Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.3 LAccepted-AOC 37 1634 IMPERIAL HOUSE KALOOR KATHRIKADAVU KATHRIKADAVU ERNAKULAM KERALA 682017 | ERNAKULAM | KERALA | 682017 | L1 | Accepted-AOC L1 | |
| 2 | L2₹31.0 L+₹4.3 L (16.1%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹31.2 L+₹4.5 L (16.8%)Rejected-AOC 8 34A FATHIMAPURAM TAMILNADU | TAMILNADU | L3 | Rejected-AOC L3 | |
| 4 | L4₹32.8 L+₹6.2 L (23.1%)Rejected-AOC | L4 | Rejected-AOC L4 |
Tender Value
₹25.9 L
EMD Value
₹50,000
Closing Date
20 Jun 2023, 3:00 pmClosed
Chief Executive Officer
Park Centre- Technopark Phase-I Campus, Thiruvananthapuram
SITC of 11kV VCBs and 110kV CT for 110kV/11kV Substation, Technopark Phase-III Campus
2023_ETPK_580223_1
ETPK/PH-III/2023-24/E-02
Open Tender
Electrical Works
Item Rate
60 days
Technopark 110kV Substation Phase-III
Please refer tender document
2 documents required · 2 mandatory
₹2,950
₹50,000
Yes
29 Nov 2023
6 Jun 2023
21 Jun 2023
6 Jun 2023
20 Jun 2023
6 Jun 2023
Amount
Supply, Installation, Testing and Commissioning of 1250A, Ics:26.3kA, 12kV withdrawable, retrofit type VCB of ABB make , complying IEC 62271 standard, in the existing panel (Model: VD4/W 12.12.25 11kV VCB-EL2) with necessary modification in the panel with all accessories including control wiring, plugs/ assemblies, fuses etc.
Supply, Installation, Testing and Commissioning of 11kV Resin Cast wound CTs suitable for indoor applications with ratio 800/5-5, Class: 5P10/0.2s, 15VA, B.I.L: 12/28/75 kV, Ith: 18kA in the existing panel with necessary modification as required.
Supply, Installation in the existing strucuture, Testing and Commissioning of 110kV Outdoor oil immersed CT (Design- Live Tank) with following details. Ratio: 75/1-1-1-1A. Core-1: Accuracy Class: 0.5, Burden: 10 VA, ISF: <5. Core-2: Accuracy Class: 5P20, Burden: 30 VA Core-3: Accuracy Class: PS, VK: >160V, RCT: <=1.5 Ohms, Imag @ VK/4: <30mA Core-4: Accuracy Class: PS, VK: >160V, RCT: <=1.5 Ohms, Imag @ VK/4: <30mA STC: 25kA for 1.0 Second. BIL: 123/230/550 kVp, Freq : 50 Hz.
Dismantling of 1 No. of 110 kV CT from the existing structure using crane, leading to place of stotage carefully keeping at vertically not allowing tilting from vertical position more than the specified angles, keeping lines and levels as per the direction of the Engineer in Charge/ Supervisor, including all labour charges, hire charges of tools & tackles etc.
Supply and providing 11kV, 2.5 mm thick synthetic type and 1 m wide electrical grade chequered type mat conforming to IS 15652 (2006).
Leela Electricpower Services Pvt.Ltd
Fathima Engineering Co. Pvt. Ltd.
VIJAYA ELE TECHS PRIVATE LTD.
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .