Loading…
Loading…
Tender Value
₹43.7 L
EMD Value
₹87,380
Closing Date
26 Sept 2026, 6:00 pm3d left
CWE NB KOCHI
CWE (NB) KOCHI, Kataribagh, Naval Base PO, Kochi-04
REPLACEMENT OF BER 750 KVA TRANSFORMER AND LT PANELS AT SUB STATION NO 04 AT INS DRONACHARYA UNDER GE FORT KOCHI
2026_MES_781665_2
81279
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KOCHI
as per NIT
7 documents required · 7 mandatory
₹500
GE FORT KOCHI
₹87,380
Yes
12 Sept 2026
12 Sept 2026
28 Sept 2026
12 Sept 2026
26 Sept 2026
20 Sept 2026
14 Sept 2026 - 19 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Dismantling and taking down of Unserviceable Transformer of 750 KVA capacity from at site, after properly disconnect of input/output (HT/LT) connections and taking out and including arrange lifiting, loading to lorry and transport to deposit AGE EM storeyard complete all as specified and as directed by Engr-in-charge. | 1 | EACH JOB | - | - |
| 2 | Supply, installation ,testing and commissioning of distribution transformer mounted on existing surface place stepdown 11 KV /0.433 KV three phase complying with IS 2026 and IS 1180 (part-1) 2014 and IEC 600676 with latest ammendments, indoor type,copper wounded suitable for 50 Hz system of capacity 800 KVA oil immerged ONAN (Oil Natural Air Natural) coooled Delta connected on HT side, impulse withstand 2.5 times rated high voltage and Star connected on LT side, power frequency withstand voltage HV/LV ),Victor group Dyn 11, provided with OFF circuit Load tappings change to vary secondary voltage from (+) 7.5 % to (-) 7.5 % in steps of 2.5 % losses should be confined to the limits specified as follows: maximum allowable losses at full load (100%) and half load (50%) shall not be exceeded 1.12 % and 0.79% respectively asper GRIHA RATING , Percentage impedance 5% losses and impedance are subjected to tolerance as specified in IS 1180. The transformer should be supplied with first filling of oil confirming to IS 335. The transformer should have both side cable end box with neutral brought out and including making good existing PCC surface with PCC 1:2:4 ,B1 20 mm aggregate complete all as directed by Engineer - in - Charge and installation of transformer shall be carried out as per IS - 10028 and comprising with the following standard fittings / technical specification :- Transformer 800 KVA ,Star rating by BEE with labeling ,BIS certification is mandatory under the Compulsory Registration Scheme and Quality Control Orders issued by Govt of India for each rating of distribution Transformer and valid type test report duly issued by NABL accredited BIS approved Lab ,Level - II ,Rated, and complying with the following: | 1 | EACH JOB | - | - |
| 2.1 | (a) Lifting lug for Transformer and Tank
(b) Earthing terminal rating and diagram plate
(c) Air release device or plug
(d) Off Circuit Tap Switch
(e) Enclosure IP 54
(f) Pressed Steel Radiators
(g)18 mm dia Foundation Holes in Bottom channel
(h) Bottom channel
(j) Explosion Vent with Diaphram
(k) Fillter Valve,Drain Valve, Drain outlet pipe with brass gate valve
(l)Conservator Oil Level Gauge,Conservator , Conservator drain plug
(m) Conservator tank with oil level indicator
(n)Thermometer Pocket
(o) Oil filling inlet pipe with plug
(q) Silica Jel Breather (Clear view Type)
(r) first fill of oil up to level including conservator tank with fresh new oil confirming to IS335
(s) Type of connection delta/star
(t) Type of cooling: Oil and natural Air
(u) Vector group:DYN11
(v) Temperature rise over an ambient of 50 0C maximum
(w) Cable and box on both side of HT/LT cable of suitable size.
(x) Provision of thermometer with pocket,including all tehnically site requirement complete all specification and as directed
(y) Provn of Buchholz relay with alarm and trip contacts connecting up with VCB panel wiring etc | - | - | - | - |
| 3 | Taking down unserviceable LT panel /APFC panel of any type/any capacity/any size from existing position after disconnection of all electric connection & temporary restoration of normal electric supply till final installation of LT panel including making good disturbed surfaces if floor/walls etc complete as directed by Eng-in-Charge. | 2 | EACH JOB | - | - |
| 4 | Supply, installation, testing and comissioning of weather and vermin proof indoor type (made out of 2 mm thick CRCA sheet) LT Panel box type factory made, front & back openable type, CPRI approved,compartmentalized design including mild steel channel frame of ISMC 75 mm at the base of panel only for grouted,duly epoxy powder coated, complete with heat shrink insulated aluminium bus bar of 2000 Amps rating 4 Nos,with heat shrinkable insulated sleeves with colour code and insulated support, cable galleries inter connecting bus bar connecting linkage , digital type multifunction meter complete and conforming to IS 8623 and IP 54 class of protection as per IS 2147 complete, including all connections with aluminium strips, Pillar box shall be provided with danger notice plate with skull & bone sign, PVC gasketed and sealed, making all incoming and out going electrical cable connecetions with new lugs, glands to be provided at cable entries, including angle iron support 50x50x6 mm with from ground level at the base of panel complete etc, installation, testing & commissioning complete and mounting the panel board all specified and as directed all as The panel shall be comprising of following accessories: | 1 | EACH JOB | - | - |
| 4.1 | Incommer :-
(a) ACB, Draw out type, 415 Volts, 50Hz,1200 Amps, 4 pole,maximum current loading capacity, Over load current protection and short circuit breaking system,ON/OFF switch system complete - 01 Each
(b) Multi function digital energy meter with communication port with CTs -01 set
(c) Phase Indicator LED lamp assy RYB - 01 Set.
Out going :-
(a) MCCB, TPN 415 Volts, 50Hz,400 Amps, 4 pole, 36 kA, thermal magnetic release, front face isolataion with positive break indication with double break contacts with spreader and phase barrier - 02 Each
(b) MCCB, TPN 415 Volts, 50Hz,320 Amps, 4 pole, 36 kA, thermal magnetic release, front face isolataion with positive break indication with double break contacts with spreader and phase barrier - 02 Each
(c) MCCB, TPN 415 Volts, 50Hz,250 Amps, 4 pole, 25 kA, thermal magnetic release, front face isolataion with positive break indication with double break contacts with spreader and phase barrier - 02 Each
(d) MCCB, TPN 415 Volts, 50Hz,200 Amps, 4 pole, 25 kA, thermal magnetic release, front face isolataion with positive break indication with double break contacts with spreader and phase barrier - 02 Each
(e) MCCB, TPN 415 Volts, 50Hz,160 Amps,4 pole, 16 kA, thermal magnetic release, front face isolataion with positive break indication with double break contacts with spreader and phase barrier - 02 Each
(f) MCCB, TPN 415 Volts, 50Hz,100 Amps, 4 pole, 16 kA, thermal magnetic release, front face isolataion with positive break indication with double break contacts with spreader and phase barrier - 02 Each
(g) Stencelling of panel board including marking distributions -01 job
(h) Spare Compartment for future expension -02 Nos | - | - | - | - |
| 5 | Supply & installation of APFC Panel, fixing connecting and commissioning and testing of power factor improvement static condenser (capacitor banks) of capacity 450 KVAR, indoor type panel made out through factory fabricated, factory assembled and pre connected, weather, dust and vermin proof suitable for 1100 V grade 03 Phase 50 Hz AC supply floor mounted, fabricated out of 2 mm thickness CRCA sheet, CPRI approved with front door and back opening having locking arrangement pre-wired with copper conductor PVC Insulated cable / Extension strips and connected with suitable size thimbles / lugs duly painted with darken grey epoxy power coating after suitable chemical treatment, legs duly imbedded in floors above ducts in PCC 1:3: 6 of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles, includina making good existing hard standing floor damages, making good PCC surface using PCC 1:2:4 type B1, graded 20 mm stone aggregate work and finished even and smooth using extra cement work complete all as specified and as directed by Engr - in - Charge and all other electrical control CTs required on mother circuit (ie on main LT panel of transformer) complete all as required and comprising of following :
(a) Bus bar of copper of 1000 Amps Capacity 04 Nos for 3 phase and neutral mounted on Insulators with heat shrinkable insulated sleeves with colour code.
(b) Incoming MCCB 800 Amp, 36 KA, 03 pole- 01 No
(c) Capacitor 450 KVAR (05 KVAR X 8 + 10 KVAR X 5 + 15 KVAR X 8 + 20 KVAR X 6
+ 30 KVAR X 4), MDXL type, IP set dry type capacitor non toxic and ecological polyurethane resin with self healing film 03 phase 50 Hz with out put tolerance -5% to 10% having discharge device, THD, should be 30%, heavy duty, Square or Round type with suitable capacity control contactors and MCCBs TP 25 KA for each step separatly ie for 12 steps complete. Make : L&T / ABB /CROMPTON/SEIMENS
(d) Programmable APFC relay having following features, display of Current, Voltage, P.F, KW .12
step (144 mm X 144mm ) - 1 No
(e) Ammeter 0 - 5 Amp, 230 Volts, AC with selector switch - 01 No
(f) Volt meter (0 - 500 Volts), AC with selector switch- 01 No
(g) CT 500 / 05 A CL -01 -03 No
(h) Air cooling system with fans- 2 Nos
(j) Auto Manual Select Or switch - 01 No
(k) ON/OFF push button along with indication lamps with suitable protections / control wirings - 12 Sets
(l) Indicator lights RYB - 03 Nos
(m) Multifunction digital energy meter with communication port with CTs -01 set
(n) Phase Indicator LED lamp assy RYB - 01 Set.
Note:- Make of Capacitors and Switch gears - L&T / ABB /CROMPTON/ SEIMENS | 1 | Each Job | - | - |
| 6 | Taking out UNSV HT UG cables of any sizes from trenches/walls incl all mounting accessories and GI tubing and keeping aside in safe custody for relaying after repairs incl making good to disturbed area complete all as specified and as directed | 30 | RM | - | - |
| 7 | Taking out UNSV LT UG cables of any sizes from trenches/walls incl all mounting accessories and GI tubing and keeping aside in safe custody for relaying after repairs incl making good to disturbed area complete all as specified and as direct | 110 | RM | - | - |
| 8 | Supply and laying for XLPE cable insulated sheathed earthed pvc bedded galvanized steel strip or wire armoured electric power cable heavy duty with aluminium conductor 11000 volt (E) grade cross sectional area 185 sqmm 3 core, Heavy grade , laid in trenches/Ducts or passing through pipes or fixing on poles etc from trenches/ Poles/ Surface complete all as specified and as directed | 30 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
81279tender.pdf
Tender Documents • 0.79 MB
BOQ_884501.xls
BOQ • 0.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .