SITC OF ELECTRICAL SUBSTATION AND REPAIRING OF HVAC WORK AT INDIRA GANDHI SPORTS COMPLEX, GOLAPAAR, HALDWANI
2024_MDPEY_78660_1
4895/Nivida(Garh)Elect.DDun/35 Dt.09/12/24
Open Tender
Electrical Works
Item Rate
365 days
HALDWANI
Please refer tender document
3 documents required · 3 mandatory
₹5,900
PM,Const.Unit(Elect.),UKPJN, Dehradun
₹9.9 L
Dehradun
29 May 2025
11 Dec 2024
28 Dec 2024
12 Dec 2024
26 Dec 2024
17 Dec 2024
16 Dec 2024
Amount
Electrical Work Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 120 sq. mm and upto 400 sq. mm
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Package/Compact Substation
Design, Supply, Installation, Testing and commissioning of 11kV,1000 KVA Package Substation with Non - extensible compact 3Way RMU consisting of 2 Nos. feeder with manually operated fixed type load break switch & 1 No. feeder with manually operated VCB 630A, 1 No. 11kV/433V, 1000kVA Cast Resin Dry Type Transformer & 1 set of LT device.
The 11KV Outdoor type Package Sub-Station shall be consisting of following:
HT Switchgear
3 Way 11kV 630Amps 21KA for 3 Sec. SF6 insulated with COPPER BUSBAR Non-Extinsible Compact Switchgear(RMU) consisting of Two Nos.Fixed Manual Load Break Switches and One No. Fixed Manual Vacuum Circuit Breaker in SF6 insulated non-ferrite non magnetic stainless steel enclosure of thickness 2.5mm of ingress protection IP, with series trip,live cable indicators,self powered microprocessor based numerical over current relay (IDMTL + Inst.) protection. Interconnection between HT switchgear and transformer shall be using 1Cx3x95 sq.mm Al. unarmorured XLPE Cable.
(i)Self powered over current and earth fault protection Relay with RS 485 Commuication Port.- 1No. (ii)Protection CT of ratio 100/1A 2.5VA 5P10.- 3 Nos. (iii)Capacitive based voltage presece idication-3Nos. (iv)Manometer- 1 No. (v)Operating Handle- 1 No.
Each VCB Feeder consists of following : (i) Manually spring charging arrangement and manual close & open push buttons, ON /OFF indication. -1 No. (ii) Microprocessor based Self powered O/C & E/F relay type CSPR with Single core castresin type CT (Protection Core – 2.5VA & CL-5P10)-1 Set (iii) Manually operated 630A load breaker switch with built in earth switch having full making capacity.-1 No. (iv)Mechanical position indicator Switch ON/OFF/EARTHED.-1 No. (v) Live Cable Indication.-1 Set (vi) Cable compartment cover interlocked with earth switch.-1 No. (vii) Cable termination bushings suitable for 3 no. 1C X 300 mm 2 Al. armoured XLPE cable.-3 No. (viii) Cable termination cover boots (Push on type)-1 Set. (ix)Metering module comprising MFM,with space heater and thermostat.
TRANSFORMER (C.S.S)
1000KVA, 11KV/433V DYn11 Cast Resin Copper Wound Dry Type Transformer with Off load tap switch of rating +5% to - 5% in steps of 2.5% , Impedance: 6.25% (With IS Tol.), Class of Insulation - H, NLL and FLL Standared losses as per ECBC2017, Temperature Rise in winding over ambient temp. shall be 115 Deg. C.- 01 NOS. Winding Temperature Indicator,Surge Arrestor and Alarm and trip contact.-1 Nos.
LT PANEL OUTGOINGS
433V indoor LT panel with 2000 Amps Aluminum Bus bars (100% for Phase & 100% for Neutral, Current Density- 1Amp/Sq.mm ),Farication using 2mm CRCA sheet steel), Ingress protection IP4X, complete with internal wiring consisting of following:
INCOMER FROM TRANSFORMER
1600 AMPS, 433V 4P 50Hz 65KA Fixed manual type Air Circuit Breaker (ACB) with Microprocessor based over current,short circuit and Earth fault protection release - Qty: 1 set
Multi Function meter with Cl.1 accuracy and RS 485 port- 1 No.
R/Y/B, ON/OFF/TRIP Indications.-1 Set
1000 AMPS,433 V, 4P, 50 Hz, 50KA, fixed manual type ACB with Microprocessor based over current,short circuit and Earth fault protection release (DG Incomer/changeover) -01 No.
Multi Function meter with Cl.1 accuracy and RS 485 port- 1 No., ON-OFF Indication- 01 no.
Manual Castell key lock between 2 incomer shall be provided (2 locks and 1 key)- 01 No. (changeover)
OUTGOINGS
1600Amps 433V 4P 50Hz 50KA Fixed Manual Type Molded Case Circuit Breaker (MCCB) with Microprocessor based overcurrent, short circuit & Earth Fault Protection- 1 No.
MFM- 01 No.
ON/OFF Indications-1 No.
400Amps 433V 4P 50Hz 36KA Fixed Manual Type Molded Case Circuit Breaker (MCCB) with Microprocessor based overcurrent, short circuit & Earth Fault Protection- 04 Nos.
MFM- 04 Nos.
ON/OFF Indications-04 Nos.
250Amps 433V 4P 50Hz 36KA Fixed Manual Type Molded Case Circuit Breaker (MCCB) with Microprocessor based overcurrent, short circuit & Earth Fault Protection.- 03 Nos.
MFM- 03 Nos.
ON/OFF Indications-03 Nos.
OUTDOOR ENCLOSURE
INTERCONNECTION AND EARTHING
Interconnection Between HT switchgear & Transformer using 1Cx3x95Sq.mm XLPE Single core cable & Interconnection between Transformer & LT switchgear using Al.Busbars of suitable capacity.Internal earthing connections by using 50x 6mm GI/Copper(As per standard) strips including Transformer neutral.. -1 Set
Components to be connected to the Earth system shall include:
(a) Enclosure of package sub station
(b) Enclosure of HV switchgear & control gear from terminal.
(c) Metal screen & high voltage cable Earth conductor.
(d) Transformer tank
(e) frame/enclosure of LV switchgear.
MAIN LT PANEL OUT DOOR TYPE
Supplying, installation, testing & commissioning cubical type outdoor (IP-55) double door with canopy feeder pillar type construction locking arrangement with go down locks in front & back with rain cap cover suitable for 3 phase, 4 wire 415 volt 50Hz dust and vermin proof made out of design from CRCA sheet steel of 2mm thick for frame work and covers with provision for connections of incoming cable and outgoing cables, i/c providing & fixing following switch gears i/c powder coated with siemens gray paint after prepaint treatment, painting. Panel suitable for 415 Volt, 3 Phase, 4 wire, 50Hz AC supply system fabricated in compartmentalized , 3mm thick for gland plates i/c cleaning & finishing complete with 9 tank process for powder coating in approved shade, having 3200 Amps capacity extensible type FP Aluminum
Alloy bus bars of high conductivity DMC/SMC bus bar supports, with short circuit with stand capacity of 31 MVA for 1Sec., bottom base channel of MS section not less than 100mm x 50mm x 5mm thick, fabrication shall be done in transportable section, entire panel shall have a common copper earth bar of suitable size at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with 2.5 sq mm PVC insulated copper conductor single core cable, cable alleys, cable gland plates in two half, i/c providing and fixing following switch gears. old existing panel dismounting complete as per site requirement included
(i) Incomer (CSS 1 & 2)
a) Independent electrical and manual spring closing mechanism - 1 No.
b) Microprocessor releases based release for adjustable setting for over current, short circuit and Earth Fault (LSIG) protection with4 line LCD (R,Y,B,N) display with bar graph display for % loading of phases. all RYBN current and Voltage, release should selfpowered requiring no external power supply. LED fault Indication on release. confirming to IEC:60947/ IS:13947, Part- II/1993.. - 1 set.
c) Under voltage release for each ACB's- 1 No
d) Digital type Multifunction Meter(IV, KW, KWH, KVA, PF, HZ), 96mm square flush pattern with one set of 4 nos. CT's of 200/5A Class I accuracy and 15 VA burden - 1 Set.
e) 3 Nos. Phase indication LED lamps and breaker ON,OFF,TRIP indicating light , test terminal block set, circuit wiring as per standard practice, auxiliary contacts for positive interlocking of the breaker as reqd.
f) Electrical Interlocking - 1 No.
h) Aux. Contactor + Add On Block 2no+2nc - 3No.
i) 4P high protection 70kA, surge protectors with MPCB for incomer- 1
j) 2A SP Control MCB's for protection of control circuit - 7 Nos.
l) 06A DP MCB 10kA -3 Nos.
m) 25A Breaker Control Switch -1 Nos.
n) 3 Nos. CT 3200/5A Class 1 accuracy for APFC Relay Sensing
APFC relay sensing.
(ii) BUS COUPLERS :
1 Set. - 1600 Amps four pole horizontal draw out type air circuit breaker of fault breaking capacity 50 kA (Ics = Icu = Icw=100% ) for 1 sec .electrically operated (EDO) without release, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, conforming to IEC 60947/IS-13947/Part- II/1993 latest version as amended up-todate complete with following accessories for each ACB.
a) Independent electrical and manual spring closing mechanism - 1 No.
b) Breaker ON,OFF Indicating LED indicating light, test terminal block, circuit wiring as per standard practice, auxiliary contact for positive electrical interlocking of breakers etc. as reqd - 1 set.
c) Under Voltage release-220 V AC - 1 No.
d) Electrical Interlocking - 1 No.
e) Aux. Contactor +Add On Block 2no+2nc-3 Nos.
f) 6A SP MCB -4 Nos.
g)25A Breaker Control Switch -1 Nos.
h) On Delay Timer (240VAC)-2 Nos.
(iii) BUS BARS
TPN aluminum bus bars of minimum of 2000A capacity with heat shrinkable colored sleeves and i/c DMC/SMC bus bars supports at required intervals complete, for cross section, size supports & their SPacing etc. for withstanding fault level of 31 MVA for 1 Sec. (For this the current capacity/density shall not be the limiting factor).
(iv) OUTGOING:-
Section -1
a) 2 Set. 630A FP MCCB 50kA with Thermal Magnetic release with adjustable setting overload setting Thermal magnetic release with adjustable setting overload setting up to 70% of rated current and Extended Handle + 1 C/O Aux. Contact (ICS=ICU=100%) with Digital Meter VAF ,Metering CT-400/5Amp Meter VAF ,Metering CT-400/5Amp - CL-1.0 ( 3 Nos) , ON,OFF Indicating LED
b) 1 Set. 400A FP MCCB 50kA with Thermal Magnetic release with adjustable setting overload setting Thermal magnetic release with adjustable setting overload setting up to 70% of rated current and Extended Handle + 1 C/O Aux. Contact (ICS=ICU=100%) with Digital Meter VAF ,Metering CT-400/5Amp Meter VAF ,Metering CT-400/5Amp - CL-1.0 ( 3 Nos) , ON,OFF Indicating LED
c ) 4 Set. 250A FP MCCB 50kA With Thermal Magnetic release with adjustable setting overload setting up to 70% of rated current and Extended Handle + 1 C/O Aux. Contact (ICS=ICU=100%) with Digital Meter VAF ,Metering CT-250/5Amp - CL-1.0 ( 3 Nos) , ON,OFF Indicating 30 LED.
APFC Section for CSS 1 -900KVAR
1600A TP Pole + N, horizontal draw out type air circuit breaker up to 433V AC, 50Hz AC operation of fault breaking capacity 50 kA (Ics = Icu = Icw =100%) for 1 sec. electrically operated (EDO), fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, Microprocessor releases based release for adjustable setting for over current & short circuit protection with 4 line LCD (R,Y,B,N) display with bar graph display for % loading of phases. all RYBN current and Voltage. release should self powered requiring no external power supply. LED faults Indication on release. confirming to IEC:60947/ IS:13947, Part-II/1993
a) 12 Stage APFCR Relay -1 Nos.
b) Louver With Fan -2 Nos.
c) Timer ON Delay -1 Nos.
d) Aux. Contactor +Add On Block 2no+2nc -5 Nos.
e) Digital VAF Meter -1 Nos.
f) C.T's 1600/5Amp , CL-1.0 -3 Nos.
g) C.T Shorting Link -4 Nos.
i) R,Y,B, ON and OFF Phase Indicating LED -5 Nos.
j) 32A Neutral Link -2 Nos.
k) 6A SP MCB -7 Nos.
OUTGOINGS;-
STEP DETAILS 100 KVAR - 7 Nos.
1) 7 Set 250A TP MCCB 25kA Thermal Magnetic release with adjustable setting for overload and short circuit Protection & Rom with following accessories each capacitor bank (Feeder) :-
a) 100KVAR 440V AC CAPACITOR duty contractor -1 Nos.
b) START/STOP Push Button -2 Nos.
c) ON/OFF Indicating Lamp -2 Nos.
d) 440V AC CAPACITOR MPP TYPE Heavy duty-100KVR -1 Nos.
e) 32A Neutral Link -1 Nos.
f) 6A SP MCB -1 Nos.
STEP DETAILS 50 KVAR - 3 Nos.
1) 3 Set 100A TP MCCB 18kA Thermal Magnetic release with adjustable setting for overload and short circuit Protection & Rom with following accessories each capacitor bank (Feeder) :-
a) 50KVAR 440V AC CAPACITOR duty Contactor -1 Nos.
b) START/STOP Push Button -2 Nos.
c) ON/OFF Indicating Lamp -2 Nos.
d) 440V AC CAPACITOR MPP TYPE Heavy duty -50KVR -1 Nos.
e) 32A Neutral Link -1 Nos.
f) 6A SP MCB -1 Nos.
STEP DETAILS 25 KVAR - 2 Nos.
1) 2 Set 63A TP MCCB 18kA Thermal Magnetic release with adjustable setting for overload and short circuit Protection & Rom with following accessories each capacitor bank (Feeder) :-
a) 25KVAR 440V AC CAPACITOR duty Contactor -1 Nos.
b) START/STOP Push Button -2 Nos,
c) ON/OFF Indicating Lamp -2 Nos.
d) 440V AC CAPACITOR MPP TYPE Heavy duty -25KVR -1 Nos.
e) 32A Neutral Link -1 Nos.
f) 6A SP MCB -1 Nos.
SECTION 2
a) 1 Set. 400A FP MCCB 50kA With Thermal Magnetic release with adjustable setting overload setting up to 70% of rated current and Extended Handle + 1 C/O Aux. Contact (ICS=ICU=100%) with Digital Meter VAF ,Metering CT-400/5Amp - CL-1.0 ( 3 Nos) , ON,OFF Indicating LED.
b) 4 Set. 250A FP MCCB 50kA With Thermal Magnetic release with adjustable setting overload setting up to 70% of rated current and Extended Handle + 1 C/O Aux. Contact (ICS=ICU=100%) with Digital Meter VAF ,Metering CT-250/5Amp - CL-1.0 ( 3 Nos) , ON,OFF Indicating LED.
APFC Section for CSS 2
1600A TP Pole + N, horizontal draw out type air circuit breaker up to 433V AC, 50Hz AC operation of fault breaking capacity 50 kA (Ics = Icu = Icw =100%) for 1 sec. electrically operated (EDO), fitted with interlocked door, automatic safety shutters, mechanical ON/OFF and service/test/isolated position indicators and frame earthing contact, Microprocessor releases based release for adjustable setting for over current & short circuit protection with 4 line LCD (R,Y,B,N) display with bar graph display for % loading of phases. all RYBN current and Voltage. release should self powered requiring no external power supply. LED faults Indication on release. confirming to IEC:60947/ IS:13947, Part-II/1993
a) 12 Stage APFCR Relay -1 Nos.
b) Louver With Fan -2 Nos.
c) Timer ON Delay -1 Nos.
d) Aux. Contactor +Add On Block 2no+2nc -5 Nos.
e) Digital VAF Meter -1 Nos.
f) C.T's 1600/5Amp , CL-1.0 -3 Nos.
g) C.T Shorting Link -4 Nos.
i) R,Y,B, ON and OFF Phase Indicating LED -5 Nos.
j) 32A Neutral Link -2 Nos.
k) 6A SP MCB -7 Nos.
OUTGOINGS;-
STEP DETAILS 100 KVAR - 7 Nos.
1) 7 Set 250A TP MCCB 25kA Thermal Magnetic release with adjustable setting for overload and short circuit Protection & Rom with following accessories each capacitor bank (Feeder) :- a) 100KVAR 440V AC CAPACITOR duty contractor -1 Nos. b) START/STOP Push Button -2 Nos. c) ON/OFF Indicating Lamp -2 Nos. d) 440V AC CAPACITOR MPP TYPE Heavy duty-100KVR -1 Nos. e) 32A Neutral Link -1 Nos. f) 6A SP MCB -1 Nos. STEP DETAILS 50 KVAR - 3 Nos.
1) 3 Set 100A TP MCCB 18kA Thermal Magnetic release with adjustable setting for overload and short circuit Protection & Rom with following accessories each capacitor bank (Feeder) :- a) 50KVAR 440V AC CAPACITOR duty Contactor -1 Nos. b) START/STOP Push Button -2 Nos. c) ON/OFF Indicating Lamp -2 Nos. d) 440V AC CAPACITOR MPP TYPE Heavy duty -50KVR -1 Nos. e) 32A Neutral Link -1 Nos. f) 6A SP MCB -1 Nos. STEP DETAILS 25 KVAR - 2 Nos. 1) 2 Set 63A TP MCCB 18kA Thermal Magnetic release with adjustable setting for overload and short circuit Protection & Rom with following accessories each capacitor bank (Feeder) :- a) 25KVAR 440V AC CAPACITOR duty Contactor -1 Nos. b) START/STOP Push Button -2 Nos, c) ON/OFF Indicating Lamp -2 Nos. d) 440V AC CAPACITOR MPP TYPE Heavy duty -25KVR -1 Nos. e) 32A Neutral Link -1 Nos.
f) 6A SP MCB -1 Nos.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mmm nominal size derived from natural sources) (4.6x4x0.50m)
Supplying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade, Overall PVC Sheathed HT Power Cables, Conforming to IS 7098 (Part II) 2011 with Latest Amendments of following size in the existing RCC/ HUME/ METAL pipe/on wall surface/ for loose wire etc.as required.
3C X 185 Sqmm. (E)
DWC/GI PIPE
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc.conforming to IS 14930, Part II complete with fitting and cutting,jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
120 mm dia (OD-120 mm & ID-103 mm nominal)
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required.
150 mm dia
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
Supplying of following sizes of XLPE insulated PVC sheathed armored Al. cond. Power Cable of 11 KV grade as required.
3.5 c x 240 sqmm
3.5 c x 150 sqmm
HVAC for Cricket Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
300 mm width X 62.5 mm depth X 2.0 mm thickness
600 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays bends with perforation not more than 17.5%,, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
300 mm width X 62.5 mm depth X 2.0 mm thickness
600 mm width X 62.5 mm depth X 2.0 mm thickness
Supplying and installing following size of perforated painted with powder coating M.S. cable trays Reducer with perforation not more than 17.5%, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.
300 mm width X 62.5 mm depth X 2.0 mm thickness
600 mm width X 62.5 mm depth X 2.0 mm thickness
Supply and fixing of thread rod
Supply and fixing of cassette A.C sensor
Supply and fixing of split A.C sensor
Supply and fixing of 18 H.P ODU sensor
Supply and fixing of 18 HP ODU fan motor
Supply and laying of 118 insulation
Supply and laying of 5/8 insulation
Supply and fixing of 410 Kg Gas
Supply and fixing of concealed A.C remote
Supply and fixing of cassette A.C remote
Supply and fixing of PCB card cassette A.C 1.0 TR IDU
Supply and fixing of PCB card cassette A.C 1.5 TR
Supply and fixing of PCB card cassette A.C 2.0 TR
HVAC MPH Chiller Plant Descalling Work- Chemical Circulation, Mechanical Brushing , Scale Remove, flush the condenser
AHU servicing
Nitrogen Pressure Testing, Replacement of Oil Filter, O rings, Vaccumising , Refill the refrigerant
Oil Filter
O Ring Set
Temperature Sensor Assembly
Chiller Commissioning Charges
Butterfly Valve/ CHW/CCW valves
Refeigrant Charging
Y strainer Cleaning
Cooling Tower Servicing , end cap, nipple, risen fiber, nozzle
Condenser Line Flushing Charges-Circulation of scale removable Chemical
Duct repair
CHW/CDW motor repairs
Operation & routine maintenance of electrical work at Indira Gandhi International Sports Stadium, Golapar, Haldwani by deputing minimum staff as following complete etc. as required on all days i/c Sunday & holidays
Skilled Staff - 1 No.
Unskilled Staff - 1 No
Budhiraja Electricals (BID ID -353159)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .