Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹93.5 LAccepted-AOC 3A GAYATRI SADAN 2060 SADASHIV PETH NEAR S P COLLEGE PUNE MAHARASHTRA | PUNE | PUNE | MAHARASHTRA | 411030 | L1 | Accepted-AOC As per approval of TEC Report by the competent authority | |
| 2 | L2₹94.5 L+₹1.0 L (1.09%)Rejected-Finance 24 4 D SECTOR GOVINDPURA INDUSTRIAL AREA BHOPAL 462023 | BHOPAL | BHOPAL | MADHYA PRADESH | 462023 | L2 | Rejected-Finance As per approval of Competent Authority | |
| 3 | L3₹98.8 L+₹5.3 L (5.70%)Rejected-Finance | L3 | Rejected-Finance As per approval of Competent Authority | |
| 4 | L4₹99.7 L+₹6.2 L (6.60%)Rejected-Finance Y 51 GF OKHLA INDUSTRIAL AREA PHASE II DELHI 110020 | DELHI | SOUTH DELHI | DELHI | 110020 | L4 | Rejected-Finance As per approval of Competent Authority | |
| 5 | L5₹1.2 Cr+₹30.7 L (32.8%)Rejected-Finance 101 102 CHAMPAKLAL UDYOG BHAVAN SION EAST MUMBAI 400 022 | MUMBAI | MUMBAI | MAHARASHTRA | 400022 | L5 | Rejected-Finance As per approval of Competent Authority |
Tender Value
Refer Docs
Closing Date
4 Jun 2021, 6:55 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Dy. General Manager (PnC),
Dy. General Manager (PnC),Parbati HE Project, Stage-II, Parbati Complex, Nagwain, Distt. Mandi (H.P), Pin - 175 121
Restoration (repairing, dismantling, installation, testing and commissioning of supplied spares) of damaged fire detection and protection System (FDPS) in Power House of Parbati HE Project (Stage-II) (PROC-1857)
2021_NHPC_628999_1
NH/PP-II/PROC/1857/2021
Open Tender
Miscellaneous Works
Works
150 days
Power House of PHEP-II, Suind, Sainj, Kullu(H.P.)
As per Tender Document
8 documents required · 8 mandatory
₹1,180
NHPC Limited
Exempted
24 Aug 2021
5 May 2021
9 Jun 2021
5 May 2021
4 Jun 2021
5 May 2021
120 days
Fire Hose reel 25 mm 40 mtr, wall mounting type, Swinging type, Operating pressure:10.5 Kg/cm², Flow rate: 24 LPM @ 7 Kg/cm²
Hose Box Double Door, Wall mounted, For accommodating 2 Nos. 15 Mtr Hoses and one nozzle, Sizes : Width 750mm x Length 600mm x Deep 250m, Material: MS & Glass
Branch Pipe , SS as per IS 903, Instantaneous Male Inlet: 63mm, NozzleSize:20 mm.
MCC PANAL as per the drawing attached (Drawing No: 14011266E)
1C X 300 Sq MM-Aluminum Cables FR HR PVC Armoured LT cable
3.5C X 185 Sq MM-Aluminum Cables FR HR PVC Armoured LT cable
3.5C X 70 Sq MM-Aluminum Cables FR HR PVC Armoured LT cable
4C X 16 Sq MM-Aluminum Cables FR PVC Armoured LT cable
4C X 6 Sq MM-Copper Cables FR PVC Armoured LT cable
1P X 1.5 Sq. MM-Copper Cables FRLS PVC Armoured LT cable
MCP, Notifier,NBG-12LX, Normal operating voltage:24 VDC,Maximum SLC loop voltage:28.0 VDC, Type:Pull Type,Mounting: Wall
MONITOR MODULE, Notifier, FMM-101, Nominal operating voltage: 15 to 32VDC, Average Operating Current: 375μA, 600 μA Max. (Communicating, IDC Shorted), EOL resistance: 47K Ohms
HOOTER, NOTIFIER, P2R, Operating voltage:24 V DC supply, Sound level of hooter:88 Db
CONTROL MODULE, Notifier, FCM-1, Nominal operating voltage: 15 to 32VDC, Maximum SLC current draw: 6.5mA
FAULT ISOLATOR MODULE, NOTIFIER, ISO-X, No. of addressable devices between isolators-20 Nos,Operating Voltage: 15-32 VDC, Stand-By Current: 450μA
2 Loop panal, Notifier 3030 / NFS 640
Repeater Panal, Operating Voltage: 24V DC, NOTIFIER,LCD-160, Type: Network Control Annuciator
Gate Valve 200NB,CS, Class:150, End Connection: Flanged end, Flange to flange distance: 295mm, Pressure: Upto12Kg/cm²
Gate Valve 80 NB, CS, Class:150, End Connection: Flanged end, Flange to flange distance: 200mm,Pressure: Upto12Kg/cm²
Multisensor detector, Notifier FAPT-851, Photoelectric, thermal, Operating Temperature: 32°F to 100°F (0°C to 38°C)
Control cable (2C x 2.5 Sq.mm)-Copper Armoured FRLS PVC Cable (with copper drain wire)
Power cable (24V DC) (2C x 2.5 Sq.mm)-Copper Armoured FRLS PVC Cable (with copper drain wire)
LHS cable, Type: Twin conductor digital heat sensing cable, suitable for maximum ambient of 70° C, Insulation: Thermoplastic, No. of core: 2 Nos, Conductor Dia: 0.9mm,Response time: 5sec)
Beam Detector (transmitter & receiver) Projected Beam Type, Detection Range:5– 100 meters, Operating Range:10.2 to 32 VDC,Operating Temperature Range:-22°F to +131° F (-30°C to 55°C)
Sprinkler Std response 79 ⁰ C (5mm glass blub), Pendent Type, Sprinkler K factor: 80
Air release valve 25 mm, End Connectors: flanged male threaded, Working Pressure: 7.7 Kg/Cm², Material: Brass
Telephone Handset ( BPL 7110N Corded Landline Phone or equivalent)
Telephone conduit, 25mm dia PVC conduit including-a) PVC saddle 25mm with base – 1520 Nos. b) Screw 3/4" – 1500 Nos. c) 90° PVC bend -90 Nos.
Telephone cable, 2 pair 0.5mm² Unarmoured
Galvanized pipe Size 100NB, Working Pressure: 06 Kg/cm²
Galvanized pipe Size 80NB, Working Pressure: 06 Kg/ cm²
Galvanized pipe Size 50NB, Working Pressure: 06 Kg/ cm²
Galvanized pipe Size 40NB, Working Pressure: 06 Kg/ cm²
Galvanized pipe Size 25NB, Working Pressure: 06 Kg/ cm²
Galvanized pipe Size 25NB Working Pressure: 06 Kg/ cm² for Detection Line
Deluge Valve Assembly Size 100NB, Working Pressure: 06 Kg/ cm²
Gate Valve Size 100NB, Working Pressure: 06 Kg/ cm²
Gate Valve Size 25NB, Working Pressure: 06 Kg/ cm²
Y-Type Strainer Size 100NB, Working Pressure: 06 Kg/ cm²
HVW Spray Nozzle
Quartzoid Bulb Detector
Pressure Switch
Solenoid Valver
Limit Switch
Deluge Valve Local Control Panel
Seamless MS pipe Size 200MM as per Schedule 40 having working pressure: 06 Kg/cm²
Seamless MS pipe Size 100MM as per Schedule 40 having working pressure: 06 Kg/cm²
Seamless MS pipe Size 80MM as per Schedule 40 having working pressure: 06 Kg/cm²
Seamless MS pipe Size 25MM as per Schedule 40 having working pressure: 06 Kg/cm²
Repairing/servicing of gate Valve
Restoration (repairing, dismantling, installation, testing and commissioning of supplied spares) of damaged fire detection and protection System (FDPS) in Power House of Parbati-II Power Station
BANSAL LABORATORIES AND EQUIPMENTS PRIVATE LIMITED
apexfireguardengineer
M/S ADVENT ELECTRIC TECHNOLOGIES PVT LTD
M/S.Newage Fire Protection Engineers Pvt Ltd,
DES TECHNICO LIMITED
stage.html
html • 0.06 MB
technical_661912.pdf
PDF • 0.36 MB
techsummary_661912.pdf
PDF • 0.42 MB
finance_661912.pdf
PDF • 0.51 MB
BOQ Comparative Chart
xlsx • 0.02 MB
finsummary_661912.pdf
PDF • 0.34 MB
LOA_Ultra.PDF
PDF • 2.42 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .