Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.5 LAccepted-AOC HOUSE NO 102 LANE NO 4 C ANAND NAGAR BOHRI JAMMU 180002 J K | JAMMU | JAMMU AND KASHMIR | 180002 | L1 | Accepted-AOC Tender accepted due to lowest and quoted reasonable rates | |
| 2 | L2₹22.2 L+₹1.7 L (8.34%)Rejected-Finance R O 218 05 OPP J D A COMPLEX TRIKUTA NAGAR JAMMU J K PIN 180020 | JAMMU | JAMMU AND KASHMIR | 180020 | L2 | Rejected-Finance higher side quoted amount | |
| 3 | Rejected-Technical | - | Rejected-Technical Not Recommended being DD uploaded was expired on 20 May 2024 and DD uploaded is on name of M/s Kiran Electric Works. |
Tender Value
Refer Docs
EMD Value
₹38,000
Closing Date
31 May 2024, 6:00 pmClosed
CWE Khumbathang
HQ CWE Khumbathang PIN-900270 C/o 56 APO
REPAIR AND MAINTENANCE OF HT LINES, UG CABLES, TRANSFORMER ANHD ALLIED WROKS OF VARIOUS UNITS AT KARGIL, KAKSAR, HINSKUT, BUDHKHARBU, APATI, CHHANIGUND AND HARDAS UNDER GE KARGIL
2024_MES_651862_1
80051/08/E8
Open Tender
Support/Maintenance Service
Item Rate
180 days
GE Kargil
Class E Cat B (ii)
8 documents required · 8 mandatory
₹500
GE KARGIL
₹38,000
Yes
2 Sept 2024
1 May 2024
1 Jun 2024
1 May 2024
31 May 2024
16 May 2024
Amount
S&F in replacement of lightening arrester for outdoor use, non liner resister type, horn gap and choking coil, maximum working pressure 11000 Volts, discharge capacity 65 kilo amp, complete all as specified and directed by the Engr-in-Charge.
Straining and re-stretching of existing over head aluminium conductor steel reinforced (ACSR) of any size on HT poles with mechanical tool, including binding and jointing the conductor with and including 14 SWG binding wire and jumpers connections with PG clamps, complete all as specified and directed by the Engr-in-Charge.
Straining and re-stretching of existing over head aluminium conductor steel reinforced (ACSR) of any size on LT poles with mechanical tool, including binding and jointing the conductor with and including 14 SWG binding wire and jumpers connections with PG clamps, complete all as specified and directed by the Engr-in-Charge.
Dismantling of ACSR conductor any type any size, complete all as specified and directed by the Engr-in-Charge.
ACSR conductor of (weasel) 6/1/2.59 for HT line (11 kv), straching properly on insulators and binding with aluminium binding wires, jumpers including fixing on insulators on each poles in span and tightening with permissible sag in between span etc, complete all as specified and as directed by Engineer-in-charge.
ACSR conductor or service feeder distribution span of (Rabbit) 6/1/3.35 for LT line (440 Volts), straching properly on insulators and binding with aluminium binding wires,jumpers including fixing on insulators on each poles in span and tightening with permissible sag in between span etc, complete all as specified and as directed by Engineer-in-charge.
Dismantling cross-arms of M.S. channel or angle sections etc, complete all as specified and as directed by Engineer-in-charge.
Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, complete all as specified and as directed by Engineer-in-charge.
Supply and fix in repairs ON LOAD change over switch with sheet metal enclosure 415V , 4 pole of capacity 100 Amps including connecting up incoming/ out going cables with suitable lugs and testing, complete all as specified and directed by the Engr-in-Charge.
Supply and fix in repairs ON LOAD change over switch with sheet metal enclosure 415V , 4 pole of capacity 200 Amps including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and directed by the Engr-in-Charge.
Supply and fix as in repairs ON LOAD change over switch with sheet metal enclosure 415V , 4 pole of capacity 320 Amps including connecting up incoming/ out going cables with suitable lugs and testing complete all as specified and directed by the Engr-in-Charge.
Supply and fix MCCB 250 Amps, 415 volts,Thermal Magnetic released based 4 pole 415 Volts, 36 KA breaking capacity, complete all as specified and directed by the Engr-in-Charge.
Supply and fix MCCB 200 Amps, 415 volts,Thermal Magnetic released based 4 pole 415 Volts, 36 KA breaking capacity, complete all as specified and directed by the Engr-in-Charge.
Supply and fix MCCB 160 Amps, 415 volts,Thermal Magnetic released based 4 pole 415 Volts, 36 KA breaking capacity, complete all as specified and directed by the Engr-in-Charge.
Supply and fix MCCB 125 Amps, 415 volts,Thermal Magnetic released based 4 pole 415 Volts, 25 KA breaking capacity, complete all as specified and directed by the Engr-in-Charge.
Supply and fix MCCB 100 Amps, 415 volts,Thermal Magnetic released based 4 pole 415 Volts, 16 KA breaking capacity, complete all as specified and directed by the Engr-in-Charge.
Dismantling and taking out the old stay assembly complete incl demolition of plain cement concrete, complete all as specified and directed by the Engr-in-Charge. Note : (i) Unit rate of this item includes the loose/disconnect the all accessories which are connected to stay assy includng necessary excavation as directed. (ii) Existing stay assy are fixed on the LT/HT pole of PCC or steel tubular pole, nothing extra shall be paid on this account.
Stay assembly complete with GI stay rod 20 mm dia 1800 mm long, MS plate 230x2306 mm, stay bow, loop insulator, PCC 1:3:6 type C-I using 20mm graded crushed stone aggregate, connecting bracket of suitable MS flat and nut bolt washers etc complete all as specified in electrical plate No 1 of SSR Part-I, complete all as specified and directed by the Engr-in-Charge.
Dismantling of air break gang operated switches vertical / horizontal mounted including insulators and operating mechanism for replacement repair/ replacement of broken/worn out components and insulators etc. or carrying to MES store, complete all as specified and directed by the Engr-in-Charge.
Switch air break gang operated triple pole mechanically operated mounted on insulator and steel frame with operating mechanism woked from ground level for current rating upto 400 Amps 11000 volts, complete all as specified and directed by the Engr-in-Charge.
S & F in replacement LT bush assembly brass complete with double check nuts, washers and oil seal including all accessories with bushing insulators for transformer capacity 63/100 KVA complete, complete all as specified and directed by the Engr-in-Charge.
S & F in replacement LT bush assembly brass complete with double check nuts, washers and oil seal including all accessories with bushing insulators for transformer capacity 200/250 KVA, complete all as specified and directed by the Engr-in-Charge.
S & F in replacement HT bush assembly brass complete with double check nuts, washers and oil seal including all accessories with bushing insulators for transformer capacity 63/100 KVA, complete all as specified and directed by the Engr-in-Charge.
S & F in replacement HT bush assembly brass complete with double check nuts, washers and oil seal including all accessories with bushing insulators for transformer capacity 200/250 KVA, complete all as specified and directed by the Engr-in-Charge.
Attending minor transformer complaints/ Preventive maint of Transformer by taking proper shutdown of HT feeder from concerning power house checking, testing and locating faults of HT side/LT side of transfamer of any make / any capacity kept on four / two pole structure/plinth etc. Opening/ disconnecting HT electric connectios removal of old jumpers by cutting of old rusted nuts, bolts & washers etc. Replacement of unserviceable jumpers, tightening connections , checking load balancing etc incuding routine maintenance such as checking of minor oil leakage from transfarmer, silica gel , breather,oil level including replacement of LT /HT side bushing rod etc all as specified and directed by Engineer-in-Charge. Note :- (i) transfamer oil / silica gel breather if replaced shall be measured and paid separatly under appropriate item. (ii) The Supply only spare parts excluding minor parts will be measured and paid under relevent items. T & P and minor repair i.e. replacement of the nut/bolts etc. shall be arranged by the contractor and the cost deemed to be included in the quoted rates. During currency period of contract , contractor shall depute high skilled trades men for attending the complaint of transformer regularly as and when called with in 24 hours & maintanance shall be carried out accordingly for smooth functioning of transformer and cost of the same shall deemed to be included in the above quoted rates. Please note one time payment shall be made to contractor for these items.if any fault / defects occured , contractor shall rectify / replace the same without any extra cost in terms of condition 46 of IAFW-2249 of General condtion of contracts.
Disconnecting HT/LT connections of burnt / defective copper / aluminum wound transformer of capacity 63 KVA ,taking down from site of installation, opening up the top cover, draining out transformer oil from transformer in suitable containers (containers to be provided by the contractor ) inspection / assess the defective / burnt out parts, core assembly of transformer in the presence of AGE / GE and prepare list and then shifting the transformer to trade / contractor's workshop for repair, cleaning and making good surface and rewinding the same with existing size of new copper / aluminum conductor, strip wound coils, limb for HT / LT , fixing of class 'E' insulation in core assembly etc. including internal cleaning, removing sludge, washing and painting with one coat of zinc chromate paint to inner side of the transformer body and one coat on outer side with synthetic enameled Grey paint (spray painting) after cleaning and removing oil spot from the body and re assembling, reinstalling, commissioning the transformer to its original place and testing at site on full load after connecting the HT / LT connections complete all as specified and directed by Engineer-in-Charge. Notes :- (i) HT/LT copper/aluminum coil, transformer oil and other required parts as mentioned here-in-after shall be measured and paid separately under appropriate item. (ii) The T & P/ vehicles and minor parts/nut bolts etc. will be arranged by the contractor and the cost of same shall be deemed to be included in the quoted rates. (iii) The rates quoted is deemed to be included in the unit rate for cutting/chipping of RCC/PCC/plastering of foundation/platform and minor grill work/welding work.
Disconnecting HT/LT connections of burnt / defective copper / aluminum wound transformer of capacity 100 KVA ,taking down from site of installation, opening up the top cover, draining out transformer oil from transformer in suitable containers (containers to be provided by the contractor ) inspection / assess the defective / burnt out parts, core assembly of transformer in the presence of AGE / GE and prepare list and then shifting the transformer to trade / contractor's workshop for repair, cleaning and making good surface and rewinding the same with existing size of new copper / aluminum conductor, strip wound coils, limb for HT / LT , fixing of class 'E' insulation in core assembly etc. including internal cleaning, removing sludge, washing and painting with one coat of zinc chromate paint to inner side of the transformer body and one coat on outer side with synthetic enameled Grey paint (spray painting) after cleaning and removing oil spot from the body and re assembling, reinstalling, commissioning the transformer to its original place and testing at site on full load after connecting the HT / LT connections complete all as specified and directed by Engineer-in-Charge. Notes :- (i) HT/LT copper/aluminum coil, transformer oil and other required parts as mentioned here-in-after shall be measured and paid separately under appropriate item. (ii) The T & P/ vehicles and minor parts/nut bolts etc. will be arranged by the contractor and the cost of same shall be deemed to be included in the quoted rates. (iii) The rates quoted is deemed to be included in the unit rate for cutting/chipping of RCC/PCC/plastering of foundation/platform and minor grill work/welding work.
Disconnecting HT/LT connections of burnt / defective copper / aluminum wound transformer of capacity 200/250 KVA ,taking down from site of installation, opening up the top cover, draining out transformer oil from transformer in suitable containers (containers to be provided by the contractor ) inspection / assess the defective / burnt out parts, core assembly of transformer in the presence of AGE / GE and prepare list and then shifting the transformer to trade / contractor's workshop for repair, cleaning and making good surface and rewinding the same with existing size of new copper / aluminum conductor, strip wound coils, limb for HT / LT , fixing of class 'E' insulation in core assembly etc. including internal cleaning, removing sludge, washing and painting with one coat of zinc chromate paint to inner side of the transformer body and one coat on outer side with synthetic enameled Grey paint (spray painting) after cleaning and removing oil spot from the body and re assembling, reinstalling, commissioning the transformer to its original place and testing at site on full load after connecting the HT / LT connections complete all as specified and directed by Engineer-in-Charge. Notes :- (i) HT/LT copper/aluminum coil, transformer oil and other required parts as mentioned here-in-after shall be measured and paid separately under appropriate item. (ii) The T & P/ vehicles and minor parts/nut bolts etc. will be arranged by the contractor and the cost of same shall be deemed to be included in the quoted rates. (iii) The rates quoted is deemed to be included in the unit rate for cutting/chipping of RCC/PCC/plastering of foundation/platform and minor grill work/welding work.
Supply only new copper LT coils made out of proper size of DPC copper wire/strip super enameled of high quality matching with existing impedances and providing class 'E' insulation suitable for transformer 63 KVA to 250 KVA complete all as specified and directed by Engineer-in-Charge. Note :- The rate quoted is deemed to be included in the unit rate for varnishing, sleeving and insulating materials and the Contractors shall not have any claim on this account at a later sage.
Supply only new copper HT coils made out of proper size of DPC copper wire/strip super enameled of high quality matching with existing impedances and providing class 'E' insulation suitable for transformer 63 KVA to 250 KVA complete all as specified and directed by Engineer-in-Charge. Note:- The rate quoted is deemed to be included in the unit rate for varnishing, sleeving and insulating materials and the Contractors shall not have any claim on this account at a later sage.
Supplying and filling new mineral grade transformer oil EHV type confirming to IS-3357 of 1983 for filling and for topping up in transformer duly filtered with filtration plant to obtain high dielectric strength not less than 60 KV (Gap 2.5mm) complete all as specified and directed by Engineer-in-Charge. Note:- Empty barrel will be property of contractor and same will be returned to contractor when barrel will be empty.
Cleaning and preparation of old painted surface of transformer ( Exposed external surface only) installed at site of any installation in cantt area capacity 63 KVA to 250 KVA transformer installed on pole mounted , indoor / out door, plinth mounted by using course cloth/wire brush and painting with one coat of synthetic enamel grey paint with the help of spray gun including writing the SM No/MES No. on transformer with white paint in the existing style/pattern, complete all as specified and directed by Engineer-in-Charge.
Dehydration & filtration of transformer oil with portable filtration cum dehydration machine to improve the dielectric strength not less than 50 KV within 1 minute with 2.5 mm gap at site of any installation in cantt area and any capacity / make of transformer installed on pole mounted, indoor/out door, plinth mounted. Testing of dielectric strength of dehydrated transformer oil of each transformer will be carried out in the presence of JE/ Engineer-in-Charge complete all as specified and directed by Engineer-in-Charge. Notes:- (i) Contractor shall ensure no wastage of transformer oil occurs. (ii) Contractor shall ensure that the conservator tanks are full to its level before starting the dehydration.
M&L for servicing and greasing of mechanical parts of existing 11KV horizontal/vertical type GOD including replacement of parts i.e Male/female contact, jumper ,operating mechanism, GOD rod, bearing etc specified and directed by Engr-in chargeNote:-The cost of spare parts shall be deemed to be included in quoted rates and nothing extra should be paid on this account.
Earthing complete with galvanized steel earth plate electrode 60 cm x 60cmx6 mm thick, buried directly in ground vertically (earth pit not less than 2.25 m deep below ground level) with top edge of the earth plate not less than 1.5m below ground level , connected to GI strip size 32X6mm as earthling lead by means bolts and nuts check nuts and washers of galvanized iron and connected to main switch board including 20mm bore medium grade GI pipe for watering arrangement with PCC chamber , MS funnel, wire mesh, CI cover with frame , 40 MM dia GI pipe light grade for protection of strip etc including necessary excavation in any type of strata , returning, filling removal of soil outside MD land ,filling of charcoal and salt complete all as shown in electrical plate No. 5 of MES Sch Part I , connected to Earthing test point all as specified and directed on testing on completion.
Supply and fix LT spacer 4 ways made out of PVC material, complete all as specified and directed by Engr-in-Charge.
S&F in replacement of pin type insulator,Polymer type, white, brown or green insulator one galvanised MS spindle, two GI washers and one GI nut, 150mm height, 150 mm dia for 11000 volts grade, complete all as specified.
Material and labour for preparation of old surface of steel pole 9/11 mtr including channels and applying two coats of aluminium paint including making five no. alternative yellow & black strips 30 cm height each (upto 1.50 metre height from top of PCC coping & numbering to the poles with synthetic enamel paint complete all as specified and directed by the Engr-in-Charge.
Dismantling of steel tubular swaged poles of any length complete with cast iron base plate including necessary demolition and excavation complete all as specified and directed.
Supply ,transporting, errecting and fixing Steel tubular swaged poles type 410 SP-64 (12 metre long) complete with cast iron/mild steel base plate, finial taper plug, bolts, nuts & screws as specified including necessary excavation and earth work,PCC 1:4:8 type D-2 in foundation & around poles and PCC 1:2:4 type B1 as in plinth block,disposal of surplus soil to a distance not exceding 50 meter and depositing where directed,painting steel tubular pole`s exposed surface with two coats of aluminium paint over one coat of red oxide primer and making five nos alternative white and black strip 30 cm height each upto 1.5 meter height from top of PCC coping with synthetic enemel paint and numbering of pole complete with painting of embeded portion of pole with two coat of bituminous paint complete all as specified. (i) Cost of painting & numbering on poles i.e. making five no. alternative white & black strips 30 cm height each (upto 1.50 metre height from top of PCC coping & numbering to the poles with synthetic enamel paint etc shall be deemed to be included in the rates of above items (ii) Earthwork PCC foundation & coping shall be included in over all cost quoted.
S&F in replacement of pin type insulator, Polymer type, white, brown or green insulator one galvanised MS spindle, two GI washers and one GI nut, 100mm height, 100 mm dia for 3300 volts grade, complete all as specified.
Taking out of XLPE cable of any type any size from trenches/pole including PCC precast cable cover.
XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 95 sq. mm 3 core complete all as specified
S&F in replacement of Cable jointing kit for 11000 volt (Earthed) grade cable for outdoor termination hot shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured stranded aluminium conductor cable of size 50 sq mm to 95 sqmm complete all as specified.
S&F in replacement of prodigy electronic meters temper proof LCD display with polycarbonate cover 3 phase, 415 V, 40-200Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH,KVAH, complete all specified and directed by Engr-in-charge.
Supplying and laying synthetic rubber insulated mat 2.5 mm thick for voltage upto 11 kv size 2x1 mtr, complete all as specified and directed by the Engr-in-Charge.
Supplying and laying guard wire (cradle wire) rectangular fabricated with 3.15 mm GI wire complete all as specified and directed by the Engr-in-Charge.
Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and directed by the Engr-in-Charge.
Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm complete all as specified and directed by the Engr-in-Charge.
Taking out of unserviceable breather assembly complete from 63KVA to 500 KVA transformer and supply and fixing new breatherv assembly complete filled with fresh blue coloured silica gel including connecting with proper rubberized gasket complete all as specified and directed.
Note:-The accepted amount will be arrived after deducting the Sch of credit i.e. Rs 2,05,613.00 and any other reduction if any from quoted amount.
M/S ZTECH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .