Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹42.6 L
EMD Value
₹85,300
Closing Date
9 Dec 2026, 6:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
GE (I) DM Visakhapatnam
GE (I) DM Visakhapatnam
SERVICING MAINTENANCE OF HT VCBS LT PANELS AND TRANSFORMER AND OTHER MISCELLANEOUS WORKS AT SLIPWAY AND DEGAUSSING BAY AT SBC UNDER NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) (DM) VISAKHAPATNAM
2026_MES_799291_1
8735/C/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Naval Dockyard Visakhapatnam
As per tender document
8 documents required · 8 mandatory
₹500
GE (I) DM Visakhapatnam
₹85,300
Yes
18 Nov 2026
18 Nov 2026
11 Dec 2026
18 Nov 2026
9 Dec 2026
2 Dec 2026
19 Nov 2026 - 30 Nov 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Overhauling and servicing of 400 Amp to 800 Amp 11 KV HT breakers for proper functionalling including/ repairs, replacement of defective worn out components and refixing back including testing and commissioning with comprising the following:-
(a) Disconnecting form socket contacts, cleaning and adjustment of gap, replacement of rings etc.
(b) Checking the brekaer bushing of bus bar and circuit side, inspection/ servicing of internal surface for any arcing/ tracks.
(c) Checking the epoxy body completely for any cracks, any sign of arcs/ tracks, cleaning thorougly with CTC including applying bectrol red varnish if necessary.
(d) Checking the drive rod & drive beam insulator assembly and inspect for chocking/ tracks/ arcing.
(e) Checking the condition of the spring charging motor along with gear box including servicing the motor & replacement of motor bearings if required.
(f) Checking/ servicing of ratchet wheel assembly, driving and charging parts.
(g) Chekcing the auxiliary switch, its contacts for proper functional operation. | 10 | Job | - | - |
| 1.01 | (i) Checking & servicing of raising/ lowering mechanisim and its locking system for proper functioning.
(j) Checking & servicing of shutter assembly for its automatic opening/ closing
(k) Testing of VCB to confirm healthiness up to satisfactory results before reinserting in VCB panel.
(i) Insulation Resistance test with 5000V digital insulation tester.
(ii) Timing test at 70%, 100%, of rated control voltage.
(iii) Contact Resistance Measurement test.
(l) Replace both the closing & tripping buffers and if required adjust VCB timing up to satisfactory limit.
Note :- (i) Test results should be submitted to Engineer in-Charge to keep on record duly signed by all concerened complete all as specified and as directed.
Submission of latest and valid calibration certifcate of all used testing kits and equipment from reputed laboratories approved by NABL. Calibration should be carried out through authorised CEIG Licenced agency only. (ii) Any abnormality found during testing, same shall be brought to the notice of Engineer in -Charge. (iii) The items like testing equipment, nuts, bolts, spring washers, petroleum jelly, CTC etc. Required to put the breaker in serviceable condition shall be supplied by the contractor and rate shall be deemed to be included in the unit rate quoted. | - | - | - | - |
| 2 | Supply only Resin Cast CT dual core, CT ratio - 100/50/5A-5A for 800A to 2500A Schneider make 11 KV VCB all as specified and directed. | 3 | Each | - | - |
| 3 | Supply and fix space heater, 230V, 100 Watt inside cable chamber including necessary connection, testing complete all as specified and directed.
Make: Schneider, Part No. EHT-A-AA000-001 | 5 | Each | - | - |
| 4 | Supply and fix including dismantling taking out unserviceable thermostat for space heater for 800 A to 1600 A Schneider make 11 KV VCB compete all as specified and directed.
Make: Schneider only, Part No ETH-E-B000-001 | 5 | Each | - | - |
| 5 | Supply and fix including dismantling taking out unserviceable Buffer (For Opening Spring ) For 630A to 800A Schneider make 11 KV VCB complete all as specified and as directed.
Make-Schneider only, Part No- MVIJ00098-01 | 1 | Each | - | - |
| 6 | Supply and fix including dismantling taking out unserviceable Buffer (For Closing Spring ) For 630A to 800A Schneider make 11 KV VCB complete all as specified and as directed.
Make-Schneider only, Part No- MVIJ00056-01 | 1 | Each | - | - |
| 7 | Supply and fix including dismantling taking out unserviceable single (Read-Blue) phase busbar spout suitable for 630A to 800A VCB complete all as specified and as directed. Make-Schneider only, Part No- MEP-39-32185 | 1 | Each | - | - |
| 8 | Supply and fix including dismantling taking out unserviceable single (Y) phase busbar spout for 630A to 800A 11 KV VCB complete all as specified and as directed.
Make :- Schneider Model No MEP-39-32186 | 1 | Each | - | - |
| 9 | Supply and fix including dismantling taking out unserviceable CT Spout suitable for VCB 630A to 800A complete all as specified and as directed.
Make :- Schneider Model No MEP-39-32187 | 3 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
8735Tender.pdf
Tender Documents • 0.99 MB
BOQ_896758.xls
BOQ • 0.70 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .