Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹68.6 L
EMD Value
₹69,000
Closing Date
21 Nov 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Chief Officer, Kalol Nagarpalika
Selection of Developer for construction, supply, installation, erection, testing and commissioning of a 2 TPD Biomethanation Plant including civil works with Operation & Maintenance (O&M) for 3 years at Kalol Nagarpalika, Gandhinagar.
364297
001
Open
Solid Waste Management
Works
Gandhinagar
3 documents required · 3 mandatory
₹2,832
Chief Officer, Kalol Nagarpalika, Dist.- Gandhinagar
₹69,000
7 Nov 2026
7 Nov 2026
7 Nov 2026
21 Nov 2026
7 Nov 2026
120 days
Name of Work : Selection of Developer for construction, supply, installation, erection, testing and
commissioning of a 2 TPD Biomethanation Plant including civil works with Operation & Maintenance
(O&M) for 3 years at Kalol Nagarpalika, Gandhinagar.
PERCENTAGE RATE TENDER
Description Amount
1 Construction of Pre Processing Shed
2 Construction of Waste Processing Platform
3 Construction of Anaerobic Digestor (120 Cum)
4 Construction of Slurry Tank
5 Construction of Inlet Chamber
6 Construction of Outlet Tank
7 Construction of Drying Beds
Pulper / Shredder – Size/Capacity: 3–5 HP (≈1 m × 1 m); Specification: SS-304 blades,
8 MS body, hopper-fed; Workmanship: vibration-free, anchored on RCC base with proper
earthing; Output/Performance: 200–500 kg/hr waste processing.
Agitator – Size/Capacity: 1–2 HP (tank mounted); Specification: vertical shaft mixer,
9 MS/SS shaft; Workmanship: rigid mounting, proper alignment, noiseless operation;
Output/Performance: uniform slurry mixing and prevents settling.
Gas Holder – Size/Capacity: 50 m³ (≈4 m dia × 4 m height equivalent); Specification:
10 HDPE balloon/MS dome, UV-resistant, gas-tight; Workmanship: anchored on RCC
base, leak-proof installation; Output/Performance: stores 30–40% daily gas (≈50 m³).
Gas Pipeline – Size/Capacity: 1.5–2 inch dia (≈30 m); Specification: GI pipes with
11 fittings; Workmanship: leak-proof joints, proper slope for condensate;
Output/Performance: efficient gas transfer with minimal loss.
Moisture Trap – Size/Capacity: ≈0.5 m × 0.5 m; Specification: MS/SS condensate trap
12 with drain valve; Workmanship: installed at lowest point; Output/Performance: removes
moisture from gas.
Flame Arrester – Size/Capacity: standard inline; Specification: certified biogas safety
13 device; Workmanship: installed in gas line; Output/Performance: prevents flame
Control Valves – Size/Capacity: standard inline; Specification: brass/CI ball valves;
Workmanship: leak-proof installation; Output/Performance: regulates gas flow.
Biogas Burners – Size/Capacity: as required; Specification: biogas-compatible burners;
15 Workmanship: installed with safety fittings; Output/Performance: efficient gas utilization
Electrical System – Size/Capacity: 5–7 kW (≈1.5 m × 1 m panel); Specification: panel,
16 wiring, earthing; Workmanship: proper insulation and installation; Output/Performance:
reliable power supply.
17 Construction of Genset Room
18 Construction of Equipment Room
H₂S Scrubber, Size/Capacity: ~120 m³/day gas (~1.5–2 m height vessel); Specification:
FRP/SS vessel with packing media, corrosion-resistant; Workmanship: proper vertical
installation, leak-proof connections, chemical/media loading; Output/Performance:
removes H₂S up to acceptable limits <100 PPM
Moisture Removal Unit, Size/Capacity:- ~1 m × 1 m skid; Specification:-
20 condenser/dryer type unit, MS/SS body; Workmanship:- inline installation with proper
drainage outlet; Output/Performance:- reduces moisture content in biogas.
Gas Blower, Size/Capacity:- ~1 m × 0.8 m, suitable for 120 m³/day; Specification:- low-
pressure blower, continuous duty motor; Workmanship:- vibration-free mounting,
proper alignment and electrical connection; Output/Performance:- maintains gas flow
and pressure stability.
KALOL NAGARPALIKA, KALOL DIST.- GANDHINAGAR
Name of Work : Selection of Developer for construction, supply, installation, erection, testing and
commissioning of a 2 TPD Biomethanation Plant including civil works with Operation & Maintenance
(O&M) for 3 years at Kalol Nagarpalika, Gandhinagar.
PERCENTAGE RATE TENDER
Description Amount
Biogas Genset, Size/Capacity:- 20–25 kW (~3 m × 1.5 m footprint); Specification:-
biogas engine generator, skid mounted, control panel integrated; Workmanship:-
proper foundation mounting, exhaust system, electrical synchronization;
Output/Performance:- generates ~200–240 kWh/day electricity.
Control Panel, Size/Capacity:- ~2 m × 1 m; Specification:- electrical panel with
23 PLC/basic automation, MCB, relays; Workmanship:- proper wiring, earthing, panel
mounting; Output/Performance:- monitoring and control of plant operations.
Gas Flow Meter, Size/Capacity:- inline; Specification:- digital/analog gas flow meter;
24 Workmanship:- installed inline with proper sealing; Output/Performance:- measures
biogas flow accurately.
Pressure Sensors, Size/Capacity:- inline; Specification:- industrial grade pressure
25 sensors; Workmanship:- proper installation and calibration; Output/Performance:-
monitors gas pressure for safety.
Temperature Sensors, Size/Capacity:- probe type; Specification:- RTD/thermocouple;
26 Workmanship:- properly mounted in digester with sealing; Output/Performance:-
monitors process temperature.
Total Net Amount Rs.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Tender Data.pdf
Schedule-B.pdf
SC-B 002_compressed.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .