| 1 | L1₹26.2 LAccepted-AOC 274 210 DAFNALA ROAD SHAHIBAUG AHMEDABAD GUJARAT 380009 | AHMADABAD | GUJARAT | 380009 | ₹26.2 L Quoted ₹26.9 L | L1 | Accepted-AOC BEING THE LOWEST BIDDER |
| 2 | L2₹28.4 L+₹1.5 L (5.48%)Rejected-Finance 74 AJANTA COMMERCIAL CENTRE ASHRAM ROAD AHMEDABAD 380014 | AHMEDABAD | AHMEDABAD | GUJARAT | 380014 | ₹28.4 L+₹1.5 L (5.48%) | L2 | Rejected-Finance OTHER THAN THE LOWEST BIDDER |
| 3 | L3₹28.9 L+₹2.0 L (7.52%)Rejected-Finance | ₹28.9 L+₹2.0 L (7.52%) | L3 | Rejected-Finance OTHER THAN THE LOWEST BIDDER |
| 4 | L4₹29.1 L+₹2.2 L (8.20%)Rejected-Finance | ₹29.1 L+₹2.2 L (8.20%) | L4 | Rejected-Finance OTHER THAN THE LOWEST BIDDER |
Tender Value
Refer Docs
EMD Value
₹57,800
Closing Date
19 May 2020, 6:00 pmClosed
GE AF CHILODA
VAYU SHAKTI NAGAR CHILODA
REPAIR AND MAINTENANCE OF STREET LIGHTS, PERIMETER SECURITY LIGHTS, POLE PAINTING AND CERTAIN E/M WORKS AT VAYU SHAKTI NAGAR CHILODA
2020_MES_338176_1
8808/20-21/E8
Open Tender
Electrical and Maintenance Works
Item Rate
273 days
VAYU SHAKTI NAGAR CHILODA
AS PER NOTICE OF TENDER
8 documents required · 8 mandatory
₹500
Yes
GE AF CHILODA
₹57,800
Yes
30 Jul 2020
9 Apr 2020
21 May 2020
9 Apr 2020
19 May 2020
23 Apr 2020
9 Apr 2020 - 30 Apr 2020
Amount
Excavation in trenches not exceeding 1.5m width and not exceeding 1.5 m in depth and getting out in soft/loose soil for taking up/laying cable/pipe etc completed all as apecified and directed.
M & L for dry Sand cushioning to underground cable with screened, washed river sand, including punning gently all as specified and directed. Note: - Thickness after punning will be measured for payment.
Supply and lay burnt brick sub class `B' old size in trenches abutting each other width equal to length of brick etc complete as directed
Returning, filling including spreading, leveling watering & well ramming in laying not exc. 25cm for :- (a) Soft/loose soil
Removal of excavated material at a distance not exc 50 mtr and dipositing where directed at a level not exc. 1.5 mtr above the starting point for :-(a) Soft / loose soil
Laying only burnt bricks (old size) retrieved from item No.7,8 and 9, laid in trenches as cable protection complete.
Labour only for boring under road/drain by manual method for inserting the light grade pipe GI tubing up to 50 mm dia for cable protection all as specified and directed by Engineer In Charge.
Supply and laying in trenches in road cross / floors tube galvanished iron light grade with all fittings for protection of cable of following dia/bore of pipe
40 mm bore
50 mm bore
Supply and laying in repair XLPE insulated PVC inner sheathed, armoured with galvanised steel strip or wire heavy duty underground cable with aluminium multi stranded conductor 1100 volt grade of size 10 Sqmm 2 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing complete. Note:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule.
Supply and lay in repairs and testing cable LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with stranded aluminum conductor, 1100 Volts grade, of size 25 Sqmm 4 Core. Note:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule.
Supply and lay in repairs and testing cable LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with stranded aluminum conductor, 1100 Volts grade, of size 35 Sqmm 3.5 Core. Note:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule.
Supply and lay in repairs and testing cable LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with standerd aluminum conductor, 1100 Volts grade, of size 50 Sqmm 3.5 Core. Note:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule.
Supply and lay in repairs and testing cable LT XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable heavy duty with standerd aluminum conductor, 1100 Volts grade, of size 70 Sqmm 3.5 Core. Note:-Excavation, earthwork, will be measured and paid separately under respective items of this Schedule.
Labour for laying only in repair XLPE insulated PVC inner sheathed, armoured with galvanised steel strip or wire heavy duty underground cable with aluminium multi stranded conductor 1100 volt grade of size 10 Sqmm 4 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing complete. Note:- (i) Excavation, earthwork, brick, sand etc will be measured and paid separately under respective items of this Schedule. (ii) Cable will be provided under Schedule 'B' free for fixing.
Labour for laying only in repair XLPE insulated PVC inner sheathed, armoured with galvanised steel strip or wire heavy duty underground cable with aluminium multi stranded conductor 1100 volt grade of size 16 Sqmm 4 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing complete. Note:-(i) Excavation, earthwork, brick, sand etc will be measured and paid separately under respective items of this Schedule. (ii) Cable will be provided under Schedule 'B' free for fixing.
Labour for laying only in repair XLPE insulated PVC inner sheathed, armoured with galvanised steel strip or wire heavy duty underground cable with aluminium multi stranded conductor 1100 volt grade of size 25 Sqmm 3.5 core laid in trenches / duct passing through pipe / duct or fixed on pole and connecting and testing complete. Note:-(i) Excavation, earthwork, brick, sand etc will be measured and paid separately under respective items of this Schedule. (ii) Cable will be provided under Schedule 'B' free for fixing.
Taking down / out underground cable of aluminium conductor of 10 to 35 Sqmm any core after disconnecting from sheet metal enclosure / panel board or from OH line and taking out from trenches including taking out brick cable cover complete . Note:-Excavation, earthwork, brick, sand etc will be measured and paid separately under respective items of this Schedule.
Taking down / out underground cable of aluminium conductor of 50 to 70 Sqmm any core after disconnecting from sheet metal enclose / panel board or from OH line and taking out from trenches including taking out brick cable cover complete. Note:-Excavation, earthwork, brick, sand etc will be measured and paid separately under respective items of this Schedule.
Supply and fix in repair 2.5 Sqmm two core PVC insulated, unsheathed multistranded copper conductor flexible cable1100 volts grade from junction box to street light fitting complete all as specified and directed by Engr in Charge.
Supply and fix in repair 1.5 Sqmm two core PVC insulated, unsheathed multistranded copper conductor flexible cable 1100 volts grade from junction box to street light fitting complete all as specified and directed by Engr in Charge.
Taking down PVC insulated, unsheathed multistranded copper conductor flexible cable of size 1.5 Sqmm and 2.5 Sqmm, 1100 volts grade from junction box after disconnecting from MCB in PVC Junction box and opening the connections from top of the street light fitting from the pole 09/11 mtr hight and from existing building security lights complete all as specified and directed by Eng-In-Charge
Material & Labour for opening the existing cable connections from existing junction boxes of street light poles, post top lanterns and building security lights and refixing the same with newly fitted lugs of appropriate size 10, 16, 25, 35, 50, 70 and 95 as the case may be, by opening the existing loop of cable in the roots of street light pole and making the connections new by peeling the insulation with strapper, making proper connections of cable in bus bar of junction box by fixing the new Nut bolts/studs and making flexible wire connection in MCB, MCB should be fixed properly also the junction box covers should be closed in proper manner and fixing the junction boxes on the clamp on the pole by bolts complete all as specifeid and directed by Eng-In-Charge. Note:- Necessary excavation work for opening the loop and return filling of the excavated material, lugs of appropriate sizes, Nut bolts and tape roll box and other associated works will be the part of this Job and no additional cost will be paid to the contractor, Cost of MCB, New Junction boxes, clamps, flexible wire if fitted newly will be paid under respective item of this schedule.
Material & Labour for load balacing at different control panels of street lights at different locations of HQ SWAC Chiloda by proper R,Y, B phase sequencing of the street light fittings so that the load in each phase will be equal and unbalace of load in any of the phase be sorted out. the test report before and after balancing will be submitted by the contractor complete all as specified and directed by Eng-In-Charge
Taking down of old existing MS Clamp and Supply and fix new MS clamps of size 40 x 5 mm in cros sectional area and upto 500 mm in length suitable for fixing the PVC Junction boxes to the street light poles and boundary walls as the case may be, including making necessary holes and nuts/bolts required for fixing the junction box to the poles either steel tubular or PCC Pole or at the boundary wall for post top lights complete all as specified and directed by Eng-In-Charge
Taking down of old GI Pipe of any size and Supply and fixing on street light steel tubular Poles /PCC Poles /Walls galvanished iron light grade pipe upto 25 mm dia with all fittings for protection of cables hangig from the street lights to the junction boxes complete all as specified and directed by Eng-In-Charge
Material & Labour for preparation of old painted surface of steel tubular pole (9/11 meter long above coping) and applying two coat of aluminium paint, making of strip of 20 cm width (sky blue and white in alternate band) upto 1400 mm height with one synthetic enamel paint , rewriting pole No by painter with enamel paint, and painting the existing MS clamp with one coat of aluminum paint complete all as specifeid and directed.
Material & Labour for preparation of old painted surface of LT RCC pole (up to 6.10 metre height above coping), applying two coat cement base paint, making of strip of 20 cm width (sky blue and white in alternate band) upto 1400 mm height with one synthetic enamel paint, rewriting pole No by painter with enamel paint, and painting the existing MS clamp with one coat aluminum paint complete all as specified and directed
Supply and paste fluorescent type reflective tape of superior quality width 450 mm (three strips, each 150 mm wide and 609 mm long of colour white, sky blue, white), paste on steel tubular pole on outer circumferences including removing old tape complete.
Material and labour for writting of Pole Nos on existing pole with stencil out with white colour in sky blue colour background of 80 mm hight around the radius of pole and all as specified and directed by Engr in charge.
Supply and fix in repair to timer switch Digital type 24 hours with 15 min and 30 min, 16/100 Amp contact rating 230 volts AC 50 Hzs suitable for street lights and all as specified and directed by Engr in charge. Make : Legrand Cat Part No.CX3 CT 230V 2NO 40 A or equivalent in Phillips/Crompton
Supply and fixing 3 pole power contactor type ML 3 AC 3 rating(100A) Aux Contactors 2NO+2NC Cat No SS90721 of Make- L&T compatible with digital timer of suitable capacity complete all as specified and directed by EIC.
Supply only MCB’s double pole with neutral, 6 to 32 Amps, 250 volts with ‘C’ curve, fixed in existing PVC box including connecting complete.
Supply only MCB’s DB TPN, 32 to 100 Amps, 250 volts with ‘C’ curve, fixed in existing PVC box including connecting complete.
Disconnecting the existing unserviceable PVC box and Supply and fix in repair PVC box of outside size 350mm x 250mm x 150mm and inside size 300mm x 200mm x 105 mm including 4 Nos of bus bar strip of aluminium of size 25x4 mm suitable for 440 volts of suitable amps rating including 1 No MCB SPN ,6 to 32 Amps, 250 volts with 'C' curve, to be fixed on pole with clamp.
Dismantling and taking down unserviceable PVC Junction boxes of any size, any description from 09/11 metre high steel tubular or PCC electric pole all as specified and directed
Dismantling and taking down serviceable CFL street lights fitting of any type, any description and of any capacity from 09/11 metre high steel tubular or PCC electric pole all as specified and directed
Dismantling and taking down OF defective/unserviceable LED street lights fitting and post top lantern/gate lights, flood lights, building security lights of any type and of any description and capacity from 09/11 metre high electric pole and gates.
Taking down unserviceable LED bollard light fitting 1x6 Watt , spike lights, fountain lights and LED Square lights complete all as specified and directed by Engineer in Charge.
Supply & fix in repair LED post top lanterns of 40 Watt rated power and rated CCT 3000k, IP65 aesthatically designed spun Al spigot for mounting LED Driver and spun aluminium canopy which is painted white inside. Epoxy powder coated matt black finish after phosphochromate treatment, weather proof construction having robust design delivers to meet the landscaping needs , Luminaire type,Opaline Model No. CELESTA BGCL 40 W LED, product code- 111538, Make- Bajaj,C&S or equivalent suitabkle to be fixed over galvanised pole of daimeter upto 50 mm, complete all as specified and directed.
Supply & fix in repair LED post top lanterns of 40 Watt rated power and rated CCT 3000K, IP65 aesthatically designed spun Al spigot for mounting LED Driver and spun aluminium canopy which is painted white inside. Epoxy powder coated matt black finish after phosphochromate treatment, weather proof construction having robust design delivers to meet the landscaping needs , Luminaire type,Opaline Model No. BGCT W40 LED WW Make- Bajaj,C&S or equivalent fixed over galvanised pole of daimeter upto 50mm,complete all as specified and directed.
Supply & fix in repair LED post top lanterns of 25 Watt rated power and rated CCT 3000K, IP65 aesthatically designed spun Al spigot for mounting LED Driver and spun aluminium canopy which is painted white inside. Epoxy powder coated matt black finish after phosphochromate treatment, weather proof construction having robust design delivers to meet the landscaping needs , Luminaire type,Opaline Model No. BLPTSP 25 W NW LED Make- Oreint,Bajaj,C&S or equivalent fixed over galvanised pole of daimeter upto 50mm,complete all as specified and directed.
Supply and fix in repair 200 Watt LED flood light with pressure die- cast aluminium housing, complete with all accessories, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural facade highmast and general purposelighting W Turo Floodlight luminaires with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66 Protection fixed in existing clamp and connecting with existing cable, including nuts, bolts and washer etc complete. Make :Havells (Ordering Code - LHFPCZBFP46J200),Bajaj, C&S,Wipro or equivelent approved by GE
Supply and fix in repair 150 Watt LED flood light with pressure die- cast aluminium housing, complete with all accessories, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural facade highmast and general purposelighting W Turo Floodlight luminaires with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66 Protection fixed in existing clamp and connecting with existing cable, including nuts, bolts and washer etc complete. Make :Havells (Ordering Code - LHFPCZBFP46J150),Bajaj, C&S,Wipro or equivelent approved by GE
Supply and fix in repair 100 Watt SMD LED flood light with pressure die- cast aluminium housing, complete with all accessories, Energy saving, environmental friendly, long life, exclusive innovative die-cast aluminium IP65 flood light with high power LEDs as light source, suitable for highlighting architectural facade highmast and general purposelighting W Turo Floodlight luminaires with secondary optics made in pressure die cast housing and heat sink in aluminium extrusion and IP 66 Protection fixed in existing clamp and connecting with existing cable, including nuts, bolts and washer etc complete. Make :Oreint (Product code- LFAP-100-C Code),Bajaj, C&S, Crompton Greaves, Wipro or equivelent approved by GE
Supply and fix in repair LED street light fitting of 90 Watt LED Cat Part No. LHETAXU7IN6J090 IP-66, sealed optic luminaire with housing made of die cast aluminium with smooth finish powder coated for better environmental protection complete all as specified below:- (i) The fixture shall be designed so as to ave lumen maintenance of at least 70% at the end of 70000 hours. (ii) The luminaire should be operable with auto adjustable 120-240 volt supply using the same driver. Ambient temperature at LED should not be more that 70 degree centigrade. (iii) Power factor of the electronic driver should be at least 0.90 abd efficiency of the luminaire to be more than 85%. (iv) The fixture should be dark sky complaint. The fixture should use aluminium, MCPCB printed circuit boards for better thermal management. (v) The luminaire should throw the perfect amount of uniform lught with exactly the desired intensity, and best pole spacing , along with better light control. (vi) The luminaire shall employ indivdual optical lens for the each of the LED's to ensure better uniformity of light distribution. (vii) The fixute should be vibration resistance, if the fixture is also to be used in vibration prone areas like flyovers/bridges. (viii)Heat dissipation should be managed through a built in external heat sink. (ix) Colour rendering index of minimum 65 with color temprature of 4000K. Make : Phillips luxeon or equivalent of Wipro/Havells/Crompton Graves
Ditto as per item No 45 above but 60 watt complete all as specified and directed by EIC Make : (Cat Part No.LHETAXU7PN6J060) or equivalent Cat Part of another approved make
S&F in repairs Decorative LED Bollard light with opel diffuser & alminium reflector of 9 watt with all accessories prewired fixed with PCC with nut/Bolt on exising Location complete all as specified and directed. Make:-Cat Part No.BGBOL 605 9 W LED Bajaj/C&S/ HAVELLS/ PHILIPS/ CG
S&F in repairs Decorative LED Bollard light with opel diffuser & alminium reflector of 9 watt with all accessories prewired fixed with PCC with nut/Bolt on exising Location complete all as specified and directed. Make:-Cat Part No.BGBOL 600 9 W LED Bajaj/ C&S / HAVELLS/ PHILIPS/CG
S&F in repairs Decorative LED Bollard light with opel diffuser & alminium reflector of 6 watt with all accessories prewired fixed with PCC with nut/Bolt on exising Location complete all as specified and directed. Make:-Cat Part No.GRUS-M 6W LED, LTGLCGM6WLED Make: Bajaj/C&S/HAVELLS/PHILIPS/CG
S&F in repair LED security light luminaire 1x25 W having IP-65 protection, with minimum system efficency > 85% made of pressure die cast housing toughened glass in the front and peanut lens for batwing light distribution with excellent thermal management. The filling should have rated CCT 5000K complete with all accessories and all as specified and directed by Engineer in Charge. Make:- cat No.BRLEP-025-LED or equivalent of Havells/ Bajaj/ Philips /CG.
S&F in repair bush and spike LED light luminaire 1x9 W having IP-65 protection, with minimum system efficency > 85% made of pressure die cast aluminium housing toughened glass in the front and peanut lens for batwing light distribution with excellent thermal management. The filling should have rated CCT 5000K complete with all accessories and all as specified and directed by Engineer in Charge. Make:-cat No.BGSBL-9W-LED-WW or equivalent of Havells/ Bajaj/ Philips/CG.
S&F in replacement LED 12 V, 3X3W colourful water proof underwater submersible Fountain lights in RGB Combination of colours, IP 68 complete all as specified and directed by E-in- Charge. Make:- Cat Part No.MJJC-UWL3X3W-12V LED Fountain Lights, with Automatic Controller System of 9 W 3 LED BIG / Havells / Bajaj/ Philips/ CG/ makes specified in Appendix-B of PS.
S&F in replacement LED 12 V, 6 W LED Square false ceiling lights, IP 65 complete all as specified and directed by E-in- Charge. Make:- Cat Part No.MJJC-UWL3X3W-12V LED Fountain Lights, with Automatic Controller System of 9 W 3 LED BIG / Havells / Bajaj/ Philips/ CG/ makes specified in Appendix-B of PS.
S&F in repairs wire mesh net suitable for bollard light fitting of size 0.4m x 0.4m x 0.65m and all the four corner and top bottom angle iron framing of size 15x15x3mm and wire mesh net wire size 1.4mm dia and wire mess square gap 20mm with four no ring of size 10mm dia and tickness 3.0mm and made 5mm hole for inserting the stud size 5 cm long and 4 mm thic with suitable size bolt also welded in the bottom outer side for holding the casing including PCC 1:2:4 of 20 mm aggregate of size with one coat of red oxide primer and one coat blue colour paint all sas specified and directed.
Supply only driver of LED bollard light fitting suitable for model No.MUSCA 6W at certain locations all as specified and directed by Engr in Charge. Make- crompton greaves/Havells/Orient/CG/Bajaj/Phillips
Supply only driver of LED light suitable for existing model -LSTO 30/60 or equivallent in havells, bajaj and oreint suitable for existing LED Street lights all as specified and directed by Engr in Charge. Make- crompton greaves/Havells/Orient/CG/Bajaj/Phillips
Supply only driver of LED light suitable for existing model -LSTO 90 CDL or equivallent in havells, bajaj and oreint all as specified and directed by Engr in Charge. Make- crompton greaves/Havells/Orient/CG/Bajaj/Phillips
M & L for repairing the Existing LED Streeet light drivers for light Model LSTO 30/60 and LSTO 90 CDL by taking down the unserviceable LED street light drivers from the street light and repairing/replacing the unserviceable parts of drivers like internal wiring etc and refitting the same with all connection after making serviceable complete (Note :-Drivers to be paid saperately)
M & L for repairing the Existing LED light Model LSTO 30/60 and LSTO 90 CDL by taking down the unserviceable LED light fitting from the pole and repairing/replacing the unserviceable parts like LED bulb, driver, internal wiring etc and refitting the same with all connection after making serviceable complete (Note :-Drivers to be paid saperately)
Material & Labour for earthing complete in repairs with galvanized iron earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m deep below normal ground connected to GI strip of size 25x4 by means of bolts nuts check nuts and washer of galvanized steel, watering pipe of 20 mm bore, galvanised iron, medium grade, and 40 mm bore galvanised iron light grade for earth wire protection including all excavation earth work in any type of soil, PCC pit with RCC pit cover charcoal salt, funnel complete all as shown in the electrical plate No 3 of SSR part – I and tested on completion.
Disconnecting the existing Unserviceable MCCB from the cable, taking out from the panel board and supply and fix new MCCB triple pole with neutral, 100 Amps, 35 KA breaking capacity suitable for 415 Volt, 50 Hz, 3 phase supply, fixed in existing panel and connecting with existing cable, including nuts, bolts and washer etc complete.
All as per Item no 61.00 above, but 63 Amps MCCB complete.
M & L for servicing and repair of printronix brand straight running target type MTST2009 moving target machine including servicing of all components including TGM 301, TGM 302, BSR, Plug in relay, brush holder, limit switch, PCCU, LCU and all other associated services with the machine like railway track -18 mtrs in length complete all as specified and directed by E-IN-C
S&F in repair digital voltmeter 0-500 volts of size 96x96mm complete all as specified and directed by Engr in Charge. Make : C&S/BHEL/ABB/SIEMENS
S&F in repair digital Ampere meter 0-500 volts of size 96x96mm complete all as specified and directed by Engr in Charge. Make : C&S/BHEL/ABB/SIEMENS
Material and labour for fixing only exhaust fan 450 mm propeller type ventilating fans all as directed and specified
Material and labour for fixing only accessories for exhaust fan 450 mm propeller type ventilating fans all as directed and specified
Material and labour for fixing only double FTL fitting for T-5 lamp 2 x 28 watt Make-Bajaj Cat Part No.160484 all as directed and specified
Material and labour for fixing only FTL fitting for T-5 lamp 1 x 28 watt Make-Bajaj Cat Part No.530447 all as directed and specified
Material and labour for fixing only tubular fluorescent double lapped T-5 lamp 1 x 28 watt Make-Bajaj all as directed and specified
Material and labour for fixing only fluorescent tube light fitting box type 1 x 40 watt with tube road Make-Bajaj all as directed and specified
Material and labour for fixing only HPSV Street light fitting 150 watt Make-Bajaj all as directed and specified
Material and labour for fixing only HPSV Bulb of 150 watt Make-Bajaj all as directed and specified
Supply and fix in repair MH bulb of 150 watt all as directed and specified by engineer in charge
Supply and fix in repair MH bulb of 250 watt all as directed and specified by engineer in charge
Supply and fix in repair electronic ballast of 150 watt cap MH all as directed and specified by engineer in charge
Supply and fix in repair electronic ballast of 250 watt cap MH all as directed and specified by engineer in charge
Supply and fix in repair igniter of cap upto 250 Watt MH all as directed and specified by engineer in charge
S & F in repair flexible conduit suitable for 3 core/1.5 Sqmm/2.5 Sqmm wire
S & F in repair electronic ballast of 18 watt as per existing at site.
S & F in repair electronic ballast of 28 watt as per existing at site.
S & F in repair electronic ballast of 36 watt as per existing at site.
Electricals India
Jinendra Chemicals
Ramdev and Sons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .