GE (AF) Jodhpur
REPAIR/MAINT OF FIRE ALARM PANEL, CRANES AND OTHER E/M ASSETS IN TECHNICAL AREA AT AF STN JODHPUR
2021_MES_436266_1
8453/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) Jodhpur
As per NIT
6 documents required · 6 mandatory
₹500
GE (AF) Jodhpur
Exempted
22 May 2021
14 Apr 2021
12 May 2021
14 Apr 2021
10 May 2021
28 Apr 2021
Amount
Supply and fixing in repairs 12 Volt 7AH capacity Battery suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs 12 Volt 36AH capacity Battery suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs Power Supply/SMPS suitable for conventional Fire Alarm Panel complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs Power Supply/SMPS suitable for addressable Fire Alarm Panel complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs Complete Main Control Card (Mother Card) suitable for addressable fire alarm panel for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs Zone Card with complete IC suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs non addressable type Photo Electric Smoke/heat Detector suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs addressable type Photo Electric Smoke/heat Detector suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs Manual Call Point (Pill Box, Aluminium Body) suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs addressable type Manual Call Point (Pill Box, Aluminium Body) with extra key suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs Hooter capable to work on 24 DC Volt suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs addressable type Hooter with indicator light capable to work on 24 DC Volt suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs Response Indicator (RI) suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs Complete FIRE ALARM PANEL non addressable type 04 zone with all accessories conventional type suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs Complete FIRE ALARM PANEL non addressable type 08 zone with all accessories conventional type suitable for Automatic Fire Detection & Alarm System complete all as specified and directed by the Engineer in charge.
Material and labour for rewiring of faulty area of fire alarm system zone wise, rewiring with 1.5 Sqmm (nominal area) PVC insulated and PVC unsheathed FRLS cable, stranded copper conductor with and including steel rigid conduit 20 mm dia medium grade ISI marked with all fittings and accessories complete all as specified & directed by Engineer-in-Charge.
Material and labour for general servicing of over head crane of capacity up to 2 Ton capacity (hand operated crane) with suitable T&P and replacement all connected deffective spare parts of crane and re-assembeling with necessary electric connections including greasing, gear box maintenece, chain pulley, color coating, crane rail allignment, chain replacement and all connecting items for fully operational cranes etc including load testing in presence of engineer in charge. Note :- Contractor shall rectify the problem within 4 days from receipt of complaint from engr-in-charge, panelty for not attending the complaint shall be 3% of quoted rate per day.
Material & labour for replacement of top lever with suitable machanical arrangement, suitable for crane capacity up to 2 Ton complete all as specified and directed by the Engineer in charge.
Material & labour for replacement of master lock with suitable machanical arrangement, suitable for crane capacity up to 2 Ton complete all as specified and directed by the Engineer in charge.
Material & labour for replacement of BEARING SET with suitable machanical arrangement, suitable for crane capacity up to 2 Ton complete all as specified and directed by the Engineer in charge.
Material & labour in replacement of loading chain for wheel of existing crane of suitable size with suitable machanical arrangement, suitable for crane capacity up to 2 Ton complete all as specified and directed by the Engineer in charge.
Material & labour for replacement of pull chain for wheel of existing crane of suitable size with suitable machanical arrangement, suitable for crane capacity up to 2 Ton complete all as specified and directed by the Engineer in charge.
Material & labour for replacement of steel side plate with suitable machanical arrangement, suitable for crane capacity up to 2 Ton complete all as specified and directed by the Engineer in charge.
Repair / maintenance of unserviceable electrically operated crane of capacity upto 2 Ton with suitable T&P and painting of crane replacement all connected deffective spare parts of crane and re-assembeling with necessary electric connections, fully blocking of leakage of hydraullic oil etc, including load testing in presence of engineer in charge complete all as specified and directed by the Engineer in charge.
Material & labour for replacement of EOT electric panel wiring including heavy duty contactor (upto 125A) , relay, fuse replacement with suitable electrical arrangement, suitable for crane capacity up to 2 Ton complete all as specified and directed by the Engineer in charge.
Material & labour for replacement of EOT limit switch, suitable for crane capacity up to 2 Ton complete all as specified and directed by the Engineer in charge.
Material & labour for repair and general servicing of EOT gear box with bushing and break oil, suitable for crane capacity up to 2 Ton complete all as specified and directed by the Engineer in charge.
Material & labour for repair and general servicing of gear box suitable for 7.5 HP electric motor for both side hanger door including painting complete all as specified and directed by the Engineer in charge.
Material & labour for replacement of gear box chain of suitable size as on site for 7.5 HP electric motor for both side hanger door complete all as specified and directed by the Engineer in charge.
Material & labour for rewinding of 7.5 HP motor by opening the motor, taking out burnt out winding and rewinding of motor with super enamelled copper conductor of same gauge and size as per existing, varnishing, heat drying inclujding scrappin of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and tested and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for rewinding of 10 HP motor by opening the motor, taking out burnt out winding and rewinding of motor with super enamelled copper conductor of same gauge and size as per existing, varnishing, heat drying inclujding scrappin of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and tested and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for rewinding of 10 HP to 12.5 HP motor of jocky pump or mud pump by opening the motor, taking out burnt out winding and rewinding of motor with super enamelled copper conductor of same gauge and size as per existing, varnishing, heat drying inclujding scrappin of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and tested and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for rewinding of 5 HP motor by opening the motor, taking out burnt out winding and rewinding of motor with super enamelled copper conductor of same gauge and size as per existing, varnishing, heat drying inclujding scrappin of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and tested and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for rewinding of 7.5 HP to 12 HP submersible pump set by opening the motor, taking out burnt out winding and rewinding of motor with super enamelled copper conductor of same gauge and size as per existing, varnishing, heat drying inclujding scrappin of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and tested and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for rewinding of 1 HP to 3 HP motor by opening the motor, taking out burnt out winding and rewinding of motor with super enamelled copper conductor of same gauge and size as per existing, varnishing, heat drying inclujding scrappin of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and tested and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for rewinding of 7.5 HP to 12 HP fountain pump by opening the motor, taking out burnt out winding and rewinding of motor with super enamelled copper conductor of same gauge and size as per existing, varnishing, heat drying inclujding scrappin of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and tested and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for dismantling the WORM GEAR UNIT, Ratio 30:1, Model AU overhauling the same by repair/replacing the defective parts as ordered, cleaning varnishing and drying, re-erecting, aligning with the motor, testing and commissioning, any other minor parts required for proper functioning, painting the unit with two coats of synthetic enamel paint after preparing the surface and replacement of worn out nut bolts, stud of gland capacity complete all as directed by Engineer-in-Charge
Material & labour for general servicing of 100 HP centrifugal pumpset with electric motor including replacement of worn out impellers-01 set with bronze impellers, replacing bearing-02 Nos, replacement of worn out bearing housing, replacement of gland bush , unserviceable nut bolts and washers and bringing back the pump to the pump house re-assembling with motor and foundation and testing and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for General servicing of 75 to 100 HP diesal engine used in fire fighting including engine oil change, diesal and oil fielter change, radiator cleaning, coolant chage , air fielter replacement, cleaning of diesal tank, general servicing of DG set self and testing and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for general servicing of 75 HP centrifugal pumpset with electric motor including replacement of worn out impellers-01 set with bronze impellers, replacing bearing-02 Nos, replacement of worn out bearing housing, replacement of gland bush, unserviceable nut bolts and washers and bringing back the pump to the pump house re-assembling with motor and foundation and testing and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for general servicing of 7.5 HP to 10 HP centrifugal pumpset with electric motor including replacement of worn out impellers set with bronze impellers, replacing bearing, replacement of worn out bearing housing, replacement of gland bush, unserviceable nut bolts and washers and bringing back the pump to the pump house re-assembling with motor and foundation and testing and make it functional to the entire satisfaction of the Engineer in Charge.
Material & labour for general servicing of 5 HP centrifugal pumpset with electric motor including replacement of worn out impellers set with bronze impellers, replacing bearing, replacement of worn out bearing housing, replacement of gland bush, unserviceable nut bolts and washers and bringing back the pump to the pump house re-assembling with motor and foundation and testing and make it functional to the entire satisfaction of the Engineer in Charge.
Supply and fixing in repairs DC electric motor gear box upto 2.5 HP capacity with megnatic coupling of electric motor, for hanger door complete etc complete all as specified and directed by the Engineer in charge
General servicing of unserviceable hydaullic operated crane of capacity upto 1 Ton with suitable T&P and painting of crane replacement all connected deffective spare parts of crane and re-assembeling with necessary electric connections testing at LDP lab area, fully blocking of leakage of hydraullic oil etc for fully operational cranes including load testing in presence of engineer in charge complete all as specified and directed by the Engineer in charge.
Supply and fixing in repairs single pointed air termination aluminium rod 12mm dia 300mm long complete all as specified and directed by Engr-in-Charge
Material & labour in repairs 40 mm bore galvanised steel tubing, light grade, 1.50 m long with MS plate of minimum 3 mm thick welded as base for fixing of air termination rod including thrust block complete as specified and directed by engr in charg
Material & labour for precast cement concrete 1:2:4 type B1 (Using 20 mm graded stone aggregate) block masonry with solid blocks, exceeding 10 cm in width and setting in cement mortar 1:6, for fixing/ mounting of running earthing conductor complete all as specified and as directed by the Engr-in - Charge.
Material & labour in repairs earthing complete with galvanised steel earth electrode 60cmx60cmx6mm buried directly in ground vertically to depth not less than 2.25m below normal ground level with top edge of the earth plate at a depth not less than 1.5m below ground level connected to and including GI earth strip 32mm x 6 mm, by means of nuts, bolts, check nuts and washer etc, made of GI and connected to test point and earth dolly all as shown in electrical plate No. 3 SSR Part-I 2009 and specified or indicated including excavation and earthwork in any type of soil PCC (1:3:6) Type C1 in chamber, precast RCC 50 mm thick in cement concrete (1:2:4) type B1, reinforced with welded steel wire fabric or XPM (Weight not less than 4.00 Kg/Square metre) with cast iron frame, funnel with wire mesh, 20mm bore medium grade GI watering pipe, lugs, 40 mm bore medium grade GI protection pipe, test point etc. complete all as specified and directed. NOTE :- The rate of above Item includes the cost of earth lead and GI protection pipe up to 7.5 Metres. GI strip beyond 7.5 Metre shall be measured and paid for separately.
Material & labour in repairs for earthing complete with copper earth plate electrode 60cm x 60cm x 3.15 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to and including earth lead of copper strip 20 mm X 3 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion and excavation and earth work in any type of strata, PCC 1:3:6 type C1 in chamber, precast RCC cover 50mm thick in cement concrete 1:2:4 type B1, reinforced with welded steel wire fabric or XPM (Weight not less than 4 Kg/Sqm) with cast iron frame, funnel with wire mesh, 20mm bore GI pipe medium grade watering pipe, lugs, 40mm bore GI pipe medium grade protection pipe up to 7.5m complete all as specified and directed by the Engineer-in-Charge NOTE :- The rate of above Item includes the cost of earth lead and GI protection pipe up to 7.5 Metres. Copper strip beyond 7.5 Metre shall be measured and paid for separately.
SMaterial & labour in replacement copper strip 20mmx3mm complete with, protection sleeves, saddles, seperator and fixing screws at surrounding inside and outside the building complete all as specified and directed by the Engineer-in-Charge.
Material & labour for replacement of aluminium strip 25mmx3mm complete with, protection sleeves, saddles, seperator and fixing screws at surrounding inside and outside the building complete all as specified and directed by the Engineer-in-Charge.
Supply and fixing in repairs 150 mm bore cast iron sluice valve heavy duty, class PN 1.6 flanged ends any pattern with head wheel and bras spindle ISI marked, conforiming to IS 780 with jointing material, flanged joint rubber gasket 6mm thick nuts, MS nuts, bolts, washers, rubber flange complete all as specified and as directed by the Engr-in - Charge.
Supply and fixing in repairs 100 mm bore cast iron sluice valve heavy duty, class PN 1.6 flanged ends any pattern with head wheel and bras spindle ISI marked, conforiming to IS 780 with jointing material, flanged joint rubber gasket 6mm thick nuts, MS nuts, bolts, washers, rubber flange complete all as specified and as directed by the Engr-in - Charge.
Supply and fixing in repairs CI reflux valve of size 150mm dia bore with bypass arrangement complete all as specified and as directed by the Engr-in - Charge.
Supply and fixing in repairs pressure differential switches universal type with wiring etc complete all as specified and as directed by the Engr-in - Charge.
Supply and fixing in repairs 25 mm dia Auto Air Surge and Drain valve for water piping complete all as specified and as directed by the Engr-in - Charge.
Supply and fixing in repairs rubber/tyre coupling of pumping set of 100 HP complete all as specified and directed by the Engr - in Charge.
Supply and fixing in repairs rubber/tyre coupling of pumping set of 75 HP complete all as specified and directed by the Engr - in Charge.
Supply and fixing in repairs rubber/tyre coupling of pumping set of 5 to 7.5 HP complete all as specified and directed by the Engr - in Charge.
Material & labour for replacement of water pressure gauge 0-7 kg / cm2 any type Make Febig or equivant suitable makes as per appx 'B' complete all as specified and as directed by the Engr-in Charge.
Material & labour for replacement of Indicating Light, 240V AC, LED Type Red, Yellow, Blue complete all as specified and as directed by the Engr-in Charge..
Material & labour for replacement of ON/OFF Push Button complete all as specified and as directed by the Engr-in Charge.
Material & labour for replacement of Timer GIC star/delta complete all as specified and as directed by the Engr-in Charge.
Material & labour for replacement of star delta starter used in mud pumps, fountain pumps of capacity 5 HP complete all as specified and as directed by the Engr-in Charge.
Material & labour for replacement of star delta starter used in mud pumps, fountain pumps of capacity 7.5 HP to 10 HP complete all as specified and as directed by the Engr-in Charge.
Material & labour for General servicing and calliberation of fire Fighting system panel of capacity of pump 100 HP with complete testing of power supply cable including lug connection, contactor trip circuit, measuring meter calliberation, No NC point cleaning, complete control wiring repair, relay and trip circuit, maint and all connected accessories regarding serviceability of fire fighting system and testing of system in presence of and upto the entire satisfaction of Engr in charge.
Supply and fix in replacement GI pipe medium grade 100 mm dia, on wall, by suitable arrangement of clamps and other connected items Complete all as specified and directed.
Supply and fix in replacement GI pipe medium grade 50 mm dia, in ground Complete all as specified and directed.
Supply & fixing butterfly valve of 50 mm size Complete all as specified and directed.
General servicing and routine check up of passenger lift of capacity of 5 person by manufacturers's Service Engineer/Authorised channel partner/ OEM, for every Quarter or any unserviceability of lift to ensure the serviceability of lift cosisting of following Job:- 1) it will provide emergency services for break down as and when required on priority basis. 2) user complain will be attended on priority basis. 3) time to time general check up of the lift during contract period. Note:- (a) For servicing contractor will provide manufacturer service engineer for passenger lift and testing of the same in the presence of engineer in charge. (b) Items to be replaced in general servicing shall be paid as supply only.
Supply only SMPS 24 V as existing at site Complete all as specified and directed.
Supply only SMPS 12 V as existing at site Complete all as specified and directed.
Supply only battery charger 48V as existing at site Complete all as specified and directed.
Supply only door sensor as existing at site Complete all as specified and directed.
Supply only CVT transformer of 24V as existing at site Complete all as specified and directed.
Supply only limit switch as existing at site Complete all as specified and directed.
Supply only PBX system 3 line 1 outgoing Complete all as specified and directed.
Supply only heavy duty contactor used in lift upto 40A Complete all as specified and directed.
Supply only FLOOR sensor Complete all as specified and directed.
Supply only LIFT INDOOR LIGHT Complete all as specified and directed.
Supply only LIFT INDOOR EXHAUST FAN Complete all as specified and directed.
General servicing of Automated vertical storage & retrieval system (Lean lift) by by manufacturers's Service Engineer/Authorised channel partner/ OEM in the presence of engineer in charge consisting of jobs as under :- (a) Mechanical maintenance:- 1)Retriever levelling and allignment 2) Guide wheel alignment 3) checking of laoding runners oil 4) Pushers positioning user manual mode 5) checking of bolted joints 6) checking of chain tension 7) checking of break adjustment 8) checking of gear box oil level 9) Lubrication of chains (b) Electrical Jobs:- 1) checking & cleaning of all contacts 2) checking of looser wire connection 3) checking of limit switches (c) Electronic Jobs:-checking and cleaning of all PCBs, checking of sensors, checking of relay functioning. (d) Software Jobs:- upgradation in PLC programme and user interface. Note:- (i) Each job consists general servicing as described above for one lift. (ii) Major items to be replaced in general servicing shall be paid as supply only. 2. Replacement of minor items / spares shall deemed to be included in the above items & not to be paid separately.
Supply only NPN/PNP sensor Complete all as specified and directed.
Supply only magnetic sensor Complete all as specified and directed.
Supply only UPS of 1 KVA capacity for lean lift complete all as specified and directed by the Engineer-in-Charge.
Supply only DS2 Area sensor Ht -844mm analog O/P Make:-Banner or equivellent
Supply only Height curtain sensor PLCP1-780-A2-V1
Supply only machanical spare part kit (pushers, bolts, tray moulds, rollers, main runners, loading runners, diamond chains, spockets, auto door sliding system etc)
Material and labour for general servicing of moving target shooting system including cleaing of movement rail, pulley cleaning and greasing, servicing of control panel, cleaning of movement area of target etc complete all as specified and as directed by the Engr-in Charge.
Material and labour for rewinding of DC electric motor of single phase 1.5 HP geared motor used in moving target shooting system with same existing copper winding wire including replacement of bearing, carbon bushes and all other accessories complete all as specified and as directed by the Engr-in Charge.
Supply & Fixing in replacement of limit switch used for rolling of wire rope over it Complete all as specified and directed by the Engineer-in-Charge.
Supply and fixing in replacement of support pully of suitable size used for rolling of wire rope over it Complete all as specified and directed by the Engineer-in-Charge.
Material and Labour for Repair to gear box used in EOT crane of 02 ton capacity including replacement of worn out gear part complete all as specified and directed by the Engineer-in-Charge.
Repair to existing ELECRTONIC THYRISTOR MODULE or without thyristor module TYPE automatic / manual type APFC panel including painting of APFC panel, cleaning of dust inside the panel from electric blower cleaning of contractors, relays junction points / connectors servicing overhauling of cooling fan complete testing of APFC relay including necessary setting with CTs load adjustment to match with replacement of U/S parts of capacity 5 KVAR to 200 KVAR to set the power factor in range between 0.96 to 0.990 complete all as directed as specified by Engr in Charge. Note : 1. Replacement of U/S items which are covered under respective items of BOQ shall be measured & paid separetely. 2. Replacement of minor items / spares shall deemed to be included in the above items & not to be paid separately.
Supply and fixing in replacement of contactor capacitor heavy duty type 3 pole AC of capacity having coil voltage 250 volt upto 10 KVAR along with 1 No + 1 NC auxilary contact complete all as directed as specified by Engr in Charge.
Supply and fixing in replacement of contactor capacitor heavy duty type 3 pole AC of capacity having coil voltage 250 volt upto 25 KVAR along with 1 No + 1 NC auxilary contact complete all as directed as specified by Engr in Charge.
Supply and fixing in replacement of contactor capacitor heavy duty type 3 pole AC of capacity having coil voltage 250 volt upto 40 KVAR along with 1 No + 1 NC auxilary contact complete all as directed as specified by Engr in Charge.
Supply & fix in repairs APFC relay/PLC source type with protection device intelligent automatic processor has on electric controller unit up to 12 stage for contactor type APFC panel complete all as specified and directed by Engr-in-Charge. Make as existing at site
Supply & fix in repairs APFC relay/PLC source type with protection device intelligent automatic processor has on electric controller unit up to 12 stage for thyrister based panel complete all as specified and directed by Engr-in-Charge. Make as existing at site
Supply & fix in repairs CT coil suitable for amp meter 100/5 amp ratio, accurracy Class-I complete all as specified and directed by Engr-in-Charge. make AE/ ENERCON/ EPCOS,
Supply & fix in repairs CT coil suitable for amp meter 200/5 amp ratio, accurracy Class-I complete all as specified and directed by Engr-in-Charge. make AE/ ENERCON/ EPCOS,
Supply and fixing in repairs existing ELECRTONIC THYRISTOR MODULE of each APFC PANEL 3 pole / 4 pole AC, of capcity having coil voltage 250 volt upto 10 KVAR along with 1 No + 1 NC auxilary contact complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repairs existing ELECRTONIC THYRISTOR MODULE of each APFC PANEL 3 pole / 4 pole AC, of capcity having coil voltage 250 volt above 10 KVAR and upto 20 KVAR along with 1 No + 1 NC auxilary contact complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repairs existing ELECRTONIC THYRISTOR MODULE of each APFC PANEL 3 pole / 4 pole AC, of capcity having coil voltage 250 volt above 20 KVAR and upto 50 KVAR along with 1 No + 1 NC auxilary contact complete all as specified and directed by Engr-in-Charge.
Supply and fixing in repairs capacitor 440 volts 50 HZ electric complete of capacity 10 KVAR (Bottle type ) gas filled complete all as specified and directed by Engr-in-Charge
Supply and fixing in repairs capacitor 440 volts 50 HZ, ULTRA HEAVY DUTY complete of capacity 12.5 KVAR (Bottle type ) gas filled complete all as specified and directed by Engr-in-Charge
Supply and fixing in repairs capacitor 440 volts 50 HZ, ULTRA HEAVY DUTY complete of capacity 15 KVAR (Bottle type ) gas filled complete all as specified and directed by Engr-in-Charge
Supply and fixing in repairs capacitor 440 volts 50 HZ, ULTRA HEAVY DUTY complete of capacity 20 KVAR (Bottle type ) gas filled complete all as specified and directed by Engr-in-Charge
Supply and fixing in repairs capacitor 440 volts 50 HZ, ULTRA HEAVY DUTY complete of capacity 25 KVAR (Bottle type ) gas filled complete all as specified and directed by Engr-in-Charge
Supply and fixing in repairs capacitor 440 volts 50 HZ, ULTRA HEAVY DUTY complete of capacity 7.5 KVAR (Bottle type ) gas filled complete all as specified and directed by Engr-in-Charge
Supply and fixing in repairs capacitor 440 volts 50 HZ, ULTRA HEAVY DUTY complete of capacity 5 KVAR (Bottle type ) gas filled complete all as specified and directed by Engr-in-Charge
Supply and fixing in repairs of SCRs used in thyrister switching suitable for 100 KVAR APFC panel complete all as specified and directed by engr in charge
Supply and fixing in repairs of SMPS 220 V AC input and 24 V DC output and used in APFC panel complete all as specified and directed by engr in charge.
Supply and fixing in repairs MCB TP 450 volts 10 KA 'C' curve type of capacity 32 amp complete all as specified and directed by engr in charge
Supply and fixing in repairs MCB TP 450 volts 10 KA 'C' curve type of capacity 63 amp complete all as specified and directed by engr in charge
Supply and fixing in repairs fountain water distribution chamber for 10 HP water pump complete all as specified and directed.
Supply and fixing in repairs hose pipe of 40mm size used in fountain complete all as specified and directed.
Excavation in trenches not exceeding 1.5 metres wide and not exceeding 1.5 metres in depth for foundation etc or for laying of cables, errection of poles, struts / stays etc not exceeding 10 Sqmm on plan and getting out in any type of soil complete all as specified and directed by the Engineer-in-Charge.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soil complete all as specified and directed by the Engineer-in-Charge.
Removing excavated materials to a distance not exceeding 50 m and depositing where directed, at a level not exceeding 1.5 m above the starting point complete all as specified and directed by the Engineer-in-Charge.
Material and labour in replacement of steel wire rope of 4mm size complete all as specified and directed by the Engineer-in-Charge.
Shri Electrical Enterprises
Om Trading Corporation
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .