| 1.00SITC of 25 KVA DG SET | |||||
| 1.00 | OD97432/2023-2024:Supply & Installation of 25 KVA Diesel Generator set including required control devices, protection such as suitable MCCB and earth fault relay using CT in neutral earthing conductor, and accoustic enclosure as per CPCB 4 norms and as per technical details given below on suitable size CC foundation. 1. Engine.a) Make of Engine - Krilosker/ Cummins/ Greaves/ b).Type of Engine - Diesel Engine. c). No. of Cylinders - As per manufactures standards. d). Method of cooling - Water cooled with radiator e). Aspiration - Turbo charged after cooled f). Design - Suitable for generating set operation. g). Out put - Required HP as per manufacturers standards at 1500 rpm under NTP condition. 2). Standard accessories with Diesel Engine a). Fly wheel to suit flexible coupling b.) Close Coupling. c.) Air cleaner. d.) Radiator with fan provided with fan guard e). Fuel Pump. f). Mechanical governor. g). Fuel filter. h.) Lubricating oil filter. i.) Exhaust silencer. j). Exhaust Muffler k). Battery Charging Generator 3.) Engine Instrument Panel with the following items. a). Starting switch with key or button b). Lubricating oil pressure gauge. c). Water temperature gauge. d). RPM Indicator with hour meter. e). Battery charging ammeter. f). Fuel indicator 4). Safety Controls for Engine a). Trip for low lubricating oil pressure. b). Trip for high water temperature. c). Alarm for low fuel level 6). Brushless Alternator a). Make - Stamford/ LS/ KOEL/Cummins/ KEL b). Type - Self exited and self regulated. c.) Capacity - 25 KVA/ 20 kW @ 0.8 PF d.) System of Voltage - 3 Phase, 415 V, 4 wire system e). Speed - 1500 rpm. f). Voltage regulation band - +/- 5% of rated voltage g). Frequency : 50 Hzh). Insulation - Class F / H The alternator should confirm to IS 4722 and warranted for 3 years. Operation and service manual , spares and tools shall be provided. 8. Fuel Tank Suitable size built in type integrated with the acoustic enclosure with full tank Diesel Fuel connection shall be done as per standards 9. Battery. Suitable capacity fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 10. Supplying and providing 11. standard manual control system including all necessary accessories and meters Acoustic enclosure: As per CPCB norms The DG set should have warranty of 3 years from the date of installation | 1 | each | 5,50,000 ₹5.5 L | 5,41,376.31 ₹5.4 L |
| 1.00 | OD97433/2023-2024:Supply and providing 12V,5A, Automatic Battery charger suitable for 180Ah Battery, having . Full protection against battery overcharging & reverse polarity. Over voltage, overload & short circuit protection, reverse battery protection. Battery
connecting terminals with lead wire, Float and Boost Charging Mode , LED Indication for charger status indication, etc: and giving necessary connections as required . | 1 | each | 5,000 ₹5,000 | 4,806.52 ₹4,806.52 |
| 1.00 | OD97434/2023-2024:Charges for conducting load test of 25 KVA DG set at standardized Factory bed as per standard norms and condition. ie in various steps load up to full load for 3 hours & 10% over load for 20 minutes and the rate includes hire and rent of test bed equipment's, labour charges ,loading and unloading and fuel etc.The test certificate should be given the client in standard format. | 1 | each | 1,500 ₹1,500 | 1,437.5 ₹1,437.50 |
| 1.00 | 14.2:Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres. | 3 | cum | 500 ₹1,500 | 460.12 ₹1,380.36 |
| 1.00 | 14.8:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. | 1 | cum | 10,000 ₹10,000 | 9,367.85 ₹9,367.85 |
| 1.01 | 14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels. | 1 | cum | 10,000 ₹10,000 | 9,182.45 ₹9,182.45 |
| 1.01 | OD97435/2023-2024:Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels including labour charges | 3.5 | sqm | 1,000 ₹3,500 | 940.82 ₹3,292.87 |
| 1.01 | OD133394/2023-2024:Steel reinforcement for RCC work including straightening , cutting , bending and placing in position and binding all complete. | 30 | per kg | 200 ₹6,000 | 129.12 ₹3,873.60 |
| 1.01 | OD97436/2023-2024:Supply and providing following size M. S. pipe - 5mm thickness complete with
suitable size 12mm flange coupling with minimum 4/5mtr using allied packing with
MS bolt with washer and rising the same on the wall/ parapet using chain pullies,
scaffoldings, supports with M.S angles/channels etc. including painting the pipe with
one coat of zinchromate primer over a coat of high temperature resistance alu. paint
etc. for extending the exhaust pipe of the newly errected D. G. sets. 65 mm dia or
nearest size B class MS pipe | 3 | each | 2,600 ₹7,800 | 2,532.71 ₹7,598.13 |
Tender Value
Refer Docs
EMD Value
₹19,873
Closing Date
11 Nov 2025, 3:00 pmClosed
Assistant Executive Engineer
PWD Electrical Subdivision, Kottayam
DEPOSIT Supply Installation Testing and Commissioning of Diesel Generator set at District Jail Kottayam DG set General Electrical Work
2025_PWD_818400_1
ESDK_ET_121_2025-2026
Open Tender
Electrical Works
180 days
Kottayam
Please refer Tender documents.
10 documents required · 10 mandatory
₹1,755
₹19,873
24 Dec 2025
3 Nov 2025
13 Nov 2025
3 Nov 2025
11 Nov 2025
3 Nov 2025
Amount
SITC of 25 KVA DG SET
OD97432/2023-2024:Supply & Installation of 25 KVA Diesel Generator set including required control devices, protection such as suitable MCCB and earth fault relay using CT in neutral earthing conductor, and accoustic enclosure as per CPCB 4 norms and as per technical details given below on suitable size CC foundation. 1. Engine.a) Make of Engine - Krilosker/ Cummins/ Greaves/ b).Type of Engine - Diesel Engine. c). No. of Cylinders - As per manufactures standards. d). Method of cooling - Water cooled with radiator e). Aspiration - Turbo charged after cooled f). Design - Suitable for generating set operation. g). Out put - Required HP as per manufacturers standards at 1500 rpm under NTP condition. 2). Standard accessories with Diesel Engine a). Fly wheel to suit flexible coupling b.) Close Coupling. c.) Air cleaner. d.) Radiator with fan provided with fan guard e). Fuel Pump. f). Mechanical governor. g). Fuel filter. h.) Lubricating oil filter. i.) Exhaust silencer. j). Exhaust Muffler k). Battery Charging Generator 3.) Engine Instrument Panel with the following items. a). Starting switch with key or button b). Lubricating oil pressure gauge. c). Water temperature gauge. d). RPM Indicator with hour meter. e). Battery charging ammeter. f). Fuel indicator 4). Safety Controls for Engine a). Trip for low lubricating oil pressure. b). Trip for high water temperature. c). Alarm for low fuel level 6). Brushless Alternator a). Make - Stamford/ LS/ KOEL/Cummins/ KEL b). Type - Self exited and self regulated. c.) Capacity - 25 KVA/ 20 kW @ 0.8 PF d.) System of Voltage - 3 Phase, 415 V, 4 wire system e). Speed - 1500 rpm. f). Voltage regulation band - +/- 5% of rated voltage g). Frequency : 50 Hzh). Insulation - Class F / H The alternator should confirm to IS 4722 and warranted for 3 years. Operation and service manual , spares and tools shall be provided. 8. Fuel Tank Suitable size built in type integrated with the acoustic enclosure with full tank Diesel Fuel connection shall be done as per standards 9. Battery. Suitable capacity fully charged battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 10. Supplying and providing 11. standard manual control system including all necessary accessories and meters Acoustic enclosure: As per CPCB norms The DG set should have warranty of 3 years from the date of installation
OD97433/2023-2024:Supply and providing 12V,5A, Automatic Battery charger suitable for 180Ah Battery, having . Full protection against battery overcharging & reverse polarity. Over voltage, overload & short circuit protection, reverse battery protection. Battery connecting terminals with lead wire, Float and Boost Charging Mode , LED Indication for charger status indication, etc: and giving necessary connections as required .
OD97434/2023-2024:Charges for conducting load test of 25 KVA DG set at standardized Factory bed as per standard norms and condition. ie in various steps load up to full load for 3 hours & 10% over load for 20 minutes and the rate includes hire and rent of test bed equipment's, labour charges ,loading and unloading and fuel etc.The test certificate should be given the client in standard format.
14.2:Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres.
14.8:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
OD97435/2023-2024:Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels including labour charges
OD133394/2023-2024:Steel reinforcement for RCC work including straightening , cutting , bending and placing in position and binding all complete.
OD97436/2023-2024:Supply and providing following size M. S. pipe - 5mm thickness complete with suitable size 12mm flange coupling with minimum 4/5mtr using allied packing with MS bolt with washer and rising the same on the wall/ parapet using chain pullies, scaffoldings, supports with M.S angles/channels etc. including painting the pipe with one coat of zinchromate primer over a coat of high temperature resistance alu. paint etc. for extending the exhaust pipe of the newly errected D. G. sets. 65 mm dia or nearest size B class MS pipe
OD97437/2023-2024:Supply and filling high speed Diesel for generator
OD220400/2024-2025:Supply and providing 63A 4P Motorized change over (HPL Make ATS0634POS/ L andT/Socomec make) with ATC controller unit, Power supply/control contractor and wire way kit including control wiring for auto manual operation for DG starting/stoping in the existing Panel board etc as required
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.3:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardSupply and providing 'U' section PVC beeding in the panel board
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD115921/2023-2024:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia
OD115922/2023-2024:upply and providing Blue colour LED indicator lamp, AC/DC, 22.5 cm cut out dia-
OD97442/2023-2024:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 1.50 sq mm single run with required sockets. conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
OD97447/2023-2024:Supply and installation of ABC type fire extinguisher 5kg capacity consisting of M.S cylindrical body, squeeze lever discharge valve fitted with pressure indicating gauge internal discharge tube, 30cm long high pressure discharge hose, nozzle etc.
OD97448/2023-2024:Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required.
OD97449/2023-2024:Painting letters or figuresof the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required 2.50 cm, 4 cm or 5 cm height
OD97450/2023-2024: Supply and providing 2mm thick Elastomeric fire retardant insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength including painting in ground with suitable synthetic adhesive.
90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface
1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
90.11.1.15:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way, Double door
90.16.1.1:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
90.16.2.1:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.15.mm dia. G.I pipe ( medium class)
90.16.1.5:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.75 mm copper conductor (6 SWG)
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
90.16.5.5:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.75 mm (6 SWG)
OD97445/2023-2024:Supply and providing brass bolt and nut 25x3mm
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
90.12.5.41:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 16 sq mm
OD97446/2023-2024:Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required - 25 x 6 mm brass bolt & nut
OD220389/2024-2025:Supply and providing and fixing 63A TPN disconnector fuse switch unit in a sheet steel enclosure with ISI marked HRC fuses on wall/angle iron frame including drilling holes in the frame, making connections, etc. as required Materia
OD220391/2024-2025:Supply and fixing 63A Cutout Fuse with 25/40/50A HRC Link connection in existing meter board
OD220392/2024-2025:Supplying and fixing 63 A, 2 Way neutral links mounted on DMC/SMC base with connections in existing meter board
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD220417/2024-2025:Supply, conveyance, installation, testing and commissioning of Bulk head light fittings directly on wall including giving connections with required length of 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS making good the damages, colour washing etc as required.
OD220418/2024-2025:Supplying and fixing 9W LED Bulb. as required.
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
90.6.6.2:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.2.50 sq mm
OD97452/2023-2024:Charges for preparation of Electrical/fire Drawing per A3 sheet first copy
OD97451/2023-2024:Copying charges of Electrical/fire Drawing per A3 sheet additional copies
OD220385/2024-2025:Provision for correcting the existing installation as per the direction from electrical inspectorate after submitting drawing for approval and inspection (The item rate as per the present DSR with quoted variation) Non competition item App rate Rs 15000.00
All Star Electricals (BID ID -2435263)
Bidder Name
M Y ASSOCIATES
All Star Electricals
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1371645.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Document
0.05 MB
Tender Documents
Tender Documents • 1.63 MB
BOQ
BOQ • 0.35 MB
Additional Documents
Additional Documents • 0.03 MB
Additional Documents
Additional Documents • 0.13 MB
Download all tender documents and submit your bid