Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.9 CrAdmitted-Finance | ₹5.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹7.8 Cr+₹1.9 Cr (31.8%)Admitted-Finance 1 SHAKTI NAGAR JAMMU JAMMU KASHMIR 180001 | JAMMU | JAMMU AND KASHMIR | 180001 | ₹7.8 Cr+₹1.9 Cr (31.8%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | KAPAHI CONSTRUCTION COMPANY L1 | Bee Kay Protection Systems L2 |
|---|---|---|---|---|---|
| 1.00 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.(b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration pads.2280 lpm at 70 m Head | 1 | set | - | - |
| 2.00 | Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following,complete in all respects, as required : (Diesel Driven Pump)Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520 Suitable HP, 1500 RPM water cooled with radiator,diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated
with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer,instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads 2280 lpm at 70 m Head | 1 | set | - | - |
| 3.00 | Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type
suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation,
conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling
guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.180 lpm at 70 m Head | 2 | set | - | - |
| 4.00 | Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all
respects, as required: (Terrace Pump) (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation,
conforming to IS-325.(c) M.S.fabricated common base plate, coupling, coupling
guard, foundation bolts etc.as required.(d) Suitable cement concrete foundation duly plastered and with anti vibration pads.4.900 lpm at 35 m Head | 2 | Set | - | - |
| 5.00 | CONTROL PANELS Fabrication, supply, Insallation testing & commissioning of Electrical control panel of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors,dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, interconnection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect,suitable for main fire pump, pressurisation pump &diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable foroperation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required Incomings 400A, 50kA 4 Pole MCCB, Ics=100% Icu rating Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps Set of Copper Bus Bar 500A Outgoings ( Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps) Main Fire Pump 200 A, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation. Jockey Pump 100 A, 50kA TPN MCCB, Ics=100% Icu, with suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, auto/manual/OFF operation.Diesel Engine Control Control for diesel engine comprising - Automatic/Manual selctor switch & 3 attempt starting device, timers and relays as required, push buttons,start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0- 20 A DC Ammeter All standard relays and accessories for automatic operation of diesel engine System Controller Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump, Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers. Sensors, annunciation window for fault indication, complete as per specifications. | 1 | set | - | - |
| 6.00 | Providing laying, testing & commissioning of 'MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports,anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 200 mm. dia (wall thickness = 6.3 mm) | 540 | Mtrs | - | - |
| 7.00Providing, laying, testing & commissioning of MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : | |||||
| 7.10 | 25 mm dia | 450 | m | - | - |
| 7.20 | 32 mm dia | 410 | m | - | - |
| 7.30 | 40 mm dia | 280 | m | - | - |
Tender Value
₹6.6 Cr
EMD Value
₹13.2 L
Closing Date
20 Feb 2020, 4:00 pmClosed
Executive Engineer
PWD(RnB) Diviison Rajouri
Construction of Allied Works in Govt. Medical College at Rajouri by way of Fire fighting System, Street lighting, Exit Sign board I c electric signage n laboratory counters
2020_PWDJK_92626_1
NIT No 71 of 2019-20 Dated 11-02-2020
Open Tender
Civil Works
Item Wise
90 days
Rajouri
Plz refer NIT
3 documents required · 3 mandatory
₹6,000
Executive Engineer PWD(RnB) DIvision Raj
₹13.2 L
Yes
Superintending Engineer
6 Mar 2020
12 Feb 2020
22 Feb 2020
13 Feb 2020
20 Feb 2020
13 Feb 2020
17 Feb 2020
Amount
Supplying, installation, testing and commissioning of Electric driven Main Fire Pump suitable for automatic operation and consisting of following, complete in all respects, as required :(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520.(b) Suitable HP Squirrel cage induction motor, TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration pads.2280 lpm at 70 m Head
Supplying, installation, testing and commissioning of diesel engine driven main fire pump suitable for automatic operation and consisting of following,complete in all respects, as required : (Diesel Driven Pump)Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS 1520 Suitable HP, 1500 RPM water cooled with radiator,diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12 /24 volts electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer,instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads 2280 lpm at 70 m Head
Supplying, installation, testing and commissioning of electric driven pressurisation pump suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal conforming to IS : 1520. Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS : 325. M.S.fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. Suitable cement concrete foundation duly plastered and with anti vibration pads.180 lpm at 70 m Head
Supplying, installation, testing and commissioning of electric driven terrace pump suitable for automatic operation and consisting of following, complete in all respects, as required: (Terrace Pump) (a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical confirming to IS : 1520 b) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase, 50 Hz, AC supply with IP55 class of protection for enclosure, horiziontal foot mounted type with Class-'F' insulation, conforming to IS-325.(c) M.S.fabricated common base plate, coupling, coupling guard, foundation bolts etc.as required.(d) Suitable cement concrete foundation duly plastered and with anti vibration pads.4.900 lpm at 35 m Head
Providing laying, testing & commissioning of 'MS Pipe conforming to IS 1239/3589 i/c fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports,anticorrosive treatment with coaltar/asphalt tape as per IS 10221, refilling the trench etc. of following sizes complete as required. 200 mm. dia (wall thickness = 6.3 mm)
Providing, laying, testing & commissioning of MS pipe conforming to IS 3589/IS 1239 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
25 mm dia
32 mm dia
40 mm dia
50 mm dia
65 mm dia
80 mm dia
100 mm dia
150 mm dia
200 mm dia (wall thickness 6.3 mm)
Providing, laying, testing & commissioning of 'B' class heavy duty G.I. pipe conforming to IS 1239 including welding, fittings like elbows, tees, flanges, tapers, nuts, bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required :
50 mm dia
65 mm dia
80 mm dia
100 mm dia
Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required : Single headed Gunmetal
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal/Stainless Steel cap and chain as required :Single headed Gunmetal
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required
80 mm dia
100 mm dia
150 mm dia
Supplying, fixing, testing & commissioning of double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with nuts, bolts, washers, gaskets and conforming to IS 780 of following sizes as required
80 mm dia
100 mm dia
150 mm dia
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, GI bolts, nuts, washers etc.as required
80mm dia
150mm dia
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Gun Metal
Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required.20 mm nominal internal dia water hose thermoplastic (Textile reinforced) type -2 as per IS: 12585 20 mm nominal internal dia gun metal globe valve &nozzle.Drum and brackets for fixing the equipmets on wall.Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 17.1 30 m
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required :Gun metal
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required :4 way - 150 mm dia M.S. Pipe
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degree centigrade with required accessories : Pendent Sprinkler
Providing & fixing of pressure switch in M.S. pipe line including connection etc. as required
Providing & fixing flow switch in following sizes M.S. pipe including connection etc as required
100mm dia
150mm dia
Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases,strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of follwing sizes as required
80mm dia
100mm dia
150 mm dia
Supplying, installation, testing & commissioning of sprinkler flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required.
Supplying, installation, testing & commissioning of deluge valve (to be used for water curtains) UL listed with wet pilot basic trim assembly for DVA with test and alarm, drip and drain valve with water motor gong complete as required.
50 mm dia
80 mm dia
100 mm dia
150 mm dia
Providing, installation, testing & commissioning of water curtain nozzle 15mm dia nickel chrome plated brass, BSPT, K-factor as per design consideration complete as required
Providing, installation, testing & commissioning of electric release trim assembly for deluge wall with two way solelnoid valve, weather proof operation on 24 volts DC supply complete as required.
Providing, installation, testing & commissioning of adjustable rosette plate for 15mm dia in white finish UL Listed or FM approved complete as required
Portable Fire extinguishers Providing and fixing Portable fire extinguishers carbon dioxide type flat base and wall suspension beacket
capacity 4.5 kg ABC Type fire Extinguishers
4.5 Kg Co2 type
8 Fire Bucket with MS Stand
50 ltr Mech Foam Troley fire Extinguishers
Construction of laboratory counters with Jet Black Mirror Polished Granite top upto all floor levels. (including Brick Masonary 1:6 , Half Brick Masonary 1:4, RCC slab (M-25), Plaster 1: 4, Jet Black Mirror Polished Granite, cut for sink, required moulding on granite edges & all required centering & shuttering all lead lift complete job as per the direction of Engineer incharge & drawings).(For Payment purpose granite top shall be measured only)
Providing and fixing white vitreous china laboratory sink of CERA/Hindware/Jaquar/ Duravit with C.I. brackets, C.P. brass chain with rubber plug, 40 mm C.P brass waste and 40mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required Size 610 x410 x200 mm all lead lift complete job as per the direction of Engineer incharge ).
Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded brick aggregate 40mm nominal size) in R/Wall/Return Wall, columns, under flooring etc. including the cost of centering and shuttering, all works upto all floor levels all lead lift complete job as per the direction of Engineer incharge & drawings).
Construction of RCC water / sump / Septic tanks including all required CI mainholes complete job including all lead lift complete job as per the direction of Engineer incharge & drawings). .(For Payment purpose slab top shall be measured only)
Construction of CGI sheet shed including side walls, roof & RCC foundations (raft) complete Job including all lead lift complete job as per the direction of Engineer incharge & drawings). .(For Payment purpose inner size shall be measured only)
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. Makes : Duraline/Rex Polymer/Zenduct/Prince
63 mm dia (OD-63 mm & ID-51 mm nominal)
120 mm dia (OD-120 mm & ID-103 mm nominal)
160 mm dia (OD-160 mm & ID-135 mm nominal)
200 mm dia (OD-200 mm & ID-175 mm nominal)
Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep) and re-filling etc as required Makes : Tata/Jindal/Surya/Adarsh
Supply of 1.1kV Grade Power cables with Aluminum Stranded Conductor, XLPE Insulated,Cores Laid Up, PVC innersheathed, Armoured , Extruded PVC Type ST2 Sheathed, 650/1100V Grade As Per IS 7098(Part 1) 1988. Makes : Finolex/RRKabel/General/Havells/Anchor
3.5cx95sqmm
3.5cx50sqmm
3.5cx35sqmm
3.5cx25sqmm
4cx16.0sqmm
2cx10.0 sqmm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Supply of following Octagonal Galvanised Steel Poles Makes including luminaire mounting Bracket / Headframe, foundation bolts as per approved design/drawing. GA drawing of Mast and foundation drawing to be submitted .The poles shall be designed based on loading details of luminaires and as per IS 875 and other relevant standards. Make of GI Octagonal Poles : Valmount/Philips/ Transrail
7m with Single Arm
9m with Single Arm
Supply of 4.5m Pole made of ISI Galvanised Medium Pipe of 80mm dia duly painted with approved color including luminaire mounting Bracket as per approved design/drawing. Foundation above Ground level shall have provision for fixing of Cable junction box.
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.
Above 4.5 metre and upto 6.5 metre
Above 6.5 metre and upto 8.0 metre
Above 8.0 metre and upto 10.0 metre
Providing and making steel pole collar with cement concrete (1 cement : 3 coarse sand : 6 stone aggregate 20mm) of specified size and shape including form work, plastering if required, curing etc as required. (volume of pole/ pipe not to be deducted)
Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required.
40 mm dia
Supplying and drawing following 2.5sqmm of PVC insulated copper conductor, 3 core cable in the existing surface/ recessed steel/ PVC conduit as required. Makes : Finolex/RR Kabel/Anchor
Supply , Installation , Testing and commissioning of LED Post Top with a system lumen output of 2000 lumens and a minimum system efficacy of 80 lm/W. The luminaire shall have a rated system lifetime of 25,000 burning hours at L70. The luminaire should have a color temperature of 3000K/4000K and CRI > 70. The luminaire shall meet IP65 with THD < 20% and PF > 0.9. The luminaire shall have closed diffused optics with polycarbonate diffuser board. The total power consumption should not exceed 30W (including driver). Similar to Philips Make LED POST TOP G3 "BGP161". Job includes wiring with 3x2.5 sqmm wire, making terminations etc. Makes of LED Luminaire : GE/Philips/Trilux/ Disano/ Panasonic/ Wiproo
Supply and Installation of 12.5m High Mast including foundation bolts with Motorised Carriage suitable to carry LED Flood lights along with accessories. Mast shall be made of Galvanised Steel Sheet of 4mm Thickness with Top Dia of 166mm and Bottom Dia of 410mm. The accessories such as rope system, suspension system, drum wich and power tool shall be as per relevant IS. Thickness of Galvanisation shall be min. 65 microns for top and 86mm for bottom. Weight of mast shall be between 450 to 475kgs. GA drawings for the mast Foundation design shall be provided by mast manufacturer after placement of purchase order for verification and approval. Makes: Valmount/Philips/Transrail/Wiproo
Supply and Installation of Loop in Loop out thermoplastic cable junction box of makes Schneider/Hensel/OBO/ suitable for 25sqmm 4C loop in loop out of aluminium cable Outdoor weather proof made black color IP67 along with terminals of along with loop in loop out Terminals and one no. 6A SP MCB on Din Rail, internal wiring, mounting clamp complete job
Supply, Installation , Testing and commissioning of LED basedStreet light, housing made up of Pressure Die Cast Housing LM 6 Alloy/ Anti Dust Exposed Lens,sturdiness and embossed brand name/logo name of manufacturer. The fixture should have a minimum system efficacy of 100 lumen/Watt and a minimum system lumen output of 7200 lumens and maximum system wattage of 72 Watts.The fixture shall have a CRI of minimum 70. The fixture shall be designed for a system life of 50,000 hours @70% lumen maintenance. Ingress Protection of IP66 (lamp and gear Compartment) and Mechanical Impact Resistance Rating of IK >=05.The fixture driver should have an operating voltage range of 140-270 V, surge protection of >=3KV, PF >0.9 , THD<20% and SDCM<5. The driver should be BIS approved, fully potted and encapsulated .The fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Similar to Philips CAT No. - BRP410 LED CW 072 Makes of LED Luminaire : GE/Philips/Trilux/Disano/Panasonic/ Wiproo
Supply, Installation , Testing and commissioning of LED based Street light, housing made up of Pressure Die Cast Housing LM 6 Alloy/ Anti Dust Exposed Lens,sturdiness and embossed brand name/logo name of manufacturer. The fixture should have a minimum system efficacy of 100 lumen/Watt and a minimum system lumen output of 9400 lumens and maximum system wattage of 94Watts.The fixture shall have a CRI of minimum 70. The fixture shall be designed for a system life of 50,000 hours @70% lumen maintenance. Ingress Protection of IP66 (lamp and gear Compartment) and Mechanical Impact Resistance Rating of IK >=05.The fixture driver should have an operating voltage range of 140-270 V, surge protection of >=3KV, PF >0.9 , THD<20% and SDCM<5. The driver should be BIS approved, fully potted and encapsulated .The fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Similar to Philips CAT No. - BRP410 LED 094 CW HE MR FG S2 PSU GRMakes of LED Luminaire : GE/Philips/Trilux/Disano/Panasonic /Wiproo
Supply , Installation Testing and commissioing of LED based Flood light, housing made up of pressure die cast aluminum Alloy with effective thermal management,sturdiness and embossed brand name/logo name of manufacturer. The fixture should have a minimum system efficacy of 110 lumen/Watt and a minimum system lumen output of 15000 lumens and maximum system wattage of 140 Watts.The fixture shall have a CRI of minimum 70. The fixture shall be designed for a system life of 50,000 hours @70% lumen maintenance. Ingress Protection of IP66 (lamp and gear Compartment) and Mechanical Impact Resistance Rating of IK >=05.The fixture driver should have an operating voltage range of 140-270 V, surge protection of >=3KV, PF >0.9 and THD<20%. The fixture should comply with the parameters as per IS10322. The LED driver shall comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India. LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Similar to Philips CAT No. - BVP122 LED 150 CW HE NB FG XTFCL S4 Makes of LED Luminaire : GE/Philips/Trilux/Disano/Panasonic/Wiproo
Supply Installation Testing and commissioning of LED based Flood light, housing made up of pressure die cast aluminum Alloy with effective thermal management, sturdiness and embossed brand name/logo name of manufacturer. The fixture should have a minimum system efficacy of 100 lumen/Watt and a minimum system lumen output of 26000lumens and maximum system wattage of 255Watts.The fixture shall have a CRI of minimum 70. The fixture should have assymetric/ symmetric narrow beam and Narrowm beam angle options available. The fixture shall be designed for a system life of 50,000 hours @70% lumen maintenance. Ingress Protection of IP66 (lamp and gear Compartment) and Mechanical Impact Resistance Rating of IK >=05.The fixture driver should have an operating voltage range of 140-270 V, surge protection of >=3KV, PF >0.9 and THD<20%. The fixture should comply with the parameters as per IS10322. The LED driver should comply to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, CISPR-15 for EMI. Manufacturer shall have inhouse lab approved by NABL or ministry of science of govt of India.LM 79 and LM80 reports need to be submitted from a NABL/UL accredited lab to verify above parameters. Similar to Philips BVP410 LED 260 CW HE AK55 FG S4 XTFCL .Makes of LED Luminaire :GE/Philips/Zumtobel/Trilux/Disano/Panasonic
Supply, Installation , Testing and commissioning of LED Bollard light Long life time high power LED light source >25,000 hours, 70% lumen maintenance having Neutral white(NW) Light output with min Lumen o/p of 300lumens power consmption shuld not be more than 8W. Aluminum housing with glare free polycarbonate Diffuser tube & silicone rubber, heat-resistant gasket for maintaining IP 65 / IK10 / Class I. Ht should not be more than 0.5m. Provision for cable junction box shall be made in fondation. PCC (1:2:4) Foundation shall be 450mmx450mmx1000mmMakes of LED Luminaire :GE/Philips/Zumtobel/Trilux/Disano/Panasonic/Wiproo
Supply, installation, testing & Commissioning of long life maintenance free Ring Earthing System consisting of UL Listed 1No copper coated 14.2 mm dia Solid steel Rods shall be made of high tensile low carbon steel rod, with molecular bonded with 99.9% electrolytic copper coating of 250 mircon min, minimum length of the earth rod shall be 3 meters . The rod shall be surrounded by Earth Enhancement compound Procem , that has to produce low resistance of an earth termination system and it should not danger to persons and the surroundings 12.5 kg or sufficient quantities required as per the conditions. Heavy duty Fibre Glass Reinforced Under floor earth inspection should have dimension of 250 mmX 150 mm X 130 mm . Flush Mounted, removable and of the earth pit should be able to withstand 5000 Kg. The systems has to be conforming to IEC 60364, IEC 62561, IEC 62305, IS 2309 & IS 3043. Make OBO/Furse/KLK
Supply , Installation of indoor equipotential bonding rail equivalent to 1801VDE of OBO betterman including connections to earth conductors
Supply , Installation of outdoor equipotential bonding rail equivalent to 1801VDE of OBO betterman including connections to earth conductors
Supply and laying 5052 DIN 30x3 flat conductor of size 30mmx3mm , galvanised steel having weight of 70.65kg/100m in ground/at surface.
Supply and laying of 8mm round conductor aluminium RD 8 ALU of OBO
Supply, Installation, Testing and commissioning of Outdoor Floor Mounted Low Voltage panel (Street Lighting/Flood Lighting)suitable for operation on 433V 3 Phase, 50Hz supply, enclosure made of 2.0mm thick CRCA sheet steel material Alumium bus bar with following switchgears and metering. Necessary arrangement be made for termination of incoming cable and outgoing cables. Contractor to get the G.A. drawings approved before execution.Make of Panel Integrator : Make of LT Panels : Tricolite/Adlec/Legrand/BPS/BCH. Job includes making foundation for external lighting panel of Suitable size with provision for incoming and outgoing cables. Incomers :125A 4pole MCCB Ics=Icu=16kA - 1 Nos 63A 4P MCCB 16KA - 1 Nos All Incomers shall be provided with digital multi function metering display showing, V,A,kVA,kW, p.f., kVAR, harmonics readings, set of suitable rating CTs etc. Meters shall be compatible with Building Management System. 65A 4 Pole Contactor - 2Nos., Astronomical time Switch 2 Channel Busbar : 300A Aluminium TPN Bus bar supported on DMC insulators Outgoings :63A 4P MCCB 16kA - 6 Nos All MCCBs shall have overload adjustable setting 80-100% for overload and adjustable short circuit setting. Phase Indication LED Lamps for all incomers and outgoings to be provided. ON Off Trip Indication LED Lamps to be provided for all incomer and outgoings.Make of MCCB/MCB : Schneider(NSX), Siemens(3VL), Legrand( DPX3)
Supply, Installation, Testing and commissioning of following size of Electric Powered LED Signs for installation on Building Walls / Roofs as per approved design and colour made of High Powered good quality LED Light modules, Power Supplies of suitable size, Aluminium Composite Panel sheet as base for mounting of LED lit letters made of Acrylic of high quality. The Mounting steel structure and Aluminium composite sheet shall be paid separately as per approved design and rate for the same shall not be included in the item.Job inlcudes internal wiring for lighting up of approved LED words. Makes Prolite/Equivalent
36" height letter
24" height letter
12" height Letter
Supply, Installation of Road Reflective signage mounted on steel structure made of Steel GI pipe of suitable dia , steel mounting frame for sign board sheet duly painted with primer and black paint. Road sign shall be made of 300gsm Vinyl (Retro-Reflective) having white original base / aluminium base and letters of any approved colour duly printed with high quality ink. The Steel Pipe , foundation, mounting structure not part of this item and shall be paid separately. Prolite / Equivalent
Supply, Installation of 80mm dia GI Pipe duly painted with black color along with base plate of 300x300x6mm thickness MS duly welded
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
1:2:4 (1 cement : 2 coarse sand (zone-III) : 4 graded stone aggregate 20 mm nominal size).
Centering and shuttering including strutting, propping etc. and removal of form work for :
Foundations, footings, bases for columns
Excavation work by mechanical means (Hydraulic excavator)/ manual means in foundation trenches or drains (not exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m.
Ordinary Rock
Supply, Installation Testing and commissioning of 4 Pole Structure suitable for termination of 2 Nos Overhead 11 KV Lines, consisting of SP-56 Steel Tubular Poles conforming to IS:2715, Steel parts such as angles, channels etc as per approved darwing , 2 Nos Horizontal Double Break Air Break Switches 11kV, 400Amps, 2 Nos GODO Switches, LA sets , ACSR Conductor, Pin and Strain Insulators, Cable Supports Earthing Strips, Extended handles for Air Break Switches along with Rods, hardware, nuts and bolts, PCC foundations (1:3:6) . The Contractor to get the General Arrangement and makes of equipments, drawing approved before execution from department and Architect/Consultant.
Supply, Erection, Testing and Commissioning of ONAN 1600 kVA 11kV/433V step down Transformer , 3 phase, 50 Hz, 11kV/433Vs,solidly earthed system, vector group Dyn-11, with On Load Tap changer having a voltage correction range of +5% to -15% on 11kV side of Transformer along with Remote tap Changer Panel, Automatic Voltage Regulator. The Transformer shall be copper wound , natural air cooled, having termination arrangement of cables of 11kV and 433V side . The losses of transformer shall be as per latest/ existing Energy Conservation Building Code(ECBC) rule and BEE Guidelines .Make of Transformer : Schneider/Areva/ABB/GE/Legrand/Voltamp Make of OLTC : CTR/OLG.The Transformer shall be base mounted on a RCC ( 1:2:4) foundation. Civil works mentioned above for Transformer mounting and chain link fence not is scope of this item and shall be done under civil works scope. OLTC make : OLG/CTR.
Supply, Erection, Testing and Commissioning of ONAN 1000 kVA 11kV/433V step down Transformer , 3 phase, 50 Hz, 11kV/433Vs,solidly earthed system, vector group Dyn-11, with On Load Tap changer having a voltage correction range of +5% to -15% on 11kV side of Transformer along with Remote tap Changer Panel, Automatic Voltage Regulator. The Transformer shall be copperwound , natural air cooled, having termination arrangement of cables of 11kV and 433V side . The losses of transformer shall be as per latest/ existing Energy Conservation Building Code(ECBC) rule and BEE Guidelines .Make of Transformer : Schneider/Areva/ABB/GE/Legrand/Voltamp Make of OLTC : CTR/OLG.The Transformer shall be base mounted on a RCC ( 1:2:4) foundation. Civil works mentioned above for Transformer mounting and chain link fence not is scope of this item and shall be done under civil works scope. OLTC make : OLG/CTR.
Making Cable trench using RCC of suitable mix as per design including mounting of 600mmx100mm Hot dip Galvanised steel wiremesh cable trays ( OBO/Legrand/Rittal) makes and supports inside the cable trench as per approved section and cable trench route. Job also includes making of RCC covers/ Steel covers for trench , proper drainage system for cable trench, strip earthing of cable trays
Bee Kay Protection Systems
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.66 MB
BOQ_174218.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .