mm (height).
Heat / FIRE RESISTANT COATING OF
CABLE: Supply and apply intumescent
based coating Hilti 678on cables / bunch
cables & cable tray for at least 1 mtr in
every 14 Mtrs for horizontal runs and to
entire length of vertical runs. The coating
shall have a density in the range of 1.2 to
1.4 Kg / L. The coating shall be non-toxic,
asbestos and halogen free and shall have
good mechanical strength. The coating
shall comply with IEC 332 part 3 (1992).
The product shall carry test certificate for
mold resistance rating of 0 as determined
by ASTMG21-96. The product should have
a VOC content of approx... 60g/l as per
LEED 2009 and should not have any de-
rating effect on the cable. Manufacturer
should submit relevant certificates for
mentioned attributes. Coating shall be
carried out by approved machine spraying
system which will yield uniform thickness
and better finish. Fire stop installation shall
be done by Hilti Accredited Fire stop
Specialty Contractor (HAFSC) and in
accordance with guidelines. Firestop
specialty Contractor need to submit work
completion certificate along with installation
report through Hilti documentation Software
CFS DM for periodic inspection &
maintenance purpose.
FIRE STOP FOAM Hilti CP 620 on both
sides of wall, with minimum 2 Hours fire
rating when tested in accordance with UL
1479 / ASTM-E 814, for horizontal
openings in floors or slabs made of
concrete / masonry or Gypsum after
passing service lines like cable trays or
cables / cable bundles. The expanding
foam expands seven times its volume to fill
the cavity at the time of dispensing the
material and shall fully cure within two
minutes after dispensing. The product shall
be age tested as per Dafstb and DIBT
Standards. The product shall provide water
tightness when tested for W rating as per
UL standards and shall carry test certificate
for sound insulation of 50 dB when tested
in accordance with ASTM E 90. The
product shall carry test certificate for mold
resistance rating 0 as determined by ASTM
G21-96 and shall have a VOC content of
approx... 1.3g/l as per LEED 2009. The
product shall be tested in accordance with
IEC 60068-2-57: 1999-11 (Environment
Testing) as per Part 2-57: Test for
Vibration-Time –history method and
VERTEQQII for seismic zone 4. The
system shall be UL listed & classified and
product shall bear the UL and FM approval
logo on the packing. If none of UL test
certificate comply with actual application,
an EJ document prepared by a qualified
personnel and based on nearest third party
tested & approved systems like UL test
certificates & in accordance with IFC
guidelines shall be produced by
manufacturer. A Fire stop submittal shall be
produced by manufacturer, in accordance
with approved passive fire protection
method statement, for technical approval.
Fire stop installation shall be done by Hilti
Accredited Fire Stop specialty Contractor
(HAFSC) and in accordance with Hilti
guidelines and UL system test certificates
along with installation report through Hilti
documentation Software CFC DM for
periodic inspection & maintenance
SUB TOTAL of FIRE EXTINGUISER &
Lightning Arrester
FIRE DETCTION & FIRE ALARM
Supply, Installation, Testing &
Commissioning of Microprocessor based
Networkable Analogue Addressable Fire
Alarm Control Panel. The Panel shall be
compliant with EN54-2, EN54-4 and
approved by LPCB. The Fire Alarm Control
Panel shall have inbuilt 2 loops and
expandable capacity upto 8 loops. The
Panel must have Full colour 800 x 480 LCD
with resistive touch screen and automatic
backlight dimming. The Panel must also
have the capability to take Addressable
Intelligent Wired and Wireless Devices on
same loop. Each loop shall have a capacity
of 127 analogue Addressable devices and
127 Base sounders/Base Sounder
Beacons. The panel shall have an event
log of minimum 10,000 events @ 1 second
resolution, Filterable and Printable. The
Panel shall have Three access levels.
Panel shall support upto 5000 Cause &
Effects entries, with upto 20,000 inputs
controlling & 20,000 Controlling outputs
across the network. The Panel shall have
capability for Peer to Peer networking
through RS485 network card. The Panel
must have 4 inbuilt programmable sounder
circuits, each circuit rated at 2.5A.The
Panel must have inbuilt 3 programmable
inputs and 5 inbuilt programmable relay
outputs. The Panel shall have up to sub-
addressable 512 programmable
Inputs/Outputs via optional RS485 COMMS
serially connected expansion cards. The
Panel shall have 240 V AC power supply
along with automatic Battery Charger. The
Panel shall be fully expandable via
common plug in loop driver boards. The
user shall have a choice of using the panel
with 5.25 Amp or 10.25 Amp power supply
unit which is inbuilt in the FACP and
should be approved to EN54-4. The Panel
shall have configurable via USB port to PC
or memory stick. The Panel shall have
dedicated RS232 serial port for optional
printer. Approved by LPCB
SITC of Analogue Addressable Multi-
Sensor which is fully compatible with
Analogue Addressable Protocol,having
removable high performance chamber with
Twin fire LED's allow 360 degree viewing,
3.2 130 User selectable sensitivity modes 1% to 3597.20 No
4.5% obs/m, Incorporate Optical and dual
Heat elements, lock mechanism (sensor to
base), Electronically addressed,
Pulsing/non-pulsing controlled from panel.
Approved by LPCB & VdS. (Including Five
year free maintenance with guarantee)
SITC of Analogue Addressable Multi- Heat
Sensor which is fully compatible with
Analogue Addressable Protocol,having
removable high performance chamber with
Twin fire LED's allow 360 degree viewing,
User selectable sensitivity modes 0 to
degree Celsius, Incorporates Fixed
Temperature and Rate Of Rise Heat
elements, lock mechanism (sensor to
base), Electronically addressed,
Pulsing/non-pulsing controlled from panel.
Approved by LPCB (EN54: Part 5)
(Including Five year free maintenance with
SITC of sensor common mounting base,
includes stainless steel contacts, slim
profile - only 8mm, quick connection via
square cable clamps, facility for remote
indicator, Approved by LPCB (Including
Five year free maintenance with guarantee)
Supply,Instllation,Testing and
Commissioning of Fault isolator Module
capable of monitoring shorted loop circuit
3.5 11 and automatically restore communications 2477.10 No
when shorted conditions are corrected
(Including Five year free maintenance with
Supplying, installation, testing &
commissioning of response indicator on
3.6 50 surface/recessed MS Box having two LED, 193.20 No
metallic cover complete with all
connections etc as required.
SITC of Manual Call Point approved to
3.7 8 EN54-11:2001, Approved by LPCB Easy to 4191.75 No
install, push-fit wiring terminals (Including
Five year free maintenance with guarantee)
SITC of Analogue addressable loop
powered Base Sounder, variable sound
output 50 ~ 98 dB(A) (±2 dB(A)) output at
metre, 51 user-selectable tones (all tones
EN54-3 compatible), Auto shutdown
feature prevents noise-pollution, Approved
by LPCB & VdS (Including Five year free
maintenance with guarantee)
Supplying & laying of 2x 1.5 sqmm fire
alarm armoured cable, 600/1000V rated
3.9 1410 with annealed copper conductor having 135.70 Mtr
XLPE insulation, steel wire armouring &
FRLS outer sheath complete as required.
SUB -TOTAL OF FIRE DETECTION&
I. No. Qty Items Unit Rate Per Amount
LANDSCAPING WORK :
LAYING OUT LAWN – After excavating soil
upto 30 cm. depth & removing unwanted
stuff, stones etc. Preparing soil for planting
by supplying and mixing 6 inch river fine
site and 0.5 cmt FYM maximum 100 sqmt
1 200 of lawn area and doing termicide @ 1 fit / 85.00 Sq.mt.
100 sqmt area and planting selection 1 type
/ approved lawn grass at maximum 6 cm x
6 cm distance and maintain it upto
days. Maintainance include all operations
i.e. watering, grass cutting, gap filling,
applying of fertizer if require etc.
2 60 Supplying, Spreading and leveling of good 575.00 Cmt.
earth like firtile soil as directed etc compt.
Supplying, Spreading and leveling of good
3 20 quality river Kap Filling 100 mm as directed 575.00 Cmt.
Supply and Planting saplings of Hedge
plants like kadvi mahendi, karmda,
dyuranta, nikodeviya etc. specifies bag
size is 4 inch x 6 inch, well established &
free from disease at site. as per the
Supply and Planting saplings of Ficus
panda, Ficus benjamina, Ficus benjamina
variegated, Ficus longisland bag size is
inch x 13 inch, well branched, well
established & free from disease at site as
per the instructions
Supply and Planting saplings of (Jasud,
Ixora, Ticoma Gaudi-chaudi, Gultora,
Jetropha, Haemeliya, Chandani, Mogaro,
Galfemia, , Allamenda, Desi Gulab,
Euphorbia mili, Jasud Hybrid, Chandani
6 100 double, Madhukamini, Madhumalti, Ticoma 85.00 Nos
Capensis, Ixora draft, Nikadevia, English
Karen etc.) having height of minimum
to 2.5 ft. and bag size is 8 inch x 10 inch,
well branched, well established & free from
disease at site as per the instructions.
Supply and Planting saplings of Golden
Bamboo having height of minimum 5 to
7 30 ft. and bag size is 8 inch x 10 inch, well 45.00 Nos
branched, well established & free from
disease at site as per the instructions.
Supply and Planting saplings of Palm(Botal
palm,foxtel) having height of minimum
10.00 to 12.00 ft. and bag size is 21 inch x
21 inch, well branched, well established &
free from disease at site as per the
Supply and Planting saplings of champa
(deshi) having height of minimum 8 to
9 80 ft. and bag size is 15 inch x 16 inch, well 450.00 Nos
branched, well established & free from
disease at site as per the instructions.
Supply, Spreading and leveling of Brick
10 5 dust (Chharu) particle size having 1300.00 Cmt
Supply Saplings and Planting of trees
species as specified ( Alstonia scholaris,
Erythrina indica, Jacaranda
mimosifolia,Delonix regia , Anthocephalus
cadamba, Spathodea companulata,Neem
(Azadirachta indica), Lagerstromia
speciosa , Tabebuia argentea, Cordia
sebestena, Mimusops elengi, Bauhinia
blakeana, Kigelia pinnata, Cassia fistula,
11 100 Banyan, Ficus religiosa, Peltophoroum, 250.00 Nos
Bottle brush, Silver Oak, Billi, Mahagony,
Pendula, Desi Asopalav,Sevan, Badam,
Ficus infectoria, Pinkesiya, Millingtonia
hotensis, Rain Tree, Bakm limdi, kasid,
Ashok tree, parkia, Tabebuia Rosea,
millettia, etc.) having height of minimum
7.00 to 8.0 ft. and bag size is 13 inch x
inch, well branched, well established & free
from disease at site as per the instructions.
Supplying insecticides at site well packed
in bottle of 20 litre. weight including royalty
12 50 and carriage with all leads and lifts (product 300.00
to be brought in company sealed packing
I. No. Qty Items Unit Rate Per Amount
Furniture Work ( Curtains and Cupboard
Proviging and Fixing Storage Shutter made
out of 50mm X 25 mm Indian Teakwood
Frame and 18 mm Ply Board. With 1 mm
thick laminate finish in the front and 0.8 mm
thick Laminate on Back Side with 12 mm
thick Indian teakwood beading. The scope
also include providing and fixing s.s. finish
hardware as per the Requirement. The rate
include cost of all labour, material and with
all hardware like handle, magnate, tackels,
adhesive, screws, etc.for satisfactory
completion of this items.All Exposed Wood
Work shall have malamine polish etc.
Meeting Table Ovel M4 ( 1355 MM WIDE )
Providing and supplying meeting table ovel
in shape of size 1355 mm Wide as shown
in drawing.The top made out of 19 mm
thk.ply wood with laminate top as shown in
drawing.20 mm thick teak wood beading is
provided all around table top with 5 mm
groove in the center. The top is supported
by 2 nos. of vertical square box made out
of 19 mm thick ply board of size 300mm x
300mm rest on the wooden base of size
400mm x 400mm x 40mm as shown in
drawing.The rate includes cost of all
labour,material and with necessary
tools,tackles,adhesive,screws,etc.for
satisfactory completion of this item.
Providing & Fixing Sun Control Reflective
3 500 Type Film / Frosted Film as Selected by 646.37 Sq.mt.
Architect/ Engg. In Charge For Glass Doors
/ Windows etc. as Directed.
Providing & Fixing in Position Vertical
Roller Blinds with Minimum 3 % and
Maximum 5 % Light Transperace Screen
Fabric Incuding Providing & Fixing of
Powder coated G- Channel at the Topof
Window with necessary Screw , Cleats etc.
and PVC Roller ( Weight Pipe) and PVC
Chain For Up and Down Movement of
Blinds etc. of Approved Make and as per
Drawings / Instruction of Engg. in Charge
For All Colors and Shades. Rates Includes
all Lead and Lift For All Floor Level, All
Height , All Material , Accessories, Fixing
Scaffolding , Labor etc. Complete in All
Respects. All Required Accessories &
Material must be From Same Manufacturer.
Cubical track for cubical curtain :- supply
and installation of heavy duty Aluminium
cubical track size 20mm wide x 30 mm
high, made of aluminium Extruded with
white powder coating complete with
continous PVC liner, nylon giders and
hooks , plastic end cap, connecting bridge,
overlapping joint connector, Wall bracket
with matching screws to make up cubicle
5 100 approx. height to 2100 mm clearance from 737.29 Rmt.
floor level at approx. 1000 mm spacing with
all accessories of approved brand/make
along with alluminium Extruded hospital
curtain's track system with shite powder
coating with all accessories as per
approved sample. All required accessories
and materials must be from same
manufacturer. This Item is Excluding
Cubicle Curtain :- Supply & Installation of
Water Repellant, Antimicrobial Cubicle
Curtain with High Strength18" Oval net at
Top as Approved by Consultant / Engg. In
6 250 Charge. Eyelets on Curtains & Hooks and 400.00 Sq.mt.
All other Required Accessories, Fixing
Scaffolding, Labor etc. Complete in All
Respects. All Required Accessories &
Material must be From Same Manufacturer.
Total of Furniture Work ( Curtains and Total Rs.
Cupboard Shutter)
Signature of Bidder
Special Condition For Tenderers
• Scope includes Complete Demolition of Super Structure & Sub Structure up to
Foundation Level of Existing Old Buildings in the Said Plot Under Development as
Instructed by Engg. In Charge & Then Disposal of Serviceable & Un Serviceable
Material including Cleaning & Levelling of Entire Plot. The Total Project Includes
Demolition of Existing Units and Site Clearance. The Total Responsibility and
Liability of This Demolition Works Including Site Clearance Shall Be of The
Contractor. This Demolition and Debris Removal Includes all Hidden Foundation
also at Locations Where New Foundation or New Work is To Be Done.
• Contractor Has to Visit Site with representative of A.M.C. Before Quoting Amount in
Tender. The Contractor Shall Not Be Paid For Any Dismantling, Demolition, Carting
The Debris And/ or Any Expenses Incurred For Site Clearance.
• Contractor shall have to Pay Premium Amount to A.M.C. For Disposal of Serviceable
Goods Like Old Reinforcement, Old Wooden Doors/Windows, Iron Work,
Copper/Alu. Wiring, Bricks etc. Which shall be Quoted in Part-A of Financial Bid.
• For Consideration of Lowest Eligible Bidders , Premium Amount as Mentioned
Above i.e. Part-A shall be Deducted From e-Tender Amount For Construction Work
i.e. Part-B , Quoted by the Contractors.
• The Lowest Eligible Bidder shall have to Deposit Premium Amount for the
Serviceable Goods at the Time of Submission of Security Deposit.
Signature of contractor Additional City Engineer (CENTRAL ZONE)
Seal Ahmedabad Municipal Corporation
AHMEDABAD MUNICIPAL CORPORATION
ENGINEERING DEPARTMENT- CENTRAL ZONE
Name of Work : CONSTRUCTION OF COMMUNITY HEALTH CENTER BUILDING AT F.P.NO :- 37 , T.P.NO :-
14(SHAHIBAUG) IN SHAHIBAUG WARD, CENTRAL ZONE, AHMEDABAD.
FINANCIAL BID (Online Only)
Demolition of Existing Structure
Sr.No. Description Amount
Quoted Premium Amount For Serviceable Material (Which is Payable to
1 A.M.C. at The Time of Depositing Security Deposit by the Lowest Eligible
Amount in Words Rupees :
Sr.No. Description Amount
1 Amount For Civil Work Rs.8,51,39,816.08
2 Amount For Electrical Work Rs.1,53,51,196.95
3 Amount For CCTV & ELV Work Rs.
4 Amount For Fire Fighting System Work Rs.
5 Amount For Landscaping Work Rs.
6 Amount For Furniture Work ( Curtains and Cupboard Shutter) Rs.
I/We am/are willing to carry out work at ______% above / below (should be written in figures and words)
the estimated cost mentioned above.
Estimated cost put to tender : Rs. 10,90,74,585.45 Estimated cost put to tender : Rs.
Add_____% above : Rs ___________ Deduct_____% below : Rs __________
In words : Rupees _______________________ In words : Rupees_____________________
Net Tender Amount For Consideration of Lowest Eligible Bidders
Sr.No. Description Amount
1 Net Amount For Cost of Civil , Electrical, Fire Fighting, O&M, Landscaping
and Interior & Furniture Work i.e. Part-B Rs.
2 Quoted Premium Amount Payable to A.M.C. i.e. Part-A Rs.
3 Net Tender Amount i.e. (Part-B -
Net Tender Amount in Words Rupees :
Signature of contractor Additional City Engineer ( C.Z. )
Seal Ahmedabad Municipal Corporation
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
CZ_SHAHIBAUG_CHC_Final Price Bid Vol.-II_Dt.25-03-2026.pdf
CZ_SHAHIBAUG_CHC_Vol-1 Part B TS_Civil Work Dt. 26-03-2026.pdf
CZ_SHAHIBAUG_CHC_Vol-1 part-D CCTV Work Specification.pdf
CZ_SHAHIBAUG_CHC_Vol-1 part-E Fire Fighting Specification.pdf
Part A CHC.pdf
TENDER DRAWING SHAHIBAUG CHC.pdf
CZ_SHAHIBAUG_CHC_Vol-1 part-C Electrical Specification.pdf
Download all tender documents and submit your bid