Loading…
Loading…
Tender Value
₹81,334
EMD Value
₹2,033
Closing Date
10 Jun 2026, 4:00 pm5d left
USHAR KRISHNAN G
Office of the Assistant Engineer, LID and EW Section, Kalluvathukkal Grama Panchayat
324/25-26 Maintanance of Homeo Hospital -Electrification
2026_LSGD_850180_5
T1/AE/LSGD/KVKL/26-27
Open Tender
Electrical Works
180 days
KALLUVATHUKKAL GP
Please refer Tender documents.
7 documents required · 7 mandatory
₹555
Yes
₹2,033
Yes
3 Jun 2026
3 Jun 2026
12 Jun 2026
3 Jun 2026
10 Jun 2026
3 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1Electrification | ||||||
| 1.001 | 90.2.1.1:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point | - | point | - | - | BI01010001010000000000000515BI0100001114 |
| 1.002 | 90.2.1.7:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point | - | each | - | - | BI01010001010000000000000515BI0100001115 |
| 1.003 | 90.2.1.4:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point | - | point | - | - | BI01010001010000000000000515BI0100001116 |
| 1.004 | 90.2.1.6:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points | - | each | - | - | BI01010001010000000000000515BI0100001117 |
| 1.005 | 90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required. | - | each | - | - | BI01010001010000000000000515BI0100001118 |
| 1.006 | OD526120/2025-2026:Supply and providing heavy duty type 60 cm fan rod | - | each | - | - | BI01010001010000000000000515BI0100001119 |
| 1.007 | OD526057/2025-2026:Supply, conveyance installation testing and commissioning of 230 V, 50 hz, 1800 Lumen, 0.8 pf, 15% THD, 2.5 KV Lighting surge protection type 18 w 1200 mm LED pre-wired light fittings complete with all accessories . directly on wall or ceiling and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire etc as required. | - | each | - | - | BI01010001010000000000000515BI0100001120 |
| 1.008 | OD526059/2025-2026:Supply and fixing cast aluminium stove enameled bulk head fitting with deep drawn anodised aluminium body, epoxy powder coated, heat resistant prismatic glass cover suitable for 12 W LED to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required. | - | each | - | - | BI01010001010000000000000515BI0100001121 |
| 1.009 | OD526055/2025-2026:Supply, conveyance, installation, testing and commissioning of ceiling fans of 1200mm sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required. | - | each | - | - | BI01010001010000000000000515BI0100001122 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.71 MB
Tendernotice_2.pdf
PDF • 0.25 MB
Tendernotice_3.pdf
PDF • 0.25 MB
324elebd.pdf
Tender Documents • 1.88 MB
324fot.pdf
Tender Documents • 0.25 MB
324prel.pdf
Tender Documents • 0.25 MB
342eleaffi.pdf
Tender Documents • 0.23 MB
BOQ_1443305.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid