Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
| 2 | Admitted-Fee/PreQual/Technical/Finance 3 19 ERANEESWARAN KOIL STREET ERNAVOOR CITY CHENNAI THIRUVALLUR TAMIL NADU 600057 INDIA | CHENNAI | TAMIL NADU | 600057 | Admitted-Fee/PreQual/Technical/Finance |
| 3 | Admitted-Fee/PreQual/Technical/Finance | Admitted-Fee/PreQual/Technical/Finance |
Tender Value
₹1 L
Closing Date
15 Sept 2022, 11:00 amClosed
Managing Director
Dharmapuri Dist. Co-operative Sugar Mills Ltd in Palacode - 636 808
Co. generation plant 110 KV switch yard breakers Servicing
2022_TNCSF_249499_1
DDCSM/183/Engg./2022-23/D1
Open Tender
Maintenance Services
Works
30 days
DDCSM - Palacode
Please refer Tender documents.
1 document required · 1 mandatory
₹0
Exempted
15 Sept 2022
1 Sept 2022
15 Sept 2022
1 Sept 2022
15 Sept 2022
1 Sept 2022
Amount
SF6-1 (from TNEB side) Make: Crompton Greaves Ltd Switchgear type: 120-SFM-32B Rated voltage: 145 Kv Rated Making capacity: 100kAp Rated Nominal current : 1250A Rated short-circuit breaking current : 40KA Rated Lighting Impulse withstand voltage: 650Kvp Rated SF6 Gas pressure: 7Kg/cm2g (at 20C) Rated coil Voltage (Closing & Tripping): 110VDC Rated short-circuit time current : 40KA for 3 second First pole to clear factor: 1.5 Rated operating time : Open 0.3s/Co-3Min-Co Gas Weight /Total weight: 8Kg /1550Kg Motor Voltage : 240V AC Aux. Circuit voltage : 1phase 240V AC Year of manufacturing : 2012 Sl No: 39610C
SF6-2 Make: Crompton Greaves Ltd Switchgear type :120-SFM-32B Rated voltage: 145 Kv Rated Making capacity: 100kAp Rated Nominal current :1250A Rated short-circuit breaking current:40KA Rated Lighting Impulse withstand voltage : 650Kvp Rated SF6 Gas pressure: 7Kg/cm2g (at 20C) Rated coil Voltage (Closing & Tripping): 110VDC Rated short-circuit time current :40KA for 3 second First pole to clear factor:1.5 Rated operating time: Open 0.3s/Co-3Min-Co Gas Weight /Total weight: 8Kg /1550Kg Motor Voltage :240V AC Aux.Circuit voltage: 1phase 240V AC Year of manufacturing :2012 Sl No:39609C
11 KV OUT-DOOR VCB Panal Make :ABB Rated voltage: 12 Kv TYPE: VD412.16.40 Year: 2012/IEC-62271-100 Rated Nominal current breaker :1600A Rated Friquency: 50Hz Insulation level: 28 kv/75kvpk short-circuit Breaking current :44kA rms short-circuit time duration: 3 sec short-circuit making current :110kApk Operating Sequence:Open 0.3s/Co-3Min-Co Rated coil Voltage (Closing & Tripping):110VDC Motor Voltage:240V AC Mass:160kg Instruction manual:1VDU09004-YN
ANNAI KALIKAMBAL ENTERPRISES
J H IRUDHIARAJ CONSTRUCTIONS AND MAINTENANCE CONTRACTOR
stage.html
html • 0.02 MB
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .