Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.5 LAccepted-AOC | L1 | Accepted-AOC accept | |
| 2 | L2₹7.4 L+₹3.1 L (72.0%)Rejected-AOC | L2 | Rejected-AOC reject | |
| 3 | L3₹9.9 L+₹5.6 L (128.5%)Rejected-AOC 00 INFRONT OF S R K PG COLLEGE KOTLA ROAD OM MARKET FIROZABAD UTTAR PRADESH 283203 | FIROZABAD | UTTAR PRADESH | 283203 | L3 | Rejected-AOC reject |
Tender Value
₹3.5 L
EMD Value
₹3,550
Closing Date
29 Sept 2023, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE EWC
Bareilly
Increasing capacity Bisauli Tehsil
2023_MVVNL_841563_2
49/EWC(B)/2023-24
Open Tender
Electrical Works
Item Rate
90 days
Pilibhit
As per tender form
3 documents required · 3 mandatory
₹1,180
SE EWC
₹3,550
19 Jan 2024
23 Sept 2023
30 Sept 2023
23 Sept 2023
29 Sept 2023
23 Sept 2023
Amount
Loading, unloading and safe carriage of the following materials from any Electy. Store Center of Electricity store division of Bareilly zone.
M.S. Channel 125x65mm
M.S.Angle 75x75x8mm
33 KV Lightening Arrestor
33 KV 400 A Bus Isolator
Control pannel I/C for 33 KV Single T/F
33 kv O/D CT CTR 200/100/1
11 KV VCB O/G CTR 200/100/5A
33KV Fuse Set.
Battery charger & 01 battery set for 24V.
11 KV 3x300 mm2 XLPE Cable
11 KV Cable jointing Kit 3x300 mm2 I/D
11 KV Cable jointing Kit 3x300 mm2 O/D
Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per details given below.
Making of triangular bridge by using MS electrode, GI strip 50x6mm and GI Pipe 40 mm dia with providing of well type pipe earthing upto 15 Mtr. depth below ground level including welding etc. by boaring process at T/F neutral, LA and newly erected structure including cost of GI pipe of size 40 mm dia 15 mtr. long of ISI mark.(all the required material will be supllied by the contractor).
Supply of GI strip of size 50x6mm for earthing of all newly erected structures and equipments in switchyard including cutting, fixing & proper welding with equipments. All LA will be seprately earth also as per RESPO norms. (All the required materials will be provided by firm.)
Fabrication, erection and grouting of the following structures as per RESSPO/ Approved Drawing and its, plinth 30cm above ground leval as directed by the Engineer Incharge (All steel sections will be provided by Deptt).
33 KV fuse structure
Installation of followig equipments on their respective structures including mechanical & electrical fixing after proper adjustment on their structure.
33 KV Bus Isolator
Lightening Arrestor
33 KV Fuse Set
Dismentaling of existing following damage equipments on their structure.
33 KV Bus Isolator
33 KV Lightening Arrestor
33 KV Fuse Set
Complete laying and termination of copper control cables from 10 MVA power T/F, 33 KV VCB, 33 KV CT in the out door switch yard to the existing transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings, including cost of testing of transformer, VCB, CT, relay pannel & proper relay settings as per requirement etc.
Control Cable 4x2.5 mm2
Control Cable 2x2.5 mm2
Laying of 11KV cable of different size from power T/F to control room I/C . 11 KV Cable will be layed in brick trench constructed below 750mm to the ground level over the ganga sand. brick trench will be constructed by Ist class bricks covering three sides of cable, after laying 11 KV Cable brick trench will be filed by Ganga sand & then will be covered by bricks & backfill of soil over cable trench as per RESPO norms.
Termination of 11 KV 3x300sqmm size XLPE cable by filling 11 KV heat shrinkable type cable boxes including hoisting of cable and proper connection with bus bar gantry and bus isolator by providing suitable connectors.
Repairing of existing 33KV VCB in switchyard including repalcement of all required accessories as motor, intrruptor etc. All type of material should be provided by the firm.
Erection & testing of 1 No. Single T/F Control penel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
Erection of 11 KV outgoing panels (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
Safely shifting and dragging of 33/11 KV 5 MVA transformer from its plinth to safe site at Sub-station. Including its proper disconnecting of HT, LT side connection, neutral , Body earthing etc.
Shifting and dragging of 33/11 KV 10 MVA transformer from road side to its plinth alongwith its erection including fixing of all assessories and top-up of T/F oil.
Carriage of old scrap/dismentaling material from site to store center Badaun.
Repairnig of swichyard fencing complete in all respect, including cost of welding painting etc.
M/S TIWARI TRADING COMPANY
SHREE KRISHNA TRADING CO
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .