Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹47.2 LAccepted-AOC | ₹47.2 L Quoted ₹48.9 L | 1 | Accepted-AOC Being L1 |
| 2 | 2₹49.5 L+₹55,090 (1.13%)Rejected-Finance THEERTHAM NADUVILEMURI PADANILAM POST NOORANAD ALAPPUZHA DIST KERALA 690529 | ALAPPUZHA | KERALA | 690529 | ₹49.5 L+₹55,090 (1.13%) | 2 | Rejected-Finance L1 being accepted |
| 3 | 3₹51.1 L+₹2.2 L (4.47%)Rejected-Finance NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | ₹51.1 L+₹2.2 L (4.47%) | 3 | Rejected-Finance L1 being accepted |
| 4 | 4₹53.2 L+₹4.3 L (8.75%)Rejected-Finance | ₹53.2 L+₹4.3 L (8.75%) | 4 | Rejected-Finance L1 being accepted |
| 5 | 5₹56.2 L+₹7.3 L (14.9%)Rejected-Finance 606 80 FEET ROAD 7TH BLOCK 2ND PHASE BANASHANKARI 3RD STAGE BANGALORE 560 085 | BENGALURU URBAN | KARNATAKA | 560085 | ₹56.2 L+₹7.3 L (14.9%) | 5 | Rejected-Finance L1 being accepted |
| Sl No | Description | Qty | Unit | Phejays Agencies L7 | Lucky Enterprises L5 | TAMS ASSOCIATES L1 | devan enterprises L3 | Aavani BUILDERS AND CONTRACTORS L6 | ELSOL ENGINEERS L4 | Green Ray Enterprises L2 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | M&L for servicing of HT 11 KV, RMU any type and make by carry out the following work once in six months :- (i) Cleaning/decarbonizing of all levers, springs using suitable cleaning agent and tightening of screws, nuts, bolts, spring etc for proper functioning. (ii) Lubricating/greasing of all operating mechanism and moving parts, switching & tripping mechanism, demoisturing of all parts. (iii) Testing of relay tripping performace of RMU. (iv) Checking of all relays and interlocking if any. (v) Caiberation, performance testing using primary injection method and necessary adjustment of relays for successful operation at the time of fault occurence etc. (vi) Checking of operating mechanism adjustments, measurements of the mechanical clearances of operating mechanism, internal wiring circuit etc, tightening of all connections, replacement of unserviceable fuse/MCB SP including removing moisture deposit inside the RMU. (vii) Checking all end terminals, tightening the nut, bolt and washers, replace the unserviceable nut, bolt & washers, engage the RMU with the supply system and testing for smooth functioning complete all as specified and as directed by the Engineer in charge. Note : (i) The cost of cleaning materials, HT Tape, thinner, cotton waste, monoplast, unserviceable cable end socket, steel nuts, bolts with double washers, MCB SP upto 32 Amp, replacement of complete HT packing/gasket shall deemed to be included in the quoted rate. (ii) Contractor shall be isolated and earth the breaker before start the work. | 36 | Each | 3,000 ₹1,08,000 | 4,500 ₹1,62,000 | 1,300 ₹46,800 Lowest | 3,200 ₹1,15,200 | 5,200 ₹1,87,200 | 6,000 ₹2,16,000 | 15,000 ₹5,40,000 |
| 2.00 | S&F in repair self power protection relay, 220 V having 400 A current capacity, 4 poles suitable for fixing in RMU and CSS having digital type screen complete all as specified and as directed. | 4 | Each | 23,000 ₹92,000 | 38,500 ₹1,54,000 | 6,000 ₹24,000 Lowest | 35,000 ₹1,40,000 | 75,000 ₹3,00,000 | 55,000 ₹2,20,000 | 32,000 ₹1,28,000 |
| 3.00 | S&F in replacement 3 phase digital Multi function meter 440 V with energy standard : IEC62053-22 CLASS 0.5 s FOR ACTIVE ENERGY AND IEC 62053-23 CLASS 1.0 for reactive energy suitable for fixing in RMU/CSS with complete wiring system all as specified and as directed. | 12 | Each | 6,000 ₹72,000 | 3,500 ₹42,000 | 4,000 ₹48,000 | 3,150 ₹37,800 Lowest | 6,900 ₹82,800 | 7,800 ₹93,600 | 5,900 ₹70,800 |
| 4.00 | S&F in replacement of 12V battery, 12 AH, 10.5 V and boost charging voltage 14.0 V per bloc @25 degree C suitable for charging the RMU including necessary wiring as required and as directed. | 12 | Each | 2,500 ₹30,000 | 2,600 ₹31,200 | 1,500 ₹18,000 Lowest | 2,210 ₹26,520 | 1,950 ₹23,400 | 1,990 ₹23,880 | 1,700 ₹20,400 |
| 5.00 | S&F in replacement battery charger suitable for existing RMU for 12V battery including all wiring connection for smooth functioning of RMU complete all as specified and as directed. | 2 | Each | 8,500 ₹17,000 Lowest | 21,500 ₹43,000 | 10,000 ₹20,000 | 18,000 ₹36,000 | 29,000 ₹58,000 | 31,000 ₹62,000 | 28,000 ₹56,000 |
| 6.00 | Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT's), Indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 200/1-1 Amps, Core 1: Class 5P10, 10VA for protection, Core 2: Class 0.5, 10VA for metering including associated wiring complete all as specified and as directed. | 2 | Set of 3 | 7,500 ₹15,000 Lowest | 38,900 ₹77,800 | 16,000 ₹32,000 | 33,000 ₹66,000 | 55,000 ₹1,10,000 | 31,400 ₹62,800 | 24,000 ₹48,000 |
| 7.00 | Supplying, installation, commissioning and testing in replacement of 11 KV Potential Transformer (PT's), Indoor type, resin cast epoxy type, of 13.1 KA/Sec 11Kv/110v having Core1: Class 5P10, 10VA for protection, Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and as directed. | 2 | Set of 3 | 35,000 ₹70,000 | 54,900 ₹1,09,800 | 15,000 ₹30,000 Lowest | 48,000 ₹96,000 | 65,000 ₹1,30,000 | 1,29,000 ₹2,58,000 | 61,000 ₹1,22,000 |
| 8.00 | S&F in replacement, drive link assembly with Adjustor as per existing size, type and suitable for 11 KV RMU all as specified and as directed. | 1 | Set of 3 | 2,000 ₹2,000 Lowest | 4,650 ₹4,650 | 12,000 ₹12,000 | 4,500 ₹4,500 | 6,000 ₹6,000 | 7,000 ₹7,000 | 4,800 ₹4,800 |
| 9.00 | S&F in repair Auxiliary Switch (7NO+7NC) as per existing size, type and suitable for 11 KV RMU including taking down old item all as specified and as directed. | 1 | Each | 2,500 ₹2,500 | 1,880 ₹1,880 Lowest | 5,000 ₹5,000 | 4,000 ₹4,000 | 2,600 ₹2,600 | 3,000 ₹3,000 | 2,000 ₹2,000 |
| 10.00 | S&F in repair Closing Coil Assembly as per existing size, type and suitable for 11 KV RMU including taking down old item all as specified and as directed. | 2 | Each | 6,000 ₹12,000 | 3,562 ₹7,124 | 6,000 ₹12,000 | 3,000 ₹6,000 Lowest | 4,400 ₹8,800 | 4,900 ₹9,800 | 4,000 ₹8,000 |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
23 Jun 2026, 6:00 pmClosed
CWE
Military Engineer Services Commander Works Engineers Indian Naval Academy -PO Kannur- Dist Kerala State-670310
As per BOQ and tender documents
2026_MES_769159_1
80526
Open Tender
Civil Works
Item Rate
CWE Ezhimala, Indian Naval Academy
8 documents required · 8 mandatory
₹500
GE (Maint) Ezhimala
₹1 L
Yes
11 Sept 2026
2 Jun 2026
30 Jun 2026
2 Jun 2026
23 Jun 2026
16 Jun 2026
3 Jun 2026 - 15 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | M&L for servicing of HT 11 KV, RMU any type and make by carry out the following work once in six months :- (i) Cleaning/decarbonizing of all levers, springs using suitable cleaning agent and tightening of screws, nuts, bolts, spring etc for proper functioning. (ii) Lubricating/greasing of all operating mechanism and moving parts, switching & tripping mechanism, demoisturing of all parts. (iii) Testing of relay tripping performace of RMU. (iv) Checking of all relays and interlocking if any. (v) Caiberation, performance testing using primary injection method and necessary adjustment of relays for successful operation at the time of fault occurence etc. (vi) Checking of operating mechanism adjustments, measurements of the mechanical clearances of operating mechanism, internal wiring circuit etc, tightening of all connections, replacement of unserviceable fuse/MCB SP including removing moisture deposit inside the RMU. (vii) Checking all end terminals, tightening the nut, bolt and washers, replace the unserviceable nut, bolt & washers, engage the RMU with the supply system and testing for smooth functioning complete all as specified and as directed by the Engineer in charge. Note : (i) The cost of cleaning materials, HT Tape, thinner, cotton waste, monoplast, unserviceable cable end socket, steel nuts, bolts with double washers, MCB SP upto 32 Amp, replacement of complete HT packing/gasket shall deemed to be included in the quoted rate. (ii) Contractor shall be isolated and earth the breaker before start the work. | 36 | Each | - | - |
| 2 | S&F in repair self power protection relay, 220 V having 400 A current capacity, 4 poles suitable for fixing in RMU and CSS having digital type screen complete all as specified and as directed. | 4 | Each | - | - |
| 3 | S&F in replacement 3 phase digital Multi function meter 440 V with energy standard : IEC62053-22 CLASS 0.5 s FOR ACTIVE ENERGY AND IEC 62053-23 CLASS 1.0 for reactive energy suitable for fixing in RMU/CSS with complete wiring system all as specified and as directed. | 12 | Each | - | - |
| 4 | S&F in replacement of 12V battery, 12 AH, 10.5 V and boost charging voltage 14.0 V per bloc @25 degree C suitable for charging the RMU including necessary wiring as required and as directed. | 12 | Each | - | - |
| 5 | S&F in replacement battery charger suitable for existing RMU for 12V battery including all wiring connection for smooth functioning of RMU complete all as specified and as directed. | 2 | Each | - | - |
| 6 | Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT's), Indoor type, resin cast epoxy type, of 13.1 KA/Sec having ratio 200/1-1 Amps, Core 1: Class 5P10, 10VA for protection, Core 2: Class 0.5, 10VA for metering including associated wiring complete all as specified and as directed. | 2 | Set of 3 | - | - |
| 7 | Supplying, installation, commissioning and testing in replacement of 11 KV Potential Transformer (PT's), Indoor type, resin cast epoxy type, of 13.1 KA/Sec 11Kv/110v having Core1: Class 5P10, 10VA for protection, Core2: Class 0.5, 10VA for metering including associated wiring complete all as specified and as directed. | 2 | Set of 3 | - | - |
| 8 | S&F in replacement, drive link assembly with Adjustor as per existing size, type and suitable for 11 KV RMU all as specified and as directed. | 1 | Set of 3 | - | - |
| 9 | S&F in repair Auxiliary Switch (7NO+7NC) as per existing size, type and suitable for 11 KV RMU including taking down old item all as specified and as directed. | 1 | Each | - | - |
| 10 | S&F in repair Closing Coil Assembly as per existing size, type and suitable for 11 KV RMU including taking down old item all as specified and as directed. | 2 | Each | - | - |
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.26 MB
TD80526.pdf
Tender Documents • 0.55 MB
80526PS.pdf
Tender Documents • 0.34 MB
BOQ_861391.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .