| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.8 CrAdmitted-Finance | ₹3.8 Cr | L1 | Admitted-Finance |
| 2 | L2₹3.8 Cr+₹25,315 (0.07%)Admitted-Finance T STATE BANJARAWALA DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | ₹3.8 Cr+₹25,315 (0.07%) | L2 | Admitted-Finance |
| 3 | L3₹3.9 Cr+₹48,320 (0.13%)Admitted-Finance | ₹3.9 Cr+₹48,320 (0.13%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | SAINKO SYSTEMS L3 | SHREE BALAJI ASSOCIATES L2 | SHUBHAM TRADERS L1 |
|---|---|---|---|---|---|---|
| 1.00MV CABLES | ||||||
| 2.00Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/DWC pipe as required. | ||||||
| 3.00 | Upto 35 sq. mm | 2,405 | Mtr | 39 ₹93,795 | 38 ₹91,390 Lowest | 38 ₹91,390 Lowest |
| 4.00 | Above 35 sq. mm and upto 95 sq. mm | 850 | Mtr | 61 ₹51,850 | 59 ₹50,150 Lowest | 59 ₹50,150 Lowest |
| 5.00 | Above 95 sq. mm and upto 185 sq. mm | 495 | Mtr | 81 ₹40,095 | 80 ₹39,600 Lowest | 80 ₹39,600 Lowest |
| 6.00 | Above 185 sq. mm and upto 400 sq. mm | 50 | Mtr | 141 ₹7,050 | 139 ₹6,950 Lowest | 139 ₹6,950 Lowest |
| 7.00Supply, connection, testing and commissioning of heavy duty, medium voltage, XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified. The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge. The scope shall include: 1) Supply of Cables.(With Non Returnable Drums) 2) Delivery of the cables at site. 3) Unloading at site store. 4) Shifting of cable from site store to place of installation. 5) Connection of cable with proper tagging as specified ni specifications. 6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely. 7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. 8) Testing of insulation and continuity of cable and submission of reports to the client's representative. 9) To prepare submission drawing and to take approval of consultant at each stage. 10) To prepare & submit as-built drawing and handing over document to end user. 11) Rate shall be inclusive of route markers at 15mtr intervals 12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written. | ||||||
| 8.00 | 3.5C x 300 Sq.mm. Aluminum XLPE armored cable | 50 | Mtr | 3,668 ₹1,83,400 | 3,664 ₹1,83,200 Lowest | 3,664 ₹1,83,200 Lowest |
| 9.00 | 3.5C x 185 Sq.mm. Aluminum XLPE armored cable | 165 | Mtr | 2,338 ₹3,85,770 | 2,336 ₹3,85,440 Lowest | 2,336 ₹3,85,440 Lowest |
| 10.00 | 3.5C x 150 Sq.mm. Aluminum XLPE armored cable | 310 | Mtr | 1,850 ₹5,73,500 | 1,846 ₹5,72,260 Lowest | 1,846 ₹5,72,260 Lowest |
Tender Value
₹3.8 Cr
EMD Value
₹7.7 L
Closing Date
24 Oct 2025, 3:00 pmClosed
DGM HQ BRIDCUL
BRIDCUL Opp Govt ITI Niranjanpur Saharanpur Road Dehradun
Electrical and Allied works for Overall Infrastructure at Mahasu Devta Hanol Uttarakhand
2025_BRID3_88056_1
2212/BRIDCUL/986/25 Dated 04.10.2025
Open Tender
Electrical Works
Item Rate
540 days
Mahasu Devta Hanol
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,900
MD - BRIDCUL
₹7.7 L
BRIDCUL Dehradun
25 Oct 2025
13 Oct 2025
24 Oct 2025
13 Oct 2025
24 Oct 2025
17 Oct 2025
16 Oct 2025
Amount
MV CABLES
Laying of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL/DWC pipe as required.
Upto 35 sq. mm
Above 35 sq. mm and upto 95 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Supply, connection, testing and commissioning of heavy duty, medium voltage, XLPE (IS 7098 - PART-II) insulated, Stranded AL / Cu conductor Armoured / Flexible cables as per specification & IS. The cable shall have outer sheeth of XLPE and inner sheath of PVC with stranded AL conductor wherever specified. The cable shall be laid underground in excavated trench / prepared trench / hume pipes when laid outside the building. Cable shall be laid throught preapred trench / cable tray / duct / hume pipe / channel / floor trunks etc when laid inside the building as instructed by PMC/Site Incharge. The scope shall include: 1) Supply of Cables.(With Non Returnable Drums) 2) Delivery of the cables at site. 3) Unloading at site store. 4) Shifting of cable from site store to place of installation. 5) Connection of cable with proper tagging as specified ni specifications. 6) Supply & fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely. 7) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. 8) Testing of insulation and continuity of cable and submission of reports to the client's representative. 9) To prepare submission drawing and to take approval of consultant at each stage. 10) To prepare & submit as-built drawing and handing over document to end user. 11) Rate shall be inclusive of route markers at 15mtr intervals 12) Each run of cable to be tested with 1KV meggar 13) Proper cables tags of Aluminium shall be made and feeder shall be written.
3.5C x 300 Sq.mm. Aluminum XLPE armored cable
3.5C x 185 Sq.mm. Aluminum XLPE armored cable
3.5C x 150 Sq.mm. Aluminum XLPE armored cable
3.5C x 120 Sq.mm. Aluminum XLPE armored cable
3.5C x 95 Sq.mm. Aluminum XLPE armored cable
3.5C x 70 Sq.mm. Aluminum XLPE armored cable
3.5C x 50 Sq.mm. Aluminum XLPE armored cable
3.5C x 35 Sq.mm. Aluminum XLPE armored cable
3.5C x 25 Sq.mm. Aluminum XLPE armored cable
4C x 4 Sq.mm. CU XLPE armored cable
4C x 6 Sq.mm. CU XLPE armored cable
4C x 16 Sq.mm. CU XLPE armored cable
3C x 4 Sq.mm. CU XLPE armored cable
3C x 2.5 Sq.mm. CU XLPE armored cable
Supplying and making end termination with brass compression gland and Copper lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required.
3.5C x 300 Sq.mm. Aluminum XLPE armored cable
3.5C x 185 Sq.mm. Aluminum XLPE armored cable
3.5C x 150 Sq.mm. Aluminum XLPE armored cable
3.5C x 120 Sq.mm. Aluminum XLPE armored cable
3.5C x 95 Sq.mm. Aluminum XLPE armored cable
3.5C x 70 Sq.mm. Aluminum XLPE armored cable
3.5C x 50 Sq.mm. Aluminum XLPE armored cable
3.5C x 35 Sq.mm. Aluminum XLPE armored cable
3.5C x 25 Sq.mm. Aluminum XLPE armored cable
4C x 4 Sq.mm. CU XLPE armored cable
4C x 6 Sq.mm. CU XLPE armored cable
4C x 16 Sq.mm. CU XLPE armored cable
3C x 4 Sq.mm. CU XLPE armored cable
3C x 2.5 Sq.mm. CU XLPE armored cable
Supply, installation, testing and commissioning following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) - 8way, Double door (IP43, IK09)
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way (4 + 18), Double door (IP43, IK09)
Supplying and fixing following rating, four pole, 415 volts, MCB in the existing MCB DB/enclosure complete with connections, testing and commissioning etc. as required. 25A
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal encloused plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A 240 V "B" curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A Double pole
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25A
Supply, installation, testing and commissioning 'C' series, SP MCB Supply, installation, testing and commissioning 5 amps to 32 amps rating, 240 volts, 'B' series, miniature circuit breaker suitable for lighting and other loads of folloeing poles int the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Point wiring in PVC conduit, with modular type switch: Wiring for light point/ fan ponit/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with modular switch, modular plate, suitable Gl box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc.as required- Group C
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point (without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, onnection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 & 15/16A amps modular socket outlet and 15/16 amps modular switch, onnection, painting etc. as required. (For light plugs to be used in non residential buildings).
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
Supplying and fixing stiff pendent with 300 mm long, 20 mm dia X 1.6 mm thick steel conduit, aluminium cast back plate and brass holder complete, including wiring the down rod with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and painting etc. as required.
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required.
2X1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 2.5 sq. mm + 1X2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 10 sq. mm + 1 X 6 sq. mm earth wire
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
Supply, installation, testing and commissioning of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
S/L SWG GI wire in ground: Supplying and laying 6 SWG G.I. wire at 0.50 metre below ground level for conductor earth electrode, including soldering etc. as required
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Earthing with GI earth plate 600 mm x 600 mmx 6 mm thick including accessories and providing masonary enclouser with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcole/coke and salt as required.
20W, 2000 Lumen, IP20 4FT Wall/Ceiling mounted LED light fixtures: 20W, 2000 Lumen, IP20 4FT Wall/Ceiling mounted LED light fixtures complete with suitable rating lamps and all other necessary accessories to complete the installations as per specifications. * Minimum lumen 2000 Lumens in CCT range of 3000/4000 as per ANSI,LED with LM80 report to be submitted at the time of Supply , life of 50000 burning hours with 70% of initial lumens maintained. * Colour of light fixture shall be WHITE as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
25x50mm Linear light fixture-10watts per meter- 10x60 deg- CCT : 3000K: Supply of Customized exterior rated wall mounted 25x50mm Linear light fixture with antiglare visor mounting without bracket, Wattage - 10 watts per meter, Beam Angle - 10X60deg, IP-66, Life of fixture L70 @Ta-35 deg C should be at least 50,000 burning hours. CCT - 3000K, Suitable driver/controller. (All the technical parameters of the luminaire need approval from the lighting consultant) With Driver * Colour of light fixture shall be Matt Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Wall Washer in ground Supply, laying, connection and testing of Wall Washer in ground , 10Watts LED, IP65/IP66. CCT: 2700/3000 K * Colour of light fixture shall be Matt Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Wall Recessed LED Step Light : (FOOT LIGHT) Supply,Installation, Testing and Commmisioning of IP65/IP66, IK10 protected Step Light Fixture. Fixture made of powder coated die cast alluminium with Toughened Glass cover and appropriate beam angle lens to be used as per requirement. The System level Luminous efficacy must be >90 Lumen/W. High Power LEDs at 1W/2W per LED. The driving current should be Minimum 350 mA per LED. CRI>70, CCT: 2700/3000 K. The integral electronic driver must be constant current and surge protection of min. 4KV(L-N) and efficiency >85%, PF>0.95 and input Voltage range of 90-270V AC at 50Hz. System life of 50000 Burning hours with 70% of Initial Lumens maintained. Light should include quick connecting cable coupled with various mounting accessories. Light output in Cool white or Warm White Colour as per engineers choice. Fixture must be in compliance with BIS * Colour of light fixture shall be Matt Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Landscape Bollard Supply, laying, connection and testing of Landscape Bollards 15Watts Bollard LED, IP65/IP66, 800/100mm. CCT: 2700/3000 K * Colour of light fixture shall be Matt Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
FIXTURE - 60W Power Module LED POST TOP: Supply, Installation, assembling, connection, testing & commissioning of post top light fixture equivalent to LED FIXTURE - 40-45W Power Module LED, -MOUNTED AT 4 METER HEIGHT POST TOP POLE, CCT: 2700/3000 K, THD <10 % :it's - Upper frame made in die-cast and sheet aluminium (thickness: 2.5mm), with threaded coupling G3/4" for fixing,Bottom frame with ring made in die-cast aluminium and two arms made in hotgalvanized steel, with flange for fixing equipped of a hole (diam. 28 mm) .Gasket between the upper and bottom frames.Painted with polyester powder coating in BLACK (As per Architectural requirement). IP Rating - IP65/IP66.Height –690mm, Dia - 550mm, Weight - 11.5Kg, Area Exposed to Wind(S) - 0.105 m2. Power LED's Module (with CREE/NICHIA/OSRAM/SEOUL SMD type LED’s with ESD=>8kV & Ceramic package are accepted. LED manufacturers tech sheet with buying documents should be submitted for verification. Individual LED's Minimum Luminous Flux (lm) is 139lm @ 350 mA (@ 85 °C) same should be supported by LED manufacturer's tech sheet) in compliance with IEC 62031(supporting type test report should be submitted), on Printed Circuit Board with metal core plate. Colour Rendering Index: Ra > 70. Electronic Power Supply for LED Module, which offers Protection against Short Circuit, Over- Voltage & Over- Current, with in-built surge protection upto 1.5kv(an additional surge protection device of 10kV also provided in-built the fixture). Optics with refractive lens (Polycarbonate), UV Resistant & Shock Resistance IK10.LM80 Reported LED Lifetime is L90@ 50,000hours minimum.(same should be supported by LM 80 report from NVLAP accredited lab) & Estimated LED Lifetime is L80 @ 100,000 hours(Ta-25°C) minimum..LM 80 report & TM 21 calculation should be submitted to support the same.The Light fixture shall be in compliance with IEC 60598-2-3; IEC 60598-1.(Supporting Test Report from NABL accredited Laboratory should be submitted) .LM79 report should be submitted from NABL accredited Laboratory. * Colour of light fixture shall be BLACK as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply, Installation, assembling, connection, testing & commissioning of ARCHITECTURAL POLE (FOR POST TOP LIGHTING) 6M height Pole (Total height of the pole is 4m including post top) Made in combination of hot dip galvanised mild steel pipe sections 114mm dia. & 140mm dia. Arch. cast iron Base design starts with min 322mm Dia. ring, radially tapers to 140 mm for a height of min 235 mm matching to the drawing. Total weight of the base is min 15 Kgs. Decorative Ring-1 (140/114mm dia. – min 3kgs.) & Top Ring (weight- 3kgs.) are made of cast iron. Entire pole shall be made to provide pleasing aesthetics as approved by Concerned Engineer in-charge. After Fabrication, Entire Pole is hot dip galvanized(60 microns Minimum ) for the effective corrosion resistance . The hot dip Galvanised pole should be provided with an inbuilt junction box (Concealed) to fix 32A connectors and 6A MCB (to terminate incoming and outgoing armoured cables with glands and lulgs), at the bottom -the inbuilt box should have a flush door of suitable size. The decorative pedastal to be mounted on a suitable size steel plate. This mounting steel plate along with foundation bolts of suitable size to be used for ensuring firm grouting into the specially designed RCC foundation. wind pressure calculation as per IS 875(part-3) & structural calculation report as per EN40 should be submitted to verify the pole design. Pole & it's parts are painted in 3 layer coating(coating thickness-100 microns minimum) in which 1st layer with etch primer, 2nd layer with epoxy primer & 3rd final layer with PU paint- customised colour Metallaic Black (As per Architectural requirement). Adequate size cutout with opeanable hinged door should be provided on pole with necessary gasket to ensure water tight arrangement for pulling cables and installation of mcb, connectors etc, complete in all respect as per requirement and instruction of engineer in charge. Scope also includes necessary foundation, cable termination, earthing as per requirement, cable entry pipes, 3 core round flexible wire from junction box to light fixture etc. all require to complete job. * Colour of Pole shall be Matt Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply, Installation , Testing and Commisioning of 120 W LED Flood Light for application , BIS approved , Body made of pressure Die cast aluminium with separate driver chamber for ease of maintenence, proper fins should be designed for better heat dessipation ,adjustable bracket should be provided to adjust the tilt of light , primary diffuser should be PMMA/PC Lenses for Better photometry and wide area coverage , The secondary diffuser should be clear toughned glass with IK08 protection . The luminaire is provided with internal surge protection of 4 KV .Fixture is having external surge protection of 10KV. Electronic potted driver having power factor>0.95, THD <10 % and input voltage range from 150-270V AC at 50Hz. Minimum lumen 13200 Lumens in CCT range of 2700/3000 K as per ANSI,LED with LM80 report to be submitted at the time of Supply , life of 50000 burning hours with 70% of initial lumens maintained.Ambient Operating Temperature is -10 Deg. to 50 Deg. Luminaire should Maintain Ingress Protection of IP65/IP66 for better weather proofing. * Colour of light fixture shall be Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supplying and fixing PVC batten/ angle holder including connections etc. as required.
Supply of exhuast fan (300mm)
Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required upto 450mm sweep.
JUNCTION BOXES
Supply, Transportation, Installation, testing and commissioning of IP 68 weather proof Outdoor type junction boxes with terminal block/connector.
Supply, Transportation, Installation, testing and commissioning of IP 68 weather proof Outdoor type junction boxes with terminal block/connector.
supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "bends" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray "Tee" (galvanisation not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc. , complete as required.
120 mm dia (OD-120 mm & ID-103 mm nominal)
200 mm dia (OD-200 mm & ID-175 mm nominal)
SITC of 315 mm dia (OD-315 mm & ID-271 mm nominal)
Providing & Laying of HDPE Pipe 32mm PE-80,PN6 direct in ground; to be laid 75-100cm below the ground level for drawing of cables including excavation and refilling the trench etc.as required, but excluding sand cushioning and protective covering,or G.I. conduit 32 mm dia( Heavy Duty) with concrete block 15cm X 15cm 1:2:4 with complete curing with splicing complete in all respect complete in all respect.
Supply, Installation, Testing & Commissiong of 5 MP IR Dome Camera 1/3″ Megapixel progressive scan Exmor CMOS, Infrared, Dome camera with D/N ICR, IR, varifocal lens, 2.8mm-12mm, F1.6, with Audio, H.264, IP66 rated 720p @ 25fps, H.264: 4–8192 kbps, BLC/HLC/DWDR, IR distance up to 30m, RJ-45 connection, Inbuilt microSD card slot, BLC/HLC/DWDR, 3D DNR, ROI, ONVIF, PoE Complete as per specification, IP66, IK10, Including necessary accessories for mounting * Colour of Camera shall be Black as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply, Installation, Testing & Commissiong of IP MFZ BULLET CAMERA Supply, Installation, Testing & Commissioning of IP Network TDN Low-Light IR Bullet Camera, 1/2.8" CMOS, 2 MP @ 25fps, Min. Illumination required 0.01 lux @ F1.4 (color), 120dB True WDR, Min. Pixels 1920 X 1080, triple stream, 2.7 -12 mm motorized focus and zoom lens, BLC, HLC, 3DNR, Privacy Mask, IR LEDs Smart IR with upto 50m IR distance, Dual channel Audio G.711a/G.711u/AAC, 128GB SD card support, Alarm: 2 In/ 1out, PoE, H.264 High Profile and MJPEG, Inbuilt analytics Trigger line/Intrusion/Loitering, PoE Class 3 and 12V DC, IP 67, IK 10 vandal proof, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S & Profile G compliant, UL, CSA 60950-22, CE (EN 50130-4 & EN 55022) , FCC Part 15 & RoHS compliant. Cyber Security PCI-DSS or equivalent Certified. * Colour of Camera shall be Black or as per Architectural requirements. * Contractor to submit samples for Approval before ordering the fixture.
Supply, Installation, testing and commissioning of 12 core OS1/OS2 - Loose tube outdoor/corrugated steel tape with multitube Jelly filled construction Crush Resistance 4000N with 11.5mm Diameter with cable attenuation dB/km 1310nm : 0.39, 1550nm : 0.25 & 1625nm : 0.24 and confirming to IEC/EN 60793-2-50 class B1.3 ITU G.652.D EN 50 173-1:2007 ISO/IEC 11801:2002 ISO/IEC 24702:2006- through existing GI/HDPE/ Hume pipe or on cable trays inside the cable duct including all necessary fixing accessories e.g. cable ties, hardware etc.
Supply, Installation, testing and commissioning of 19" slide-in modular optic drawers with galvanised steel accommodates up to 4 fibre optic units, 4 cables, accommodates up to 24 ST and SC connectors and 24 LC connectors. Should meet EN50173 and ISO/IEC 11801 operating specifications.
Supply, Installation, testing and commissioning of Single Mode OS1/OS2 9/125 μm LSZH LC Pigtails confirming to conforms to ITU-G652.D and TIA/EIA standards 492CAAA
Supply, Installation, testing and commissioning of Single Mode OS1/OS2 LC-LC Duplex Fiber Patch Cord - 3 mtrs. Conform to IEC 61754-4,61300-3-4,61300-3-34,61300-3-6,61300-2-1/2/4/5 EIA-TIA, G.657.A2 and Telecordia performances requirements
18TB Enterprise Grade HDD
Supply, Installation, testing and commissioning of UTP 4 pair 23 AWG LSZH CAT 6 LAN Cable in the existing surface/ recessed steel/ PVC conduit as required. 305 mtr per Box. Blue/Orange/White/Green in colour conforming to the following standards like ANSI EIA/TIA 568.2-D, IEC 60332-1, IEC 60754-1, ASTM 2843. Frequency tested upto 400Mhz with Third Party Certificate etc. Cable Dia 6.0 ± 0.3, Cross-member (+) fluted Spine/isolator for uniform separation for all pairs.
Supply, Installation, testing and commissioning of Cat6 Tool less Information outlet for Data & Voice. Cat6 U/UTP RJ45 socket with built in crimping mechanism with capability of retermination without refreshing the wires. Toolless RJ45 Information outlet with insertion cycle (in & out) upto 2500 times (I/O) along with front side Label holder and transparent shutter. The Information Outlet connector shall be of gold/nickel, thickness of gold > 0.8 μm. The connectors shall be compatible as per IEEE 802.3bt standard for POE++ application .
Supply, Installation, testing and commissioning of Face Plate : Flush & surface mount. Polycarbonate Hi-Grade Plastic FR Grade with ABS underplate & CRCA metal fram & UV Resistant 850 degree C/ Glow Wire Test. The face plate should be compatible for Cat5e, Cat6 range of RJ45 and different types of AV connectors.The face plate Size should be of minimum 86x86mm Plate & Frame 1M
Supply, Installation, testing and commissioning of Face Plate : Flush & surface mount. Polycarbonate Hi-Grade Plastic FR Grade with ABS underplate & CRCA metal fram & UV Resistant 850 degree C/ Glow Wire Test. The face plate should be compatible for Cat5e, Cat6 range of RJ45 and different types of AV connectors.The face plate Size should be of minimum 86x86mm Plate & Frame 2M
Supply, Installation, testing and commissioning of Back Box
Supply, Installation, testing and commissioning of 24 port Cat 6 19" Modular Toolless Patch Panel (loaded) enable all possible combinations of the various types of cable (UTP, FTP, SFTP) mounted on the same panel by using various toolless connector blocks/modules. Have a metal structure enabling them to be durably fixed to the uprights of the 19” chassis and assuring automatic grounding between toolless RJ-45 connectors, the panel, and the 19” uprights of the enclosure. Include rear cable support with plastic cable guides to hold cable without need for cable ties. Include quick mounting system to mount the panel into the 19” rails without use of cage-nuts. These may be used to secure the connections of wifi access points, IP cameras, servers, or other critical devices. Front Removal IO's option for maintenance and trouble shooting with 6 Different Colours Labels for Labelling & Identification of Individual Ports. Tested and guaranteed under dual circuit IEEE PoE++ more than 90W for up to 2500 on-load connections / disconnections.
Supply, Installation, testing and commissioning of CAT6 UTP 24 AWG Patch Cord - 1 mtr with cross separator , Manufactured from stranded wires for longer flex-life , Minimum length of 1m, and maximum length of 5m Conforming to the following standards like EN 50173, ISO/IEC 60603-7 & 11801/IEC 60332-1, UL VW-1 with tensile strength >50N, Number of Insertion upto 2500 Duty Cycle
Supply, Installation, testing and commissioning of CAT6 UTP 24 AWG Patch Cord - 2 mtr with cross separator Factory crimped multistranded copper patch cord with tensile strength of > 50N. Conforming to the following standards like EN 50173, ISO/IEC 60603-7 & 11801/IEC 60332-1, UL VW-1 with tensile strength >50N, Number of Insertion upto 2500 Duty Cycle .
Supply, Installation, Testing and Commissioning of Fully Managed Layer 3 Stackable Switch with 24x10G SFP+ and Min 2x10G copper with Management Port, Entire feature set including PTPv2, L2 switching (IGMP Plus) and L3 routing (static, RIP, OSPF, VRRP, PIM-SSM, PBR) must be from day-1 without any additional license, Minimum 5 Years hardware and software subscription as per tender specifications
Supply, Installation, Testing and Commissioning of 8 x 10/100/1000BASE-T PoE ports, Min 2 x Gigabit SFP ports, Minimum 20Gbps Bandwidth for better Performance, Advanced L2 switching and security features, Min. 75W PoE budget
Supply, Installation, Testing and Commissioning of 24 x 10/100/1000BASE-T PoE ports, Min 2 x Gigabit SFP ports, Minimum 56Gbps Bandwidth for better Performance, Advanced L2 switching and security features, L2+ Static Routing, Should support Remote and Cloud management, Min 190W PoE budget.
Supply, Installation, Testing and Commissioning of Fully Managed Layer 2 Stackable Switch with 24x1G Copper, Min 2x10G Copper, Min 2x10G SFP+ Port with Management Port, Switch must have provision to add additional power supply for redundancy, Entire feature set including PTPv2, L2 switching (IGMP Plus) and L3 routing (static, RIP, OSPF, VRRP, PIM-SSM, PBR) must be from day-1 without any additional license, Minimum 5 Years hardware and software subscription as per tender specifications
Supply, Installation, Testing and Commissioning of Fully Managed Layer 2 Stackable Switch with 48x1G Copper, Min 2x10G Copper, Min 2x10G SFP+ Port, 591W PoE+ with Management Port, Switch must have provision to add additional power supply for redundancy and inhense PoE Power Budget, Entire feature set including PTPv2, L2 switching (IGMP Plus) and L3 routing (static, RIP, OSPF,
Supply, Installation, Testing and Commissioning of 10G SFP+ Modules for Single Mode Fiber LC duplex Connector Including 5 Years Warranty as per tender specifications
Supply, Installation, testing and commissioning of 42U Rack Frame/800X1000/Steel/NRS1/ CKD/Casters Type 2/Black,Levellers,19" Adopter kit /42U/Loops/Black,Per,forated Door/42/800/Flat/NRS1/Black,Perforated Door/42/800/Dual/NRS1/Black,Swing handle / Mechanical Lock / Single Point / Common Key/Polymade Panels/1000/42U/Vented/NRS1/Black,Swing handle / Mechanical Lock / Three Point / Common Key/Polymade,Server /IT Rack mount power distribution unit, 1Ph, 230V, 32A, 50/60Hz, Zero U standard with 12 X Indian Round Pin 5/15A, 16A MCB X 2 Circuits- PDU Rating 7.3KVA/Bottom feed-3Mt/ Black/ Inlet Plug Not Installed,Horz. Cable Organiser/1U/ Channel On Front,Shelf/1000/Black,Shelf/1000/Black,Shelf/Key Board/19"Rty/1000/Black,Mounting Hardware-CR (Pack of 20),ITE / Server Rack Air Circulation module/Tower Mount/360CFM
Supply, Installation, testing and commissioning of 9U/600 Rack/ Welded/WM/Off White,Glass Door/9U/WM/Gray,Server /IT Rack mount power distribution unit, 1Ph, 230V, 16A, 50/60Hz, 2U standard with 6 X Indian Round Pin 5/15A, Inlet Plug type 16A Indian Round Pin, 16A MCB - PDU Rating 3.6KVA/Side feed-1.5Mt/ Black,Horz. Cable Organiser/1U/Loop,Cantilever Shelf/Type2/1U/Off White,Mounting Hardware-CR (Pack of 20),ITE / Server Rack Air Circulation module/90CFM
Supply, Installation, Testing and Commissioning of 55" Professional LED Display
Any other Item Not included in CCTV System but required to complete the Job:-
Supply installation Testing and commissioning of 6 KVA (SINGLE PHASE) on line UPS system confirms to IS 16242(Part-I):2014 and IEC 60240-1 : 2008 with IGBT technology pure sine wave out put, double conversion with auto and manual static by pass switch single phase input / Single phase output with minimum 15 minutes battery back up of each UPS.
LT PANEL
Supply, Installation, testing and commissioning of IP 54 (Indoor type - Double door) rated MSP OF MAHASU DEVTA Having, Incomer : 630A FP MCCB (MOTORIZED) WITH MICROPROCESSOR BASED RELEASE O/L,S/C,E/F,PROTECTION WITH UV,SHUNT RELEASE) (WITH RS-485 PORT) (01 Nos). 1 NO SPD (01 Nos). 1 NO MFM WITH RS485 PORT INDICATION LAMP- 6 NOS (R,Y,B,ON,OFF,TRIP) 6Nos. CT 630/5A CL-1.0,5VA Out Going: 63 Amp FP 10KA MCB with ON-OFF (01NOS.) 100 Amp FP 30KA MCCB with ON-OFF (02NOS.) 125 Amp FP 36KA MCCB with ON-OFF (01NOS.) 200 Amp FP 36KA MCCB with ON-OFF (01NOS.) 250 Amp FP 36KA MCCB with ON-OFF (01NOS.) 315 Amp FP 36KA MCCB with ON-OFF (01NOS.)
Supply, Installation, testing and commissioning of IP 54 (Indoor type - Double door) rated FSP-1_ZONE-1 (PARKING PLAZA) Having, Incomer : 315A FP MCCB (MOTORIZED) WITH MICROPROCESSOR BASED RELEASE O/L,S/C,E/F,PROTECTION WITH UV,SHUNT RELEASE) (WITH RS-485 PORT) (01 Nos). 1 NO SPD (01 Nos). 1 NO MFM WITH RS485 PORT INDICATION LAMP- 6 NOS (R,Y,B,ON,OFF,TRIP) 3Nos. CT 315/5A CL-1.0,5VA Out Going: 40 Amp FP 10KA MCB with ON-OFF (01NOS.) 63 Amp FP 10KA MCB with ON-OFF (01NOS.) 100 Amp FP 10KA MCCB with ON-OFF (03NOS.)
Supply, Installation, testing and commissioning of IP 54 (Indoor type - Double door) rated EMERGENCY PANEL Having, Incomer : 400A FP MCCB (MOTORIZED) WITH MICROPROCESSOR BASED RELEASE O/L,S/C,E/F,PROTECTION WITH UV,SHUNT RELEASE) (WITH RS-485 PORT) (01 Nos). 1 NO SPD (01 Nos). 1 NO MFM WITH RS485 PORT INDICATION LAMP- 6 NOS (R,Y,B,ON,OFF,TRIP) 3Nos. CT 400/5A CL-1.0,5VA Out Going: 40 Amp FP 10KA MCB with ON-OFF (01NOS.) 63 Amp FP 10KA MCB with ON-OFF (04NOS.) 100 Amp FP 10KA MCCB with ON-OFF (04NOS.) 250 Amp FP 10KA MP BASED MCCB with ON-OFF (01NOS.)
Supply, Installation, testing and commissioning of IP 54 (Indoor type - Double door) rated COMMON AREA PANEL Having, Incomer : 250A FP ATS (01 Nos). 250A FP MCCB (MOTORIZED) WITH MICROPROCESSOR BASED RELEASE O/L,S/C,E/F,PROTECTION WITH UV,SHUNT RELEASE) (WITH RS-485 PORT) (01 Nos). 1 NO SPD (01 Nos). 1 NO MFM WITH RS485 PORT INDICATION LAMP- 6 NOS (R,Y,B,ON,OFF,TRIP) 3Nos. CT 250/5A CL-1.0,5VA Out Going: 32 Amp FP 10KA MCB with ON-OFF (03NOS.) 40 Amp FP 10KA MCB with ON-OFF (02NOS.) 63 Amp FP 10KA MCB with ON-OFF (01NOS.) 63 Amp FP 10KA MCCB with ON-OFF (01NOS.) 200 Amp FP 10KA TM BASED MCCB with ON-OFF (01NOS.)
Supply, Installation, testing and commissioning of IP 54 (Indoor type - Double door) rated PHE PANEL Having, Incomer : 40 Amp FP 10KA MCB (01 No). 1 NO SPD (01 Nos). 1 NO MFM WITH RS485 PORT INDICATION LAMP- 6 NOS (R,Y,B,ON,OFF,TRIP) 3Nos. CT 40/5A CL-1.0,5VA Out Going: 25 Amp DP 10KA MCB with ON-OFF (01NOS.) 25 Amp FP 10KA MCB with ON-OFF (04NOS.) 32 Amp FP 10KA MCB with ON-OFF (01NOS.)
HT RMU
Supply, assembling, installation, testing and commissioning of 11 KV, 350 MVA,630A, 21KA Outdoor type , extensible type HT RMU panel.
The rate shall include the following job :
Call for final inspection prior to dispatch
Delivery of the breaker panel at site.
Unloading of breaker panel at site store.
Shifting of panel from site store to substation room including removing the packing.
Assembling the panel.
Testing of breaker including testing of tripping mechanism, Indicating lamps, setting of all relays etc as per fault current and O/C current.
Supplying, Testing & Commissioning of 11 kV, 630A , 21 KA SF6 Ring Main Unit complete with 2 Nos. Load break Switch + 1 Nos. Vacuum Circuit Breaker Manual operated. The panel should be extensible type for future requirements. The Panel should be complete with metering and protection as per specification. (1 incomming (LBS) + 2 outgoing (LBS+VCB)) Outdoor Type - 3 WAY RMU
CSS (COMPACT SUBSTATION)
Supply, installaton, testing & commissioning of 11000 / 433 volts, DRY type, OUTDOOR type CSS (UNITIZED COMPACT SUB STATION) with off Load circuit tap Changer as per Specification, Technical Data sheet & IS. IP rating shall be IP 54 for overall CSS and for transformer, IP rating shall be IP 34. 'The rate shall include the following : 'Delivery of the CSS at site. 'Unloading of CSS at site 'Shifting of CSS with all tools, equipment & accessories from site store to the site & placing it on the plinth at site. 'Installation and connection of CSS. 'Earthing of CSS neutral & body. 'Testing of CSS as per IS/IEC before commissioning. 'Charging of CSS gradually as per IS/IEC. 'To & fro Air charges to be provided by vendor for inspection 'Supplying,Unloading, shifting at site, assembling, installing, testing and commissioning of unitise substation (CSS) suitable for outdoor mounting having 1 no RMU including 1 no. 11 KV, 630 Amps 350 MVA draw out type HT VCB & 1 no. 630A FP LT MCCB with Microprocessor based release with antipumping feature as out going of Transformer with CT & PT of appropriate rating for metering and protection, 1 no of 315 KVA DRY Type Transformer, DY11 with +/-10% off load tap link in step of 2.5% on HT side and all losses are as per ECBC guidelines. Transformer details will be as per following: Supply and Installation of indoor type 11 KV 315 kVA 11000/433 V, copper wound, delta star connected outdoor type DRY typ (CRT) transformer, Vector Group Dyn11, off load tap changer with Taping on Primary +/-10% in steps of 2.5% , Class A Insulation level , maximum 50 Deg C temperature rise, Efficiency shall be as per ECBC , With HV cable end box and LV side bus bar connection Box, & all standard accessories like digital winding temperature indicator, rollers, Marshalling box for interconnection with incomer switch and hooters, First fill of oil, Rating and diagram Plate.Also with Control Cabling, OLTC panel, etc.. IP rating shall be IP 54 for overall CSS and for transformer, IP rating shall be IP 34.
Laying of PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Above 120 sq. mm and upto 400 sq. mm
Supply, laying, connecting, testing and commissioning of 11 KV armoured, 3 core, XLPE (Earth) cable including all accessories, supports etc. as specified and shown on drawings. The unit rate for the job shall include : Delivery of the cables at site. Unloading at site store. Shifting of cable from site store to place of installation. Laying of cable will be below ground. Cost of excavation & back filling with sand and RCC bricks shall be included in this rate. Connection of cable. Supply and fixing of route markers at every 15 mtr.and at change of direction. Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth bar. Testing of cables.
Supply, laying, testing and commissioning of 11 KV, 3C x 240 sq.mm. XLPE (Earth) armoured cable.
Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required '240 Sqmm.
The scope includes to test the DG set for factory test witnessed by Owner represantative prior to dispatch of following:- 1. Load trial test for equal ratings of load for continous 4 Hrs.2. Sudden shock load at every One hour during above test. 3. Vibration Test 4. Noise level test. 5. Fuel gas analysis. 6. Delta ` t ' inside acoustic enclosure. (2) Delivery of the DG set at site. (3)Specific Fuel Consumption Test (4) Unloading of the DG set at Required Location of Installation & test at manufacture's place. (5) Technical support & supervision during commissioning of DG Set & Synchronizing Panel. (6) To get Battery charged and to test Battery charger. (7) Testing of the DG Set with Supply of Consumable. (8) Painting of the parts damaged during Transportation or Installation (9) Power & Control cabling between D.G. Panel & D. G. Set, syncronising Panel & alternator to ACB/MCCB inside the enclosure. (10) D.G. set should have exhaust chimney of Suitable Length (AS PER LATEST CPCB NORMS/LOCAL NORMS) as per statutory requirement with suitable M.S. structure complete between exhaust of engine till out let point for discharging fuel gas. Drawing of which should be submitted for approval.(Necessary cost to shall be included.) If required Contractor has to visit site and accordingly rate shall be included. (11) The rate quoted shall be for the entire job including exhaust piping complete up to trial test. No extra rates to be quoted for any items for the DG set. (12) The day tank must be part of acoustic enclosure. No external fuel tank required. 13) All Necessary control cables of between DG set, AMF panel/Sync Panel, MLTP and Battery charger shall be part of supply. Necessary BOM shall be submitted during approval process. 14)To prepare & submit as-built drawing and handing over document to end user. 15) Scope also includes preparing necessary drawing submitting to authorities, getting their approval / sanction and final certificate including NOC from pollution board(if required) to energize the D G Set. 16)DG vendor has to arrange for inspection and factory acceptance test as detailed in specification. The Item shall include TO and FRO travelling economy class Air ticket/second class AC/Air-conditioned car, whichever feasible from the port of boarding of client/consultant lodging/boarding as necessary for at least three representatives of client/consultant.
Supply of Prime duty 250 KVA DG set, acoustic enclosure suitable for 75 db(A) sound level reduction to be measured at 1 mtr. from the enclosure. Cost should cover D.G. set control panel, necessary control and metering, control & power wiring, indication /annunciation & other accessories.
Providing & erecting approved make AMF control panel suitable for following size of 3 phase, 415 V, 50 cycles, A.C. diesel generating set along with required MCCB protection complete of scope as detailed below: 1) Power module: A pair of electromechanically interlocked contactors (for mains & generator) Overload relay for generator contactor Neutral contactor for mains and generator Power socket for connections. 2) Control and metering module: Line voltage monitor. Generator voltage monitor Ammeter 3 items attempt start facility. Air circuit breakers/MCB/MCCB of suitable rating for auto/manual operation. Auto/manual switch. Emergency stops push buttons. Manual start push button. frequency meter. Engine hour meter. Two earthing studs. 3) Protection module: The engine shutdown in the unlikely event of Low lube oil pressure High cylinder head temperature. V belt failure. 4) Indicators with alarm Load on generator. 5) Indicators Load on mains Engine fails to start . Emergency stop battery charger. The AMF Panel of following capacity AMF Control Panel for 250 KVA, 3 phase DG Set
SERVO STABILIZER
Supply, Installation, testing and commissioning of Indoor Type Three phase servo controlled voltage stabilizer suitable for input voltage range 340 to 480VAC upto 200 KVA and above 200 KVA 360-480VAC And output voltage range 415V + 1%. A.C Three Phase. Natural Air Cooled with Input MCB / MCCB & Bypass switch (L&T, ABB, schneider) , Air cooled upto 60 KVA & above oil cooled Type. (i) Rating : 60 KVA approved make: ENGISOL / NEEL / Jindal / Servokon / Krykard
LIAISON WORK
Liaison with Local Electricity board for Permanent Electrical Power & Getting Approval from Licensee, Electrical Inspector - IM & E Dept. The scope includes to get the required power with providing necessary drg/document/arranging visit etc from requirement of statutory authority. Note : - The payment towards official payment shall be reimbursed against receipt of such payment.
6 Kg ABC (Powder Type) Fire Extinguisher. In HP Mild Steel Cylinders ISI marked fitted with pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all respects including wall suspension bracket and conforming to IS:15683 Providing & Fixing of fire extinguishers with necessary accessories, stand, trolley, etc.
ISI Marked portable fire extinguisher, 4.5 kg CO2 type fire extinguishers complete in all respect including initial fill and wall suspension brackets & shall conform to IS 2878 Providing & Fixing of fire extinguishers with necessary accessories, stand, trolley, etc.
Providing AUTOGLOW Signages in Block / Small Letters of Specified Sizes: "ABC" Extinguisher: 8" X 4"
Providing AUTOGLOW Signages in Block / Small Letters of Specified Sizes: "CO2" Extinguisher: 8" x 4"
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gun metal coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank gunmetal cap and chain as required
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required : Gun metal
Providing and fixing approved fire hose cabinet stand mount type for external size 600x 750x 250mm to house fire hydrant & hose, including all other related accessories fabricated from SS 316 of fully welded construction having front door with locking arrangement, partially glazed with 4 mm thick glass. Cabinet shall be powder coated & painted with post office red colour of size as mentioned in drawing (or as approved by the Architect) to house 15 mtr.x2 No. hoses including Signages
Supplying & fixing Stand Mounted type first aid fixed type with MSEP Fabricated Stand fire hose reel of braided rubber suitably reinforced 25 mm size & 40 m standard length with 5 mm tapering branch nozzle ,32mm dia. Pipe to connect to riser with cut off ball valve attachment. Hose to be fixed type stand mounted drum & recessing into hose cabinet to suit location including fixing with lead anchor fasteners & bolts ( Including drum and fixing type arrangement ) etc. complete.
Supplying & fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required : Gun metal
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 2 way-100 mm dia M.S. Pipe
Supplying and fixing of fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia MS pipe connection conforming to IS 904 as required : 4 way-100 mm dia M.S. Pipe
SITC of fire brigade draw out connection with 100 mm MS suction pipe & 100 mm dia foot valve. The scope shall also include required valves, piping, M.S cabinet as required
Supplying, installation testing and commissioning of the 25 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete.
Supplying, installation testing and commissioning of the 40 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of the 50 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of the 65 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of the 80 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of the 100 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of the 150 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of the 200 mm dia nominal bore ‘C' class GI pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including GI C class pipe of shorter lengths, tapering connecting pieces, short or long bends, GI C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA/ authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fasteners. The work includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable code & standard before applying paint etc. complete
Supplying, installation testing and commissioning of 80 mm dia nominal bore ‘C’ class GI Pipe as per IS : 1239-1973 tested to 200 PSI complete with fitting & welding of pipes & fittings wherever required complete with flanges & painting , with all the engineered support as per detail technical specification. underground/overground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over heads pipes and providing and fixing pypkote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc. complete as per ASTM standards/IS:10221 for corrosion protection of pipes for the under ground installation. Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.
Supplying, installation testing and commissioning of 100 mm dia nominal bore ‘C’ class GI Pipe as per IS : 1239-1973 tested to 200 PSI complete with fitting & welding of pipes & fittings wherever required complete with flanges & painting , with all the engineered support as per detail technical specification. underground/overground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over heads pipes and providing and fixing pypkote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc. complete as per ASTM standards/IS:10221 for corrosion protection of pipes for the under ground installation. Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.
Supplying, installation testing and commissioning of 150 mm dia nominal bore ‘C’ class GI Pipe as per IS : 1239-1973 tested to 200 PSI complete with fitting & welding of pipes & fittings wherever required complete with flanges & painting , with all the engineered support as per detail technical specification. underground/overground pipes with welded / flanged connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA authorities the pipes will have to be laid and fixed in trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Architect and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over heads pipes and providing and fixing pypkote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for underground piping (wrapping should have overlap of 15 to 20 mm) etc. complete as per ASTM standards/IS:10221 for corrosion protection of pipes for the under ground installation. Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe coating or wrapping etc. complete.
Supplying & installing completely testing & commissioning of centrifugal main fire pump(electrical driven) for hydrant main / sprinkler main with cast iron casing & bronze impeller & internal parts, make as approved by ISO/CFO for fire duty, complete with coupling, coupling guard necessary base frame, foundation bolts, RCC foundation, antivibration paid , capable of discharging 2280 lt/min against 60 mtr. head against all losses complete. The scope shall also include electrical TEFC motor, operated on 3-ph, 440-V, 50 Hz, 2900 RPM Syn. speed with ‘B’ class winding, make as approved by LFA. The pump shall be capable of giving not less than 150% discharge at a head not less than 65% of the rated head. Motor to be of continuous rating etc. complete. Each incomer and Outgoing feeder should be capable for protection against Overload, Short Circuit and Phase reversal condition and shall be capable to communicate with BMS . System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in the controller and BMS. System should be equipped with dry running protection. Indication of all type of faults / on-off status / electrical parameters shall be available on panel and central IBMS monitors. On-off operation for all pumps shall be available on BMS system. Pump - Motor : Discharge : 2280 LPM, Head 60 mtr
Supplying & installing completely testing & commissioning centrifugal main fire pump (diesel driven)with cast iron casing & bronze or phosphor bronze internal parts, make as approved by ISO/CFO for fire duty, complete with coupling, coupling guard necessary base frame, foundation bolts, RCC foundation,antivibration paid , capable of discharging 2280 lt/min against 60 mtr. head against all losses complete with suitable diesel engine of speed matching the pump speed ,auto start facility with battery & battery charger, necessary wiring, fuel tank ,exhaust system, foundation gauges & wired for automatic start of the water pump on drop of pressure in the hydrant and sprinkler system. The pump should confirm to LFA / SEB & and IE Regulations. The pump shall be capable of giving not less than 150% discharge at a head not less than 65% of the rated head. Pumping System shall be capable to communicate with BMS . System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in the controller and BMS. Indication of on-off status parameters shall be available on panel and central IBMS monitors. On-off operation for all pumps shall be available on BMS system. Pump - Diesel Engine : Discharge : 2280 LPM, Head : 60 mtr.
Supplying, installing, testing and commissioning of Vetrical Centrifugal jockey pump-motor with discharge 180 lpm against 60 mtr. head with 3 phase, 415 V, 50 Hz motor having 2900 RPM, complete with coupling, coupling guard necessary base frame, foundation bolts, RCC foundation,antivibration paid , as per site conditions and instructions of site engineer-in-charge including proper fixing, The electrical motor for the pump should comply as per Specification. The scope shall also include necessary coupling, coupling guard, base frame, foundation bolts, RCC foundation, etc. complete. Each incomer and Outgoing feeder should be capable for protection against Overload, Short Circuit and Phase reversal condition and shall be capable to communicate with BMS . System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in the controller and BMS. System should be equipped with dry running protection. Indication of all type of faults / on-off status / electrical parameters shall be available on panel and central IBMS monitors. On-off operation for all pumps shall be available on BMS system. Pump - Motor : Discharge : 180 LPM, Head : 60 mtr.
EARTHING Supply, Installation, Testing and Commissioning of UL Listed maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 25.0 mm with copper coating thickness of 250micron tested as per IEC 62561-2 + Universal clamp (SS), 25mm + Earth conductivity enhancing mineral compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested OEC 2 25 + The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system Under floor earth inspection pit. Cost include to have earth pit cover, testing of all things, etc. in all complete manner.
Supply, laying, connection and testing bare earthing conductor for inter-connecting the earthing stations and various equipment in built up trenches, walls/ceiling, buried in ground generally as specified and shown on the drawing complete with : 1)Supply & fixing accessories like earthing clamp, saddle, etc. 2)Supply of corrosion protection of buried conductors with bituminous coating 3)'Supply of Test links (Copper) etc. 4)Supply and fixing of Equipotential bar. 25 X 6 G.I Strips
8 SWG GI wire
Equipotential Bar Supply, installation, testing and commissioning of 25 x 6 mm GI Equipotential bar of 500 mm length with suitable. junction box to connect earthing conductor from building earthing to the equipment. (With six knock outs for connecting the equipment earthing
Supply, laying testing and commissioning of L.T. XLPE armoured / unarmoured cable conforming to IS : 7098 Part - II with cable end termination as per the description given below: 3 C x 95 Sq. MM. Al. XLPE ARM Cable
3 C x 25 Sq. MM. Al. XLPE ARM Cable
3 C x 6 Sq. MM. Cu. XLPE ARM Cable
3 C x 2.5 Sq. MM. Cu.PVC Armoured Cable (Control Cable)
3 C x 10 Sq. MM. Cu. XLPE ARM Cable
3 C x 4 Sq. MM. Cu. XLPE Aarmoured Cable
CABLE END TERMINATION 'Supply, fixing, connection, testing and commissioning of double compression brass cable glands and crimping type lugs / sockets with necessary tools and equipments as specified in specifications and IS. The glands and lugs / sockets shall be suitable for cable size and type mentioned above. The job also includes, if necessary, supply and fixing of extension busbar of same material on circuit breaker / FSU or panel board terminal / connector to connect more than one no. of parallel cables or to connect higher size cable to lower size unit. The job also includes earthing the glands and armour of the cable with common earth bar or flexible copper mesh. 3 C x 95 Sq. MM. Al. XLPE ARM Cable
3 C x 25 Sq. MM. Al. XLPE ARM Cable
3 C x 6 Sq. MM. Cu. XLPE ARM Cable
3 C x 2.5 Sq. MM. Cu.PVC Armoured Cable (Control Cable)
3 C x 10 Sq. MM. Cu. XLPE ARM Cable
3 C x 4 Sq. MM. Cu. XLPE Aarmoured Cable
Providing and fixing Power wiring with 2 core x 1.5 sq.mm. PVC armoured copper cable for wiring with termination of pressure switches, etc. Including all required material and labour, terminations, etc. Complete.
Providing and fixing Power wiring with 12 core x 1.5 sq.mm. PVC armoured copper cable for wiring pressure switches, etc. Including all required material and labour, terminations, etc. Complete.
Providing and fixing Power wiring with 3 core x 2.5 sq.mm. PVC armoured copper cable and PVC Conduit Pipe for wiring with termination of FHC from Fire Panel , etc. Including all required material and labour, terminations, etc. Complete.
SITC of precharged MSEP air vessel (size 600mm dia x 2000 mm height) with adequate pressure switches with valves to operate as per operating sequence including 25 mm drain valve, air release valve with stop cock on top, 25 mm inlet with isolation valve & the vessel shall be painted inside & outside. The tank shall be fabricated from 8 mm thick MS plate with painting Air Vessel : 600 mm dia x 2000 mm h
Providing, installation, testing and commissioning of stainless steel Y-strainer fabricated out of 1.6 mm thick stainless steel, Grade 304, sheet with 3 mm dia holes with stainless steel flange. 200 mm
Supplying, fixing, testing and commissioning of butterfly valve of PN 1.6 rating with bronze/gunmetal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095. 200 mm dia.
Size : 150 mm
Size : 100 mm
Size : 80 mm
Size : 50 mm
Size : 40 mm (Ball Valve)
Size : 25 mm (Ball Valve)
Providing, installation, testing and commissioning of non-return valve of following sizes confirming to IS: 5312 complete with rubber gasket, Gl bolts, nuts, washers etc.as required Size : 150 mm
Size : 100 mm
Size : 40 mm
Providing & fixing of pressure switch in pipe line including connection etc. as required.
Providing and fixing in position the industrial type pressure gauges with gun metal / brass valves complete as required
Supply, testing & commissioning of flange ends PN 1.6 Expansion Bellow as per EJMA standards of overall length of minimum 300 mm, designed for 15 mm axial compression and 5 mm axial extension with tie rods etc. of following MOC & pressure ratings. with all hardwares, companion flanges & gaskets, etc. MOC: Bellows: SA 240 Gr. 304, Internal Sleeve: SA 240 Gr. 304, Weldends: IS 2062 Gr. B, Flanges: IS 2062 Gr. B (Drilling as per IS 1538 /IS 6392 ) & Limit Rods & Nuts: CS - IS 1367. Size : 200 mm
Size : 150 mm
Size : 50 mm
Size : 40 mm
Electromagnetic Flow Meter Supply and fixing of Full Bore Electromagnetic Flow Meter( inline) with factory calibrated, IP - 68, Battery with Electrical operated, flanged connection, flow meter, indicator, transmitter and totaliser with all accessories viz. power and control cables upto starter panel, cabinets, hardwares, , communicate all data to BMS, BMS Compatible etc. complete as per following specifications including fixing using flanged specials with bolts, nuts & packing with testing. Scope also including testing and commissioning complete as per standard design as per detail technical specification etc. complete as per standard as directed by Engineer-in-charge to complete the job. I) Flow Sensor: Neoprene/Polurethene lining, DC Pulsed, SS 316 electrodes, CS / SS 316 flanges, fully welded / SS 304 sensor construction & housing. II) Flow Transmitter / converter: Micropressor based/Modular design/HART type, 2 line back lit LCD for indication of actual flow rate, forward, reverse, sum totaliser display, one current (4-20 mA)/one scalable pulse / one status output, IP 67, Die cast alluminium with PU finish with glass window enclosure, 10 metres length sensor cable. 150 mm dia.
Sypplying , fixing, teating & commisioning of double flanged sluice valve of rating PN 1.6 with non rising spindle , bronze/gun metal seat, ISI marked complete with nuts , bolts, washers, guslets and conforming to IS 780 of following sizes as required: 150 mm dia
Providing and fixing C.I. double acting air valve of approved quality with bolts, nuts, rubber insertions etc. complete (The tail pieces, tapers etc if required will be paid separately) : 50mm dia
Charges for Liasoning with Fire officer and getting all approvals and permissions & NOC 's required for fire fighting at various stages & after completion of the project including All official payments.
SHREE BALAJI ASSOCIATES (BID ID -403420)
SAINKO SYSTEMS (BID ID -403404)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.64 MB
sbdelectricaloverallinfrastructuref.pdf
Tender Documents • 1.78 MB
BOQ_104497.xls
BOQ • 0.53 MB
2276_Corrigendum.pdf
PDF • 0.66 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .