Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.3 LAdmitted-Finance | ₹40.3 L | L1 | Admitted-Finance |
| 2 | L2₹41.6 L+₹1.4 L (3.39%)Admitted-Finance D NO 35 14 13 1 R P PETA KANCHARAPALEM VISAKHAPATNAM 530 008 | VISAKHAPATANAM | ANDHRA PRADESH | 530008 | ₹41.6 L+₹1.4 L (3.39%) | L2 | Admitted-Finance |
| 3 | Rejected-Technical DOOR NO 44 19 10 RAILWAY NEW COLONY BEHIND SIVALAYAM VISAKHAPATNAM AP 530016 | VISAKHAPATANAM | ANDHRA PRADESH | 530016 | - | - | Rejected-Technical Not recommended as not enlisted in category B iii |
| 4 | Rejected-Technical D NO 38 22 40 NEAR LAKSHMI NARASHIMA THEATER 104 AREA VISAKHAPATNAM 530007 | VISAKHAPATANAM | ANDHRA PRADESH | 530007 | - | - | Rejected-Technical Not recommended as not enlisted in category B iii |
| 5 | Rejected-Technical | - | - | Rejected-Technical Not recommended as not enlisted in category B iii |
| Sl No | Description | Qty | Unit | M/S CHANDRA ENGINEERS AND CONTRACTORS L2 | UV POWER TECH L1 |
|---|---|---|---|---|---|
| 1.00 | Supply and applying Si-COAT 570 RTV/ equivalent Silicone High Voltage Insulator Coating solution using an Sprayer on supporting insulators and equipments bushing in 132 KV in incoming side at MRS with minimum thickness of 500 Micron to be coated on every insulator including testing and commissioning all as specified and as directed. | 2 | Per Bay | 43,500 ₹87,000 | 42,000 ₹84,000 Lowest |
| 2.00 | Supply and applying Si-COAT 570 RTV/equivalent Silicone High Voltage Insulator Coating solution using an Sprayer on supporting insulators and equipments bushing of Power Transformers on both 132KV & 11 KV side outdoor complete with thickness of 500 Micron to be coated on every insulator including testing and commissioning all as specified and as directed.
Note for item No. 1.00 & 2.00 :-
1.Surface preparation of all insulation surfaces of the equipment to be coated shall be made free from dust, grease, oil and any other foreign material without damaging the surface. The surface of the equipment shall be made dry before application of the RTV coating.
2.All the required materials, tools & tackles, testing equipment, consumables etc. for application of HVIC coating shall be in bidders’ scope | 3 | Per Bay | 45,500 ₹1,36,500 | 43,590 ₹1,30,770 Lowest |
| 3.00 | Supply & fixing 132KV, horizontal double break isolators "GRPS" /"CG"make or equivalent 132 KV, triple pole, 31.5 KA centre post rotating horizontal double break type isolators suitable for upright mounting with manual operated mechanism for main switch and earth switch including interlock of main and earth (i.e. mechanically gang operated) with all accessories required for normal operation of the isolator, without supporting structure and without terminal connectors with following configuration (copper design) : - a) For 800 Amps with one earth switch. b) Support insulators for the above isolators. One stack consisting of 325 KV having a creepage distance of 4495 mm and cantilever strength of 6 KN as manufactured & tested (31mm/KV) (Per No.). c) Terminal connectors for the above isolators a set of 06 Nos. Rigid type bimetallic terminal connectors suitable for single ASR Zebra conductor. | 2 | Each Set | 3,95,000 ₹7,90,000 | 3,92,000 ₹7,84,000 Lowest |
| 4.00 | Supply and applying Si-COAT 570 RTV/equivalent Silicone High Voltage Insulator Coating solution using an Sprayer to the 11KV Indoor VCB panel Cable chamber (installed in 132KV MRS) testing complete all as specified and directed.
Note :- The coating to be ensured with minimum thickness of 500 micron and the overall qty per panel should be minimum 5 Kg. | 35 | Per Panel | 21,500 ₹7,52,500 | 21,000 ₹7,35,000 Lowest |
| 5.00 | Supply and applying Si-COAT 570 RTV/equivalent Silicone High Voltage Insulator Coating solution using an Sprayer to the 11KV Indoor VCB panel Bus bar chamber (installed in 132KV MRS) testing complete all as specified and directed.
Note for item No. 5 & 6 : (a) Surface preparation: All insulation surfaces of the equipment to be coated shall be made free from dust, grease, oil and any other foreign material without damaging the surface. The surface of the equipment shall be made dry before application of the RTV coating.
(b) All the required materials, tools & tackles, testing equipment, consumables etc. for application of HVIC coating shall be in bidders’ scope
(c) The coating to be ensured with minimum thickness of 500 micron and the overall qty per panel should be minimum 5 Kg. | 35 | Per Panel | 19,000 ₹6,65,000 Lowest | 19,500 ₹6,82,500 |
| 6.00 | M&L for taking down safely unsv / burnt existing 11KV ACSR conductor from the 4 pole RCC/iron structure (HT 11KV) not below than 15 Mtr including disconnecting the insulator, HT cable & clamps. Breaking the foundation completely and removing the RCC/PCC pole complete with structure and moving outside the dockyard premises by using crane and lifter/truck etc., all as specified and directed. | 10 | Each Job | 22,500 ₹2,25,000 | 22,000 ₹2,20,000 Lowest |
| 7.00 | M&L for taking down safely unsv/ burnt existing 11KV ACSR conductor from the 2 pole RCC/iron structure (HT 11KV) not below than 15 Mtr including disconnecting the insulator, HT cable & clamps. Breaking the foundation completely and removing the RCC/PCC pole complete with structure and moving outside the dockyard premises by using crane and lifter/truck etc., all as specified and directed. | 10 | Each Job | 12,500 ₹1,25,000 | 12,000 ₹1,20,000 Lowest |
| 8.00 | M&L for taking down safely unsv/ burnt existing 11KV ACSR conductor from the RCC/iron structure (HT 11KV) not below than 15 Mtr including disconnecting the insulator, HT cable & clamps. Breaking the foundation completely and removing the RCC/PCC pole complete with structure and moving outside the dockyard premises by using crane and lifter/truck etc., all as specified and directed. | 90 | Each Job | 5,510 ₹4,95,900 | 5,500 ₹4,95,000 Lowest |
| 9.00 | Dismantling existing 132KV conductor & taking down safely from structure after disconnecting the pad clamps by removing rusted nuts & bolts and supply, stringing, sagging & tensioning 132 KV ACSR conductor (as per approved specification) and make if testing & energization all as specified and directed. Note :- Rates for dead end clam set, suspension clamp set, joint sleeve, T-clamp/ T connector complete with jointing compound & insulator hardware fitting etc are inclusive in bidder scope. No extra charges shall be given for these materials. | 150 | Mtr | 1,520 ₹2,28,000 | 1,500 ₹2,25,000 Lowest |
| 10.00 | M&L required for cleaning of internal components of 11 KV HT panels (control compartments, busbar chamber, cable chamber & breaker compartments) using electrically non-conductive chemical (NWK -99 Opp or equivalent), in power ON/OFF condition, including removal of dust, oil, moisture, carbon deposit etc by controlled spray method with compressed air, complete as per OEM guideline and site conditions all as specified and directed.
Note :-
(A) Cleaning shall include :- (i) Relays (ii) Bus bars (accessible portion) (iii) Terminal blocks (iv) Wiring (v) CT/PT compartments (external surfaces)
(B) The contractor shall ensure :- (i) No damage to insulation or wiring (ii) No change relay setting (iii) No ingress of moisture
(C) Working condition :- (i) Shutdown condition or live condition (as permitted) by Engineer-in-Charge.
(D) Safety Precautions : (i) PPE kit mandatory (ii) Barricading of work area (iii) Fire safety measures
(E) Reporting :- (i) Before/After photographs (ii) Panel wire cleaning report (iii) Chemical usage record (iv) Waste material to be safety collected and disposed. | 6 | Each Job | 1,10,000 ₹6,60,000 | 92,000 ₹5,52,000 Lowest |
Tender Value
₹47.7 L
EMD Value
₹95,400
Closing Date
4 Aug 2026, 6:00 pmClosed
GE (I) DM Visakhapatnam
GE (I) DM Visakhapatnam
REPAIR AND IMPROVEMENT OF HT DISTRIBUTION SYSTEM WITH SILICON HVIC COATING AND REMOTE CONTROL OPERATION OF VCBs AT MRS CDS 1 AND CDS 2 AT NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) DM VISAKHAPATNAM
2026_MES_776974_1
8310/C/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Naval Dockyard Visakhapatnam
As per tender document
8 documents required · 8 mandatory
₹500
GE (I) DM Visakhapatnam
₹95,400
Yes
14 Aug 2026
7 Jul 2026
6 Aug 2026
7 Jul 2026
4 Aug 2026
21 Jul 2026
8 Jul 2026 - 19 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply and applying Si-COAT 570 RTV/ equivalent Silicone High Voltage Insulator Coating solution using an Sprayer on supporting insulators and equipments bushing in 132 KV in incoming side at MRS with minimum thickness of 500 Micron to be coated on every insulator including testing and commissioning all as specified and as directed. | 2 | Per Bay | - | - |
| 2 | Supply and applying Si-COAT 570 RTV/equivalent Silicone High Voltage Insulator Coating solution using an Sprayer on supporting insulators and equipments bushing of Power Transformers on both 132KV & 11 KV side outdoor complete with thickness of 500 Micron to be coated on every insulator including testing and commissioning all as specified and as directed.
Note for item No. 1.00 & 2.00 :-
1.Surface preparation of all insulation surfaces of the equipment to be coated shall be made free from dust, grease, oil and any other foreign material without damaging the surface. The surface of the equipment shall be made dry before application of the RTV coating.
2.All the required materials, tools & tackles, testing equipment, consumables etc. for application of HVIC coating shall be in bidders’ scope | 3 | Per Bay | - | - |
| 3 | Supply & fixing 132KV, horizontal double break isolators "GRPS" /"CG"make or equivalent 132 KV, triple pole, 31.5 KA centre post rotating horizontal double break type isolators suitable for upright mounting with manual operated mechanism for main switch and earth switch including interlock of main and earth (i.e. mechanically gang operated) with all accessories required for normal operation of the isolator, without supporting structure and without terminal connectors with following configuration (copper design) : - a) For 800 Amps with one earth switch. b) Support insulators for the above isolators. One stack consisting of 325 KV having a creepage distance of 4495 mm and cantilever strength of 6 KN as manufactured & tested (31mm/KV) (Per No.). c) Terminal connectors for the above isolators a set of 06 Nos. Rigid type bimetallic terminal connectors suitable for single ASR Zebra conductor. | 2 | Each Set | - | - |
| 4 | M&L for taking down safely unsv / burnt existing power conductor from the structure after disconnecting the pad clamps by removing rusted nuts & bolts and supply, installation of new Moose conductor in place of existing conductor and make it operational all as specified and as directed by Engineer-in-charge. | 100 | RM | - | - |
| 5 | Supply and applying Si-COAT 570 RTV/equivalent Silicone High Voltage Insulator Coating solution using an Sprayer to the 11KV Indoor VCB panel Cable chamber (installed in 132KV MRS) testing complete all as specified and directed.
Note :- The coating to be ensured with minimum thickness of 500 micron and the overall qty per panel should be minimum 5 Kg. | 35 | Per Panel | - | - |
| 6 | Supply and applying Si-COAT 570 RTV/equivalent Silicone High Voltage Insulator Coating solution using an Sprayer to the 11KV Indoor VCB panel Bus bar chamber (installed in 132KV MRS) testing complete all as specified and directed.
Note for item No. 5 & 6 : (a) Surface preparation: All insulation surfaces of the equipment to be coated shall be made free from dust, grease, oil and any other foreign material without damaging the surface. The surface of the equipment shall be made dry before application of the RTV coating.
(b) All the required materials, tools & tackles, testing equipment, consumables etc. for application of HVIC coating shall be in bidders’ scope
(c) The coating to be ensured with minimum thickness of 500 micron and the overall qty per panel should be minimum 5 Kg. | 35 | Per Panel | - | - |
| 7 | M&L for taking down safely unsv / burnt existing 11KV ACSR conductor from the 4 pole RCC/iron structure (HT 11KV) not below than 15 Mtr including disconnecting the insulator, HT cable & clamps. Breaking the foundation completely and removing the RCC/PCC pole complete with structure and moving outside the dockyard premises by using crane and lifter/truck etc., all as specified and directed. | 10 | Each Job | - | - |
| 8 | M&L for taking down safely unsv/ burnt existing 11KV ACSR conductor from the 2 pole RCC/iron structure (HT 11KV) not below than 15 Mtr including disconnecting the insulator, HT cable & clamps. Breaking the foundation completely and removing the RCC/PCC pole complete with structure and moving outside the dockyard premises by using crane and lifter/truck etc., all as specified and directed. | 10 | Each Job | - | - |
| 9 | M&L for taking down safely unsv/ burnt existing 11KV ACSR conductor from the RCC/iron structure (HT 11KV) not below than 15 Mtr including disconnecting the insulator, HT cable & clamps. Breaking the foundation completely and removing the RCC/PCC pole complete with structure and moving outside the dockyard premises by using crane and lifter/truck etc., all as specified and directed. | 90 | Each Job | - | - |
| 10 | Fixing, testing & commissioning of 1C x 630 Sqmm XLPE EHV copper cable termination (to end termination kit (OET)) outdoor type including wearing male connectors with all consumables complete as per specification.
Note:- Termination Joint shall be arranged by the department. | 6 | Each Job | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
8310Tender.pdf
Tender Documents • 0.94 MB
BOQ_870140.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .