Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹62.8 LAccepted-AOC D NO 9 947 66 DOCTORS COLONY SHIVAJI PLEM VISAKHAPATNAM 530017 | VISAKHAPATANAM | ANDHRA PRADESH | 530017 | L1 | Accepted-AOC Lowest Bid Accepted | |
| 2 | L2₹64.6 L+₹1.9 L (2.99%)Rejected-Finance DOOR NO 14 6 21 5 OPP MARVAL SCHOOL BC ROAD NEW GAJUWAKA VISAKHAPATNAM 530026 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530026 | L2 | Rejected-Finance Not Being Lowest Bidder | |
| 3 | L3₹67.9 L+₹5.1 L (8.11%)Rejected-Finance D NO 32 1 211 2 BOWDARA ROAD VISAKHAPATNAM 530004 | VISAKHAPATANAM | ANDHRA PRADESH | 530004 | L3 | Rejected-Finance Not Being Lowest Bidder | |
| 4 | L4₹73.1 L+₹10.4 L (16.5%)Rejected-Finance D NO 35 14 13 1 R P PETA KANCHARAPALEM VISAKHAPATNAM 530 008 | VISAKHAPATANAM | ANDHRA PRADESH | 530008 | L4 | Rejected-Finance Not Being Lowest Bidder | |
| 5 | L5₹73.4 L+₹10.6 L (16.9%)Rejected-Finance MIG 330 MADHAVADHARA VUDA COLONY VISAKHAPATNAM 530 018 | VISAKHAPATANAM | ANDHRA PRADESH | 530018 | L5 | Rejected-Finance Not Being Lowest Bidder |
| Sl No | Description | Qty | Unit | REAL ENGINEERING WORKS L2 | S.M.Electricals L3 | SRIVALLI ENGINEERS L1 | M/S CHANDRA ENGINEERS AND CONTRACTORS L4 | M/s.DSRK CONSTRUCTIONS L5 | Radhe Krishn Engineering L6 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supplying, Installing, testing and commissioning of Floor Mounted Compact Scroll type Water Cooled Chiller Package Units of Capacity not less than 34.5 TR, suitable for ambient conditions, complete with Hermetically sealed Scroll type Compressors with independent Circuits with minimum loading capacity 15%, operating voltage 360 – 440 Volts, 50 Hz, 3 Phase, AC supply working with refrigerant R – 407C/ R-410A, Water Cooled Shell and Tube type Condenser with internally knurled copper tubes, Horizontal Direct Expansion (DX) type Evaporator with Carbon Steel Shell and Seamless Copper Tubes with 19 mm thick Nitrile Rubber Insulation, Common Base Frame, Interconnected Copper Refrigerant Piping and Wiring, Vibration Isolators, gauge panel, Automatic Safety Controls, Flow Switch at evaporator and Condenser, Ozone friendly CFC Free Refrigerant Gas R-407C/ R-410A including Thermostatic Expansion Valve for Refrigerant Flow Control, properly spaced Baffles for maintaining Optimum Water Velocity and Heat Transfer, adequate supports for tubes complete all as per manufacturer’s instructions including Dismantling and Taking down of existing old unserviceable Central AC Plant of capacity 34.5 TR comprising of Chillers, Compressors, Cooling Towers, Pump sets/ Pipelines, AHU alongwith connected panels/ cables/ pipes/ valves, Ducts alongwith its insulation/ grills, etc. including necessary T & P, Scaffolding and making good disturbed portions to match with existing and shifting the Central AC Plant in AGE E/M MES store Yard (Dolphin Hill ) complete all as specified and as directed.
Notes:
[a] The Chiller shall be designed for a Working Pressure of 150 PSIG and Hydraulically Tested at 225 PSIG.
[b] Test certificates shall be produced for all the condensing units. | 3 | Each Job | 9,50,000 ₹28,50,000 Lowest | 11,90,007 ₹35,70,021 | 11,00,000 ₹33,00,000 | 12,50,000 ₹37,50,000 | 10,50,000 ₹31,50,000 | 11,00,000 ₹33,00,000 |
| 1.01[c] The quoted price shall be inclusive of a unit mounted Starter to ensure that the starting current does not exceed twice the full load current, System Integrator capable of giving industry standard [Modbus / Bacnet] Output to BMS for Critical Parameters. Mapping shall be required for all critical points displayed on the Chiller Control Panel. The Chiller shall be BMS compatible. [d] The Chiller shall be suitable for 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply [e] The rate quoted shall be deemed to be inclusive of necessary civil works viz. PCC foundation and connected works for installation of chillers and its accessories as required at site. [f] Any other items which are not mentioned in the description of this item or not specified in the tender documents but the same are required for smooth operation of AC Plant shall be provided by the contractor without any extra cost to the Department. [g] The Chiller shall be as approved and shall meet the following design criteria: [i] CHILLER: [a] Chilled Water IN: 54°F [b] Chilled Water OUT: 44°F [c] Fouling Factor: 0.0001 Hr.FT2. F/Btu [d] Water Flow Rate: 2.4 USgpm/TR [ii] CONDENSER: [a] Condenser Water IN: 90°F [b] Condenser Water OUT: 100°F [c] Fouling Factor: 0.00025 Hr.FT2. F/Btu [d] Water Flow Rate: 3.5 USgpm/TR [iii] Minimum Coefficient Of Performance at ARI Conditions: 4.2 | |||||||||
| 2.00 | Supplying, Installing, testing and commissioning of Chilled Water Pumps End Suction & Top Discharge, Non-Self-Priming, Single-Stage, Centrifugal Volute Type Monoblock Pump of capacity 180 USGPM Water Flow at 20 metres Head, having Cast Iron Casing, Enclosed type Dynamically balanced Phosphor Bronze / SS Impeller, High Tensile Steel Shaft, Carbon Steel Stuffing Box [Sealed by Mechanical Seal], Deep Groove Ball Bearings, TEFC Squirrel Cage High Efficiency Induction Motor, base Plate, Mounting Channel Frame, accessories and fittings, viz. Mechanical Seal, Drains, Coupling, Coupling Guard, Vibration Isolation arrangement by means of Spring / Rubber type mounting suitable for operation on 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply complete all as per manufacturer’s instructions, as specified and as directed.
Note: The rate quoted shall be deemed to be inclusive of necessary civil work viz. PCC foundation and connected works for installation of pumpset and its accessories as required at site. | 3 | Each Job | 39,500 ₹1,18,500 | 32,004 ₹96,012 Lowest | 90,000 ₹2,70,000 | 38,000 ₹1,14,000 | 1,20,000 ₹3,60,000 | 75,000 ₹2,25,000 |
| 3.00 | Supplying, Installing, testing and commissioning of Condenser water Pumps of End Suction & Top Discharge, Non-Self-Priming, Single-Stage, Centrifugal Volute Type Monoblock Pump of capacity suitable for 270 USGPM Water Flow at 25 metres Head, having Cast Iron Casing, Enclosed type Dynamically balanced Phosphor Bronze / SS Impeller, High Tensile Steel Shaft, Carbon Steel Stuffing Box [Sealed by Mechanical Seal], Deep Groove Ball Bearings, TEFC Squirrel Cage High Efficiency Induction Motor, base Plate, Mounting Channel Frame, accessories and fittings, viz. Mechanical Seal, Drains, Coupling, Coupling Guard, Vibration Isolation arrangement by means of Spring / Rubber type mounting suitable for operation on 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply complete all as per manufacturer’s instructions, as specified and as directed.
Note: The rate quoted shall be deemed to be inclusive of necessary civil work viz. PCC foundation and connected works for installation of Pump Set and its accessories as required at site. | 3 | Each Job | 35,000 ₹1,05,000 | 36,000 ₹1,08,000 | 1,10,000 ₹3,30,000 | 32,000 ₹96,000 Lowest | 1,35,000 ₹4,05,000 | 90,000 ₹2,70,000 |
| 4.00 | Supplying, Installing, testing and commissioning of FRP rectangular / Round / Bottle Shaped vertical induced/ forced draft counter flow type Cooling Tower of capacity not less than 35 TR capacity with uniform water distribution and optimal heat transfer, having tough Fiberglass Reinforced Plastic [FRP] casing of sufficient structural strength to withstand vibrations and wind velocity up to 60 Metres/ Second, FRP Basin, Rigid Honeycomb Type PVC Fill of suitable thickness, SS Sprinklers and Non Clogging Sprinkler Pipes, FRP Drift Eliminator, Energy Efficient Induced Draught Axial Type Fans with factory set and dynamically balanced blades pitch, TEFC Squirrel Cage High Efficiency Induction Motor with IP 65 Protection suitable for 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply, Inlet, Outlet, Drain and Over Flow Nozzle connections etc. complete all as per manufacturer’s instructions, as specified and as directed.
Note: The rate quoted shall be deemed to be inclusive of necessary civil work viz. PCC foundation and connected works for installation of Cooling Tower and its accessories as required at site. | 2 | Each | 1,35,000 ₹2,70,000 | 1,60,002 ₹3,20,004 | 2,00,000 ₹4,00,000 | 1,32,000 ₹2,64,000 Lowest | 1,80,000 ₹3,60,000 | 1,90,000 ₹3,80,000 |
| 5.00 | Supplying, Installing, testing and commissioning of Double Skin Air Handling Unit with Air Stream Disinfection system, 34.5 TR Capacity / 75mm Static 24000/ CFM, Horizontal, Floor Mounted, Top / Side Discharge having corrosion resistant extruded aluminum hollow profile with Thermal Break, Heavy Gauge Galvanised Steel Channel Base Frame, 43 mm thick Double Skin Panel with pressure injected CFC & HCFC free PUF with 'k' value of 0.02 W/°C m & density 40 KG/Cu.m, Pre-Coated, Pre-Plasticized galvanised outer and inner skin of 0.60mm thick, Air-Tight Casing using Gaskets and Self-Adhesive Tapes, AMCA certified energy efficient fans with double inlet double width forward or backward curved impellers for high static pressure mounted on Aluminum Extruded Slide Rail Base Frame, Chilled water Coils with combination of 6 Rows deep with anti-corrosion Aluminum fins, PVC Nylon Hinges & Handles, View Port and Marine Lamp, Limit Switch, SS-304 Drain Pan, 10 Micron Pre-Filters, Inspection Windows / Doors complete all as per manufacturer’s instructions, as specified and as directed.
The Design Criteria of the AHU shall be as under:
[a] Suitable DIDW [Double Inlet Double Width] Fan with AMCA certified Blower having outlet velocity not exceeding 9.2 Metres / Second
[b] 4 Pole, TEFC, High Efficiency, Squirrel Cage Induction Motor Drive having BHP rating 20% higher than the peak capacity, suitable for 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply
[c] V-Belt Drive Assembly with Pulleys, Belt, Guard, etc., Double Canvass Connections with Zip to Discharge Duct / Plenum, etc.
[d] 50 mm thick, Washable HDPE, 90% down 10 Micron Pre-Filters, Filters, Fixing Framework, Hinge Type Access Doors etc. | 1 | Each | 20,50,000 ₹20,50,000 | 15,80,004 ₹15,80,004 | 3,00,000 ₹3,00,000 Lowest | 23,00,000 ₹23,00,000 | 6,00,000 ₹6,00,000 | 15,00,000 ₹15,00,000 |
| 5.01[e] 6 Row deep Chilled Water Coil section with Copper Fins and Copper Tube tested on 21 KG / Sq.cm with SS Sandwiched Drain Tray, etc. [f ] S & F 3-Way temperature control modulating mixing Valve of 65 mm nominal bore, cast iron body duly insulted, Class PN-16, suitable for operation up-to 10 Bar, with Electronically operated Actuator for AHUs including all Joints with Jointing Materials, Bolts, Nuts, Washer complete all as specified and as directed. [g] S & F of Strip Heater Bank of capacity not less than 12 Kw to maintain RH factor including necessary wiring, accessories complete. [h] S & F of Humidistats and Thermostats suitable for AHU Room complete all as specified and as directed. [j] M & L for Under Deck Insulation for AHU Rooms, conditioned areas & Sun exposed Salbs with 18mm thick Fire Retardant XPE Closed Cell with Metalized Polyester Film and Self Adhesive Backing with Protection Peel off Paper with 50 mm projection for overlap and butting complete. [f] AHU shall be provided with UVC emitters & fixture in sufficient quantity so as to provide equal distribution of UVC energy on the coil and in the drain pan all as recommended by the OEM. | |||||||||
| 6.00 | S & F Mild Steel ERW Pipe of 100 mm Nominal Bore Class 'C' Heavy Grade, conforming to IS – 1239 as in Chilled Water Piping duly Insulated with 50mm thick Expanded Polystyrene Insulation of density 30 Kg/ Cum and Covered with 28 Gauge Aluminium Cladding including all fittings i.e. Bends, Tees, Teducers, Flanges, Structural Support, Wooden / Puff Blocks, etc.complete all as specified and as directed. | 30 | RM | 1,650 ₹49,500 | 1,242 ₹37,260 Lowest | 1,600 ₹48,000 | 1,250 ₹37,500 | 2,750 ₹82,500 | 2,900 ₹87,000 |
| 7.00 | S & F Mild Steel ERW Pipe of 80 mm Nominal Bore Class 'C' Heavy Grade, conforming to IS – 1239 as in Chilled Water Piping duly Insulated with 50mm thick Expanded Polystyrene Insulation of density 30 Kg/ Cum and Covered with 28 Gauge Aluminium Cladding including all fittings i.e. Bends, Tees, Teducers, Flanges, Structural Support, Wooden / Puff Blocks, etc.complete all as specified and as directed. | 25 | RM | 1,550 ₹38,750 | 1,125 ₹28,125 | 1,440 ₹36,000 | 900 ₹22,500 Lowest | 2,350 ₹58,750 | 2,100 ₹52,500 |
| 8.00 | S & F Mild Steel ERW Pipe of 65 mm Nominal Bore Class 'C' Heavy Grade, conforming to IS – 1239 as in Chilled Water Piping duly Insulated with 50mm thick Expanded Polystyrene Insulation of density 30 Kg/ Cum and Covered with 28 Gauge Aluminium Cladding including all fittings i.e. Bends, Tees, Teducers, Flanges, Structural Support, Wooden / Puff Blocks, etc.complete all as specified and as directed. | 15 | Each | 1,250 ₹18,750 | 1,080 ₹16,200 | 1,200 ₹18,000 | 750 ₹11,250 Lowest | 1,950 ₹29,250 | 1,500 ₹22,500 |
Tender Value
₹79.5 L
EMD Value
₹1.4 L
Closing Date
2 Mar 2026, 6:00 pmClosed
Col Shinde SS, Commander Works Engineer
Commander Works Engineers, Station Road, Visakhapatnam - 530 004
SPECIAL REPAIRS REPLACEMENT TO AC PLANT 3 X 34.5 TR AGAINST BER ITEMS AT INS EKSILA UNDER GE U-I, VISAKHAPATNAM
2026_MES_750893_1
82644/E8
Open Tender
Civil Works
Item Rate
360 days
Visakhapatnam
As per NIT
9 documents required · 9 mandatory
₹1,000
Garrison Engineer Utility - I
₹1.4 L
Yes
7 May 2026
2 Feb 2026
4 Mar 2026
2 Feb 2026
2 Mar 2026
23 Feb 2026
2 Feb 2026 - 9 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, Installing, testing and commissioning of Floor Mounted Compact Scroll type Water Cooled Chiller Package Units of Capacity not less than 34.5 TR, suitable for ambient conditions, complete with Hermetically sealed Scroll type Compressors with independent Circuits with minimum loading capacity 15%, operating voltage 360 – 440 Volts, 50 Hz, 3 Phase, AC supply working with refrigerant R – 407C/ R-410A, Water Cooled Shell and Tube type Condenser with internally knurled copper tubes, Horizontal Direct Expansion (DX) type Evaporator with Carbon Steel Shell and Seamless Copper Tubes with 19 mm thick Nitrile Rubber Insulation, Common Base Frame, Interconnected Copper Refrigerant Piping and Wiring, Vibration Isolators, gauge panel, Automatic Safety Controls, Flow Switch at evaporator and Condenser, Ozone friendly CFC Free Refrigerant Gas R-407C/ R-410A including Thermostatic Expansion Valve for Refrigerant Flow Control, properly spaced Baffles for maintaining Optimum Water Velocity and Heat Transfer, adequate supports for tubes complete all as per manufacturer’s instructions including Dismantling and Taking down of existing old unserviceable Central AC Plant of capacity 34.5 TR comprising of Chillers, Compressors, Cooling Towers, Pump sets/ Pipelines, AHU alongwith connected panels/ cables/ pipes/ valves, Ducts alongwith its insulation/ grills, etc. including necessary T & P, Scaffolding and making good disturbed portions to match with existing and shifting the Central AC Plant in AGE E/M MES store Yard (Dolphin Hill ) complete all as specified and as directed.
Notes:
[a] The Chiller shall be designed for a Working Pressure of 150 PSIG and Hydraulically Tested at 225 PSIG.
[b] Test certificates shall be produced for all the condensing units. | 3 | Each Job | - | - |
| 1.01 | [c] The quoted price shall be inclusive of a unit mounted Starter to ensure that the starting current does not exceed twice the full load current, System Integrator capable of giving industry standard [Modbus / Bacnet] Output to BMS for Critical Parameters. Mapping shall be required for all critical points displayed on the Chiller Control Panel. The Chiller shall be BMS compatible.
[d] The Chiller shall be suitable for 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply
[e] The rate quoted shall be deemed to be inclusive of necessary civil works viz. PCC foundation and connected works for installation of chillers and its accessories as required at site.
[f] Any other items which are not mentioned in the description of this item or not specified in the tender documents but the same are required for smooth operation of AC Plant shall be provided by the contractor without any extra cost to the Department.
[g] The Chiller shall be as approved and shall meet the following design criteria:
[i] CHILLER:
[a] Chilled Water IN: 54°F
[b] Chilled Water OUT: 44°F
[c] Fouling Factor: 0.0001 Hr.FT2. F/Btu
[d] Water Flow Rate: 2.4 USgpm/TR
[ii] CONDENSER:
[a] Condenser Water IN: 90°F
[b] Condenser Water OUT: 100°F
[c] Fouling Factor: 0.00025 Hr.FT2. F/Btu
[d] Water Flow Rate: 3.5 USgpm/TR
[iii] Minimum Coefficient Of Performance at ARI Conditions: 4.2 | - | - | - | - |
| 2 | Supplying, Installing, testing and commissioning of Chilled Water Pumps End Suction & Top Discharge, Non-Self-Priming, Single-Stage, Centrifugal Volute Type Monoblock Pump of capacity 180 USGPM Water Flow at 20 metres Head, having Cast Iron Casing, Enclosed type Dynamically balanced Phosphor Bronze / SS Impeller, High Tensile Steel Shaft, Carbon Steel Stuffing Box [Sealed by Mechanical Seal], Deep Groove Ball Bearings, TEFC Squirrel Cage High Efficiency Induction Motor, base Plate, Mounting Channel Frame, accessories and fittings, viz. Mechanical Seal, Drains, Coupling, Coupling Guard, Vibration Isolation arrangement by means of Spring / Rubber type mounting suitable for operation on 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply complete all as per manufacturer’s instructions, as specified and as directed.
Note: The rate quoted shall be deemed to be inclusive of necessary civil work viz. PCC foundation and connected works for installation of pumpset and its accessories as required at site. | 3 | Each Job | - | - |
| 3 | Supplying, Installing, testing and commissioning of Condenser water Pumps of End Suction & Top Discharge, Non-Self-Priming, Single-Stage, Centrifugal Volute Type Monoblock Pump of capacity suitable for 270 USGPM Water Flow at 25 metres Head, having Cast Iron Casing, Enclosed type Dynamically balanced Phosphor Bronze / SS Impeller, High Tensile Steel Shaft, Carbon Steel Stuffing Box [Sealed by Mechanical Seal], Deep Groove Ball Bearings, TEFC Squirrel Cage High Efficiency Induction Motor, base Plate, Mounting Channel Frame, accessories and fittings, viz. Mechanical Seal, Drains, Coupling, Coupling Guard, Vibration Isolation arrangement by means of Spring / Rubber type mounting suitable for operation on 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply complete all as per manufacturer’s instructions, as specified and as directed.
Note: The rate quoted shall be deemed to be inclusive of necessary civil work viz. PCC foundation and connected works for installation of Pump Set and its accessories as required at site. | 3 | Each Job | - | - |
| 4 | Supplying, Installing, testing and commissioning of FRP rectangular / Round / Bottle Shaped vertical induced/ forced draft counter flow type Cooling Tower of capacity not less than 35 TR capacity with uniform water distribution and optimal heat transfer, having tough Fiberglass Reinforced Plastic [FRP] casing of sufficient structural strength to withstand vibrations and wind velocity up to 60 Metres/ Second, FRP Basin, Rigid Honeycomb Type PVC Fill of suitable thickness, SS Sprinklers and Non Clogging Sprinkler Pipes, FRP Drift Eliminator, Energy Efficient Induced Draught Axial Type Fans with factory set and dynamically balanced blades pitch, TEFC Squirrel Cage High Efficiency Induction Motor with IP 65 Protection suitable for 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply, Inlet, Outlet, Drain and Over Flow Nozzle connections etc. complete all as per manufacturer’s instructions, as specified and as directed.
Note: The rate quoted shall be deemed to be inclusive of necessary civil work viz. PCC foundation and connected works for installation of Cooling Tower and its accessories as required at site. | 2 | Each | - | - |
| 5 | Supplying, Installing, testing and commissioning of Double Skin Air Handling Unit with Air Stream Disinfection system, 34.5 TR Capacity / 75mm Static 24000/ CFM, Horizontal, Floor Mounted, Top / Side Discharge having corrosion resistant extruded aluminum hollow profile with Thermal Break, Heavy Gauge Galvanised Steel Channel Base Frame, 43 mm thick Double Skin Panel with pressure injected CFC & HCFC free PUF with 'k' value of 0.02 W/°C m & density 40 KG/Cu.m, Pre-Coated, Pre-Plasticized galvanised outer and inner skin of 0.60mm thick, Air-Tight Casing using Gaskets and Self-Adhesive Tapes, AMCA certified energy efficient fans with double inlet double width forward or backward curved impellers for high static pressure mounted on Aluminum Extruded Slide Rail Base Frame, Chilled water Coils with combination of 6 Rows deep with anti-corrosion Aluminum fins, PVC Nylon Hinges & Handles, View Port and Marine Lamp, Limit Switch, SS-304 Drain Pan, 10 Micron Pre-Filters, Inspection Windows / Doors complete all as per manufacturer’s instructions, as specified and as directed.
The Design Criteria of the AHU shall be as under:
[a] Suitable DIDW [Double Inlet Double Width] Fan with AMCA certified Blower having outlet velocity not exceeding 9.2 Metres / Second
[b] 4 Pole, TEFC, High Efficiency, Squirrel Cage Induction Motor Drive having BHP rating 20% higher than the peak capacity, suitable for 3 Phase, 415 Volts ± 10%, 50 Hz, AC Supply
[c] V-Belt Drive Assembly with Pulleys, Belt, Guard, etc., Double Canvass Connections with Zip to Discharge Duct / Plenum, etc.
[d] 50 mm thick, Washable HDPE, 90% down 10 Micron Pre-Filters, Filters, Fixing Framework, Hinge Type Access Doors etc. | 1 | Each | - | - |
| 5.01 | [e] 6 Row deep Chilled Water Coil section with Copper Fins and Copper Tube tested on 21 KG / Sq.cm with SS Sandwiched Drain Tray, etc. [f ] S & F 3-Way temperature control modulating mixing Valve of 65 mm nominal bore, cast iron body duly insulted, Class PN-16, suitable for operation up-to 10 Bar, with Electronically operated Actuator for AHUs including all Joints with Jointing Materials, Bolts, Nuts, Washer complete all as specified and as directed. [g] S & F of Strip Heater Bank of capacity not less than 12 Kw to maintain RH factor including necessary wiring, accessories complete. [h] S & F of Humidistats and Thermostats suitable for AHU Room complete all as specified and as directed. [j] M & L for Under Deck Insulation for AHU Rooms, conditioned areas & Sun exposed Salbs with 18mm thick Fire Retardant XPE Closed Cell with Metalized Polyester Film and Self Adhesive Backing with Protection Peel off Paper with 50 mm projection for overlap and butting complete.
[f] AHU shall be provided with UVC emitters & fixture in sufficient quantity so as to provide equal distribution of UVC energy on the coil and in the drain pan all as recommended by the OEM. | - | - | - | - |
| 6 | S & F Mild Steel ERW Pipe of 100 mm Nominal Bore Class 'C' Heavy Grade, conforming to IS – 1239 as in Chilled Water Piping duly Insulated with 50mm thick Expanded Polystyrene Insulation of density 30 Kg/ Cum and Covered with 28 Gauge Aluminium Cladding including all fittings i.e. Bends, Tees, Teducers, Flanges, Structural Support, Wooden / Puff Blocks, etc.complete all as specified and as directed. | 30 | RM | - | - |
| 7 | S & F Mild Steel ERW Pipe of 80 mm Nominal Bore Class 'C' Heavy Grade, conforming to IS – 1239 as in Chilled Water Piping duly Insulated with 50mm thick Expanded Polystyrene Insulation of density 30 Kg/ Cum and Covered with 28 Gauge Aluminium Cladding including all fittings i.e. Bends, Tees, Teducers, Flanges, Structural Support, Wooden / Puff Blocks, etc.complete all as specified and as directed. | 25 | RM | - | - |
| 8 | S & F Mild Steel ERW Pipe of 65 mm Nominal Bore Class 'C' Heavy Grade, conforming to IS – 1239 as in Chilled Water Piping duly Insulated with 50mm thick Expanded Polystyrene Insulation of density 30 Kg/ Cum and Covered with 28 Gauge Aluminium Cladding including all fittings i.e. Bends, Tees, Teducers, Flanges, Structural Support, Wooden / Puff Blocks, etc.complete all as specified and as directed. | 15 | Each | - | - |
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.65 MB
BOQ_841002.xls
BOQ • 0.40 MB
82644Tender.pdf
Tender Documents • 1.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .