Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.6 LAccepted-AOC 186 GANDHI MARKET AMBALA CANTT 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹34.0 L+₹4.3 L (14.3%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹36.9 L+₹7.2 L (24.3%)Rejected-Finance 44 NEAR DURGA MANDIR TRIPURI TOABA TRIPURI TOWN PATIALA 147004 PB | PATIALA | PUNJAB | 147004 | L3 | Rejected-Finance Other than lowest bidder |
Tender Value
₹46 L
EMD Value
₹92,000
Closing Date
27 Jun 2024, 6:00 pmClosed
GE UTILITY AMBALA
GE UTILITY AMBALA CANTT 133001
REPAIR REPLACEMENT MAINT OF LT PANELS UG CABLE NETWORK STREET LIGHTS LT SWITCH GEARS INCL ALLIED WORK AT SECTOR B UNDER GE UTILITY AMBALA CANTT
2024_MES_656493_1
CA NO GE U AMB T 46 OF 2024-25
Open Tender
Civil Works
Item Rate
240 days
GE UTILITY AMBALA CANTT
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹92,000
20 Jul 2024
29 May 2024
29 Jun 2024
29 May 2024
27 Jun 2024
13 Jun 2024
29 May 2024 - 5 Jun 2024
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation, shafts, man holes,for under ground cable / erection of poles, stays, locating fault of LT cable and stay assembly etc not exceeding 10 square metre on plan and getting out in any type of soil including dressing/trimming of sides and leveling, grading and ramming of bottom of excavation complete all as specified and directed.
All as per Ser item No 1.00 here in before but depth exceeding 1.5 metre and not exceeding 3.0 metre.
Returning, filling in, in soil, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick each layer complete all as specified and directed.
Removing excavated material/soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Material and labour for sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable) complete all as specified and directed.
Supply and lay bricks, common burnt clay, sub class "B', old size, laid in perpendicular direction to cable as cable protection complete all as specified and directed.
All as per Ser Item No 6.00 here in before but except bricks, all as specified and directed. Note:- Old bricks retrieved from Ser Item No 11.00 here in after shall be re-used.
Material and labour for PCC 1:4:8 type D-2 using 40mm graded stone aggregate, mechanically crushed stone for mass filling in pole pit and foundation etc. complete all as specified and directed.
Material and labour for cement concrete (1:3:6) type C-1 using 20mm graded crushed stone aggregate as in coping of pole and strut, stay around the pole etc complete all as specified and directed.
Material and labour for PCC 1:2:4 Type B-1 using 20 mm graded stone aggregate for coping of poles including necessary form work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site.
Disconnecting & taking out defective underground cable from trenches, pole, pipe, floor, wall etc and locate the fault, rectify the defect and relaying the XLPE cable underground PVC insulated and overall sheathed aluminum conductor heavy duty 1100 volts including connecting and testing for any size complete all as specified and directed. Note:- Excavation/earth work & sand cushioning, bricks and joint shall be measured & paid for separately.
Supply and laying, connecting, testing in replacement of XLPE underground cable insulated, and overall sheathed with aluminium conductor heavy duty 1100 volts grade 10 sqmm 4.0 core laid in trenches/ on pole/road crossing or passing through existing/new pipe under road crossing clamping on wall incl aluminium thimbles/lugs etc complate all as specified & directed . Note: (i) Earth work, sand, bricks removing, returning filling will be paid seperately. (ii) Cost of laying electrical cable through new/existing pipe under road, buildings, railway tracks, highways are incl in the quoted rates. (iii) All equipments, machinery or tool if required for laying electrical cable through new/existing pipes are provided by the contractor without any extra cost.
All as per item ser No 12 here in before but for 16 Sqmm 4 core complete all as specified and directed
All as per item ser No 12 here in before but for 25 Sqmm 3.5 core complete all as specified and directed
All as per item ser No 12 here in before but for 35 Sqmm 3.5 core complete all as specified and directed
All as per item ser No 12 here in before but for 50 Sqmm 3.5 core complete all as specified and directed
All as per item ser No 12 here in before but for 70 Sqmm 3.5 core complete all as specified and directed
All as per item ser No 12 here in before but for 95 Sqmm 3.5 core complete all as specified and directed
All as per item ser No 12 here in before but for 150 Sqmm 3.5 core complete all as specified and directed
All as per item ser No 12 here in before but for 185 Sqmm 3.5 core complete all as specified and directed
All as per item ser No 12 here in before but for 240 Sqmm 3.5 core complete all as specified and directed
All as per item ser No 12 here in before but for 300 Sqmm 3.5 core complete all as specified and directed
Supplying and fixing in replacement of size PVC insulated aluminium conductor 10 sqmm 2 core, 1100 volts grade heavy duty cable served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular complete all as specified and directed.
Supply and fixing in replacement of 2.5 sqmm 3 core copper cable PVC unsheathed multi stranded (FRLS) 1100 volts grade PVC insulated round passing through PVC conduit pipe heavy duty, including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed.
Supply and fixing in replacement of 1.5 Sqmm single core copper cable PVC unsheathed multi stranded (FRLS) nominal cross sectional area 1100 volts conforming to IS 694 passing through PVC conduit pipe including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed.
Supply and fixing in replacement of 2.5 Sqmm single core copper cable PVC unsheathed multi stranded (FRLS) nominal cross sectional area 1100 volts conforming to IS 694 passing through PVC conduit pipe including electrical connection suitable size of lugs, nuts and bolts complete all as specified and directed.
Supply and fixing in replacement of rigid non-metallic PVC conduit of dia 20 mm exclusive of boxes (Junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed. Note: PVC pipe will be clamped at three position on pole and cost of clamp, nut, bolts etc are incl in quoted rates
Supplying and fixing in replacement of light grade galvanised mild steel pipe 80 mm bore with all fittings, laid under roads, drain, paths, fixed to poles/walls with suitable mild steel clamps, bolts, nuts and washers complete all as specified and directed. Note:- Excavation & earth work shall be measured and paid for separately under appropriate item of this schedule.
All as per Item No 28.00 here-in-before but of size 50 mm bore.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique or manual boring and necessary machine including HDPE pipe of 50mm to 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
Dismantling and taking down security light, street light, hanger light, flood light and high mast lights of any type at any height fittings such as HPSV/HPMV/MH/LED light of 50 Watt/ 60 watt / 70/72 watt/ 90 watt/ 120 watt/ 150 watt/ 200 watt and 300 watt of any make etc. AC 230 volts any wattage from pole/wall roof top/hanger roof including washing/cleaning of perplex cover inspection for location of fault and replacing of defective spare/parts required for smooth functioning, tightening of electric connection and assembling and reconnecting all as per site requirment complete all as specified and directed. Note: Defective spare/ part of relevant light fitting shall be measured and paid separately under relevant item as supply only.
Supply only LED electronic driver/adaptor/SPD for 50-72 watt LED security light fitting existing make complete all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 90-120 watt LED security light fitting existing make complete all as specified and directed.
Supply only LED electronic driver/adaptor/SPD for 100-300 watt LED flood light fitting existing make complete all as specified and directed.
Rectification of complaints under Bravo and Race course PH area of security light, street light, hanger light, flood light and high mast lights and allied works by attendng daily complaints including Sunday and other holidays for round the clock and making the same serviceable in all respects alongwith replacement of any major part but including small length of cable (not more than 20 mtr), adhesive tape and other connected minor accessories shall also include to visual inspection of OH lines, Earth Resistance of street poles etc. Quoted rate also include excavation of faulty cable/all type lights are making seviceable with accessories of all nature like No light, faulty insulator, broken conductor & cable fault , burnt out MCCB`s, MCBs, isolators, switch fuses, service cables etc complete all as directed to the entire satisfacation of Engineer-in-charge. Note ‘A’ :- (i) Any complaint left unattended by the electrician will be communicated to the JE in-charge /AGE E/M with reason. No charge will be paid for the per complaint till the complaint is resolved. (ii) New material /stores provided for completing the job shall be measured and paid for separately under relevant items of BOQ. (iii) Contractor shall provide all type of T&P of LT street lights network, bamboo ladder with safety gloves to each electrician for attending the external electric complaints. (iv) Contractor shall provide the complaint register 200 pages – 3 No, complaint book with 100 slips- 5 No. Booklets serially numbered in triplicate. (v) Contractor will provide 01 No. Experienced Electrician having minimum 5 years experience ( 01x one shifts per day) and 01 No. Helper having minimum 2 years experience ( 01 x one shifts per day) including Sundays and Holidays to attend HT Complaints. (vi) Contractor will provide well experienced and well conversant of one person for lodging the complaint in complaint cell of each power house during working hours from 0900hrs to 1700hrs on all working days including Sunday & all Holidays. (vii) The Contractor will provide insurance cover of minimum Rs 5 lakh per head under IE Rules 2003 and Minimum wages Act. (viii) The Electrician and helper will be interviewed by JE E/M /Engr-in-charge for verification of experience, character and sound mind and body.
Taking down old unsv Prestressed Concrete LT pole and supply and erection of Prestressed Concrete LT pole 9.0 mtr long in true vertical position 102x172 mmm at top and 102 x 279 mm at bottom class-10 incl providing black and white strips with synthetic enamel paint 30 cm each alternate upto 1.5 mtr above the coping of pole starting with black strip complete all as specified & directed. Note:- (i) Earth work and PCC shall be measured and paid seperately. (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Taking down old unsv Steel tubular LT pole and supply and erection of steel tubular swaged poles 9.0 mtr long complete with cast iron base plate, finial taper plug, bolts,nuts and screws as specified type 410 SP-31, providing synthetic enamel aluminium paint over one coat of red oxide primer and black and white strips with synthetic enamel paint 30 cm each alternatively upto 1.5 mtr above the coping of pole starting with black strip complete all as specified & directed. Note:- (i) Earth work and PCC shall be measured and paid seperately. (ii) Description as per direction of Engineer-in-Charge will be printed on each pole without any extra cost.
Supply and fixing in replacement of stay assembly complete with all accessories, such as stay plate 230x230x6 mm, stay rod 215 cm long and 16 mm dia with nuts incl GI bow turn buckle, GI stay wire, Loop type insulator etc all as per electrical plate No 1 or SSR part 1 and as directed incl taking down old unsv stay assy complete all as specified & directed. Note- The quoted rate shall include the cost of loop type insulator, stay clamps, excavation, PCC, stay wire, stay bow, turn buckle, nuts etc. complete.
Material and labour in replacement of Loop insulator Porcelain, vitreous white/brown/green insulator including one galvanized mild steel spindle, two galvanized iron washers and one galvanized iron nut, large size with overall dimensions 90mm x 140mm, clearance of hole 25.5 mm, complete all as specified & directed
Material and lobour in replacement for shackle type porcelain vitreous white or brown insulator including GI straps washers, insulator bolts and nuts for working pressure 1100 volts, 75 mm hight, 90 mm dia, section of strip 30mmx3mm & dia of bolt 12 mm complete all as specified & directed.
Taking down old unserviceable ACSR conductor and material and labour for aluminium conductor steel reinforced (ACSR) conductor of size 6/1 x 2.59 (Weasel) and 6/1 x 2.11 (Squirrel) or other existing type conductor ISI marked for LT over head lines on poles including stretching, tightining of poles insulator with winding wire of suitable size with insulator/streching of ACSR conductor complete all as specified and directed.
Taking down old unserviceable cross-arms and material and labour for cross arms,bracings, supports, clamps and back plates fabricated from structural steel section incl nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape of size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
Supply and fix in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 50-150 Sqmm complete all as specified & directed
Supply and fix in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-240 Sqmm complete all as specified & directed
Supply and fix in replacement indoor/outdoor end termination joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 300-400 Sqmm complete all as specified & directed
Supply and fix in replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 35-150 Sqmm complete all as specified & directed. Note: The quoted rate shall include the earth work, RF and removal of soil etc.
Supply and fix in replacement straight through joint heat shrinkable 1100 Volts for XLPE cable of size 3.5 x 185-400 Sqmm complete all as specified & directed. Note: The quoted rate shall include the earth work, RF and removal of soil etc.
Dismantling and taking down old u/s earthing and provision of earthing complete with galvanised earth plate electrode 600mm x 600mmx 6.00mm thick surrounded by charcoal and salt, burried directly in ground vertically in a pit of depth not less than 2.25m below ground level with top edge of the earth plate not less than 1.5m below normal ground level, connected to 25x4 mm GI strip earth lead by means of bolts, nuts, checks nuts and washers made out of galvanized iron or steel, earth wire protected by galvanized steel pipe 40mm bore medium grade and connected to main switch or main control board all as shown in electrical plate No.3 of SSR Part-I & including necessary excavation and earth work. The rate also include charcoal & salt in alternate layers, 20mm bore GI pipe medium grade for watering and 40mm bore GI protection pipe (light grade), funnel, wire mesh, cast iron cover and frame etc including testing on completion complete all as specified and directed. Note : (i) The quoted rate shall include the cost of earth work, GI pipe for watering, GI protection pipe, funnel, wire mesh, RCC cover, etc. complete. RCC cover shall be 50mm thick in 1:2:4 type B-1 using 8mm bars @10cm c/c both way. (ii) The quoted rate shall include the cost of the earth pit covers to be conspicuously marked of plate with stand grouted in PCC. (iii) On testing after completion if the desired earth resistance is more than 2Ώ the earthing will be redone at no extra cost.
All as per item ser No 48 here in before but for connected to galvanised earth lead wire of 4.0 mm dia by means of GI nuts bolts, check nuts and washers and connected to earthing test point drawn through 15 mm bore GI pipe medium grade for protection of GI earth lead wire including 20mm bore GI pipe medium grade for watering GI funnel.
Supply and fixing in replacement MCCB TPN 630 Amps, 415 Volts, 50 KA, 4 pole , Ics=100% Icu, overload adjustable short circuit adjustable type complete all as specified & directed.
All as per item ser No 50 here in before but MCCB TPN 400 Amps, 415 Volts, 36 KA, 4 pole complete all as specified & directed.
All as per item ser No 50 here in before but MCCB TPN 250 Amps, 415 Volts, 25 KA, 4 pole complete all as specified & directed.
All as per item ser No 50 here in before but MCCB TPN 200 Amps, 415 Volts, 25 KA, 4 pole complete all as specified & directed.
All as per item ser No 50 here in before but MCCB TPN 125 Amps, 415 Volts, 16 KA, 4 pole complete all as specified & directed.
All as per item ser No 50 here in before but MCCB TPN 100 Amps, 415 Volts, 16 KA, 4 pole complete all as specified & directed.
Material and labour for Detecting of fault in cable HT/LT with fault locator equipment which is capable to supply as per cable of HT/LT (11 KV/430 Volts) serviceable to cable with Straight through joint of size 70-300 Sqmm complete all as specified & directed. Note:- (a) The HT fault which is detected through cable fault locator will only be paid under this item including transportation charges deemed to be included in the quoted rate. (b) Charge of cable fault locator and DG set, transportation charge deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single HT fault and no delay on this account will be acceptable otherwise penalty will levied Rs. 500/- per hour.
Supply and fixing in replacement of LT line separators 1100 V grade PVC spacer to separate LT conductor from each other 5 line as per IS complete all as specified & directed
All as per item ser No 57 here in before but 4 line complete all as specified & directed
Re-streching of loose over head ACSR conductor of any type/GI wire and repair of the broken conductors and adding new length (if required) in place of old and burnt conductor of any size on existing poles with proper sagging including winding with winding wire complete all as specified & directed. (Old conductor shall be reused where required for repairing broken length of conductor as directed by Engr-in-charge).
Trimming of Tree branches falls into OH lines of HT/LT & minimum clearance of 3 Mtr from branches ,proper shutdown will be taken and maintained in the register complete all as specified & directed
Material and labour in replacement of aluminium terminals (thimbles) after cutting the worn out/faulty cable end from LT pillar/panel box including necessary earth work for taking out the cable from loop line, returning, filling in and making cable lead by providing aluminium lugs including crimping with crimping tools in the existing LT cable 16 Sqmm 4 core upto 50 Sqmm & necessary connection complete all as specified & directed
All as per item ser No 61 here in before but size of LT cable 70 Sqmm 3.5 core upto 120 Sqmm 3.5 core.
All as per item ser No 61 here in before but size of LT cable 150 Sqmm 3.5 core upto 400 Sqmm 3.5 core.
Material and labour for shifting heavy items / excavation / cleaning areas / cleaning site by providing crane/hydra/excavators/tractors/trolley ect as required at site complete, all as specified and as directed.
Material & Labour for spray painting on complete LT panels/Feeder Pillar Boxes of any size and any type two coats of synthetic enamel aluminium paint on outer shell and inner shell over a coat of red oxide including stand complete all as specified & directed.
Repair of LT panel of any type and any size including replace of old unsv items such as busbar, insulaor, CT/PT coils, insulating sleaves, front and rear doors, door hinges, gland, lugs volt meter, ammeter, indicator, locking arrangement and internal copper wiring after cleaning of surface including removing rusted particles removing dust tightening nut, bolts welding complete all as specified and directed. Note: (i) Cost of marking description on the front door as per direction of Engr-in-Charge is incl in quoted rate (ii) Cost of misc items like copper cable, lugs thimbles etc if required are included in quoted rates. (iii) Cost of welding works such as hinges, locking arrangement, door and angles are included in qouted rates.
Material & Labour for surface cleaning of LT steel tubular poles 9 mtrs long including removing rusted particles painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including stand cross arms, bracing, supports,clamps eye hooks, security light bracket clamps etc providing black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl repairing and painting on coping with cement base white paint complete all as specified & directed. Note: (i) The quoted rate shall includes marking of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the repairing of coping with cement / PCC
Material & Labour for cement base paint for Prestressed Concrete pole 9 mtr including black & white strips alternatively 30cm each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paint and painting with two coats of synthetic enamel aluminium paint over a coat of red oxide including cross arms bracing supports, clamps, eye hooks, security light bracket, clamp etc incl repairing and painting on coping with cement base white paint complete all as specified & directed. Note: (i) The quoted rate shall includes making of numbers on each LT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the repairing of coping with cement / PCC
Material and labour for spraying chemical (Round up) on area to remove unwanted vegitation/grass at various locations complete all as specified & directed.
Supply and fixing in replacement of on load change over switch with sheet steel Enclosure 415 V, 4 pole, 100 Amps capacity fixed on walls for electric supply distribution between main and DG set incl necessary connection of cable from LT panels to change over switches complete all as specified and directed.
Material and labour for Chemical spray (DC 2.26 contact cleaner) in container of 415 ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricants, displaces and seals out moisture release rusted mechanisum cleanese etc complete all as specified and directed.
Supply and fixing in replacement of fabrication of Kiosk box made out of fibre material complete with TPN ,aluminium bus and suitable for one number MCB (SP) including one No MCB (SP) 6 Amps 240 volts with glands for incoming & out going cable including fixing of flat iron clamps of size 20x4mm on PCC/Steel tubular pole complete all as specified and directed. Make: Havells/Sintex.
Supply and fix in replacement of MCB SP 6-32 Amps, 240 volt,10 KA 'C' curve including all accessories complete all as specified and directed.
Supply & fixing in replacement of Automatic Street Light Control Switch with Infrared Sensor based NATURE SWITCH & Voltage Monitoring System (VMS). Three phase, 25 Amps per phase, MCB rating 32 Amp, max load 8-12 kw incl circuit copper wire 10 sq.mm. Nature Switch operation should be based on Natural Light Lux level. Required Illuminance Level for Switching ON is ≤ 60 Lux and for switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 to max. 12 hrs. VMS should have Adjustable Over & Under Voltage Trip level and Protection against Phase Loss, Neutral Loss & Phase Reverse. The Sensor & VMS along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Enclosure made of Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Junction box conforming to IP54. The circuit should also have provision for Manual Operation (i.e. By-Pass Option for both Sensor (NS-02) and VMS) complete all as specified and directed. Note :- (i) S S Nut bolts, clamp for fixing on poles/wall are included in quoted rates. (ii) The sensor must have the warranty of min of 2 years. (iii) The test certificate and warranty certificate must be provided by supplier. (iv) Cost of marking description on the box is incl in quoted rate.
All as per item ser No 74 here in before but for single phase, 25 Amps per phase, MCB rating 40 Amp, max load 5-8 kw complete all as specified and directed.
Supply and fix in replacement of Lithium based Energy Efficient Integrated Solar Street Light of 24Watt” in Single FRP body with duly Polyurethane coating (Camouflage color) , encases with Monocrystalline Solar PV Panel of 53/55Wp , Lithium Battery 11.1/12.8V, 28.6AH with inbuilt BMS, IP 66, IK 08, High brightness W-LED(160-180lm/watt) lamp with Aluminum reflector for better light distribution , CRI >70, Color Temperature 5700K - 6500K, Microcontroller based charge controller cum driver, automatic dimming function ( first four hours at full brightness & rest of the time at lower light level with Microwave Sensor), Dusk to Dawn Operation, suitable to working temperature: (-) 10C to (+)55C, weight not more than 12-14kg with adjustable MS clamp suitable for pole/wall mounting etc complete as required. Protections: Short Circuit, overload, Reverse polarity and battery protections. Firm should provide Vital Parameters Test report from NABL accredited lab and should be of made in India with CE & ROHS compliant including tubular pole 6 mtr height with bottom base plate 200x200x12 mm , outdoor dia not less than 65 mm with heavy duty GI pipe or steel thickness 3mm and suitable arrangement to mount solar light as directed on pole including foundation PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate and erection as per manufacturer drawing, providing synthetic enamel aluminium paint over one coat of red oxide complete all as specified and directed.
Supply & fixing in replacement of Integral LED Flood light Luminaries 100 Watts consisting of suitable number of LEDs and mounted on MCPCB high pressure die cast aluminium housing with sealed toughened glass cover with secondary optics lens, IP 66 protection suitable for mast light mounting, 5700K, LED efficiency >130 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 160 V-270 V, Power factor> 0.95, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV , Confirm the tests from auth labs : LM79 & LM 80, incl proper fixing and testing of flood lights on 9/11 mtr long steel tubular pole and provide facility of power supply as suitable for maint work of light fittings incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed.
All as per item ser No 77 here in before but for 150 Watts
All as per item ser No 77 here in before but for 200 Watts
All as per item ser No 77 here in before but for 300 Watts
Supply & fixing in replacement of LED street light fitting 60 watts made up of pressure die cast aluminium housing with high efficiency LEDs as lighting source and lens embedded , toughened glass having TOP Opening seperate driver compartment with IP 66 protection and impact resistance of IK07 consisting of suitable number of LEDs with sealed toughened glass cover, 5700K, LED efficiency >110 lm/Watt and system efficiency 110 lm/W , 240 Volts AC, 50 Hz, CRI>70% operating voltage range 140 V-270 V, Power factor> 0.95,mains current 0.270A, working temperature range -10ºC to 50ºC,built in surge protection of more than 10 kV, better optics for uniform distrubution with multiple LEDs not less than 2 watt each and having optical grade polycarbonate lens with all accessories , suitable for side entry, pole mounting with bracket arm OD 40 mm, recommended mounting height with suitable inground reinforcement is 8 mtrs, Confirm the safety test as per IS 15885 part-2 from auth labs : LM79 & LM 80, incl proper fixing and testing of street lights on 9/11 mtr long steel tubular pole incl make proper connection of new and existing light fittings complete with cutting , welding , drilling holes, nut bolts, washer complete all as specified and directed. Note :-PVC heavy duty conduit pipe along with 3/1 run of 1.5/2.5 sqmm PVC insulated unsheathed/sheathed copper multistranded conductor from MCB box to street shall be measured and paid for separately.
All as per item ser No 81 here in before but for 70/72 Watts complete all as specified and directed.
All as per item ser No 81 here in before but for 90 Watts complete all as specified and directed.
Supply, installing, testing & commissioning in replacement of outdoor type cubical panel board of size 1.2mX1.10mX.6m, outer shell made out of 3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front and back openable double door system and cable alley (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able with arrangement of pad locking on both doors incl 2 no. of pad locks of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, incl Al bus bar of 600 A , tested at factory CPRI for 4000 Amps rupturing capacity at 415 volts, having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011 Part-1 and part -2 type test certificate with not less than IP-56 and breaking capacity 65 KA comprising of the following :- (a) TPN Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size F class insulators not less than 1.4 metre long. (b) Incoming MCCB 400 Amps, 4 pole, 415 volts, AC with thermal magnetic adjustable type 36 KA, --1 No. (c) Outgoing MCCB 100 Amps, 4 pole, 25 KA, 415 volts --03 Nos. (d) Outgoing MCCB 63 Amps, 4 pole, 25 KA, 415 volts --01 No. (e) Indicator lamp RYB 22.5 mm dia, LED type, 240 volts, AC with incoming including back up protection by 2 Amp MCB RYB with holder --1 set of three. (f) Multi function meter with KWH, voltage, Amp, frequency meter -- 01 No (g) CT coils of suitable ratio--1 set. (h) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc are included in quoted rates.
All as per item ser No 84 here in before but size 1.10Mx1.15Mx 50Cm comprising of the following :- (a) TPN Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size F class insulators not less than 1 metre long. (b) Incoming MCCB 315 Amps, 4 pole, 415 volts, AC with thermal magnetic adjustable type 36 KA, .--1 No. (c) Outgoing MCCB 100 Amps, 4 pole, 16 KA, 415 volts --04 No. (d) Multi function meter with KWH, voltage, Amp, frequency meter -- 01 No (e) Indicator lamp RYB 22.5 mm dia, LED type, 240 volts, AC with incoming including back up protection by 2 Amp MCB RYB with holder --1 set of three. (f) CT coils of suitable ratio--1 set. (g) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc are included in quoted rates.
All as per item ser No 84 here in before but size 1.10Mx1.15Mx 50Cm comprising of the following :- (a) TPN Aluminium bus bar 600 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size F class insulators not less than 1 metre long. (b) Incoming MCCB 400 Amps, 4 pole, 415 volts, AC with thermal magnetic adjustable type 36 KA, .--1 No. (c) Outgoing MCCB 250 Amps, 4 pole, 25 KA, 415 volts --02 Nos. (d) Outgoing MCCB 100 Amps, 4 pole, 16 KA, 415 volts --02 No. (e) Multi function meter with KWH, voltage, Amp, frequency meter -- 01 No (f) Indicator lamp RYB 22.5 mm dia, LED type, 240 volts, AC with incoming including back up protection by 2 Amp MCB RYB with holder --1 set of three. (g) CT coils of suitable ratio--1 set. (h) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc are included in quoted rates.
All as per item ser No 84 here in before but size 1.15Mx1.1Mx 50Cm comprising of the following :- (a) TPN Aluminium bus bar 350 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size F class insulators not less than 1 metre long. (b) Incoming MCCB 250 Amps, 4 pole, 415 volts, AC adjustable type 25 KA,--1 No (c) Outgoing MCCB 100 Amps, 4 pole, 16 KA, 415 volts --04 Nos. (d) Multi function meter with KWH, voltage, Amp, frequency meter -- 01 No (e) Indicator lamp RYB 22.5 mm dia, LED type, 240 volts, AC with incoming including back up protection by 2 Amp MCB RYB with holder --1 set of three. (f) CT coils of suitable ratio--1 set. (g) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc are included in quoted rates.
All as per item ser No 84 here in before but size 1.1Mx1.0Mx 50Cm comprising of the following :- (a) TPN Aluminium bus bar 350 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size F class insulators not less than 1 metre long. (b) Incoming MCCB 250 Amps, 4 pole, 415 volts, AC adjustable type 25 KA,--1 No (c) Outgoing MCCB 100 Amps, 4 pole, 16 KA, 415 volts --02 Nos. (d) Outgoing MCCB 63 Amps, 4 pole, 16 KA, 415 volts --04 Nos. (e) Multi function meter with KWH, voltage, Amp, frequency meter -- 01 No (f) Indicator lamp RYB 22.5 mm dia, LED type, 240 volts, AC with incoming including back up protection by 2 Amp MCB RYB with holder --1 set of three. (g) CT coils of suitable ratio--1 set. (h) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc are included in quoted rates.
Supply and installing, testing & commissioning in replacement of factory fabricated outdoor type feeder pillar board of size 700X600X500 mm , outer shell made out of 3.15 mm thick CRCA sheet and inner shell made out of 2 mm thick CRCA sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 60 cm above and 45 cm below the ground level, frame factory fabricated with front openable double door system and cable alley (Each door hinged with body at 3 places with body and hinges should be welded with body and door) lockable/open able with arrangement of pad locking on door 01 no of pad lock of three keys shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI factory fabricated having modern fabrication and testing process followed by powder coated painting after 7-tank pre treatement control & power wiring with suitable size of copper conductor along with suitable gasket to make it dust/vermin proof and general construction confirming to IS:61439/2011 Part-1 and part -2 type test certificate with not less than IP-56 and breaking capacity 65 KA comprising of the following :- (a) MCCB 125 Amps TPN, 25 KA -01 No (b) Al busbar of capacity 200 Amps with colour coated heat shrinkable sleeve and suitable hole for out going connection - Set of four. (c) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cabe lugs, sleeves, glands etc are included in quoted rates
All as per item ser No 89 here in before but size 750X750X500 mm comprising of the following :- (a) MCCB 160 Amps TPN, 25 KA -01 No (b) Aluminium busbar of capacity 250 Amps with colour coated heat shrinkable sleeve and suitable hole for out going connection - Set of four. (c) RYB indication LED type, 22.5 mm dia, protected with MCB SP 2 Amp showing 3 phase supply with suitable CTs -03 Nos (d) Multi function meter with KWH, voltage, Amp, frequency meter -- 01 No (e) Misc items like screws, cable tie, copper cable 1.5/2.5 Sqmm, cable lugs, sleeves, glands, suitable CTs etc are included in quoted rates.
Notes for item Sr No. 84 to 90:- (i) The quoted rate shall include minor items such as lugs, nuts & bolts, washers, top insulators, sleeves, provision of extra holes in bus bar etc. (ii) All internal wiring shall be done with suitable size of PVC insulated solid copper conductor FRLS cable conforming to IS-694. (iii) Panel drawing shall be got approved before placing of order from Engr-in-Charge/ GE. (iv) The bus connection for cable from main bus bar to outgoing MCCB will be connected through suitable rating bus bar strip type duly insulated. (v) Cable will be entered in panles through gland. (vi) Cost of marking description and matter on the front door as specified and directed by Engr-in-Charge is incl in quoted rate.
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm incl taking down old unsv HT joint complete all as specified and directed.
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm incl taking down old unsv HT joint complete all as specified and directed.
Material and Labour for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPE cable 50-95 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as specified and directed.
Material and Labour for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPE cable 120-185 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as specified and directed.
Material and labour in replacement of broken earth pit with PVC cover of size 300x300x300 mm made of PCC 1:2:4 type B1 using 20 mm graded crushed stone aggregate, and earth pit cover made out of RCC 1:2:4 type B1, cover reinforced with 8 mm dia TMT bars @ 100 mm centre to centre both ways with handle made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and including reconnecting of earth lead of any type with new nuts, bolts and washers as required at site with testing result complete all as specified and directed.
Material and labour in repairs of stay by tightening of stay wire after untying the conductor spans from the poles to make correct tensions and maintain verticality of poles, including re-jointing the conductors in position with new binding wire complete all as specified and directed.
Repairing of existing unserviceable PCC coping of LT/HT pole by breaking completely and material and labour for PCC 1:2:4 type B1, (using 20mm graded crushed stone aggregate) of size 600X600X300mm including form work and applying two coats of cement base paint complete all as specified and directed.
Taking down old unserviceable Indicator any type any colour and supply and fixing new Indicator red/yellow/green including making electrical connection with suitable size of copper lugs duly crimped complete all as specified and directed.
Dismantling of brick work or stone masonary, precast cement concrete walling built in cement mortar including all quoins, arches, pillars etc. complete all as specified and directed.
Material and labour for brick work with sub class ‘B’ bricks burnt, straight or curved on plan exceeding 6 metre mean radius built in cement mortar (1:6), complete all as specified and directed.
Material and Labour for Brick work with sub class ‘B’ bricks (Except Bricks), straight or curved on plan exceeding 6 metre mean radius, built in cement mortar (1:6), complete all as specified and directed. Note- The serviceable bricks obtained from Serial item No- 102 Shall be used after removing motar, cleaning the bricks with water, etc.
Taking down cement plaster on brick or stone walls, etc. including raking out joints, hacking for key, scrubbing down with water, etc complete all as specified and directed.
Material and labour for 15 mm thick rendering in cement mortar (1:6) on surface of any description of brick or concrete and finished the surface even and smooth without using extra cement including preparation of new plastered surfaces of walls and applying two coats of oil bound distemper on wall, complete all as specified and directed.
Material & labour for rough cast plastering over and incl 10 mm thick rendering in cement mortar 1:3 and while it is still in plastic state the roughcast mixture consisting of crushed stone or fine gravel aggregate (which is generally of size between 6 to 12 mm depending on the texture required) mixed with coarse sand and cement in the ratio of 1: 1: 1 shall be applied and finished even. The mix of cement and sand shall be made slightly wetter than normal for rendering to ensure that larger aggregates are thoroughly covered. Rough cast plaster shall be applied as specified clause 14.22 of SSR Part-I .
Material and labour for preperation of old plastered or unplastered surfaces of walls, pillars cornices etc by brooming down with steel wire brushing, scraping down smoke soot, moulds, moss and effloroscent salts, trading oil and greasy spots etc. and applying two coats of white wash etc complete all as specified and directed.
Material and labour for vibratery compactive, precast cement concrete rubber moulded, coloured ( except grey colour), interlocking designer paver blocks in Milano shape, comfirming to IS-15658-2006 of 60 mm thickness, M-35 grade, as in path, hard standing, etc laid over and including 25 mm compacted sand cushioning, including surface excavation over area n. exc. 30 cm deep and averaging 15 cm deep and getting out in soft/loose soil and removing excavated soil exc. 50 mtr but n. exc. 250 mtr, complete all as specified and directed.
Material and Labour for for 75mm thick PCC 1:4:8, type D2 (using 40mm graded stone aggregate) as in sub base complete all as specified and directed.
Supply and fixing in replacement of steel rolling shutters with out ball bearing, as specified including top cover, anchoring rod, hasp and staple and one shop coat of primer; erected in position as indicated incl gear operated type with bevel gear box, crank handle and incl all other accessories required at site for rolling shutter including dismantling of old existing rolling shutters ,complete all as specified and directed.
Material and labour for complete removal of existing treatment on surface of walls by using appropriate technique as approved by Engr-in- Charge for complete removal of all layers of treatment and reaching upto old plastered surface and applying a coat of 2 mm thick wall care putty as per manufacture instructions and applying two coats of oil emulsion distemper over a coat of primer of same manufacturer complete all as specified and directed.
Supply and fix false ceiling at all heights of perforated 600x600x0.5mm TEGULAR EDGE TILES in global white Powder Coated with 60-70 Micron front coating laid on exposed gird system. The frame work shall be comprise of main runner spaced at 1200 mm max (centre to centre). Hangers (GI wire of 4 mm dia) to be fixed by approved roof plug, level adjusters and scerws etc at 600x600 intervals. The last hanger at the end of each main runner shoud not be greater than 450 mm from the adjacent wall. Flush fitting 600 mm long cross tees (with double stiching) to be interlocked between main runner at 600 mm shall be 'T'shape section with single rotary stitching made of GS sheet and of size 15 mmx32mm and 3000mm long, crosssed runner shall be 'T' shaped with double rotary stiching made of GS sheet and size 15 mmx 32mmx 600 mm long and perimeter wall angle shall be made from GS sheet and of size 19mmx19mm and 3000mm long, colour white, centre to form 600 mm x 600 mm modules, cut cross tees longer than 600 mm to be supported independently, 600mm x 600mm modules to be formed. Perimeter trim to be wall angle secured to walls at 450mm max (centre to centre), including PVC clips to hold the ceiling tile, all as per manufacturer instructions incl dismantling and taking down of old unsv ceiling complete all as specified and directed.
Solid PVC Wall Lining consisting of 5mm thick Plain colour PVC sheet inclusive of solvent cement and fixing at site on PVC frame as per specifications and drawing and including PVC fillets and the taking down and refixing of swicth socket boards on the lining/panneling with appropriate material if required incl dismantling and taking down of old unsv wall lining complete all as specified and directed.
Roughening surfaces of old concrete floor by picking, keeping clean and washing down with water to remove dust, etc and Brushing neat cement slurry with 3.0kg of cement per sq. metre complete all as specified and directed.
Dismantling of floor or wall tiling including cement mortar bedding and removing the rubbish outside the defence land complete all as specified and directed .
Material and Labour for Premium quality, joint free, non skid coloured ceramic tiles,1200 x 600 x 8 to 10 mm thick as in floor, set and jointed in neat cement slurry @ 3.00 kg/Square metre and pointed in white or coloured cement to match the surface over and including cement screed bed 15mm thick in cement mortar (1:4) base complete all as specified and directed.
Material and Labour for for Chequered cement concrete tiles, rubber moulded 200mm x 200mm x 25mm thick, set, jointed and pointed in neat cement slurry with grey cement with pigment in floors over 15mm thick screed bed in CM (1:6) complete all as specified and as directed.
Supply and fixing in replacement of water storage tank of 500 ltr capacity, HDPE triple layer, cylindrical, vertical with closed top and FDA approved, 100% UA stabilized, rust proof, ISI marked, fixed and hoisted in position on staging or roof complete with locking arrangement including over flow pipe, air lock pipe, brass valve 20 mm high pressure with polythene float and flynut, ISI marked, screwed and suitable for iron pipe 20 mm bore including taking down of old tank of any descrption and removal from site complete all as specified and directed. Note:- Tank shall be white and make of tank shall be engraved on the tank.
Cleaning and removing all scale and dirt, etc from existing water storage tanks of capacity exceeding 250 litres and not exceeding 500 litres by emptying, drying and cleaning the tank by scrubbing the dust with wire brush from tank including cleaning from mouths of circulating pipes, to entire satisfaction of Engr-in–chargeof cleaning , including writing date of cleaning with oil paint of of visible colour in font size not less than 100 mm, complete all as specified and directed (The rates includes for disconnecting of existing water tank, lowering if required and hoisting, reconnecting and refixing in same position after cleaning) NOTE: - (i) The whole process of disconnecting, reconnecting and refixing in same position after cleaning shall be done on the same day, if failing so, Rs. 100/- shall be deducted for each tank per day from the contractor due.
Supply and fixing in replacement of rolled mild steel plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, with riveted, bolted or welded attachment Fe-290 (Gde E- 165) for existing LT panel doors/gates complete all as specified and directed.
Material & Labour for disconnecting and connecting of LT service wires and XLPE cables of any type and any size from LT panel, MCCBs, DBs, over head conductor, LT poles, street light timer including replacement of old unsv items such as nuts, bolts, thimbles, insulating seleaves and existing misc items etc, and after cleaning and removing of corbon on cables end surface including removing rusted particles removing dust tightening nut, bolts complete all as specified and directed. Note : (i) Cost of all tools and ladder required for maintenanne of LT service wires and XLPE cable end connection and disconnection is incl in quoted rate (ii) Cost of misc items like nuts, bolts, thimbles, insulating seleaves etc if required are included in quoted rates.
Supply and fixing in replacement of nature switch operation should be based on natural light lux level, required illuanance level for switching on is <30 Lux and for switching off >10 lux , the sensor should also have part night operation facility of min 4 hrs to max 12 hrs complete all as specified and directed
Supply and fixing in replacement of contactor 3 pole 18 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed.
Supply and fixing in replacement of contactor two pole 25/40 Amp in street light timer box coil operating voltage 230 volt complete all as specified and directed.
Supply and fixing in replacement of contactor coil (230V) for MU series 25/40 Amps 2 pole contactors complete all as specified and directed.
Supply and fixing in replacement of contactor coil (240V) for freedom series 18 Amps 3 pole contactors complete all as specified and directed.
Material and labour for cable route indicator showing "MES LT UG 1.1KV" and route of cable with arrow (should be embossed or engraved) made of RCC in suitable shape and fixed in PCC block 1:3:6 type C-2 using 40mm graded aggregate including bricks works and excavation, size of route indicator 60cm x 30cm, 30cm below ground level and 30cm above ground level to show clear indication of cable including painting the complete slab with red paint and making the engraved/embossed letters/arrow with white paint complete all as specified and directed.
Supply and fixing in replacement of cable route indicator or cable joint mark for 1100 volts made out of mild steel 100mm dia 6mm thick plate welded to 30 x 30 x 4mm angle iron 60 cm long embeded in PCC 1:3:6 type C-2 (using 20mm graded stone aggregate) block of size of 150mm x 200mm x 200mm including applying two coats of synthetic enamel paint over a coat of redoxide primer on steel surfaces complete all as specified and directed.
Supply and fix in replacement of bracket made out of GI tubing 40 mm dia single piece not welded, bended at proper angle, light grade 1.5 mtr long including painting with aluminium paint over one coat of red oxide primer to the bracket including 1.0 sqmm 3.0 core flexible copper cable in PVC conduit with clamp from juction box to connecter of street light fitting complete all as specified and directed.
Supply and fix in replacement of MS clamp suitable for holding street light bracket on steel/PCC pole made out of 40 mm x6 mm thick flat iron with M.S nuts bolts 50 mm long 10 mm dia -3 Nos with flat washer 3mm thick -02 No for each including painting with aluminium paint over one coat of red oxide primer to the M.S clamps complete all as specified and directed.
Supply only Hand held electric brush cutter having min 1000 RPM, with grass trimmer min 7000 RPM with 1200 watt rear motor and assist handle, split shaft with accessories for trimming Power houses lawns, sub stn surrounding etc. The handles of the cutter must be provided in loop type for easy to operate and move around complete all as specified and directed. Make :- Nepture/ Green Craft/ Moti Garden/Usha
Supply and fix in replacement of extended spreaders link should be installed both side with exisitng/new MCCBs 4P/3P of any capacity with existing LT panels complete all as specified and directed.
Supply, fixing and testing in replacement of auto day/night on and off photo cell, LDR sensor switch 6 amps for lighting on/off, water proof 220 volt 50 Hz, AC supply, Model No Quick Sense QS-301 complete with all accessories internally pre-wired including connection with 1.5 Sqmm copper conductor from main supply to sensor, sensor to fittings complete all as specified and directed.
Note:- Amount of credit of Rs. 109652.00 for retrieved materials is mentioned in Schedule of Credit of tender documents in PDF form which will be deducted offline while acceptance of tender.
Raman Electric Trading Co
Mohinder Pal and Sons
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .