Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹34.2 LAccepted-AOC | 1 | Accepted-AOC L1 accepted | |
| 2 | 2₹35.2 L+₹1.0 L (2.99%)Rejected-AOC | 2 | Rejected-AOC L2 rejected | |
| 3 | 3₹36.0 L+₹1.8 L (5.24%)Rejected-AOC | 3 | Rejected-AOC L3 rejected | |
| 4 | 4₹37.3 L+₹3.1 L (9.12%)Rejected-Finance | 4 | Rejected-Finance L4 | |
| 5 | 5₹47.5 L+₹13.3 L (38.7%)Rejected-Finance | 5 | Rejected-Finance L5 |
Tender Value
₹37.5 L
EMD Value
₹50,000
Closing Date
14 Nov 2022, 6:00 pmClosed
Executive Engineer
O/O The Executive Engineer PWD Electrical division Thiruvananthapuram
DEPOSIT-SITC of unitized substation at Govt. Homoeopathic Medical College Hospital Campus, Thiruvananthapuram.-HT Supply-HT- Electrical-Work
2022_PWD_523252_1
EDT_ET_33_2022_23
Open Tender
Electrical Works
Item Rate
182 days
Thiruvananthapuram
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹50,000
31 Dec 2022
1 Nov 2022
17 Nov 2022
1 Nov 2022
14 Nov 2022
1 Nov 2022
Amount
SITC of unitized substation
OD141005/2022-2023:Supply, conveyance, installation, testing and commissioning of 250 KVA indoor unitized sub station comprising of H.T.panel trunked with cast resin Transformer with load break switch/ Air break switch on H.T.side and manually operated, with bottom / top entry cable box as per technical details furnished below. H.T. Portion H.T. Portion consists of (1) 1 No 11K.V, 630A, 26.30 K.A Air break/Load break switch suitable for 3 phase,3wire,50 HZ system with 20 A H.R.C. fuses with earth inter lock with main switch and mechanical ON/OFF indication,(2)shunt trip coil for the remote operation of the the load break switch, Transformer Portion Supply of 250 K.V.A , 11 K.V, 50 HZ, Delta/Star connected cast resin insulated copper wound transformer. The core shall be made of high grade laser scribed core shall be protected against corrosion by epoxy resin finish. Class 'F' insulation level shall be maintained. OFF load tap changing facility shall be incorporated so as to achieve tap position of 2.5% x 4. Temperature scanner with trip annunciator, Blower for cooling shall be provided. The transformer shall confirm to IEC 726 and I.S 11171/1985 reaffirmed in 1991 . L.T.Portion The LT portion shall be provided with 1No over current earth fault relay, suitable ratio NCT and Shunt trip in existing MCCB as required. All inter connection from HT load break switch to transformer and to LT breaker shall be given using Aluminium bus bars and support insulators. All internal earth connections are to be given as per standards. Necessary protection shall be made for giving cable connections on the HT side as well as LT side. Phase barriers and shrouding as per rules has to be given. The enclosure shall comply to IP 20 standards made of 2 mm GI sheet and shall powder coating the assembly after subjecting to 7 tank process, air ventilation arrangement etc as required. The USS shall be installed as per the directions at site.
OD141006/2022-2023:Supply, installation, testing and commissioning of outdoor HT metering cubicle consists of the following; A) Resin cast CT 3Nos., ratio; - /5 or -/ 1 A, 10VA Class 0.2S B) Resin cast PT 1No., 11kV/110V, 25VA, Class 0.2S C) Test terminal block for TOD meter D)3 Phase, 4 wire, 110 V (L-L), -/1 A CT or -/5A CT, accuracy class 0.2, TOD meter as per KSEB Standards E) The enclosure shall fabricated using 2mm MS sheet and shall comply with IP 65 standards with dust and vermin proof outdoor type and shall be powder coated after seven tank processing and phosphatising. 11 KV bus bar arrangement with insulator, HT cable termination, Locking facility etc as required.
OD141025/2022-2023:SITC of Out door type 630A, 11KV,21 KA, Triple pole, 50 Hz. 1 Way Motorised SF6 Gas Insulated double side Extensible type RMU Breaker and Vacuum Circuit Breaker with Cable bushing/box mounted type Over Current protection Transformer having ratio 60/30/1A-5P10,2.5VA and earth fault protection etc, including conveyance,loading/unloading erection,testing and commissioning etc.(foundation with channel included)
OD142632/2022-2023:Supply and fixing following rating Surge Protection Devices (3P+N) 100KA protectio against direct and indirect lighting surges as required
OD142633/2022-2023:Supply and fixing 250 x 250 x 150 size SMC Junction box with hinged door directly on wall or pole using required materials
OD142630/2022-2023:MANUAL CALL POINT:- Supply Installation, Testing and Commissioning of Manual Call Points of break glass type with hammer and chain.
OD141952/2022-2023:Supply & laying of laying of 1 no. 11 KV grade XLPE cable of the following sizes in ground including excavation of trench of size 1.2 m, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil). 3 core 300sq mm
OD141953/2022-2023:Supply and laying of 1 no. 11 KV grade XLPE cable of the following sizes through DWC pipe, as required. 3 core 300sq mm
OD141954/2022-2023:Supply and laying of 1 no. 11 KV grade XLPE cable of the following sizes through open duct, as required. 3 core 300sq mm
OD141955/2022-2023:Supply, laying and clamping of 1 no. 11 KV grade XLPE cable of the following sizes using clamps fabricated from 20 x 3 mm MS flat, spacing of clamps not exceeding 60cms, making good the damages, colour washing etc. as required. 3 core 300sq mm
90.12.6.34:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 185 sq mm
90.12.7.34:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 185 sq mm
10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
10.5.4:Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
90.12.1.29:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 50 sq mm
90.12.1.35:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).3.5 core 240 sq mm
90.12.5.29:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 50 sq mm
90.12.5.35:Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.3.5 core 240 sq mm
90.12.6.29:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 50 sq mm
90.12.6.30:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 70 sq mm
90.12.6.35:Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 240 sq mm
90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
90.12.7.35:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 240 sq mm
90.12.7.30:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 70 sq mm
9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
90.12.9.8:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench125/109 mm or nearest size
90.12.9.10:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench160/135 mm or nearest size
14.13.4:Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required150 mm dia
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
90.14.10.12:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.13:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.200A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.14:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.250A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.17:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.320A/400A, 50/55 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
90.14.10.11:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.11.6:MCCB AccessoriesSupply and fixing 250 - 400A earth fault module of MCCB with builtin CBCT.
90.14.11.9:MCCB AccessoriesSupply and fixing auxiliary switch (1 NO + 1 NC) in the existing MCCB of rating up to 630 A.
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
90.14.11.15:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A
90.14.24.68:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel with block reactor.
90.14.24.71:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel with block reactor.
90.14.24.74:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.20 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel with block reactor.
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
OD141943/2022-2023:Supply & fixing the following accessories in positon and giving connection. 8 stage, 440/ 110 V, 5 A/ 1 A intelligent power factor controller.
OD142631/2022-2023:Supply and providing 150 mm panel mounting cooling fan with fresh air grill as required
OD141947/2022-2023:Supply and Fixing of Illuminated Flush head Actuator - Red with legend 'OFF', (Contact - 1 NC) and giving connection etc as required.
OD141948/2022-2023:Supply and Fixing of Illuminated Flush head Actuator - Green with legend 'ON', (Contact - 1 NO) and giving connection as required.
OD141959/2022-2023:Supply and fixing of 400/5A, 5VA accuracy class 1, Resin Cast Metering CT and giving connection as required.
OD141966/2022-2023:Supply and fixing of 250/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT and giving connection as required.
OD155078/2022-2023:Supply, Installation, Testing and commissioning of 100/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT
OD141967/2022-2023:Supply and providing Multi function meter to read: V, A, F, 3 phase accuracy class 1
OD141968/2022-2023:Supply and providing Blue colour LED indicator lamp, AC/DC, 22.5 cm cut out dia
OD141969/2022-2023:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia
OD142628/2022-2023:Supply and Fixing of Bakelite Fuse Base 20A with HRC Fuse Link 2A and giving connection as required
OD141963/2022-2023:Painting letters or figures of the 2.50 cm, 4 cm or 5 cm height sizes with enamel paint as identification mark to SB, DB, panel board etc as required
OD141965/2022-2023:Supply and Fixing of Cable alley, 100 x 40 mm aluminium anodised legend plates.
OD142629/2022-2023:Supply and fixing Bus bar chamber, 100 x 40 mm aluminium anodised legend plates
OD141964/2022-2023:Supply and fixing Aluminium anodised Danger Notice Board of size 150 x 100 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour.
OD141949/2022-2023:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 4 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.
OD141950/2022-2023:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables 2.50 sq mm single run with required sockets.conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.
OD141951/2022-2023:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.- 1.5 sq mm single run with required sockets.
OD142624/2022-2023:Supply, laying and clamping of 1 no. PVC insulated 2 Core,1.5 sq.mm, armoured copper FRLSH power cable, 1.1 KV grade ( Red Colour) using clamps noted along with the cables, spacing of clamps not exceeding 40 cms, making good the damages , colour washing etc. as required
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
90.16.1.6:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required6.00 mm copper conductor (4 SWG)
OD141944/2022-2023:Supply and providing plate earthing as per IS 3043 with 1200x1200x12 mm GI/CI earth plate, 50 mm GI watering pipe fixed to the earth plate with 25 x 3mm GI clamps, GI funnel with weld mesh, filling required quantity of charcoal including construction of inspection chamber with a bed concrete of 1:4:8 PCC using 40 mm broken stone (10 cm thick), brick work in cement mortar 1:6, plastering the surface of brick masonry and the exposed surface of PCC bed with cement mortar 1:4, 12 mm thick, (the finished inside dimension shall be 450 x 450 x 450 mm) but excluding test joint, earth continuity conductor to the plate, and covering at the top. (in hard soil)
90.16.3.11:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)32 x 3 mm copper strip
90.16.4.10:Supply and clamping the following sizes of strips on surface of wall / parapet/ existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1 m , making good the damages, colour washing etc. as required ( for vertical run).32 x 3 mm copper strip
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
90.16.5.6:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.6. mm ( 4 SWG)
OD141960/2022-2023:Supply and providing 25x6mm brass nut and bolt etc. as required.
7.9:Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required.
7.10:Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required.
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
2.22:Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
OD141961/2022-2023:Charges for preparation of additional copy schematic diagram per A3 sheet first copy
OD155083/2022-2023:Copying charges of Electrical/fire Drawing per A 3 sheet additional copies
OD155084/2022-2023:Charges for preparation of Electrical/fire Drawing per A 3 sheet first copy
OD141942/2022-2023:Supply and providing 6 Kg. ABC Fire Extinguisher with hose and clamps including fixing it to wall as required.
OD142627/2022-2023:Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint &#39;FIRE&#39; mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required. as per IS 2546&lt;br&gt; N
OD141945/2022-2023:Supply and providing 2mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength.
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.14.1:Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
90.2.1.6:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points
1.25:Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.33:Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
1.58:Supplying and fixing PVC batten/ angle holder including connection etc. as required.
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door
90.3.18.2:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
90.3.20.3:Supply & installation of light fittings on TW round block <br> Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
OD143395/2022-2023:Supply and Fixing of 9W LED Bulb
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
OD143396/2022-2023: Supply and Installation of 300/305 mm sweep Light Duty Exhaust fan in metal frame working on 230 V A/C in the existing opening, including making good the damage connection testing, commissioning etc. as required.
90.15.4.1:Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.12.7.2:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp
90.16.1.1:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.00 mm copper conductor ( 14 SWG)
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
OD155085/2022-2023:Supply, fixing and giving connection of 40 / 50 / 63 A four pole, 415 volts, MCB in the existing DB
DSK ELECTRIC POWER
S K Electrics and Infrastructures
SABI ENGINEERING COMPANY
HELSA ELECTRICALS PVT LTD
Bidder Name
SABI ENGINEERING COMPANY
D SURESH
S K Electrics and Infrastructures
HELSA ELECTRICALS PVT LTD
DSK ELECTRIC POWER
stage.html
html • 0.05 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_752952.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .