The Executive Engineer (O&M), DGVCL Piplod Division Office, Surat.
Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable end termination & straight through jointing kit (to be supplied by contractor) on ARC basis 66 KV Bhimrad Sub-Station of ALTHAN sub division as well as all sub-division in jurisdiction of Piplod Division or within the jurisdiction of Surat City Circle.
320317
DGVCLDPPL/0680/06/2026 Approved Date: 25-06-2026
Open
Electrical
Surat
1 document required · 1 mandatory
₹1,180
SURAT DGVCL
₹30,000
3 Jul 2026
3 Jul 2026
3 Jul 2026
20 Jul 2026
3 Jul 2026
Sub:-Erection & labour work of supply, laying, testing & commissioning of 11/22 kv underground XLPE cable (XLPE cable will be supplied by DGVCL) with cable
end termination & straight through jointing kit (to be supplied by contractor) on ARC basis 66 KV Bhimrad Sub-Station of ALTHAN sub division as well as all sub-
division in jurisdiction of Piplod Division or within the jurisdiction of Surat City Circle.
Item Code DETAILS OF WORKS Qty Unit Rate Amount
1 9925000001 Labour charge for excavation of cable trench of 400mm width x Meter
1200mm depth, in any type of soil for laying of cable of size up to
mm2 (For additional cable 200 mm additional width shall be considered
i.e. half trench length is to be considered)
2 9925000002 Labour charge for excavation of cable trench of 600mm width x Meter
1200mm depth, in any type of soil for laying of cable of size up to
mm2 (For additional cable 200 mm additional width shall be considered
i.e. half trench length is to be considered)
3 9925000003 Labour charge for excavation of cable trench of 400mm width x Meter
1500mm depth, in any type of soil for laying of cable of size up to
mm2 (For additional cable 200 mm additional width shall be considered
i.e. half trench length is to be considered)
4 9925000004 Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 Meter
mm2 & preparation of sand layer 100mm thick, in the cable trench &
covering the cable with 150 mm dia (Inner), thickness 25 mm,
meter long RCC half round muffs and providing and fixing of 4inch
width yellow colour polyethylene tape with printing "CAUTION ELECTRIC
CABLE BELOW" at 0.75 m depth from ground surface after laying cable
in trench. This will provide indication that electric cable is passing
underground so as to protect cable from mechnical injuries, refilling the
same, as per Instruction of Engineer in Charge (EIC).
5 9925000005 Labour charge for horizontal drilling using Auger machine without Meter
damage to surface road at max 2.0 mtrs depth & putting of 6.11 kg/cm2
, class-4,Green color, 110mm O.D. , 8.5mm thickness H.D.P.E. pipe
confirms to IS 4984-1987(3rd revision) and BIS certification and laying
of 11KV/22KV XLPE cable of size up to 300 mm2 in HDPE pipe, as per
Site Condition (excluding cost of pipe). The detail map obtained from
HDD machine and excell sheet(hard and soft copy) indicating the
respective depth and distance from adjacent landmark for each
segment for HDD is must required to be submitted. HDD to be carried
out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and as per
6 9925000006 Labour
instructioncharge
of EIC.for horizontal drilling manually without damage to Meter
surface road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-
4,Green color, 110mm O.D., 8.5mm thickness H.D.P.E. pipe confirms to
IS 4984-1987(3rd revision) and BIS certification and laying of 11KV/22KV
XLPE cable of size up to 300 mm2 size, as per Site Condition (excluding
cost of pipe). The detail map and excell sheet(hard and soft copy)
indicating the respective depth and distance from adjacent landmark
for each segment of cable to be submitted. Drilling to be carried out at
depth Minimum 1.2 mtrs to 2.0 mtrs as per site conditions as per
instruction of EIC.
7 9925000007 Supply of 6.11kg/cm2, class-4,Green color, 110mm O.D., 8.5 mm Meter
thickness H.D.P.E. pipe confirms to IS 4984 and BIS certification for
laying of underground 11KV / 22KV XLPE cable up to 300 mm2 size.
8 9925000008 Labour work for RCC concreting on disputed location and repairing of CMT
damage portion of road crossing for the work carried out for roads
crossing as well as concreting & muffing of ploes including all materials
9 9925000009 Providing & fixing concrete stone route marker of 300 mm width x 150 No
mm thick x 650 mm height embedded in earth at least 300 mm below &
350 mm above ground level respectively at distance approx 50 meters
along the length of cable. The RCC concreting (1:2:4)(all necessary
maeterials will be in bidder's scope) of route marker is to be carried out
300 mm width x 150 mm thick x 300 mm below ground level as per
instruction of EIC. The route marker should be with name of company
with approved yellow colour-DGVCL. The distance from marker to cable
and cable depth with feeder name etc., marked with arrow sign is to be
painted on it.The route marker is to be fixed at location near to any
fixed permanent location (not necessary to fix exact on top of cable) as
per instruction of EIC.
10 9925000014 Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 300 Per Job
mm 2 on DP Structure with fixing of 02 Nos polymer cleats on top and
middle part . Polymer cleats, nut bolts etc. fixing material to be
provided by contractor.
11 9925000015 Providing & fixing of 6.11kg/cm2, class-4,Green color, 110mm O.D., Per Job
8.5mm thickness H.D.P.E. pipe confirms to IS 4984 and BIS certification
on the erected DP structure for the mechanical protection of cable by
inserting the cable inside HDPE pipe. The HDPE pipe shall be erected in
such a way that 300mm shall be below the ground level and the rest
2700 mm shall be supported on the DP Structure with 01 No
Polymer cleat. All materials including polymer cleat and Nut bolt to be
provided by contractor.
12 9925000016 Providing and fixing of pipe type earthing from 80 mm dia class-B GI No
pipe with pit to be filled with salt & coke and construction of chamber
as per DGVCL Drg. No. dg /100 for DP and cable. The earthing pit
should be joined with cable by G.I. strip of size 1” width & 2 mm thick.
All material GI pipe, Coke, Salt etc will be supplied by bidder.
13 9925000017 Supply & fixing of heat shrink type end terminations (outdoor) for upto No
11kV 3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
14 9925000018 Supply & fixing of heat & shrinkable end terminations (outdoor) for upto No
22 kV 3C x 185 mm 2 size X LPE cable as per DGVCL technical
15 9925000019 Supply & fixing of heat shrink type end terminations (indoor) for upto No
11kV 3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
16 9925000020 Supply & fixing of heat & shrinkable end terminations (indoor) for upto No
22 kV 3C x 185 mm 2 size XLPE cable as per DGVCL technical
17 9925000021 Supply & fixing of heat shrinkable straight through joint for upto 11kV No
3C x 185 mm2 size XLPE cableas per DGVCL technical specification.
18 9925000022 Supply & fixing of heat shrinkable straight through joint type for upto No
22kV 3C x 185 mm2 size XLPE cable as per DGVCL technical specification.
19 9925000023 Labour charge for excavation of 2100mm long x 1200mm wide x 1200 No
mm deep joint pits for installation of 11kV/22kV Straight through joints
as per instruction of engineer-in-charge & covering the cable with
mm dia (Outer), thickness 25 mm, 1.0 meter long RCC half round muffs
& refilling same as per instruction of EIC .
20 9925000024 Providing and fixing of insulating bus bar, made from 11KV/22KV XLPE No
cable after removal of semi conducting layer and applying of PVC heat
shrinkable anti-tracking core insulating tubing (1.1KV), on both end
terminal using Aluminium long barrel heavy duty up to 240 sq mm lugs,
Aluminium bus connector. Taping with PG- clamp for bus conductor as
per drawing and as per instruction of EIC. The Alluminium lugs and PG
clamp shall be covered with 11KV/22KV HT insulating tapes.(11KV/22KV
XLPE cable will be in scope of DGVCL while all other materials will be in
bidder's scope)
21 9925000025 Testing of cable at various points and commissioning the feeder as per No
instruction of engineer-in-charge. Test result shall be submitted by
contractor with bill.
22 9925000026 Preparation and submission of 6 (six) copies , of complete layout Set
drawings with GIS mapping as per actual cable routing showing road
crossing, HDPE pipe sleeving, jointing locations, markers etc.
23 9925000027 Providing and fixing of Sign Board at junction point Made out of 2 mm No
aluminium sheet size 750x300 mm (2.5 x 1ft) rectangle, as per design,
pre treated with phosphate process and acid etching coated with one
coat of epoxy primer and two coats of best quality paints, refloctrorised
with Hi-Intensity retro – reflective sheeting as per the latest and frame
fabricated from suitable size iron angle. The Sign Board is to be fixed on
the base prepared from channel and bracing angles which is grouted by
means of cement concreting of 1:2:4 for size of 300 mm dia x 800 mm
height (500 mm to be grouted in ground). The details to be displayed on
sign board will be given by In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
24 9925000028 Providing and fixing of Sign Board (Danger Board) on Distribution No
Transformer Centers
Made out of 2mm aluminium sheet size 300x300mm (1x1ft) as per
design, pre treated with phosphate process and acid etching coated
with one coat of epoxy primer and two coats of best quality paints,
refloctrorised with Hi-Intensity retro-reflective sheeting as per the latest
and frame fabricated from suitable size iron angle. The Sign Board
(Danger Board is to be fixed at the location as per instruction of In-
charge Engineer.
(a) Hi intensity Micro prismatic Grade
25 9925000029 Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) No
from 3 mm aluminium sheet along with 1.0 mm dia aluminium binding
wire for fixing of aluminium tag near end termination joint at DP
structure for identifyng the cable. The details of feeder i.e. 11 / 22 KV
with feeder name shound be punched on the tag by letter punch of size
16 mm as per instruction of In-charge Engineer.
26 9925000030 Supply & fixing of heat shrink type end terminations (outdoor) for 11kV Nos
3C x 240 mm2 size XLPE cable as per DGVCL technical specification.
27 9925000031 Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 Nos
kV 3C x 240 mm2 size XLPE cable as per DGVCL technical specification.
28 9925000032 Supply & fixing of heat shrink type end terminations (indoor) for 11kV Nos
3C x 240 mm2 size XLPE cable as per DGVCL technical specification.
29 9925000033 Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV Nos
3C x 240 mm2 size XLPE cable as per DGVCL technical specification.
30 9925000034 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x Nos
240 mm2 size XLPE cableas per DGVCL technical specification.
31 9925000035 Supply & fixing of heat shrinkable straight through joint type for 22kV Nos
3C x 240 mm2 size XLPE cable as per DGVCL technical specification.
32 9925000047 Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade trench or per cable
in open space per mtr
33 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM
34 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC NO.
half round pipe
35 9925000010 Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with NO.
cable connection arrangement along with fitting of necessary
fabrication for 11KV cable including excavation of pit & refilling of earth
as per instruction of EIC. (Exclusive of concreting & muffing of poles)
36 9925000011 Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable NO.
connection arrangement along with fitting ofnecessary fabrication for
11KV/22 KV cable including excavation of pit & refilling of earth as per
instruction of EIC. (Exclusive of concreting & muffing of poles)
37 9925000012 Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with NO.
cable connection arrangement along with fitting of necessary
fabrication for 11KV cable including excavation of pit & refilling of earth
as per instruction of EIC. (Exclusive of concreting & muffing of poles)
39 9925000013 Erection of Single pole structure using 8.0 Mtr PSC pole with cable NO.
connection arrangement along with fitting ofnecessary fabrication for
11KV/22 KV cable including excavation of pit & refilling of earth as per
instruction of EIC. (Exclusive of concreting & muffing of poles)
40 Laying (including installation, testing and commissioning) of various size mtr 335 as per rate derived by UGVCL letter no
of ugvcl/r&c/ug/Cost Data-2022-23/816
Single circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Date:-27-01-2023
Cable in ground 1200 mm deep and 300 mm wide trench, providing
sand cushioning below (75 mm thick layer of sand) and above (75 mm
thick layer of sand) of the cable and covering it with RCC half round
hume pipe (150 mm inner
diameter with thickness of 30 mm and One meter in length) before
pre-bonding tap/warning tap should provide below 700 mm from the
ground level and back filling the same to make ground level as per
As per specification and drawing of DGVCL. ( RCC half round pipe should
provide throughout on cable without gap).
41 Laying (including installation, testing and commissioning) of various size mtr 468 as per rate derived by UGVCL letter no
of ugvcl/r&c/ug/Cost Data-2022-23/816
Double circuit 11 KV 300 sq mm XLPE insulated Aluminium armoured Date:-27-01-2023
Cable in ground 1200 mm deep and 500 mm wide trench, providing
sand cushioning below (75 mm thick layer of sand) and above (75 mm
thick layer of sand) of the cable and covering it with RCC half round
hume pipe (150 mm inner diameter with thickness of 30 mm and One
meter in length) before refilling pre-bonding tap/warning tap should
provide below 700 mm from the ground level and back filling the same
to make ground level as per original. As per specification and drawing of
DGVCL. ( RCC half round pipe should be provide throughout on cable
42 Supply & fixing of heat shrink type end terminations (indoor) for 11kV No 5549 as per rate derived by UGVCL letter no
3C x 300 mm2 size XLPE cable as per technical specification. ugvcl/r&c/ug/Cost Data-2022-23/816
43 Supply & fixing of heat shrink type end terminations (outdoor) for upto No 6676 as per rate derived by UGVCL letter no
11kV 3C x 300 mm2 size XLPE cable as per technical specification. ugvcl/r&c/ug/Cost Data-2022-23/816
44 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x No 8040 as per rate derived by UGVCL letter no
300 mm2 size XLPE cableas per L technical specification. ugvcl/r&c/ug/Cost Data-2022-23/816
Rate as per SOR 30,00,000/-
Executive Engineer (O&M)
DGVCL, Division Office,
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
TENDER APPROVAL UG 30 L ALTHAN SDN.pdf
2. BID DOCUMENT (1).pdf
3. Detail Technical Specification.pdf
SCHEDULE B UG ALTHAN.pdf
Download all tender documents and submit your bid