Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.0 LAccepted-AOC H 10 KARNI NAGAR NEW NAGAUR ROAD NEAR MANDORE POLICE STATION 8TH MILL MANDORE JODHPUR 342304 | JODHPUR | JODHPUR | RAJASTHAN | 342304 | L1 | Accepted-AOC LOWEST REASONABLE BID | |
| 2 | L2₹48.5 L+₹94,601 (1.99%)Rejected-Finance NAYA BASS MAHAMANDIR JODHPUR RAJASTHAN 342006 | JODHPUR | JODHPUR | RAJASTHAN | 342006 | L2 | Rejected-Finance NOT LOWEST | |
| 3 | Rejected-Technical | - | Rejected-Technical Not Eligible bidder being two class below the eligible class. | |
| 4 | Rejected-Technical | - | Rejected-Technical Not Eligible bidder as not enlisted in eligible cat. i.e. b ii therefore not satisfies the eligibility criteria as per NIT. |
| Sl No | Description | Qty | Unit | Shri Electrical Enterprises L1 | Anil Builders L2 |
|---|---|---|---|---|---|
| 1.00 | Supplying, laying, jointing, testing and connecting in replacement of XLPE insulated PVC outer seathed and (earthed) PVC inner sheath, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminum conductors, 11 KV(E) grade and conforming to IS : 7098 and, of size 150 sqmm, 3 core, laid in trenches / ducts / encased in GI pipe / fixed to pole, complete all as specified and directed by Engr-in-charge. Note : Earth work, protection pipe and Cable Joints etc shall be measured and paid separately. | 435 | RM | 1,337 ₹5,81,595 Lowest | 1,400 ₹6,09,000 |
| 2.00 | Supply and fixing in replacement of GI Pipe light grade 80 mm dia with necessary accessories/ fittings bracing with pole/wall by FI clamps made with 32x6mm for cable protections/pole for crossing of culverts/nallah/road and complete all as specified and directed by Engr-in-charge. | 40 | RM | 600 ₹24,000 | 500 ₹20,000 Lowest |
| 3.00 | M&L for Cutting the road / hard standings and excavating in trenches not exceding 0.40 mtr wide and not exc 0.80 mtr deep across the road for laying cable including making good the excavated portion by means of PCC 1:2:4, type B1 using 20mm graded stone aggregate complete and matching with the surroundings complete all as specified and directed by Engr-in-charge. | 30 | RM | 550 ₹16,500 Lowest | 800 ₹24,000 |
| 4.00 | Material and labour plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate as in base of the pole or in any situation complete all as specified and directed by Engr-in-charge. | 1.5 | Cum | 3,000 ₹4,500 | 2,250 ₹3,375 Lowest |
| 5.00 | Material and labour plain cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of the pole or in any situation including necessary form work complete all as specified and directed by Engr-in-charge. | 0.2 | Cum | 6,000 ₹1,200 Lowest | 6,000 ₹1,200 Lowest |
| 6.00 | Excavation in trenches in any type of soil not exc 1.5 mtr in depth and 1.5 mtr wide and getting out for laying of cables. complete all as specified and directed by Engr-in-charge. | 400 | Cum | 200 ₹80,000 Lowest | 200 ₹80,000 Lowest |
| 7.00 | All as per ser No-6 above but depth exc 1.5 mtr but not exc 3.00 mtr complete all as specified and directed by Engr-in-charge. | 0.1 | Cum | 500 ₹50 Lowest | 500 ₹50 Lowest |
| 8.00 | M&L for tibba sand filling in trenches dry and and clean sand unwashed including punning around cable for protection of under ground cable complete all as specified and directed by Engr-in-charge. | 75 | Cum | 350 ₹26,250 | 200 ₹15,000 Lowest |
| 9.00 | M&L for laying jodhpur stone quarry stone slab cover 25 to 30cm in width, 60cm long and 40 to 50 mm thick laid in trenches and abutting each other with gap between adjacent slab not exceeding 10mm over sand covered under ground cables complete all as specified and directed by Engr-in-charge. | 260 | Sqm | 235 ₹61,100 Lowest | 300 ₹78,000 |
| 10.00 | Returning and filling in including spreading, leveling , watering and well ramming in layers not exceeding 25 cm thick of excavated earth complete all as specified and directed by Engr-in-charge. | 270 | Cum | 75 ₹20,250 | 30 ₹8,100 Lowest |
Tender Value
₹55 L
EMD Value
₹1.1 L
Closing Date
22 Oct 2025, 6:00 pmClosed
CWE ARMY JODHPUR
CWE ARMY MULTAN LINE ARMY AREA JODHPUR-342010
REPAIR / MAINT OF HT OVERHEAD LINE, UG CABLES, POWER AND DISTRIBUTION TRANSFORMERS, VCB / RMUs AND OTHER CONNECTED ITEMS AT ARMY AREA BANAR UNDER GE BANAR
2025_MES_731198_1
82526/48/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
BANAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE BANAR
₹1.1 L
Yes
12 Jan 2026
16 Sept 2025
29 Oct 2025
16 Sept 2025
22 Oct 2025
8 Oct 2025
17 Sept 2025 - 7 Oct 2025
Amount
Supplying, laying, jointing, testing and connecting in replacement of XLPE insulated PVC outer seathed and (earthed) PVC inner sheath, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminum conductors, 11 KV(E) grade and conforming to IS : 7098 and, of size 150 sqmm, 3 core, laid in trenches / ducts / encased in GI pipe / fixed to pole, complete all as specified and directed by Engr-in-charge. Note : Earth work, protection pipe and Cable Joints etc shall be measured and paid separately.
Supply and fixing in replacement of GI Pipe light grade 80 mm dia with necessary accessories/ fittings bracing with pole/wall by FI clamps made with 32x6mm for cable protections/pole for crossing of culverts/nallah/road and complete all as specified and directed by Engr-in-charge.
M&L for Cutting the road / hard standings and excavating in trenches not exceding 0.40 mtr wide and not exc 0.80 mtr deep across the road for laying cable including making good the excavated portion by means of PCC 1:2:4, type B1 using 20mm graded stone aggregate complete and matching with the surroundings complete all as specified and directed by Engr-in-charge.
Material and labour plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate as in base of the pole or in any situation complete all as specified and directed by Engr-in-charge.
Material and labour plain cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping of the pole or in any situation including necessary form work complete all as specified and directed by Engr-in-charge.
Excavation in trenches in any type of soil not exc 1.5 mtr in depth and 1.5 mtr wide and getting out for laying of cables. complete all as specified and directed by Engr-in-charge.
All as per ser No-6 above but depth exc 1.5 mtr but not exc 3.00 mtr complete all as specified and directed by Engr-in-charge.
M&L for tibba sand filling in trenches dry and and clean sand unwashed including punning around cable for protection of under ground cable complete all as specified and directed by Engr-in-charge.
M&L for laying jodhpur stone quarry stone slab cover 25 to 30cm in width, 60cm long and 40 to 50 mm thick laid in trenches and abutting each other with gap between adjacent slab not exceeding 10mm over sand covered under ground cables complete all as specified and directed by Engr-in-charge.
Returning and filling in including spreading, leveling , watering and well ramming in layers not exceeding 25 cm thick of excavated earth complete all as specified and directed by Engr-in-charge.
Removal of surplus soil to a distance not exceeding 50 mtr and depositing at a leval not exceeding 1.5 mtrs above the starting point complete all as specified and directed by Engr-in-charge.
Supply and fixing the HT Cable route indicator made by Jodhpur stone well finished and marking of letter "DANGER HT 11KV", size 100mmx10mm, 75cm long, 15cm grouted with 1:3:6 PCC foundation below the ground level and 60cm of marker will be elevated on ground the embossed letters of "DANGER HT 11 KV" will be painted with post office red colour and with black colour background and complete all as specified and directed by Engr-in-charge.
Supply and fix Cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Aluminium conductor cable of size 95 Sqmm to 120 Sqmm complete all as specified and directed by Engr-in-charge.
Supply and fix outdoor type heat shrinkable end termination cable joint kit including all material and accessories suitable for 3 core 95 sqmm XLPE armed aluminium conductor cable of 11000 Volt (Earthed) grade all as per manufactuer recommendation complete all as specified and directed by Engr-in-charge.
All as per Ser No 14 above but suitable for 3 core 120 sqmm cable complete all as specified and directed by Engr-in-charge.
All as per Ser No 14 above but suitable for 3 core 150 sqmm cable complete all as specified and directed by Engr-in-charge.
All as per Ser No 14 above but suitable for 3 core 185 sqmm cable complete all as specified and directed by Engr-in-charge.
Supply and fix straight through heat shrinkable cable joint kit including all material and accessories suitable for 3 core 95 sqmm XLPE armoured aluminium conductor cable of 11000 Volt (Earthed) grade all as per manufactuer recommendation complete all as specified and directed by Engr-in-charge.
All as per Ser No 18 above but suitable for 3 core 120 sqmm cable complete all as specified and directed by Engr-in-charge.
All as per Ser No 18 above but suitable for 3 core 150 sqmm cable complete all as specified and directed by Engr-in-charge.
All as per Ser No 18 above but suitable for 3 core 185 sqmm cable complete all as specified and directed by Engr-in-charge.
All T&P expenditure for tracing out the 11 KV HT UG cable fault by pin point with cable fault locating machine mounted vahicle including all T&P expenditure to rectify the fault,disconnecting faulty cables of different sizes from both ends, removal of Fault, Re-connections and testing of ables after removal of fault complete all as specified and directed by Engr-in-charge. Note: (i) 11 KV HT cable & joints shall be measured and paid for seperately under respective items of schedule. (b) Excavation and earth work are deemed to be included in above quoted rates.
M&L and fixing in true Vertical position prestressed concrete pole 11.00 Mtr long of size 152mm x 152mm at top and 152 mm x 260mm at bottom of class-9 confirming to relevent IS-1678-1998 code and dismantling and removing the old unsv PCC pole and complete all as specified and directed by Engr-in-charge. NOTE - Excavation and Earth work and PCC in foundation shall be measured and paid seprately.
S&F in replacement of GI stay assembly set comprising of 14mm dia 400mm iron stay bow and16mm dia, 2150mm long stay rod stay plate 230x230x6mm thick, GI stay wire 7/8 SWG of required length complete with all accessories as shown in electric plate No 1 of SSR Part 1 2009 complete with excavation earth work including PCC 1:3:6 of required quantity with viterous china loop insulator, clamps nut bolts etc complete all as specified and directed by Engr-in-charge.
Supply and fixing cross arms, bracings, supports, clamps and back plate fabricated from structural steel sections including nuts, bolts, washers, welding, bending colt or hot, drilling holesfor bolt. In any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminum paint and complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement of HT 33 KV outdoor type triple pole gang operated air-break switch double stack type suitable for horizontal mounting rotating type with 9 insulator 200 amps current rating complete mechanically operated mechanism from ground level consisting of operating rod of 25 mm bore medium grade GI pipe of suitable length with locking arrangement, flat iron clamp 50x6mm including MS channel of suitable size and length for fixing GOD including bolts, nuts and washers complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement of air break switch gang operated tripple pole mechanically operated mechanism, switch air break gang operated mounted on 15 Nos insulator and steel frame with operating rod of 25 mm bore GI Pipe and locking arrangements worked from ground level for current rating 200 Amps, HT 11 KV grade including drop out fuses and necessary silver coper coating jumpers and making all electrical connections complete all as specified and directed by Engr-in-charge.
M&L for earthing in replacement with galvanized steel earth plate of size 60x60cmx6 mm thick electrode and 32x6mm GI strip length up to 7.5 mtr as earth lead, buried directly in ground (earth pit not less than 2.25 mtr below normal ground level) with top edge of earth plate should not less than 1.5 mtr below normal ground level and connected to galvanized iron earth, GI strip of size 32X6 mm dia by means of bolts, nuts, washers of galvanized iron all as shown in electrical plate No.3 of MES SSR Part I connected to earth test terminal point all asa specified or as indicated including testing on completion (Rates inclusive of neccessary excavation in any type of soil,earth work,PCC pit,PCC cover,funnel with watering pipe, protection pipe wire mesh, common salt, charcoal etc. complete all as specified and directed by Engr-in-charge.
M&L in replacement of GI strip of size 32x6 mm including mounting on PVC/Porcelain insulators on wall and burried in ground depth not less than 60 cm in ground complete all as specified and directed by Engineer-in-Charge.
Supply and Fixing in repair of Gang operated device (GOD ) Horizontal/vertical type 11 KV, 12/15 insulator incl replacing the male/female contact, MS jumper carrier, tinned copper flexible jumper, back connector plate, porcelain post insulator complete all as specified and directed by Engr-in-charge. Note:- (i) Spare parts are deemed to be included in above quoted rates.
Supply and Fix Expulsion type drop out fuse, single pole, 11000 V, 30 Amps complete with insulator 150mm dia and 150 mm height including dismantling /taking down old unserviceable one complete all as specified and directed by Engr-in-charge.
S&F in replacement 32/25 mm bore heavy grade GI pipe including all fitting for HT 11 KV Gang operated air break switch complete all as specified and directed by Engr-in-charge.
M&L for resagging of overhead conductor section of 11 KV including binding/re-binding of conductor with suitable size of wire and providing of jumpers at the ends as per site requirements complete all as specified and directed by Engr-in-Charge. Note :- (i) Length of span shall be 40 to 50m. (ii) Due care shall be given while resagging of overhead conductor that there shall be no damage to pin/post/disc insulator and pole. In case, due to any negligence, damage is caused, it shall be made good by the contractor and nothing extra shall be admissible.(iii) Proper shut down will be taken from department and T&P will be provoded by conractor.
Dismantling and taking down old ACSR conductor from HT pole complete all as specified and directed by Engr-in-Charge.
Supply, fixing, stringing, testing and commissioning of ACSR insulated rabbit conductor of size 6/1/3.35 mm binding with insulators including binding materials and connection of all services connections/existing cable complete all as specified and directed by Engr-in-charge.
Disconnecting electric outdoor/indoor transformer 11 KV capacity upto 630 KVA from HT/LT terminals and lowering down/getting out from 2/4 pole structure/plinth or from inside sub station for major/Minor repair and transportation to workshop and return back for installation it on original position/location after repairing from workshop complete all as specified and directed by Engr-in-charge. Note : (Rate is deemed to be inclusive of transportation, T&P and man power)
Labour for strip opening of distribution transformer up to 630 KVA & physical joint inspection of core coil assembly (removing all 3 limb HV & LV winding from core assembly) , washing of core assembly hot oil for removing burnt carbon & copper particles & cleaning of complete top yoke by oil , reassembly of complete core assembly & core coil assembly rewinding with new coils and new tap leads of OLTC, re-taning, tightening of top cover , fixing of HV and LV bushing, OLTC overhauling, Filling of New oil, conservator tank and Drying/Ovening of complete CCA in vaccum Chamber & continues monitoring for Improvement of IR Value. complete all as specified and directed by Engr-in-charge. Note :- (i) The quoted rates shall be deemed to include HV/LV Bushing with brass spindle, gasket, nuts, bolts, washers of different sizes (ii) HT/LT leg coils and transformer oil shall be measured and paid separately under respective items of schedule.
Supply only HT/LT coils with copper wire DPC/super enameled high quality matching with existing gauge and impedence complete all as specified and directed by Engr-in-charge.
Material and Labour for ON load centrifuging and dehydration including filteration and cleaning of transformer oil by dehydration machine electric operated without any shutdown of transformer including testing oil sample before and after dehydration and filteration oil complete all as specified and directed by Engr-in-charge. Note : (i) Transformer oil required for top up shall be measured and paid for separate (ii) Contractor have to arrange the dehydration machine and testing kit from his own resources without any extra cost. (iii) dielectric strength of transformer oil not less than 45 KV at 2.5 mm gap (iv) Record of dehydration to be maintained duly sign by GE, Engr-in Charge & Contractor
Supply and filling the transformer oil in factorey sealed barrel with IS-336 of di-electric strength not less than 45 KV at 2.5 mm gap and toping up the oil where ever required in Army area Banar and complete all as specified and directed by Engr-in-charge.
Disconnecting electrically & mechanically indoor/outdoor transforemrs upto 630 KVA capacity carefully for prevent/stoping for leakage of transformer oil by welding / tightening the loose points at site, including opening of top cover, draining out transformer oil and other items and storing the oil in suitable container including replacement of all unserviceable gasket, replacing the unsv HT/LT porcelain Bushing/studs as directed after repairing/stoping of oil leakage the same re-connecting electrically and mechanically, testing complete all as specified and directed by Engr-in-charge. Note:- (i) Spare parts ie.porcelain Bushing, brass spindle, gasket, nuts, bolts,and washers if reqd are deemed to be included in above quoted rates.
Supply and Fixing in replacement of breather incl silica gel complete with all accessories for transformer of capacity up to 630 KVA complete all as specified and directed by Engr-in-charge.
Supply and fill in replacement of silica gel in transformer complete all as specified and directed by Engr-in-charge.
M&L for cleaning, scraping out old rubbed paint / rust & Painting of transformer complete with two coat of spray painting with synthetic enamelled gray paint (first grade) by spray painting machine on transformer & Making SM NO on surface of transformer of capacity up to 630 KVAoutdoor / Indoor type fixed on poles or in Sub Station at different location complete all as specified and directed by Engr-in-charge.
Disconnecting electric indoor/outdoor transformer 11 KV capacity up to 630 KVA from HT/LT terminals or 11 KV VCB/RMU and lifting by hydra for any location to another location at Banar Army area including loading / unloading and reinstallation complete all as specified and directed by Engr-in-charge.
S&F in replacement the off load Tape changer suitable to 63 to 630 KVA indoor/outdoor transformer with fixing suitable make and fixing and making connection complete all as specified and directed by Engr-in-charge.
Material and labor for servicing the ON LOAD tap changer transformer capacity of 1500 KVA indoor type by replacing the minor parts such as gear wheels, control wiring and checking the all connections and tap changing terminals decarbonising and servicing the all moving parts of onlaod tap changer and complete all as specified and directed by Engr-in-charge.
Material and labour for Periodical servicing & Calibration of HT switch gear VCB of capacity 400-630 Amp capacity ,11KV by tripping off the breaker and draw out the trolley and servicing and overhauling the mechanical parts with applying the grease and checking the control wiring and tripping mechanism, replacement of damaged minor parts such as control wiring, ferrules, HRC fuse, caliberation of IDMT/Microprocessor numerical/digital relay existing on panels with secondery injection kit and setting the relay of earth fault, short circuit, time delay settings as per existing load of feeder and all as specified and direted by engr-in-charge at 33 KV MRS and depot area complete all as specified and directed by Engr-in-charge.
All as per Ser No 48 above but 33 KV VCB complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of spring charging motor suitable for 11 KV VCB 400-630 Amp complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of tripping coil suitable for 11 KV VCB 400 to 630 Amps complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of spring suitable for 11 KV VCB 400-630 Amp complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of vacume interruptor suitable for 11 KV VCB 400-630 Amp complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of microprocessor relay of 24 volts DC supply operated with earth fault ,over current suitable for 11 KV VCB 400-630 Amp complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of 11000 volts grade HRC fuse barrel type of rating upto 60 Amps suitable for 11 KV VCB 400-630 Amp complete all as specified and directed by Engr-in-charge.
Disconnecting HT Supply and servicing for HT switch gear RMU of 2/3/4 way ,11KV out door type tripping off the breaker servicing and overhauling the mechanical parts with applying the grease and checking the control wiring and tripping mechanism, replacement of damaged minor parts such as control wiring, ferrules, HRC fuses etc, caliberation of processor numerical/digital relay existing on panels with secondery injection kit and setting the relay of earth fault, short circuit over current, time delay settings as per existing load of feeder and complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of Standered motorised Kit for V module suitable for RMU, 11 KV, 630- 800 Amp, 2-4 way, complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of Spring charging Motor with Gear 24 V DC suitable for RMU, 11 KV, 630- 800 Amp, 3-4 way, complete all as specified and directed by Engr-in-charge.
Material and labour for filling of SF6 gas and testing suitable for RMU, 11 KV, 630- 800 Amp, 2-4 way, complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement of Operating mechanism suitable for RMU, 11 KV, 630- 800 Amp, 2-4 way, complete all as specified and directed by Engr-in-charge.
Supply & fixing in replacement of cable boot 11 KV in 630 Amps RMU, 3-4 way complete all as specified and directed by Engr-in-Charge.
Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, resin cast epoxy type, of 18.1 KA/Sec having ratio 100/50/5-15 Amps having Core1: Class 5P10, 10VA for protection , Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and directed by Engr-in-charge.
M&L in replacement of Supply, design, Installation, testing and commissioning of totally enclosed busbar chamber of outdoor type IP-55 protection fabricated out of 3.15 mm thick CRCA sheet dust and vermin proof powder coated double door type including locking arrangement, aluminum bus bar 400 Amp rating with air tight insulated mounted on insulators, incoming and outgoing cable chamer incl cable gland suitable for size upto 185 Sqmm HT cable complete suitable for operation of 11000 volts grade , 50 hz, AC supply having mounted on angle iron stand fixed at 75 cm from the ground level made out of angle size 65 X 65 X 6 mm grouted in PCC 1:3:6 and complete all as specified and directed by Engr-in-charge. (Note: (i) The size of bus bar chamber should not be less than 800x800x800mm (ii) Cost of PCC platform 50 mm thick 1:2:4 Type B-1 over 75mm thick sub base 1:5:10 type E-2 using 40mm graded stone aggregate is inclusive in the rate quoted for this item.
Supplying, laying, jointing, testing and connecting in replacement of XLPE insulated PVC outer seathed and (earthed) PVC inner sheath, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminum conductors, 11 KV(E) grade and conforming to IS : 7098 and, of size 120 sqmm, 3 core, laid in trenches / ducts / encased in GI pipe / fixed to pole, complete all as specified and directed by Engr-in-charge. Note : Earth work, protection pipe and Cable Joints etc shall be measured and paid separately.
M&L for replacement of defective/damaged type Pin type, pocelain, vitreous, white brow or green insulator including one galvanised mild steel spindle, two galvaanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000 volts grade with fixing on existing 2 pole/4pole/single pole including taking down of old unsv insulator and complete all as specified and directed by Engr-in-charge.
Supply and Fix Disc type insulator porcelain, vitreous 145mm high and 255 mm dia ball and socket type white, brown or green, double disc with tension clamp for conductor for working pressure voltage 11000 V including dismantling/ taking out unserviceable from Pole complete all as specified and directed by Engr-in-charge.
Taking out old unserviceable 33 KV pin insulator incl taking out 33 KV OH ACSR conductor and supply and fix 33 KV pin type, porcelain, vitreous, insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut for fixing of insulator on HT pole incl refixing the OH ACSR conductor at the same place incl binding the conductor to insulator with new binding wire complete all as specified and directed by Engr-in-charge.
M&L for replacement of defective/damaged Disc insulators suitable for 33 KV overhead conductors including removing/providing jumpers with line conductors as per required at site complete all as specified and directed by Engr-in-charge.
Supply and fix danger notice plate/marking plate of size 60cmx30cm with the use of ACP sheet, vitrous enamelled white with latters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of appropriate size for 11 KV system all as specified and confirming to to IS : 2551-1982. complete all as specified and directed by Engr-in-charge.
Supplying & Fixing in replacement Caution plate “CAUTION MEN AT WORK" of size 40cmx30cm made out of ACP Sheet with Red coloured complete all as specified and directed by Engr-in-charge.
Supply and Fixing in replacement of Lightning arrestor single pole zinc oxide (gapless surge type) heavy duty station class, self supporting outdoor type lighting arrester having rated voltage 09 KV (rms) discharge current 65 KA insulation level 28/75 KV/KVP (Peak) suitable for rated system voltage of 11 KV supply system with maximum continuous operating voltage (MCOV) not less than 7.65 KV (rms) with highly non linear ceramic resister made of zinc oxide in hermetically sealed container complete with metal base, base inculator and suitable terminals for ground connections and pressure relieving arragement complete all as specified and directed by Engr-in-charge.
Supply and Fixing in replacement of Lightning arrestor single pole zinc oxide (gapless surge type) heavy duty station class, self supporting outdoor type lighting arrester having rated voltage 30 KV (rms) discharge current 65 KA insulation level 35/75 KV/KVP (Peak) suitable for rated system voltage of 33 KV supply system with maximum continuous operating voltage (MCOV) not less than 17.05 KV (rms) with highly non linear ceramic resister made of zinc oxide in hermetically sealed container complete with metal base, base inculator and suitable terminals for ground connections and pressure relieving arragement complete all as specified and directed by Engr-in-charge.
M&L for Surface excavation n.exc 30 cm deep and averaging 15 cm and geeting out in any type of soil incl cutting and removing grass, vegetation, bushes/shrubs etc from surrounding of 02 Pole/ 4 Pole structure and LT/ HT Panel E/M installations and removing all rubbish and dressing the gravel/soil and spaying the one time herbicide approved brand (Roundup/Noweed) to prevent the further vegetation and complete all as specified and directed by Engr-in-charge.
Supply and laying the graded coarse aggregate 40mm size for E/M installations of 33KV MRS yard/2/4 pole HT/LT pole structures/surrounding area of RMU including cleaning the vegetation developed and making plane of surfece and complete all as specified and directed by Engr-in-charge.
Supply and laying the graded coarse aggregate 20mm size for E/M installations of 33KV MRS yard/2/4 pole HT/LT pole structures/surrounding area of RMU including cleaning the vegetation developed and making plane of surfece and complete all as specified and directed by Engr-in-charge.
Material and labour for cutting the branches/trees near the HT OH line upto clearance area 5mtr around OH line by cutting the branches and removing the wastage from site to disposal area and complete all as specified and directed by Engr-in-charge. Note :-(i) The necessary man power tool and plant , cutting tools and JCB if required for cutting/ prunning of branches is deemed to incl in the rate quoted for the job (ii) Proper shut down will be taken from JE E/M only.
Supply ,fixing and testing in replacement of 12V 150 AH Tubular type maintence free battery complete connected to existing HT VCB Panel of 33/11 KV complete all as specified and directed by Engr-in-Charge.
Preventive maintenance/servicing and testing of power transformer 3.15/2.0 MVA of 33/11KV at MRS ABOD Banar, following test shall be carried out at site complete all as specified and directed by Engineer-in-Charge. (a). IR Test (b). Earthing resistance test (c). Turn ratio test (e). Transformer oil test
Preventive maintenance/servicing and testing of Distribution Transformer cap 1500 KVA at Technical area, following test shall be carried out at site complete all as specified and directed by Engineer-in-Charge. (a). IR Test (b). Earthing resistance test (c). Turn ratio test (e). Transformer oil test
Supplying, laying, jointing, testing and connecting in replacement of XLPE insulated PVC outer seathed and (earthed) PVC inner sheath, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminum conductors, 11 KV(E) grade and conforming to IS : 7098 and, of size 95 sqmm, 3 core, laid in trenches / ducts / encased in GI pipe / fixed to pole, complete all as specified and directed by Engr-in-charge. Note : Earth work, protection pipe and Cable Joints etc shall be measured and paid separately.
Material and labour for replacement of unserviceable existing plate earthing with bore well earthing the help of mechanical boring machine of 150 mm dia, 30 mtr depth with 50 mm dia medium GI pipe duly drilled all around 15 mm dia hole at a distance of 200 mm from hole to hole upto min 20 mtr depth upto water level including supply and fix 150 mm dia MS casing pipe heavy duty 6 mm wall thickness-6 mtr length and help of suitable size clamp with nut bolt and washer -01 No. including 32x6 mm GI strip upto 7.5 mtr in ground and connected to transformer/VCB/GOD, grounding of borewell with PCC (1:2:4) type B-1 / Brick masonry pit of size 60x60x45cm complete and give the minimum earth test result below 1 Ohm complete all as specified and directed by Engineer-in-charge. Note :- (i) The charge for mechanical boring machine,MS Pipe, GI Pipe, GI Strip & PCC work is deemed to be include in above quoted rate.
Dismantling posts or struts (wood, steel or RCC) any section, including taking out embedded portion in concrete and making good distrubed ground complete all as specified and directed by Engr-in-Charge.
Excavating in post holes (or similar holes) each n.exc 0.50 Cum getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm in hard/dense soil complete all as specified and directed by Engr-in-charge.
M&L for rolled steel section as in posts, struts and staples in fencing including cutting to top to shape (swan neck) as directed, drilling holes, notching for wire, etc flat iron fillets (for securing wire mesh etc) including all necessary bolting or riveting welding etc and similar work confirming to Fe-290 Gde-165 complete all as specified and directed by Engr-in-Charge. Note fencing posts should be painted before fixing
Dismantling of wrought iron or mild steel work including of any description not otherwise provided for complete all as specified and directed by Engr-in-charge.
M&L for rolled steel section framed work as in doors or gates of angle or other section with gusset plates, rails, braces etc complete drilled for fixing of steel sheeting or other covering, doors etc to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings including all necessary bolting or riveting welding etc and similar work confirming to Fe-290 Gde-165 complete all as specified and directed by Engr-in-Charge
M & L for two coats of synthetic enamalled paint over one coat of red oxide primer on new steel surfaces exc 10cm in width or girth, including preparation of the surface complete all as specified and directed by Engr-in-charge.
Dismantling of fencing wire mesh any type and any size complete all as specified and directed by Engr-in-charge.
Supply only Chain link MS galvanised fencing, any size or type, complete all as specified and directed by Engr-in-charge. Note :- Per Sqm weight shall be derermined by BOO detailed by GE.
Fixing only chain link fencing including line wires/ MS round bar (Any numbers), any mesh, size and type to any type of standards rails, straining bolts, etc including provision of binding wire complete all as specified and directed by Engr-in-charge. (Note. Supply of flat iron, MS round bar & chain link shall be measured and paid seperately under supply only)
S & F 12 mm dia MS screw bolts any size (machine made) with hexagonal or square heads at one end and screwed the other ends, fitted with washer and one one hexagonal nut exc 5cm long but n exc 10cm complete all as specified and directed by Engr-in-charge.
Supply and fixing only MS rounded bars Fe-290 (Gde-165) 10 mm dia and over cut to length and bend to shape as required as in tie bars, secured with nut, bolt and washers complete all as specified and directed by Engineer-in-Charge.
Anil Builders (BID ID -3459678)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.56 MB
BOQ_818612.xls
BOQ • 0.48 MB
TENDER48.pdf
Tender Documents • 1.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .