Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹12.6 LAccepted-AOC | L-1 | Accepted-AOC Over all rates are reasonable and lowest. | |
| 2 | L-2₹13.8 L+₹51,944 (3.90%)Rejected-Finance 289 KASERU KHERA MAWANA ROAD MEERUT 250001 U P | MEERUT | UTTAR PRADESH | 250001 | L-2 | Rejected-Finance Over all rates are higher than L-1. | |
| 3 | L-3₹14.5 L+₹1.2 L (9.25%)Rejected-Finance | L-3 | Rejected-Finance Over all rates are higher than L-1. |
Tender Value
Refer Docs
EMD Value
₹30,000
Closing Date
28 Nov 2020, 6:00 pmClosed
Garrison Engineer, Air Force, Bareilly
Garrison Engineer, Air Force, Bareilly, 243002
REPAIR / RECHARGING AND IMPROVEMENT TO CRITICAL EARTHING SYSTEM IN TECHNICAL / WSA BUILDING AND REPAIR / REVIVING AND IMPROVEMENT TO EARTHINGS OF E/M INSTALLATIONS AT AF STATION BAREILLY.
2020_MES_374854_2
8539 / E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Bareilly
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Garrison Engineer, Air Force
₹30,000
Yes
8 Feb 2021
29 Oct 2020
30 Nov 2020
29 Oct 2020
28 Nov 2020
16 Nov 2020
29 Oct 2020 - 16 Nov 2020
Amount
Repairing to existing defective earthing by taking out carefully earth plate, watering pipe, protection pipe and re-buried the same after removing sludge from the plate and pipes. The earth plate shall be buried directly in ground with top edge of earth plate not less than 1.50 m below normal ground level, connected to GI earth wire or GI / copper earth strip any size by means of nut-bolts, check nuts and washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2009, Part–I (Specifications) and other end connected to main switch board / main DB’s / earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust & common salt in alternate layers all around the earth plate minimum 150 mm in all directions with & including GI funnel made out of 0.63 mm thick GI sheet, wire gauge, 50 mm thick RCC cover in cement concrete 1:2:4, type B-1, duly reinforced with 8 mm dia mild steel TMT bars @ 100 mm both ways center to center with suitable lifting handle made of 10 mm dia mild steel bars to lift the cover, earth pit of PCC 1:3:6 type C-1, as required at site to complete the earthing including testing of earthing on completion of job complete all as specified and directed. NOTE: - ON TESTING AFTER COMPLETION OF JOB, IF DESIRED EARTH RESISTANCE (i.e. LESS THAN ONE OHM) IS NOT OBTAINED, THE EARTHING SHALL BE REDONE BY THE CONTRACTOR WITHOUT ANY EXTRA COST TO GOVT. THE EARTH PLATE, PROTECTION PIPE AND WATERING PIPE OF OLD EARTHING SHALL ONLY BE REUSED IN THE SAME PIT. REST OF THE MATERIALS AS REQUIRED SHALL BE PROVIDED BY THE CONTRACTOR.
M & L for construction of cement concrete earth pit chamber in PCC 1:3:6, type C-1, 450 X 450 X 50 mm thick Pre-cast RCC cover in cement concrete 1:2:4, type B-1, duly reinforced with 8 mm dia mild steel TMT bars @ 100 mm both ways center to center with suitable lifting handle made of 10 mm dia mild steel round bar to lift the cover with and including necessary excavation, earth work in any type of soil and dismantling of old broken earth pit chamber and disposal of spoil to a distance not exceeding 50 m compete all as specified and as directed. NOTE: - THIS ITEM IS AN INDEPENDENT ITEM AND THE SAME IS NOT CONNECTED WITH ANY OTHER ITEMS OF THIS BOQ.
M & L for replacement of old defective earthing by providing new earthing comprising of galvanised steel earth plate electrode 600 mm X 600 mm X 6 mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, connected to galvanised earth strip of size 32 X 6 mm by means of nuts, bolts, check nuts & washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2009, Part–I (Specifications) and connected to main switch board / main DB’s / earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust & common salt all around the earth plate minimum 150 mm in all directions with & including watering pipe 20 mm dia GI medium grade, GI funnel made out of 0.63 mm thick GI sheet, wire gauge, 50 mm thick RCC cover in cement concrete 1:2:4, type B-1, duly reinforced with 8 mm dia mild steel TMT bars @ 100 mm both ways center to center with suitable lifting handle made of 10 mm dia mild steel round bar to lift the cover, earth pit of PCC 1:3:6 type C-1, GI protection pipe light grade 40 mm bore including testing on completion of job complete all as specified and directed.
All as per Item No. 3.00 hereinbefore but using 4.00 mm dia GI earthing wire and 15 mm bore GI light grade protection pipe complete all as specified and directed.
M & L for replacement of old defective earthing by providing new earthing comprising of copper earth plate electrode 600 mm X 600 mm X 3.15 mm thick buried directly in ground (earth pit not less than 2.25 m below ground level) with top edge of earth plate not less than 1.50 m below normal ground level, connected to copper earth strip of size 20 X 3 mm by means of nut-bolts, check nuts and washers of galvanised iron or steel all as shown on electrical plate No. 3 of MES schedule 2009, Part–I (Specifications) and connected to main switch board / main DB’s / earthing test point including all necessary excavation and earth work in any type of soil, adequate quantity of charcoal dust and common salt all around the earth plate in alternate layers minimum 150 mm (compacted thickness) in all directions with and including watering pipe 20 mm dia GI medium grade, GI funnel made out of 0.63 mm thick GI sheet, wire gauge, 50 mm thick RCC cover of size 450 mm X 450 mm in cement concrete 1:2:4, type B-1, duly reinforced with 8 mm dia mild steel TMT bars @ 100 mm both ways center to center with suitable lifting handle made of 10 mm dia mild steel round bar to lift the cover, earth pit of PCC 1:3:6 type C-1, GI protection pipe light grade 40 mm bore including testing on completion of job complete all as specified and directed. NOTE FOR ITEM NO. 3.00 TO 5.00: - ON TESTING AFTER COMPLETION OF JOB, IF DESIRED EARTH RESISTANCE (i.e. LESS THAN ONE OHM) IS NOT OBTAINED, THE EARTHING SHALL BE REDONE BY THE CONTRACTOR WITHOUT ANY EXTRA COST TO GOVT.
Taking down old existing earthing strip of any size and description from roof, floor, ceiling, surface of poles or from ground including air termination rod and making good the disturbed surface of wall, roof, floor etc. and keep the same in safe custody for re-using the serviceable earth lead strip complete all as specified and directed.
Fixing only old serviceable earthing strip retrieved from dismantling vide item No. 6.00 hereinbefore on suitable size porcelain insulators / saddles and fixing screws complete all as specified and directed for the following sizes: - NOTE: - New porcelain insulators / saddles as required at site to be provided by the contractor and cost of the shall deemed to be included in unit rate of this item. The Number of insulators shall be used in a mannar so that strip should not touch the surface of wall / roof / floor / pole etc. The joints of each lead or strip shall be welded / brazed and the cost of brazing / welding shall deem to be included in unit rate of this item.
(a) GI earth strip of size 32 mm X 6 mm.
(b) Copper earth strip of size 32 mm X 6 mm.
(c) Aluminium earth strip of size 20 mm X 3 mm.
Material and Labour for earth continuity conductor or main earthing lead burried in ground, fixed to wall, any other indicated situation for loop earthing and the like upto test point on necesarry insulators and fastning screws, rawl plugs complete all as specified and directed for the following: - NOTE: - The joints of each lead strip shall be welded / brazed and the cost of brazing / welding shall deem to be included in unit rate of this item.
(a) GI earth strip of size 32 mm X 6 mm.
(b) Copper earth strip of size 32 mm X 6 mm.
(c) Copper earth strip of size 20 mm X 3 mm.
(d) Aluminium earth strip of size 20 mm X 3 mm.
Taking down old existing GI earth lead wire 4.00 mm dia from roof, floor, ceiling, surface of poles or from ground and making good the disturbed surface complete all as specified and directed.
M & L for 4.00 mm dia galvanised iron or steel wire earth continuity conductor or main earthing lead fixed to wall, on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing and the like as required complete all as specified and directed.
Fixing only old serviceable Air-termination rod of any size retrieved from dismantling vide item No. 6.00 hereinbefore on suitable type insulation material for keep the same isolated roof surface complete all as specified and directed.
Supply and fixing as in replacement test point terminal block made of gun metal or phasphorous bronze size 75 X 75 X 25 mm drilled and screwed including 3 Nos. 8 mm dia 25 mm long hexagonal head screw fixed to wall and connected with earth strip complete all as specified and directed.
S & F as in replacement single pointed air termination aluminum rod, 12 mm dia and 300 mm long including 20 mm size air terminal base / ridge saddle made of gun metal with and including fixing arrangment on the ridge of RCC roof / on pole as required complete all as specified and directed.
M & L for providing earth marking plate made out of cast iron plate fixed on suitable size of angle iron of 60 cm long grouted (15 cm below ground level) in PCC 1:2:4, type B-1, (using 20mm graded stone aggregate) and including painting and marking the detail of earthing such as type of earthing and resistance value etc. as per electric colour codeing complete all as specified and directed.
S & F of 40 mm nominal bore GI tubing, light grade with all fittings including fixing arrangement with screws, clamps on insulator for protection of Aluminium earh strip upto 1.50 metres from ground level including taking out unserviceable one complete all as specified and directed.
M & L for earthing enhancing back fill compound (Powder) suitable to increase the earth resistant value complete all as specified and directed. Make- Ennov, True Power Earthing, Alopp, Gravin.
M & L for replacement of old defective earthing by providing new chemical earthing comprising copper earth plate electrode 900 x 600 x 5 mm thick burried directly in ground, earth pit not less than 5.10 metres below normal ground level and complete size of pit shall be 1.60 m x 1.60 m x 5.10 metres, with top edge of the plate not less than 3.75 metres below normal ground level, earth plate surrounded from all sides by 20 cm thick salt and charcoal dust and Magnisium sulphate filling in alternate layers of 20 cm thick up to 1.8 metres height and including connected to copper strip 50 x 6 mm (upto 7.5 Metres) by means of brazing / coppers nut-bolts, earth strip protected with 65 mm bore light grade pipe from electrode and upto and including the earth test point of galvanised iron / steel of size 75 x 75 x 25 mm test point, 15 mm bore watering pipe light grade GI funnel, wire mesh, earth plate surrounded from all sides by 20 cm thick salt (40 Kg), charcoal dust (40 Kg) and Magnisium sulphate (50 Kg) filling in each alternate layers upto 1.80 m height including excavation, removal surplush soil to a distance not exc. 50 m, PCC pit in PCC (1:3:6) type C-1, using 20 mm graded stone aggregate, RCC cover 40 mm thick in RCC (1:2:4) type B-1, using 20 mm graded stone aggregate reinforced with 8 mm dia mild steel deformed bars @ 75 mm centre to centre both ways complete all as specified and directed. NOTE:- Additional Chemical compound if required on account to achieve earth resistance less than 1.00 ohm shall deemed to be included in the unit rate of this item. On testing after completion of job, if desired earth resistance (i.e. less than one ohm) is not obtained, the earthing shall be redone by the contractor without any extra cost to Govt.
Shikha Enterprises
M/S SARTHAK INFRASTRUCTURE AND ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .