Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.7 LAccepted-Finance | L1 | Accepted-Finance QUALIFIED | |
| 2 | L2₹4.8 L+₹4,960 (1.05%)Accepted-Finance | L2 | Accepted-Finance QUALIFIED |
Tender Value
₹5.3 L
EMD Value
₹10,700
Closing Date
8 Jan 2025, 12:00 pmClosed
Executive Engineer, PDD kargil
Baroo, kargil
Creation of 100 KVA Substation along with HT Line and underground LT Cabling at Jamia Masjid, Sankoo.
2025_PDNRE_15355_1
E-NIT NO 121 of 2024-25
Open Tender
Electrical Works
Works
15 days
Sankoo Kargil
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Executive Engineer, EDD, kargil
₹10,700
9 Jan 2025
2 Jan 2025
9 Jan 2025
4 Jan 2025
8 Jan 2025
7 Jan 2025
Creation of 100 KVA Substation along with HT Line and underground LT Cabling at Jamia Masjid Sankoo.
11/0.433kV, 3-phase 100 kva Distribution Transformerswith Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound upto 200kVA, Copperwound for63kVA or higher kVA with LV Cable Box having detachable Aluminiumratings) , and Gland plate ( to be Provided by Department)
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp,Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
120 Sqmm Cable,1.1kV Grade, PVC Insulated Stranded ConductorFRLS type
9 Mtr. Long Pole,ST-410 SP33) ( to be Provided by Department)
33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative,creepage distance 900mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
LT Distribution box for 100KVA DTR MCCB for incomer & SFU's for outgoing Circuits
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Cement bottoming 1:2:4 mix as per REC standards .5cum/pole
Painting of Poles Red Oxide
Painting of Poles Aluminium Paint
3PH 4W Prodigy meter
Sundry items like aluminium lugs, Jumpers,binding Tape,
9 Mtr. Long Pole( ST-410 SP33) ( to be Provided by Department)
GI V cross-arm with top Bracket including clamp/GI Channel X-arm including clamps and braces.
30 mm² ACSR Conductor ( to be Provided by Department)
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Red Oxide
Aluminium Paint
Cement bottoming 1:2:4 mix as per REC standards .5cum /pole
120 Sqmm Cable,1.1kV Grade, PVC Insulated XLPE Armoured Stranded ConductorFRLS type
HDPE/PVC Pipe suitable for 120 Sqmm Cable.
Execution of Cable Trench including refilling of Trench 170 ft x 3 ft x 3 ft
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .