Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.4 LAccepted-AOC | ₹16.4 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹21.0 L+₹4.6 L (28.2%)Rejected-AOC GP KIZHAKKAMBALAM KOLENCHERY | THRISSUR | KERALA | 680667 | ₹21.0 L+₹4.6 L (28.2%) | L2 | Rejected-AOC Not being L1 |
| 3 | L3₹21.8 L+₹5.4 L (33.2%)Rejected-AOC | ₹21.8 L+₹5.4 L (33.2%) | L3 | Rejected-AOC Not being L1 |
| 4 | L4₹24.5 L+₹8.1 L (49.1%)Rejected-AOC BIG NO 7 104 MANAKKATTU VAYANAKOM NJAKKAL POST KRISHNAPURAM VIA OACHIRA PANCHAYAT ALAPPUZHA KOLLAM DISTRICT KERALA STATE PIN 690 533 | ALAPPUZHA | KOLLAM | KERALA | 690533 | ₹24.5 L+₹8.1 L (49.1%) | L4 | Rejected-AOC Not being L1 |
| 5 | Rejected-Technical N A | - | - | Rejected-Technical Not enlisted in required category a(ii) |
Tender Value
₹26.5 L
EMD Value
₹53,000
Closing Date
18 Jan 2023, 6:00 pmClosed
GE(I)(CG)KOCHI
GE(I)(CG)KOCHI BUILDING NO.22/2614, OPP. SANTHOM CHURCH MUNDAMVELI POST RAMESWARAM KOCHI-682 507
DAY TO DAY MAINT REPAIR TO INTERNAL EXTERNAL WATER AND ELECTRIC SUPPLY, DG SET, LIGHTNING PROTECTION SYSTEM, SECURITY STREET LIGHTS, AIR CONDITIONERS, FIRE FIGHTING SYSTEM ETC AT ICGS BEYPORE AND CGRA KOZHIKODE
2022_MES_570447_1
GE/CG/8857
Open Tender
Electrical and Maintenance Works
Item Rate
365 days
KOZHIKODE
AS PER NIT/TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
Yes
GE(I)(CG)KOCHI
₹53,000
Yes
4 Mar 2023
21 Dec 2022
25 Jan 2023
21 Dec 2022
18 Jan 2023
6 Jan 2023
21 Dec 2022 - 28 Dec 2022
Amount
Taking down carefully (copper/aluminum) point wiring complete of any type (batten/surface conduit) for light point, fan point, bell point socket point or power point complete with all fitting such as switches, sockets pendants regulators etc complete and making good disturbed surfaces of wall, floor or ceiling with plaster or tiles or roof treatment etc and finishing the surfaces with distemper/white washing/colour washing to match with the existing surface complete all as specified and directed.
Material and Labour for point wiring complete using 1.5 Sqmm PVC insulated unsheathed copper conductor, stranded cable (FR) upto and including working voltage 1100volts grade, drawn through and including non metallic rigid PVC conduit or PVC casing and caping of suitable size including all accessories ISI marked including pressed steel terminal sunken boxes of size 1.2mm covered with 3mm thick plastic laminated sheet ISI marked top cover fixed with Brass screws and unsheathed copper conductor stranded cable(FR) earth continuity wire connected to DBs/sunken boxes/fittings of size 1.5 Sqmm Cross sectional area and all other metal parts with earth dolly for the following:-
(a ) one light point controlled by one switch 5 Amps
(b ) one fan point point controlled by one switch 5 Amps
(c) One 3 pin socket outlet 5 Amps on Independent board
(d ) One 3 pin socket outlet 5 Amps on same board
( e) One bell point controlled by one bell push
Supply and fix Switch piano Flush, single pole, one way 5 amp 230 Volts, AC, with ISI mark complete all as specified and directed.
Supply and fix Bell push, single pole, one way 5 amp 230 Volts, AC, with ISI mark complete all as specified and directed.
Supply and fix Socket outlet 2 in 1, 5 Amps flush type 230 Volts, AC, with ISI mark complete all as specified and directed.
Supply and fix Bell electric Ding Dong 230 Volts, AC, with ISI mark complete all as specified and directed.
All as per item No.2 above but with 2.5 sqmm PVC insulated unsheathed copper conductor for 15 Amps 3 pin socket.
Supply and fix Switch Socket Combination 2 in 1, 5 Amps /16 Amps flush type 230 Volts, AC, with ISI mark complete all as specified and directed.
Attending internal/ external electric complaint for maintenance/breakdown, round the clock for maintenance, checking, fault finding and rectification of fault in LT panels/Overhead HT/LT lines, transformers, switchgears and carry out repairs and resume electric supply complete all as specified and directed by Engineer-in-charge. Note:- (a)Day to day complaint rectified by the Electrician shall be written in complaint register and completion report recorded in complaint register and complaint document slip rectified complaints only will be paid. (b) The spares required for the rectification of fault shall be measured under items 10 to 32.(c). (c) 5 Nos complaints will be measured as one job.
Supply only Switch piano Flush, single pole, one way 5 amp complete all as specified and directed.
Supply only of Socket outlet 2 in 1, 5 Amps flush type complete all as specified and directed.
Supply only Switch Socket Combination 2 in 1, 5 Amps /16 Amps flush type Complete all as specified and directed.
Supply only Bell electric ding dong 230 V complete all as specified and directed.
Supply only Bell push 5 Amps one way complete all as specified and directed.
Supply only Electronic fan regulator 230 volts, step type,2 module, 120 watt ISI Marked complete all as specified and directed.
Supply only Ceiling rose in poly carbonate 3 plates flush type 6 Amps, 250 volts AC complete all as specified and directed.
Supply only Lamp holders bakelite body with back plate suitable for battern fitting/angle fitting complete all as specified and directed.
Supply only of Modular switch, one way, 6Amps, one module complete all as specified and directed.
Supply only Modular switch, one way, 16Amps one module complete all as specified and directed.
Supply only Modular switch, two way, 6 Amps one module complete all as specified and directed.
Supply only Modular socket outlet, 6 Amps, 2/3 pin two module complete all as specified and directed.
Supply only Modular socket outlet, 6 Amps/ 16 Amps, 2 and 3 pin two module complete all as specified and directed.
Supply only Modular Bell push, 6 Amps one module complete all as specified and directed.
Supply only Condenser 2.5 Mfd AC 240V, complete all as specified and directed.
Supply only Condenser 4 Mfd AC 240V, complete all as specified and directed.
Supply and fixing LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed. Make: Bajaj / Havells/Philips/Crompton Greaves.
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed. Make: Bajaj / Havells/Philips/Crompton Greaves.
Supply and fixing LED luminaire 600 mm x 600 mm,35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed. Make: Bajaj / Havells/Philips/Crompton Greaves.
Supply only LED bulb 9 watts, 230 volt complete all as specified and directed. Make: CELS Cat part No CLLC-LP-10 or equivalent in Havells/Philips/Crompton Greaves.
Supply only MCB double pole 240 volt B curve 10 KA 25 Amps capacity complete all as specified and directed. Make: Indoasian/equivalent in Havells or standard.
All as per ser item No 30 above but MCB TP 415 volt C curve 10 KA, rating 16-32 Amps capacity complete all as specified and directed. Make: Indoasian/equivalent in Havells or standard.
All as per ser item No 30 here-in-before but MCB single pole, 6 to 32 Amp 240 volt B curve 10 KA complete all as specified and directed.
Material and labour for Sub main wiring using two runs of single core PVC insulated cable(FR) 4 sqmm copper conductor multi stranded and one run of 4 sqmm copper conductor insulated cable (FR)using as earth wire drawn through and including suitable size PVC Casing and Caping including taking down old aluminium/Copper Sub main wirng complete all as specified and directed. Note- 3 run of 4 sq mm PVC copper wire and One run of PVC casing caping shall be measured and paid as one unit.
Material and labour for Sub main wiring using two runs of single core PVC insulated cable (FR) 6 sqmm copper conductor multi stranded and one run of 6 sqmm copper conductor insulated cable (FR)using as earth wire drawn through and including suitable size PVC Casing and Caping including taking down old aluminium/Copper Sub main wirng complete all as specified and directed. Note- 3 run of 6 sq mm PVC copper wire and One run of PVC casing caping shall be measured and paid as one unit.
Material and labour for Sub main wiring using four runs of single core PVC insulated cable(FR) 6 sqmm copper conductor multi stranded and two runs of 6 sqmm copper conductor insulated cable (FR)using as earth wire drawn through and including non metallic PVC conduit pipe ISI marked of size 32 sq mm including taking down old aluminium/Copper Sub main wirng complete all as specified and directed. Note- 6 run of 6 sq mm PVC copper wire and One run of PVC conduit shall be measured and paid as one unit.
Supply and fix in repairs Distribution board (DB) made out of sheet metal enclosure (CRCA sheet), dust and vermin proof, TPN 4 way, single door, IP-30 protection (4 + 12 module) TPN MCB, 415 V as incomer, SP/DP/TP/TPN as outgoing complete all as specified and directed .
Supply and fix in repairs Distribution board (DB) made out of sheet metal enclosure (CRCA sheet), dust and vermin proof, SPN 4 way, single door, IP-30 protection DP MCB, 240 V as incomer, SP MCBs as outgoing complete all as specified and directed .
All as per ser item No 37 above but SPN 8 way, double door 240 volts
Supply and fix in repairs single pole and neutral enclouser with a two pin and earth plug and socket complete with and including one MCB single pole 20 Amps complete all as specified and directed.
Taking down fan of any type and size after disconnecting, depositing to store yard and Hanging/fixing only after repair/reconditioning fan of any type and size all as directed. NOTE: Repair and reconditioning of fan shall be measured and paid separately under Item Nos.48 to 52.
Collecting unserviceable ceiling fan 1200mm sweep 230V, AC single phase from store yard of AGE E/M and transporting to local market, cutting unserviceable winding from fan stater & rewinding same with super enamelled copper winding wire of existing gauge size including throughly cleaning all the components, oiling greasing & replacement of rusted unserviceable screws, hanging clamps with rubber reel, canopy condensers, bush, bearing & flexible copper connection wire etc complete all as directed. Note : (i) Taking down for repair and refixing after repair work shall be measured and paid under Item No.47 above. (ii) Spare such as Hanging clamps, canopy, condenser and flexible copper connection wire, painting, down rod, bearing, bush, clamps etc shall be measured & paid separatetly under item Nos.53 to 65.
All as per item No 41 above but exhaust fan 300 mm sweep complete all as specified and directed.
All as per item No 41 above but exhaust fan 200/230 mm sweep complete all as specified and directed.
Material and Labour for Scraping down old paint of ceiling fan of any size 1200 mm sweep complete body & blade including down rod filling the cavities with filler and making smooth surface by applying sand paper painting the ceiling fan by means spray gun/brush with two coats of synthetic enamel white paint complete all as specified and directed.
All as per item No 44 above but exhaust fan 300 mm sweep complete all as specified and directed.
All as per item No 44 above but exhaust fan 200/230 mm sweep complete all as specified and directed.
Material and Labour for lathe work for proper filling/fixing of bearing/bushes in the top cover of the fan by filling a layer of matter after blazing & bottom cover of fan complete all as specified and directed.
Supply only Ball bearing Ser No 6201 or 6202 complete all as specified and directed. Make : MDS/SKF/NBL
Supply only Ball bearing Ser No 6203/6204 complete all as specified and directed. Make : MDS/SKF/NBL or as per existing specifications as per sample
Supply only Gun metal bush for ceiling fan complete all as specified and directed.
Supply only Shackle type rubber reel,'U' clamps, bolts,split pin & washer complete all as specified and directed.
Supply only Canopy top/bottom suitable for 20mm dia rod complete all as specified and directed.
Supply only Down rod 300mm long of size 20mm dia ISI marked complete all as specified and directed.
Supply only Fan blades (three leaves)suitable for 1200mm sweep fan make & type complete all as specified and as directed .
Supply only 1.2mm thick mild steel top/bottom cover for ceiling fan any size and make complete all as specified and as directed .
Supply and fixing in repairs Exhaust fan blade (three leaves) of 300/230/200 mmsweep complete as per sample of the following sizes complete all as specified and as directed .
Taking down carefully geyser of any make and capacity 25/50ltrs, dismantling the geyser for inspection, cleaning of tank, repalcement of defective part such as heating element, thermostat switch, spacer ring, safety plug, glass wool, neon lamp, head assembly, rubber gasket, top and bottom cover, inspection plate, copper cable 3 core, 3 pin Top plug, element holding clamp, welding of studs for head assembly, defective inner and outer shell reassembling the geysers with one coat of milky white synthetic enamel spray paint of approved quality after cleaning of all dust rust etc and writing of MES No on the geyser using black paint, Reinstallation of geysers to its original postion complete all as specified. Note : Spare parts such as heating element thermostat switch, spacer ring, heon lamp, head assembly, glass wool, safety plug rubber, gasket, copper cable, top & bottom cover, inspection plate, CP & PVC connection, Plug Top, Outer & Inner shell element holding clamps etc shall be measured & paid for seperately in respective items here in after.
Supply only heating element any type (i.e; Cup,thread or triangular) 1.5 KW, 220/230 volts ISI marked complete all as specified and directed.
Supply only heating element any type (i.e; Cup,thread or triangular) 2.0 KW, 220/230 volts ISI marked complete all as specified and directed.
Supply only Thermostat ISI marked complete all as specified and complete all as specified and as directed .
Supply only Head Assy "Brass" 8 to 9 holes suitable for 25 ltrs capacity all complete all as specified and as directed .
Supply only Safety plug "brass" ISI marked suitable for 25/50 ltrs geyers complete all as specified and directed.
Supply only PVC connections 15mm size for Hot and cold water connection with rubber washer & brass nuts, ISI marked of length 600mm complete all as specified and directed.
Supply only copper flexible 3 core PVC insulated,PVC sheathed FR, ISI marked of size 2.5 sqmm copper conductor complete all as specified and directed.
Supply only geyser inner assembly of brass with inlet/outlet & over flow provision rubber washer suitable for 25 ltrs capacity all as specified and complete all as specified and as directed .
Supply only bottom cover plate in two halves with self toppiry suitable and as per sample complete all as specified and directed. Make :Bajaj, Peeco, Recold/DITZ
Supply only phase indicator red colour circular/rectangular shape as suitable and as per sample complete all as specified and directed.
Supply and fixing in repairs non return brass valve of 15mm bore, ISI marked complete all as specified and as directed .
Supply and fixing in repairs pressure release brass valve of 15mm bore ISI marked complete all as specified and as directed .
Supply only PVC connections 15mm size for Hot and cold water connection with rubber washer & brass nuts, ISI marked of length 450mm complete all as specified and directed.
Supply and fixing in repairs Plug top 3 Pin 15 Amps 230 volts complete all as specified and as directed .
Material and labour for servicing including cleaning of condensor & eveporator coils fins with mild detergent and descaling of condensor coil for split type AC of any make/ capacity after taking down the whole unit and refixing at the existing location or any other new location after servicing all as specified and directed. Note: Spare parts shall be measured and paid separately under relevant item.
Material and labour for Shifting of split type AC existing location to the new location and making good the opening of old location with cement mortor 1:3, treating the wall to matching with existing surfacce finish and making opening holes on brick wall at new location and gap well finish with cement mortor 1:3, making good the wall surface to match with existing surface, installation and commissioning with replacement of insulation of suction & discharge line complete all as directed.
Supply and fix in repairs Printed Circuit Board suitable for 2TR Capacity Split Unit Air Conditioners including remote, etc. all as specified and as directed. NOTE: Make of PCB & remote shall be of existing manufacturer as compatible with the AC.
Supply and fix in repairs Printed Circuit Board suitable for 1.5TR Capacity Split Unit Air Conditioners including remote, etc. all as specified and as directed. NOTE: Make of PCB & remote shall be of existing manufacturer as compatible with the AC.
Disconnecting, dismantling and taking out existing burnt out compressor from Split type Air conditioner 2 TR Capacity and supply and fixing sealed unit compresser of existing capacity 2 TR, single phase, 230 V AC supply initialy filled with compressor oil as speciifed by Engr-in-charge and testing on load for 24 hrs in summer complete all as specified and as directed. Make : LG/ Voltas/ Samsung
Supply and fix in repairs AC blower fan motor for AC suitable for 2 TR AC suitable operate on 230 Volt AC supply at 50 Hz complete all as specified and directed.
Supply and fix in repairs Capacitor 45/50 MFD complete all as specified and directed.
Supply and fix in repairs Drier stainer filter suitable for AC/Water cooler/Refrigertor complete all as specified and directed.
Supply and fix in repairs insulation Nytrile foam insulation suitable for 5/8 inch copper tube as per site requirement of approved make all as specified and directed .
Supply and fix in repairs insulation Nytrile foam insulation suitable for 1/4 inch copper tube as per site requirement of approved make all as specified and directed .
Supply and fix in repairs Copper tube 5/8 inch size as per site requirement of approved make all as spd and directed .
Supply and fix in repairs Copper tube 1/4 inch size of approved make all as specified and directed .
Supply and fix in repairs Evaporator unit (indoor unit ) complete suitable for 2 TR Capacity Split type Air Conditioners 5 star rating with latest ISEER complete all as specified and directed. Make : LG/ Voltas/Goderj
Supply and fix in repair Bracket stand suitable for 2 TR Capacity Split type AC including Fastners, etc. Complete all as specified and directed.
Supply and charging R-22 gas to maintain the required cooling effect as and when required in the split AC/ window type AC & other cooling applinces complete all as specified and as directed.
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 meter in depth for taking out and laying UG cable and getting out, excavated earth, forming bottom surfaces to required level complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and as directed.
Removing excavated soil and depositing to the sides and returning filling in including spreading leveling watering and well ramming in layers n.exc 25cm thick in soft/loose soil after cable is laid complete all as specified.
Supply and fix High density polyethelene (HDPE) pipe of pressure rating 6kg/sq.cm 50 mm dia laid in trenches/wall/floor with all accessories complete all as specified and as directed. Make: Supreme/Finolex/Prince. NOTE: Excavation and earth work shall be measured and paid separately under relevent items.
Supply and fix High density polyethelene (HDPE) pipe of pressure rating 6kg/sq.cm 40 mm dia laid in trenches/wall/floor with all accessories complete all as specified and as directed. Make: Supreme/Finolex/Prince. NOTE: Excavation and earth work shall be measured and paid separately under relevent items.
Supply and lay cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric cable, heavy duty, 1100 volt grade with stranded aluminium conductor cables of following sizes fixed in wall/ roof or laying in trenches etc., 50 Sqmm 3.5 core, 1100 Volts grade, 415 v, 50 Hz including taking out old one complete all as specified and as directed.
All as per item No 92 above but of size 35 Sqmm 3.5 core.
All as per item No 925 above but of size 16 Sqmm 4 core.
All as per item No 92 above but of size 10 Sqmm 4 core.
Supplying and laying 62.5 mm inner dia CPVC pipes Schedule 80 pipes & plain CPVC Schedule 80 fittings and taking down unserviceable pipe complete all as specified.
Supplying and laying 32 mm inner dia CPVC pipes SDR 11 & plain CPVC SDR 11 fittings after taking out unserviceable pipe complete all as specified and directed.
Supplying and laying 25 mm inner dia CPVC pipes SDR 11 & plain CPVC SDR 11 fittings after taking out unserviceable pipe complete all as specified and directed.
Supplying and laying 20 mm inner dia CPVC pipes SDR 11 & plain CPVC SDR 11 fittings after taking out unserviceable pipe complete all as specified and directed.
Supply & Fix in repairs MCCB 4 pole 415 Volts adjustable type of capacity 160 Amps, 36 KA breaking capacity fixed properly at directed location and connecting/testing complete all as specified and directed. Make: Havells or Equivalent in L&T / Legrand.
All as per Item No 100 here-in-before but of capacity 200 Amps, 36 KA complete all as specified and directed. Make: Havells or Equivalent in L&T / Legrand.
All as per Item No 100 here-in-before but of capacity 250 Amps, 36 KA complete all as specified and directed. Make: Havells or Equivalent in L&T / Legrand.
Supply and fixing in repairs shock treatment chart duly mounted on a wooden frame with 5mm thick glass as directed having front area 1.20 Square Metre complete all as specified and directed.
Supply and fixing Cable jointing kit for 11 KV (Earthed) grade cable for straight through Heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm complete all as specified and directed.
Supply and fixing , cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of size 185 sqmm x 3 core including taking down old item, all as specified. Make : 3M M-seal / Raychem / Denson / Cab Seal
Supply and fix XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured,electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed grade, 3 core cross sectional area 185 sq. mm including taking out complete all as specified and directed.
Supply and fix in repairs Copper Air termination rod 12 mm dia single pointed 300mm long along with base plate welded at bottom of termination rod, of size 10 cm long fabricated out of 32 x 6 mm thick Copper strip along with making 9mm dia for fixing in fastners complete all as specified.
Material and labour for general servicing of VCB of capacity 630/400 Amp by drawing out the VCB, removing the dust, general servicing of the mechanism such as lubricating and applying jelly, cleaning the insulators, providing new nuts and bolts etc and recaliberation of relay, remove moisture, replace unserviceable relay, batteries if any, for auxillary supply, re-installing the VCB in its original position, testing and commissioning etc complete all as specified and as directed.
Material and labour for General maintenance /repair of 160 KVA transformers installed at ICGS Beypore and CGRA Kozhikode Sub Stations, including disconnecting the HT/LT cables, earth strips etc. from the transformer, draining the complete oil for removing sludge from the tank and removing the top cover, conservator, expulsion tank etc for detecting the leakage and repairing by welding, replacing all the gaskets & neoprene washers for leakage arresting, the HT /LT bushings if required, refill the oil, top up to required level without any extra cost, reassembling the transformer and testing etc complete all as specified and as directed.
Dehydration / filtration of transformer oils of transformer/switch gears to achive die-electric strength not less than 40Kv for 1 miniute at 4mm gap as per relevent IS using portable filteration plant including testing of oil for die electric strength before and after filtration complete all as specified and directed. Note:- (i) Test results before and after filteration shall be submitted on completion in tripilicate. (ii) Necessary electricity for filtration plant shall be issued by department,required length of cable/switch etc shall be arranged by the contractor.
Supply and topping up new transformer oil into conservator tank/body tank of transformer using portable filtration plant complete all as specified and directed. Note:- (i) The transformer oil for topping up shall be with di electric strength more than 40kv for 1 miniute at 4mm gap. (ii) Oil shall be supplied at site in sealed barrel.
Supply and fix in repairs breather assembly suitable for out door type transformer including taking down u/s from the transformer complete all as specified.
Supply and filling silica gel inside breather assembly of transformer complete all as specified and directed.
Supply and fix in repairs danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white with letters figures and conventional skull and bones in signal red clour and fixed with MS clamps bolts ans nuts of approved size for HT 25x20 cm size complete all as specified and directed.
All as per Item No.114 above but LT 20 X 15 cm size.
Cleaning and preparation of old painted surface of steel pole 9 mtr long excluding planting depth complete and painting with one coat of aluminium paint and making black and white strips with synthetic enamel paint 30 cm height, each alternative strips ,up to 1.5 mtr height and writing pole Nos and applying one coat of cement base paint on PCC coping complete all as specified and as directed.
Cleaning and preparation of old painted surface of LT PCC pole 9 mtr long excluding planting depth complete painting with one coat of aluminium paint to all steel structure such as channel, cross arms , bracings, bracket, clamps, street light fitting anti climbing device including making black & white strips with synthetic enameled paint 30 cm height each alternative strips, upto 1.5 mtr height and writing pole Nos and applying one coat of cement base paint on PCC coping where provided complete all as specified and as directed.
Taking out unserrviceable earthing completely and providing Earthing complete with Galvanized steel earth plate electrode of size 600mmX600mm, 6.00 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below the normal ground level with top edge of the plate not less than 1.5m below normal GL and connected to galvanized earth strip of size 25 x 4 mm by means of bolts, nuts, check nuts and washers of galvanized iron steel all as shown in Electrical Plate No.3 connected to earthing test point, including necessary earth work in any type of soil, PCC earth chamber made in PCC 1:3:6 type C1 (using 20mm graded aggregate), common salt, charcoal, CI funnel, earth pit cover in RCC 1:2:4 type B1 (using 20mm graded aggregates), with 8mm CTD bars @ 100mm c/c in both ways, including necessary form work complete including necessry test on completion all as specified and as directed. Note : The unit rate shall also include for excavation, earth work in hard/dense soil PCC (1:3:6) type C1 pit, RCC cover slab, GI funnel with 40 mm dia watering pipe, wire mesh, 50mm dia light grade GI protection pipe for earth lead etc., complete.
Material and Labour for general servicing of Diesel Engine of DG set of capacity 125 KVA including cleaning of DG Set, greasing, lubrication complete including the following job works mentioned from (i) to (viii) complete in all respect up to the satisfaction of Engineer-in-charge. Note: (a) All T&P items should be brought at site by the contractor. (b) Grease,lubrication are to be measure in general servicing charges of DG set and no extra cost will be paid by Deptt to the contractor. (c) Parts to be replaced shall be measured and paid separately. The makes of spares shall be of respective DG set manufacturer and as approved by Engineer in charge conforming to the OEM machine. (d) The rate quoted shall be excluding servicing of alternator & selt starter which shall be measured and paid separately under relevent items here-in-after. (i) Caliberation of Fuel injection pump (FIP) (ii) Taking out the Self starter to the repair shop and servicing works like replacement of brushes, replacement of burnt wire etc. (iii) Taking out the Fuel tank, removing all the sediments from the tank, pressure cleaning, final cleaning with suitable cleaning materials and chemicals/lotion drying, welding and other repair work for any damage to tank, testing for leakage and refixing complete. (iv) Taking out the radiator, removing all the sediments from the radiator tubes, pressure cleaning, final cleaning with suitable cleaning materials and chemicals/lotion, drying, welding and other repair work for any damage to tank, testing for leakage and refixing complete. (v) Dismantling old unservicable Air cleaner elements and supply and fixing new Air cleaner elements inner and outer including dust cap recommended by the maunufacturer complete. (vi) Dismantling old unservicable oil filter elements and supply and fixing new oil filter recommended by the maunufacturer complete. (vii) Dismantling old unservicable fuel filter elements and supply and fixing new fuel filter recommended by the maunufacturer complete. (viii) Cleaning of carbon from silencer pipe and exhauist pipe and two coats od aluminium paint over one coat of red oxide primer.
All as per item no. 119 but for DG Set of capacity 62.5 KVA.
All as per item no. 119 but for DG Set of capacity 50 KVA.
All as per item no. 119 but for DG Set of capacity 40 KVA.
Supply and fix PVC flexible pipes with brass end connections special grade for fuel and engine oil.
Supply only generator battery lead of copper PVC insulated standard (heavy duty) for DG set complete all as specified and as directed .
Supply only Grease of standard make complete all as specified and directed.
Supply only Lubricating oil (10W40) complete all as specified and directed. Make : Castrol/Hindustan Petroleum/Indian oil
Supply only Coolant oil standard as recommended by Engine Manufacturer. Make : Castrol/Hindustan Petroleum/Indian oil
Supply and fixing in repairs Heavy duty Acid lead battery 12 volt, capacity of 180 Ah for DG set 160 KVA complete all as specified and directed. Make: EXIDE or Equivalent in Luminous/Amron.
All as per item no. 128 but 12 V 90 Ah
All as per item no. 128 but sealed Lead-Acid Battery, type EP 42-12, Volts 12 V, Capacity 42 AH. Suitable for 30 KW, UPS system.
Disconnecting existing PVC water tank not exceeding 250 Ltrs capacity and Cleaning water tank with wire brush, cloth, bleaching powder, removing dirt, scale from the tank and from mouths of circulating pipes etc through drain pipe or by manually all as specified and directed by Engineer-in-Charge (Tank shall be cleaned quarterly and writing with white paint over black base on the tank as "TANK CLEANED ON" with date with 5 cm high letters/ numbers and reconnecting and refixing in the same position after cleaning and testing for leakages of service tanks complete all as specified and directed.
All as per item No. 131 above but exceeding 250 but not exceeding 500 Ltrs capacity.
All as per item No. 131 above but exceeding 500 but not exceeding 1000 Ltrs capacity.
All as per item No. 131 above but exceeding 1000 but not exceeding 2000 Ltrs capacity.
Taking down existing unserviceable water tank after disconnecting water supply line and supply and fix new Rotational moulded polyethylene water storage tanks having capacity 500 Ltrs (cylindrical vertical with closed top) hoisted and fixed in position all as specified and directed.
All as per item No. 135 above but 1000 Ltrs capacity.
All as per item No. 135 here-in-before but 2000 Ltrs capacity.
Supply and fix in repairs Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed 25 mm bore complete all as specified and directed.
All as per item No. 138 here-in-before but 40 mm bore
All as per item No. 138 here-in-before but 50 mm bore
Taking out old unserviceable Foot valve and supply and fixing new CI Foot valve 100mm dia approved make including jointing complete all as specified and directed.
All as per item No. 141 here-in-before but 80mm dia
Supply and fixing in repairs CI sluice valve both end flanged, gun metal spindle, iron wheel head including jointing, size of Sluice Valve Class PN 1.6 , 100 mm dia approved make complete all as specified and directed.
All as per item No. 143 above but 80 mm dia.
Supply and fixing in repairs cast iron non return valve, 100 mm dia approved make complete all as specified and directed.
Supply and fixing galvanised steel water tubing medium grade 25 mm bore including all necessary fittings such as bends, elbows, short piece connections, backnuts, caps plugs, unions couplings, flanges, sockets etc, laid in trenches including inter connection between buildings/pumps/pump houses and taking out old existing GI tubing complete all as specified and as directed.
Supply and fixing galvanised steel water tubing medium grade 40 mm bore including all necessary fittings such as bends, L bows, short piece connections, backnuts, caps plugs, unions couplings, flanges, sockets etc, fixed to wall/floor/ceiling including inter connection between buildings/pumps/pump houses and taking out old existing GI tubing complete all as specified and as directed.
Supply and fixing galvanised steel water tubing medium grade 50 mm bore including all necessary fittings such as bends, L bows, short piece connections, backnuts, caps plugs, unions couplings, flanges, sockets etc, laid in trenches including inter connection between buildings/pumps/pump houses and taking out old existing GI tubing complete all as specified and as directed.
Material and labour for Cleaning of underground reservoir by closing of all valves in distribution and dewatering of complete tank and cleaning with wire brush, cloth, bleaching powder, removing dirt, scale from the tank and from mouths of circulating pipes etc through drain pipe or by manually, and washing of inner surface using lime and bleaching powder and removing the same until clean surface is obtained, all as specified and directed by Engineer-in-Charge (Tank shall be cleaned yearly and writing with white paint over black base on the tank as "TANK CLEANED ON" with date with 5 cm high letters/ numbers and connecting all connections after cleaning and testing for leakages of tank of capacity 75000 Ltrs complete all as directed. Note: Tank shall be cleaned yearly as directed by Engineer-in-Charge.
All as per item No. 149 above but UG sump capcity of 50,000 litres.
Material and labour for Cleaning of rain water sand filter tank of 50,000 Ltrs capacity by removing the sediments and old sand & aggregated from inside the tank, refill the sand and aggregates after sun drying to required level and adding additional sand and aggregates to the fillter tank if required including washing the tank using bleaching powder, removing sludge from tank until a clean bottom surface obtained and writing the capacity of sump and date of cleaning with synthetic enamel paint complete all as specified and as directed.
Disconnecting existing water/electric connections, dismantling unservicable electric Motor pump set having capacity 40 HP 3 Phase, opening carefully, taking out old burnt windings, cleaning of solts of motor stater and rotor complete, rewinding the same with super enamelled winding wire of existing gauge/size as per exisitng pattern with proper insulating material apply two coats of varnish and heating of windings reassemble the motor with proper sealing, including necessary lathe work to made the pump high efficiency, etc. refixing the same location, including necessary plumbing work, etc., testing and commissioning of motor pump set on full load to the entire satifcation of the Engineer-in-Charge. Note:- The quoted rate shall be after deducting the rate of old copper scrap.
All as per item No. 152 above but having capacity 20 HP.
All as per item No. 152 above but having capacity 10 HP.
All as per item No. 152 above but having capacity 5 HP.
All as per item No. 152 above but having capacity 3 HP.
All as per item No. 152 above but having capacity 1.5/2 HP.
Material and Labour for general servicing of Electrical Driven main pump of 40HP capacity including cleaning, greasing, checking alignments, meggaring, with and including replacing gland, packing, capacitors, terminal blocks etc complete all as specified and as directed. Note : The servicing shall be carried out once in a month.
All as per item No. 158 but of capacity 20 HP.
All as per item No. 158 but of capacity 7.5/10 HP.
All as per item No. 158 but of capacity 5 HP.
All as per item No. 158 but of capacity 3 /2.5/2/ HP
Supply and fix in repairs DOL Starter for 0.5 to 1.50 HP pump set, 230 volt, 415 volt, 3 phase relay max range 9-14 amps complete all as specified and directed.
Supply and fix in repairs DOL Starter for 2 to 3 HP , 415 volt, 415 volt, 3 phase relay max range 9-14 amps complete all as specified and directed.
Supply and fix in repairs DOL Starter for 5 to 7.50 HP, 415 volt, 415 volt, 3 phase relay max range 9-14 amps complete all as specified and directed.
Supply and fix in repairs Star delta starter including all accessories suitable for 20 HP, 415 volt, 3 phase relay max range 14-23 Amps complete all as specified and directed.
Cleaning the vegetation including grass, bushes, small trees & all vegetation growth complete incl digging out roots of bushes around installation/Sump/OH tanks/ valve chamber including leveling the surface by removing debris to a distance n.exc 50 mtr all as directed.
Supply only alum crystal complete all as specified.
Material and labour for General servicing of solar water heater, 100-300 ltrs capacity by checking functioning of thermostate, safety valve, indicator lamp, electric connection, water flow etc and replace the unserviceable parts if necessary and keep the geyser in serviceable condition complete all as specified. Note : The cost of labour and consumables required for replacement of parts shall deem to include in the unit rate quoted by the contractor.
Material and labour for General servicing of UPS of capacity 30 KW , opening the outer cover, checking of all the printed circuits, mother board etc. cleaning all parts from dust and mosture by applying suitable gel/ cleaning solution, complete in all respect, soldering, replacement of battery leads/clamp/copper cable/ any other minor parts and testing complete up to the satisfaction of Engr-in-Charge. Note : (i) The cost of labour and consumables required for replacement of parts shall deem to include in the unit rate quoted by the contractor. (ii) The job has to be carried out in each four months and one complete checking will be treated as one Job.
Testing of earthing of Lighning arrestor, VCBs, Transformers, DGSets, Panel boards, DBs/ or any equipment and minor repairs such as tightening of fasteners, aluminium/GI strip with insulator, replacement of small portion of earth strips/wires, replacement of bolts/nuts/screws, welding if required etc. complete all as directed by Engr-in-Charge. Note : (i) The cost of labour and measuring equipments and accessories required for earth testing shall deem to include in the unit rate quoted by the contractor. (ii) Testing of a single earthing will be treated as one Job. (iii) Each earthing has to be tested in every six months and entry to be made in Earth testing Register.
Schedule of Credit (Minus) Rs.71,326.00 NOTE: Bidder shall insert credit amount of Rs. 71,326.00 as rate in Green field under Col-13.
VIJAY CONSTRUCTIONS
R.K. Builders
STAR ENGINEERING ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .