Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.6 LAccepted-AOC 10 SUBASH COLONY DEF LAB ROAD RATANADA JODHPUR 342006 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342006 | ₹34.6 L Quoted ₹36.7 L | L1 | Accepted-AOC LOWEST REASONABLE BID |
| 2 | L2₹42.9 L+₹6.3 L (17.1%)Rejected-Finance H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | ₹42.9 L+₹6.3 L (17.1%) | L2 | Rejected-Finance NOT LOWEST |
| Sl No | Description | Qty | Unit | Shri Electrical Enterprises L2 | PANWAR ELECTRICALS L1 |
|---|---|---|---|---|---|
| 1.00 | M & L for rewinding of induction motor 3 phase, 50 Hz, 415 volt of compressor motor and AHU Blower , chiler , condeser motor comprising of the following activities for induction motor of following capacities complete all as specified and directed by Engr-in-charge as per manufacturer's instructions. | - | - | - | - |
| 1.01 | (i) Disconnecting and removing the electric motor from installed position and loading unloading, transporting to authorised/approved work shop | - | - | - | - |
| 1.02 | (ii) Dismantling existing burnt winding from the motor and rewinding complete with super enamelled copper winding wire of existing guage including all material such as insulated paper sleeves tape varnish etc complete for class F insulation and including shaft metalising, bearing cover slieving , necessary replacement of cooling fan, nut-bolt etc | - | - | - | - |
| 1.03 | (iii) Loading, unloading and transporting motor & reinstalling in position and in alignment including electric conection commissioning and testing in actual working condition for 8 hours continuosly to check the performance on full load and designed RPM to the complete satisfaction of Engr-in-Charge all as specified and directed | - | - | - | - |
| 1.04 | (iv) M&L for replacement of 02 Nos of suitable size of ball bearing as per existing size of the following type and capacity of induction motor :- | - | - | - | - |
| 1.05 | (a) 30-40 HP induction motor, 415 V, 50Hz | 3 | Each Job | 14,000 ₹42,000 | 10,000 ₹30,000 Lowest |
| 1.06 | (b) 10 - 20 HP induction motor, 415 V, 50Hz | 12 | Each Job | 8,000 ₹96,000 Lowest | 9,000 ₹1,08,000 |
| 1.07 | (c) Above 5 & upto 10 induction motor | 15 | Each Job | 4,500 ₹67,500 Lowest | 7,000 ₹1,05,000 |
| 1.08 | (d) up to 5 HP induction motor | 15 | Each Job | 3,500 ₹52,500 Lowest | 4,000 ₹60,000 |
| 2.00 | Taking out unserviceable pipes and supply and fixing Mild Steel medium grade pipe 65mm to 150 mm dia connecting, welding, smoothing and making leak proof incuding MS fittings all as per site requirment and complete all as specified and directed by Engr-in-Charge including testing complete. | - | - | - | - |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
21 Oct 2025, 6:00 pmClosed
CWE ARMY JODHPUR
CWE ARMY MULTAN LINE ARMY AREA JODHPUR-342010
REPAIR / MAINT OF CENTRAL AC PLANTS, AHUs, CHILLER, CONTROL CABLES ETC AT ARMY AREA BANAR UNDER GE BANAR
2025_MES_731322_1
82526/40/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
BANAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE BANAR
₹90,000
Yes
19 Dec 2025
17 Sept 2025
28 Oct 2025
17 Sept 2025
21 Oct 2025
3 Oct 2025
18 Sept 2025 - 1 Oct 2025
Amount
M & L for rewinding of induction motor 3 phase, 50 Hz, 415 volt of compressor motor and AHU Blower , chiler , condeser motor comprising of the following activities for induction motor of following capacities complete all as specified and directed by Engr-in-charge as per manufacturer's instructions.
(i) Disconnecting and removing the electric motor from installed position and loading unloading, transporting to authorised/approved work shop
(ii) Dismantling existing burnt winding from the motor and rewinding complete with super enamelled copper winding wire of existing guage including all material such as insulated paper sleeves tape varnish etc complete for class F insulation and including shaft metalising, bearing cover slieving , necessary replacement of cooling fan, nut-bolt etc
(iii) Loading, unloading and transporting motor & reinstalling in position and in alignment including electric conection commissioning and testing in actual working condition for 8 hours continuosly to check the performance on full load and designed RPM to the complete satisfaction of Engr-in-Charge all as specified and directed
(iv) M&L for replacement of 02 Nos of suitable size of ball bearing as per existing size of the following type and capacity of induction motor :-
(a) 30-40 HP induction motor, 415 V, 50Hz
(b) 10 - 20 HP induction motor, 415 V, 50Hz
(c) Above 5 & upto 10 induction motor
(d) up to 5 HP induction motor
Taking out unserviceable pipes and supply and fixing Mild Steel medium grade pipe 65mm to 150 mm dia connecting, welding, smoothing and making leak proof incuding MS fittings all as per site requirment and complete all as specified and directed by Engr-in-Charge including testing complete.
(a) 65mm dia
(b) 80 mm dia
(c ) 100 mm dia
(d) 150 MM dia
Supply & fix water pressure gauge 0-150 Kg/sq cm suitable for fixing with 150 mm dia water circulating inlet & out let pipe by means of proper welding and connection with checking the running water pressure as per specification all as directed by engineer in charge.
M&L for replacement of water temp gauge dial type 0-120 degree F complete all as specified and directed by Engr-in-charge.
Supply and fix flexible rubber coupling/star coupling for 5- 7.5HP elecric motor & pump, 415volts, 3 phase of existing specification complete all as specified and directed by Engr-in-Charge.
Supply and fix flexible rubber coupling for 10 - 15 HP elecric motor & pump, 415volts, 3 phase of existing specification complete all as specified and directed by Engr-in-Charge.
Supply and fix flexible rubber coupling for above 15- 20HP elecric motor & pump, 415volts, 3 phase of existing specification complete all as specified and directed by Engr-in-Charge.
Supply and fix flexible rubber coupling for 40 HP (30 TR compressor) elecric motor &pump/compresor, 415volts, 3 phase of existing specification complete all as specified and directed by Engr-in-Charge.
M&L for dismantling, disconnecting and decoupling of pumpset complete from the installation with the help of man power / chain pully and block after making temporary arrangment for hanging of chain pully block, incl shifting of pump to civil work shop for opening of pump and cleaning of all parts internally & externally and greasing of mechanical switch gear incl repairing of CI/SS impeller and replacing the unserviceable spare parts CI Casing wear ring DE/NDE, CI Gland plate, Key for impeller, Impeller nut, CI Stuffing box bush, Pump shaft SS (AISI-410), Gland packing champion, CI Bearing cartiage DE/NDE, CI star coupling, SS Eye bolt with nut, CI Shaft sleeve, Set Gasket packing, mechanical seal, remetalling of pump shaft turning and balancing, including machining work and transportation from civil work shop to site for refixing , coupling, alignment of pump with motor using steel coupling and testing of pump set complete to the entire satisfaction of Engineer-in-Charge all as specified and directed. Note:- (i) Spare parts are deemed to be included in above quoted rates.
(a) chiller/condenser pump of Capacity above 20 -25 HP
(b) chiller/condenser pump of Capacity 10 -20 HP
(c) chiler/condenser pump of Capacity above 5 -7.5 HP
(d) chiler/condenser pump of Capacity upto 5 HP
Preventive maintenance/servicing of CSU (ceiling suspended unit) type Air handling unit of capacity 3000/6000CFM (10TR), installed at NBC plant area elevated height 3.5 Mtr without any inconvinience to user and comprising of following service/ repair work (a) inspecting functioning of ball valves, balancing valves, 3way valve and replacing the U/S parts under respective item of schedule including GI/MS fittings such as flanges, elbows, Tee etc complete all as directed (b) inspecting supply & return air duct bellows, replacing u/s fastener, leak proofing, servicing air inlet, delivery, return dumper (c) Cleaning of AHU's aluminium fins by water pressure pump set (d) Cleaning of AHU Filters. Note: Minor items shall be included in quoted rate.
Supply & fix in replacement of V belt oil and heat resistant antistatic type of following size (i) A-21/27 complete all as specified and directed by Engr-in-charge.
All as per Srl item No 11 above but of size B- 58 complete all as specified and directed by Engr-in-charge.
All as per Srl item No 11 above but of size B- 84 complete all as specified and directed by Engr-in-charge.
All as per Srl item No 11 above but of size B-72 complete all as specified and directed by Engr-in-charge.
All as per Srl item No 11 above but of size B-74/76 complete all as specified and directed by Engr-in-charge.
All as per Srl item No 11 above but of size B- 88 complete all as specified and directed by Engr-in-charge.
Supply and fix in repairs of oil failure switch suitable for compressor (R-22) of Central AC plant. Complete all as specified and directed by Engr-in-charge.
Supply and fix in repairs of LP/HP Cut Out switch incl cutting, brazing complete all as specified and directed by engr in charge.
S&F in replacement discharge/suction/oil pressure sensor suitable for reciprocating compressor of capacity 0-20 Bar as per existing old sensor complete all as specified and directed by Engr-in-charge.
M&L for descaling of shell and tube type water cooled condenser and chillers shells of capacity 100TR capacity (4x25) including chiller unit & chiller pipe lines with MS shell and integral copper tubes with safety valve with Descaling compound (Copper Friendly) through cleaning with descaling brush with rod (7' long) and circulating by descaling water pump, replacement of gasket set and other minor parts. Make of descaling compound is Scalfoe-100 complete all as specified and directed by Engr-in-Charge. Note: (a) PH value of circulation water after descealing of condenser is tested and it must be lies between 6 to 8, If PH value does not found satisfactory. Descaling is carried till PH value meets requirement. (b) Descaling compound should be copper friendly.
All as per Srl item No 20 above but for 60 TR capacity. Complete all as specified and directed by Engr-in-charge.
All as per Srl item No 20 above but for 150 TR capacity. Complete all as specified and directed by Engr-in-charge.
S & F in replacement of butter fly valve of 65 mm dia, cast iron body, integrally molded close and body construction with hand lever, operated and rating of PN 10 with thermal insulation as per requirement of condensser and chilled water line complete all as specified and directed and directed by Engr-in-charge.
S & F in replacement of butter fly valve of 80 mm dia, cast iron body, integrally molded close and body construction with hand lever, operated and rating of PN 10 with thermal insulation as per requirement of condensser and chilled water line complete all as specified and directed by Engr-in-charge.
S & F in replacement of butter fly valve of 100 mm dia, cast iron body, integrally molded close and body construction with hand lever, operated and rating of PN 10 with thermal insulation as per requirement of condensser and chilled water line complete all as specified and directed by Engr-in-charge.
S & F in replacement of butter fly valve of 150 mm dia, cast iron body, integrally molded close and body construction with hand lever, operated and rating of PN 10 with thermal insulation as per requirement of condensser and chilled water line complete all as specified and directed by Engr-in-charge.
M&L for disconnecting electrical connections of motor located at the top of cooling tower and dismantling and taking out fan blade assembly along with motor mounted on base frame at the top of cooling tower after cutting all nuts, bolts and fixtures from the mounting frame and removing whole assembly including motor and base frame from the top of cooling tower with the help of T&P for servicing of cooling tower suitable upto 150 TR capacity including following complete servicing of cooling tower plant through Descaling Compound complete pipe line, including servicing of cooling tower motor, fan and make the necessary alignment with motor and replacement of bearing of suitable cap including painting of motor & base after necessary work including greasing and replacement of nut bolts and preventing leakage if any by means of suitable additives etc all as directed and specified. (a) Cleaning /scrapping of inner & outer surface of FRP basin, repair of damaged portion if any to and for FRP lining of all surfaces joints to avoid leakage including replacement of all nuts and bolts joining all parts of Basin complete (b) cleaning of serviceable PVC fills (Big size ) (c) Cleaning of serviceable PVC fills (small size ). complete all as specified and directed by Engr-in-charge.
All as per Srl item No 27 above but 60 TR capacity. Complete all as specified and directed by Engr-in-charge.
Taking down & Replacing of Existing U/s PVC fills (Big size ) in columns of size 60x30x15 cm complete all as specified and directed by Engr-in-charge.
Taking down & Replacing of Existing PVC fills (small size ) in columns of size 60x15x15 cm complete all as specified and directed by Engr-in-charge.
Supply & replacement of Power contactor with 2 NO+ NC,32 - 40 Amps,AC3,3pole,coil voltage 230/415Volt as per existing Complete all as specified and directed by Engr-in-charge.
Supply & replacement of Power contactor with 2 NO + NC,upto 30 Amps,AC3,3pole,coil voltage 230/415Volt, as per existing Complete all as specified and directed by Engr-in-charge.
S & F in replacement of Power contactor 250A with NO + NC, AC3, 3pole, coil voltage 415Volt complete all as specified and directed by Engr-in-charge.
Supply & fix in replacement of thermal type over load relay, 9- 15 Amps. Complete all as specified and directed by Engr-in-charge.
All as per Srl item No 34 above but 20 - 32 Amps complete all as specified and directed by Engr-in-charge.
Supply & replacement of thermal Over load relay, 40 -50 Amps complete all as specified and directed by Engr-in-charge.
S & F in replacement front mounting add-on-aux control block for power contactor as per existing size and make working on ground. Complete all as specified and directed by Engr-in-charge.
Supply & fix in replacement of single phase preventor DIN rail mounted 415 VAC as per existing rating complete all as specified and directed by Engr-in-charge.
Supply & fix in replacement of electronic timer for star - delta starters , with auxilary supply- 230/415 volt, AC as per existing rating complete all as specified and directed by Engr-in-charge.
S & F in replacement of Thermostatic Expansion Valve suitable for blue star make air cooled chiller having capacity of 56 TR & Model XAC2YS-060R2. complete all as specfied and directed by Engr-in-charge.
M&L for servicing of the air cooled DX type chiller system of 56 TR capacity complete all as specified and directed by Engr-in-charge. (i) Cleaning of all condensing coil units with water spray jets (set of four in one unit) of 56TR every 3 months interval. (ii) servicing of squirrel cage induction motor and fan system of cooling fan of capacity 2.5 HP including greasing of all moveable parts and refitting same after repair following all as directed and specified by OEM (iii) Cleaning of chilled water line by flushing out the water till removing all the dirty water from the line (iv) servicing of Y- strainers, non return valves, butterfly valves of chilled water line
Material and labour for carrying out leak test of central AC plants of capacity having refrigerant circuit comprising of two compressors with use of nitrogen gas and rectifying the leakages, arresting the leakages. after completion of leak test pressure testing with Nitrogen gas, refrigerant charging gas and testing commissioning complete all as specified and directed by Engineer-in-Charge.Note:- (i) Cost of Nitrogen gas, necessary copper pipes and welding works are deemed to be included in the Quoted rates. (ii) Necessary Refrigerant gas measured and paid separately.
All as above item No 42 but for AC plant having refrigerant circuit comprising of one compressor. Complete all as specified and directed by Engr-in-charge.
Supply only gas R-22 for topup / charging of refrigerant complete all as specified and directed by Engr-in-charge. Note :- Gas supplied by the contractor shall be taken on charge and issued to the contractor for top up / charging when required.
Supply only gas R-407A for topup /charging of refrigerant cpmplete all as specified and directed by Engr-in-charge. Note :- Gas supplied by the contractor shall be taken on charge and issued to the contractor for top up / charging when required.
S & F in replacement of filter drier suitable for air cooled chiller having capacity of 56 TR & complete all as specified nad directed by Engr-in-charge.
M&L for servicing of Hot water generator of 55 KW, 415 volts 3 phase 50Hz with two steps and PAN Humidifier 9kW,415V AC, single step with following repairs complete all as specified directed by engr-in-charge. (a) Cleaning the storage tank, water level indicator, heating coil/element with descaling solution/agent and soft brush with non metallic bristles without affecting thermal insulation/top cover gasket. (b ) inspecting control wiring including replacement of u/s wiring, servicing of power contactors etc. (c ) replacement of heating element,3kw capacity (d) inspecting/testing, servicing of relays, other safety valves Note: heating element shall be measured and paid separately.
Supply & fix in replacement of flow switch 25mm size for inserting in line. Complete all as specified and directed by Engr-in-charge.
S & F in replacement of heating element upto 3kW, 230 Volt, ISI marked. Complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement MCCB 3 Pole 63 Amps, 415 Volts, 16KVA fixed type including taking down old unserviceable MCCB complete all as specified and directed by Engr-in-Charge.
S & F in replacement MCB TP 25 To 63 AMP 415V 10KA 'C' curve complete all as specified and directed by Engr-in-charge.
S & F in replacement of MCCB 4 pole 250 to 350 Amps 415 Volts, 36 KA thermal magnetic release adjustable type. Complete all as specified and directed by Engr-in-charge.
S&F in replacement of MCCB 4 pole 630 Amps 415 Volts, 50 KA thermal magnetic release adjustable type. Complete all as specified and directedby Engr-in-charge.
S & F in replacement of MCCB 4 pole 100 Amps 415 Volts, 18 KA thermal magnetic release adjustable type. Complete all as specified nad directed by Engr-in-charge.
S&F in replacement air Purger Valve of suitable size as per existing size and make as specified. Complete all as specified and directed by Engr-in-charge.
M&L for Iron grill/sheet or iron angle/channel of suitable thickness as directed for fixing of motor/pump foundation and front cover of compact Air cooled chiller unit installed at various places (AHU,Pump) or making tranch/duct over Plate including necessary welding work at site as required complete all as specified and directed by Engr-in-charge.
M&L for servicing of Air handling units of capacity 10000 CFM, complete all as specified and directed by Engr-in-charge. (a) cleaning of AHU filters with water spray jet after blowing out the dust (b) cleaning of cooling coils with chemical cleaning by spraying the organic based scale removing agent Vaniklin at the appropriate ratio till removal of complete dust & scale deposits in the fin area of coil. (c) checking and servicing of electrical connections of blower motor (e) cleaning of water drain lines and replacing the drain valves. (f) cleaning out the drained water in AHU room completely and testing & commissioning the unit complete all as specified and as directed by Engineer-in-Charge.Note :- cost of minor electrical and mechanical parts required shall be included in the above quoted rate.
Same as item No. 57 But for AHU capacity of 12500 CFM complete all as specified and directed by Engr-in-charge.
Material & labour for taking down old unserviceable sealed type scroll compressor and supply and fix in repair of the same duly debrazing the suction & discharge lines. Supply, testing and commissiong of Scroll compressor of Model No as under suitable refrigerent for each model as per OEM Make Danfoss/performer made in germany of the same capacity & rating including necessay welding/brazing with silver/copper brazing rods, copper pipe, socket elbow, including nitrogen gas leak test and charging of gas at desired pressure complete all as specified and directed by Engr-in-charge. Note : Cost of Nitrogen gas,refrigerant gas, solenoid coil, expansion valve and M & L for taking down and refixing of compressors shall be included in quoted rate of following items ( 59.01 to 59.03).
(a) Scroll compressor model No SY300, 19 TR Capacity, 3 phase, 415 volts, 50Hz suitable for R407 refrigerent of 56 TR Capacity chiller unit. Complete all as specified and directed by Engr-in-charge.
(b) Scroll compressor model No SY380, 25TR Capacity, 3 phase, 415 volts, 50Hz suitable for R22 refrigerent of 100 TR Capacity chiller unit.. Complete all as specified and directed by Engr-in-charge.
(c) Scroll compressor model No SZ185S4RC, 12.5 TR Capacity, 3 phase, 415 volts, 50Hz suitable for R407 refrigerent of 34 TR Capacity chiller unit. Complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement ON/OFF Push button switch with two push buttons of existing specification complete all as specified and directed by Engr-in-Charge.
S&F in replacement anti freeze switch suitable for Central AC plants of capacity upto 100TR of air / water cooled type complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement thermometer 0-60 Degree centrigrade suitable for fixing with 150 mm dia water circulating pipe by means of proper welding and connection with checking the running water temperature as per specification complete all as directed by Engr-in-Charge.
Supply & Fix in replacement motor protection device of type MVPD and model EC No: 30-220A/230V /SS/DIN suitable for reciprocating AC compressor 30TR control panel of plate mounted complete all as specified and directed by Engr-in-charge.
S & F in replacement of Y strainer 100 mm dia made out of cast iron to be fitted in chiller / condensing line complete all as specified and directed by Engr-in-charge.
S & F in replacement of Y strainer 150 mm dia made out of cast iron to be fitted in chiller / condensing line complete all as specified nad directed by engr-in-charge.
S & F in replacement of Motor and Voltage protective device as per existing make and type complete all as specified and directed by Engr-in-charge.
(a) MVPD EC 30-220A complete all as specified and directed by Engr-in-charge.
(b) Micro VPD(Split) 360-500V AC complete all as specified and directed by Engr-in-charge.
S & F in replacement of gun metal gate or globe valve of 20 mm dia with iron wheel head screwed both ends for iron pipes complete all as specified and directed by Engr-in-charge.
S & F in replacement of gun metal gate or globe valve of 25 mm dia with iron wheel head screwed both ends for iron pipes complete all as specified and directed by Engr-in-charge.
S & F in replacement of 20 mm dia ball brass valve , high pressure, with polythene float and fly nuts complete, screw for iron pipe or brass ferrule and mixed complete all as specified and directed by Engr-in-charge.
M & L in replacement for fixed to wall and ceiling or laid in floors or trenches with all fittings of 25mm dia GI pipe medium grade complete all as specified and directed by Engr-in-charge.
M & L in replacement for fixed to wall and ceiling or laid in floors or trenches with all fittings of 20mm dia GI pipe medium grade complete all as specified and directed by Engr-in-charge.
M & L in replacement for fixed to wall and ceiling or laid in floors or trenches with all fittings of 50mm dia GI pipe medium grade complete all as specified and directed by Engr-in-charge.
Supply and Fix in replacement rotational moulded polye thylene water storage tanks capacity 1000 Ltr (cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part I complete all as specified.
M & L for cleaning and removing all scale and dirt,etc, from tanks and from mouths of circulating pipes, etc for cap 1000 Ltrs complete all as specified and directed by Engr-in-charge.
M & L in replacement for rubber expansion bellows of size 65/80mm dia in the form of coupling to the chilled water pipe line for providing mechanical strength and vibration absorption for the chiller circuit complete all as specified and directed by engr-in-charge.
S & F in replacement phase indicator set ( R, Y, B) with indicator lamps suitable for panel mounted complete all as specified and directed by engr-in-charge.
M & L for repairs to chiller/Evaporator copper coil of 10/12 mm Dia of 56 TR AC plant by blocking the damage/corroded tubes involving following activities :- complete all as specified and directed by Engr-in-charge.
(i) Disconnecting the side covers fo the chiller and the chiller valves from their existing positions.
(ii) Transportaion of evaporator shell to and fro from depot area to authorised workshop
(iii) Leakage testing of the evaporator copper tube bunch having two circuits for refrigerant using pressurized nitrogen gas and finding the leakaged tubes.
(iii) Blocking the damaged/leaked tubes by brass plugs.
(iv) Re-fixing the side covers of the chiller and the chiller valves to their existing positions with new nuts, bolts, rubber gasket and washer including insulation of evaporator complete shells
(v) Testing the system for any leakage by using pressurized nitrogen gas and by vaccumising the system.
(vi) Preparing the damage surfaces of chiller as per exisitng including repairs to damaged insulation and painting as per exisitng shade for following capacities of chillers :-
Note :- Cost of Refrigerant gas for topup to desired pressure , nitrogen gas and oxygen/LPG gas for the above work shall be included in the quoted rate of above item.
M & L for Replacement of copper tube bunches of size 10/12 mm evaporator shell as per existing size and quantity of copper tubes for 56 TR AC plant of complete all as specified and directed by Engr-in-charge.
M&L for Earthing complete with galvanised steel earth plate electrode 60cm×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 32 x 6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate connected to earthing test point including GI Pipe for watering & protection of strip complete all as specified and directed by Engr-in-charge.
Supply & fix in replacement of prefilters & fine filters box type EU4/G4 type with washable nylon filters media incl aluminium jali having 90% efficiency to control dust particles up to 10 microns fitted in aluminum framed with epoxy filled on sides of size 610mmx610mmx50mm for fine filters 99% efficiency to control dust particles up to 5 microns OR as per sample suitable upto 25000 CFM AHUs. co0mplete all as specified and directed by Engr-in-charge.
Supply & fix in replacement of prefilters & fine filters box type EU4/G4 type with washable nylon filters media incl aluminium jali having 90% efficiency to control dust particles up to 10 microns fitted in aluminum framed with epoxy filled on sides of size 610mmx305mmx50mm for fine filters 99% efficiency to control dust particles up to 5 microns OR as per sample suitable upto 25000 CFM AHUs. complete all as specified and directed by Engr-in-charge.
Supply & fix in replacement of prefilters & fine filters box type EU4/G4 type with washable nylon filters media incl aluminium jali having 90% efficiency to control dust particles up to 10 microns fitted in aluminum framed with epoxy filled on sides of size 480mmx420mmx25mm for fine filters 99% efficiency to control dust particles up to 5 microns OR as per sample suitable upto 25000 CFM AHUs. complete all as specified and directed by Engr-in-charge.
Supply & fix in replacement of prefilters & fine filters box type EU4/G4 type with washable nylon filters media incl aluminium jali having 90% efficiency to control dust particles up to 10 microns fitted in aluminum framed with epoxy filled on sides of size 305mmx305mmx50mm for fine filters 99% efficiency to control dust particles up to 5 microns OR as per sample suitable upto 25000 CFM AHUs. complete all as specified and directed by Engr-in-charge.
Supply & fix in replacement of prefilters & fine filters box type EU4/G4 type with washable nylon filters media incl aluminium jali having 90% efficiency to control dust particles up to 10 microns fitted in aluminum framed with epoxy filled on sides of size 660mmx480mmx25mm for fine filters 99% efficiency to control dust particles up to 5 microns OR as per sample suitable upto 25000 CFM AHUs. complete all as specified and directed by Engr-in-charge.
Supply, installing, testing and commissioning in replacement factory made and tested (CPRI certified) LT Panel board type suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated copper bus bars( 60 x 10 mm) size of rating 800 amps installed on porcelain insulators. The panel shall be dust and vermin proof IP-65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front & back side opening type, with apron for cable entry with single door setter and locking arrangement and PCC and earth work etc. after taking down old unserviceable panel and comprising of the following :-
Supply and fixing in replacement of CAREL PGD user interface programmable controller display suitable for 56 TR air cool AC plant Model XACZYS-060R2 as per existing make and model including control wiring and complete connection complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of user interface programmable controller with display suitable for 34 TR blue star air cooled chiller Model XAC3S036MAR2 as per existing make and model including control wiring and connection complete all as specified and directed by Engr-in-charge .
M & L for XLPE insulated,armoured heavy duty electric cable with copper conductor,1100 volts grade, cross sectional area 6 sq mm x 4 core. Complete all as specified and directed by Engr-in-charge.
M & L for XLPE insulated,armoured heavy duty electric cable with copper conductor,1100 volts gradev of cross sectional area 10 sq mm x 4 core complete all as specified and directed by Engr-in-charge
M & L for XLPE insulated,armoured heavy duty electric cable with copper conductor,1100 volts gradev of cross sectional area 16 sq mm x 4 core complete all as specified and directed by Engr-in-charge.
Shri Electrical Enterprises (BID ID -3451639)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.56 MB
TENDER40.pdf
Tender Documents • 1.26 MB
BOQ_818794.xls
BOQ • 0.38 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .