The Executive Engineer (O&M), DGVCL Piplod Division Office, Surat.
Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable end termination & straight through jointing kit (to be supplied by contractor) on ARC basis under all scheme under 66 KV Mora Sub Station ICHCHHAPORE sub division as well as all Sub-Division in jurisdiction of Piplod Division or within the jurisdiction of Surat City Circle.
320362
DGVCLDPPL/0684/06/2026 Approved Date: 25-06-2026
Open
Electrical
Surat
1 document required · 1 mandatory
₹1,180
SURAT DGVCL
₹30,000
3 Jul 2026
3 Jul 2026
3 Jul 2026
20 Jul 2026
3 Jul 2026
Sub:-Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable
end termination & straight through jointing kit (to be supplied by contractor) on ARC basis under 66 KV Mora Sub Station ICHCHHAPORE sub division sub
division as well as all Sub-Division in jurisdiction of Piplod Division or within the jurisdiction of Surat City Circle.
Item Code DETAILS OF WORKS Qty Unit Rate Amount
1 9925000001 Labour charge for excavation of cable trench of 400mm width x 1200mm depth, Meter
in any type of soil for laying of cable of size up to 240 mm2 (For additional cable
200 mm additional width shall be considered i.e. half trench length is to be
2 9925000002 Labour charge for excavation of cable trench of 600mm width x 1200mm depth, Meter
in any type of soil for laying of cable of size up to 240 mm2 (For additional cable
200 mm additional width shall be considered i.e. half trench length is to be
3 9925000003 Labour charge for excavation of cable trench of 400mm width x 1500mm depth, Meter
in any type of soil for laying of cable of size up to 240 mm2 (For additional cable
200 mm additional width shall be considered i.e. half trench length is to be
4 9925000004 Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 & Meter
preparation of sand layer 100mm thick, in the cable trench & covering the cable
with 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round muffs
and providing and fixing of 4inch width yellow colour polyethylene tape with
printing "CAUTION ELECTRIC CABLE BELOW" at 0.75 m depth from ground
surface after laying cable in trench. This will provide indication that electric cable
is passing underground so as to protect cable from mechnical injuries, refilling
the same, as per Instruction of Engineer in Charge (EIC).
5 9925000005 Labour charge for horizontal drilling using Auger machine without damage to Meter
surface road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green
color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd
revision) and BIS certification and laying of 11KV/22KV XLPE cable of size up to
300 mm2 in HDPE pipe, as per Site Condition (excluding cost of pipe). The detail
map obtained from HDD machine and excell sheet(hard and soft copy)
indicating the respective depth and distance from adjacent landmark for each
segment for HDD is must required to be submitted. HDD to be carried out at
depth 1.5 mtrs to 2.0 mtrs as per site conditions and as per instruction of EIC.
6 9925000006 Labour charge for horizontal drilling manually without damage to surface road at Meter
max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D.,
8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS
certification and laying of 11KV/22KV XLPE cable of size up to 300 mm2 size, as
per Site Condition (excluding cost of pipe). The detail map and excell sheet(hard
and soft copy) indicating the respective depth and distance from adjacent
landmark for each segment of cable to be submitted. Drilling to be carried out at
depth Minimum 1.2 mtrs to 2.0 mtrs as per site conditions as per instruction of
7 9925000007 Supply of 6.11kg/cm2, class-4,Green color, 110mm O.D., 8.5 mm thickness Meter
H.D.P.E. pipe confirms to IS 4984 and BIS certification for laying of underground
11KV / 22KV XLPE cable up to 300 mm2 size.
8 9925000008 Labour work for RCC concreting on disputed location and repairing of damage CMT
portion of road crossing for the work carried out for roads crossing as well as
concreting & muffing of ploes including all materials (1:2:4)
9 9925000009 Providing & fixing concrete stone route marker of 300 mm width x 150 mm thick No
x 650 mm height embedded in earth at least 300 mm below & 350 mm above
ground level respectively at distance approx 50 meters along the length of cable.
The RCC concreting (1:2:4)(all necessary maeterials will be in bidder's scope) of
route marker is to be carried out 300 mm width x 150 mm thick x 300 mm below
ground level as per instruction of EIC. The route marker should be with name
of company with approved yellow colour-DGVCL. The distance from marker to
cable and cable depth with feeder name etc., marked with arrow sign is to be
painted on it.The route marker is to be fixed at location near to any fixed
permanent location (not necessary to fix exact on top of cable) as per
instruction of EIC.
10 9925000014 Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 300 mm 2 on Per
DP Structure with fixing of 02 Nos polymer cleats on top and middle part . Job
Polymer cleats, nut bolts etc. fixing material to be provided by contractor.
11 9925000015 Providing & fixing of 6.11kg/cm2, class-4,Green color, 110mm O.D., 8.5mm Per
thickness H.D.P.E. pipe confirms to IS 4984 and BIS certification on the erected Job
DP structure for the mechanical protection of cable by inserting the cable inside
HDPE pipe. The HDPE pipe shall be erected in such a way that 300mm shall be
below the ground level and the rest 2700 mm shall be supported on the DP
Structure with 01 No Polymer cleat. All materials including polymer cleat and Nut
bolt to be provided by contractor.
12 9925000016 Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with No
pit to be filled with salt & coke and construction of chamber as per DGVCL Drg.
No. dg /100 for DP and cable. The earthing pit should be joined with cable by
G.I. strip of size 1” width & 2 mm thick. All material GI pipe, Coke, Salt etc will be
supplied by bidder.
13 9925000017 Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV 3C x No
185 mm2 size XLPE cable as per DGVCL technical specification.
14 9925000018 Supply & fixing of heat & shrinkable end terminations (outdoor) for upto 22 kV No
3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
15 9925000019 Supply & fixing of heat shrink type end terminations (indoor) for upto 11kV 3C x No
185 mm2 size XLPE cable as per DGVCL technical specification.
16 9925000020 Supply & fixing of heat & shrinkable end terminations (indoor) for upto 22 kV 3C No
x 185 mm2 size XLPE cable as per DGVCL technical specification.
17 9925000021 Supply & fixing of heat shrinkable straight through joint for upto 11kV 3C x 185 No
mm2 size XLPE cableas per DGVCL technical specification.
18 9925000022 Supply & fixing of heat shrinkable straight through joint type for upto 22kV 3C x No
185 mm2 size XLPE cable as per DGVCL technical specification.
19 9925000023 Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep No
joint pits for installation of 11kV/22kV Straight through joints as per instruction
of engineer-in-charge & covering the cable with 150 mm dia (Outer), thickness
25 mm, 1.0 meter long RCC half round muffs & refilling same as per instruction
20 9925000024 Providing and fixing of insulating bus bar, made from 11KV/22KV XLPE cable after No
removal of semi conducting layer and applying of PVC heat shrinkable anti-
tracking core insulating tubing (1.1KV), on both end terminal using Aluminium
long barrel heavy duty up to 240 sq mm lugs, Aluminium bus connector. Taping
with PG- clamp for bus conductor as per drawing and as per instruction of EIC.
The Alluminium lugs and PG clamp shall be covered with 11KV/22KV HT
insulating tapes.(11KV/22KV XLPE cable will be in scope of DGVCL while all other
materials will be in bidder's scope)
21 9925000025 Testing of cable at various points and commissioning the feeder as per No
instruction of engineer-in-charge. Test result shall be submitted by contractor
22 9925000026 Preparation and submission of 6 (six) copies, of complete layout drawings with Set
GIS mapping as per actual cable routing showing road crossing, HDPE pipe
sleeving, jointing locations, markers etc.
23 9925000027 Providing and fixing of Sign Board at junction point Made out of 2 mm No
aluminium sheet size 750x300 mm (2.5 x 1ft) rectangle, as per design, pre
treated with phosphate process and acid etching coated with one coat of epoxy
primer and two coats of best quality paints, refloctrorised with Hi-Intensity retro
– reflective sheeting as per the latest and frame fabricated from suitable size iron
angle. The Sign Board is to be fixed on the base prepared from channel and
bracing angles which is grouted by means of cement concreting of 1:2:4 for size
of 300 mm dia x 800 mm height (500 mm to be grouted in ground). The details to
be displayed on sign board will be given by In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
24 9925000028 Providing and fixing of Sign Board (Danger Board) on Distribution Transformer No
Made out of 2mm aluminium sheet size 300x300mm (1x1ft) as per design, pre
treated with phosphate process and acid etching coated with one coat of epoxy
primer and two coats of best quality paints, refloctrorised with Hi-Intensity retro-
reflective sheeting as per the latest and frame fabricated from suitable size iron
angle. The Sign Board (Danger Board is to be fixed at the location as per
instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
25 9925000029 Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from 3 mm No
aluminium sheet along with 1.0 mm dia aluminium binding wire for fixing of
aluminium tag near end termination joint at DP structure for identifyng the
cable. The details of feeder i.e. 11 / 22 KV with feeder name shound be punched
on the tag by letter punch of size 16 mm as per instruction of In-charge Engineer.
26 9925000030 Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x 240 Nos
mm2 size XLPE cable as per DGVCL technical specification.
27 9925000031 Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 kV 3C x Nos
240 mm2 size XLPE cable as per DGVCL technical specification.
28 9925000032 Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 240 Nos
mm2 size XLPE cable as per DGVCL technical specification.
29 9925000033 Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV 3C x 240 Nos
mm2 size XLPE cable as per DGVCL technical specification.
30 9925000034 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 240 mm2 Nos
size XLPE cableas per DGVCL technical specification.
31 9925000035 Supply & fixing of heat shrinkable straight through joint type for 22kV 3C x 240 Nos
mm2 size XLPE cable as per DGVCL technical specification.
Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade trench or in open cable
33 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM
34 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round NO.
35 9925000010 Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable NO.
connection arrangement along with fitting of necessary fabrication for 11KV
cable including excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
36 9925000011 Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable connection NO.
arrangement along with fitting ofnecessary fabrication for 11KV/22 KV cable
including excavation of pit & refilling of earth as per instruction of EIC. (Exclusive
of concreting & muffing of poles)
37 9925000012 Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable NO.
connection arrangement along with fitting of necessary fabrication for 11KV
cable including excavation of pit & refilling of earth as per instruction of EIC.
(Exclusive of concreting & muffing of poles)
39 9925000013 Erection of Single pole structure using 8.0 Mtr PSC pole with cable connection NO.
arrangement along with fitting ofnecessary fabrication for 11KV/22 KV cable
including excavation of pit & refilling of earth as per instruction of EIC. (Exclusive
of concreting & muffing of poles)
40 Laying (including installation, testing and commissioning) of various size of mtr 335 as per rate derived by UGVCL
Single circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Cable in letter no ugvcl/r&c/ug/Cost Data-
ground 1200 mm deep and 300 mm wide trench, providing sand cushioning 2022-23/816 Date:-27-01-2023
below (75 mm thick layer of sand) and above (75 mm thick layer of sand) of the
cable and covering it with RCC half round hume pipe (150 mm inner
diameter with thickness of 30 mm and One meter in length) before refilling
pre-bonding tap/warning tap should provide below 700 mm from the
ground level and back filling the same to make ground level as per original.
As per specification and drawing of DGVCL. ( RCC half round pipe should be
provide throughout on cable without gap).
41 Laying (including installation, testing and commissioning) of various size of mtr 468 as per rate derived by UGVCL
Double circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Cable in letter no ugvcl/r&c/ug/Cost Data-
ground 1200 mm deep and 500 mm wide trench, providing sand cushioning 2022-23/816 Date:-27-01-2023
below (75 mm thick layer of sand) and above (75 mm thick layer of sand) of the
cable and covering it with RCC half round hume pipe (150 mm inner diameter
with thickness of 30 mm and One meter in length) before refilling pre-bonding
tap/warning tap should provide below 700 mm from the ground level and back
filling the same to make ground level as per original. As per specification and
drawing of DGVCL. ( RCC half round pipe should be provide throughout on cable
42 Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 300 No 5549 as per rate derived by UGVCL
mm2 size XLPE cable as per technical specification. letter no ugvcl/r&c/ug/Cost Data-
43 Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV 3C x No 6676 as per rate derived by UGVCL
300 mm2 size XLPE cable as per technical specification. letter no ugvcl/r&c/ug/Cost Data-
44 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 300 mm 2 No 8040 as per rate derived by UGVCL
size XLPE cableas per L technical specification. letter no ugvcl/r&c/ug/Cost Data-
Rate as per SOR 30,00,000/-
Executive Engineer (O&M)
DGVCL, Division Office,
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
TENDER APPROVAL UG 30 L ICHCHHAPORE SDN.pdf
2. BID DOCUMENT.pdf
3. Detail Technical Specification.pdf
SCHEDULE B UG ICHCHHAPORE.pdf