Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹14.6 Cr
EMD Value
₹14.6 L
Closing Date
17 Dec 2026, 6:30 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Vice President, (P), GUDC Ltd., Gandhinagar
Chorwad UGD-II under SJMMSVY : Working Survey, Soil Investigation, Design & Construction, Testing & Commissioning, Underground Drainage Project Including Providing, Supplying, Lowering, Laying and Jointing Raising main and Gravity Main Pipeline Network, Providing House Connection, Property Connection, Road Restoration, Pumping Machinery, Pumping Station with Operation & Maintenance with All Allied Works for 02-[Two] Years Including 03-[Three] Years Defect Liability Period Including 03-[Three] Years Defect Liability Period for Chorwad Nagar palika Under Ground Drainage Phase-II Project, Taluka:- Maliya Hatina & District: - Junagadh, Gujarat” Under SJMMSVY.
366368
GUDC/PROJECTS/SJMMSVY/UGD-II/Chorwad
Open
Civil Works - Others
Works
Gandhinagar
3 documents required · 3 mandatory
₹21,240
GUDC Ltd., Gandhinagar
₹14.6 L
18 Nov 2026
18 Nov 2026
18 Nov 2026
17 Dec 2026
18 Nov 2026
180 days
Schedule-B-1 Providing & Laying Gravity Sewerage Network
Schedule-B-2 Electro-Mechanical and Instrumentation Work for SPS -01
Schedule-B-3 Electro-Mechanical and Instrumentation Work for MPS
Schedule-B-4 Electro-Mechanical and Instrumentation Work for PS-3 (O-3)
Schedule-B-5 Electro-Mechanical and Instrumentation Work for PS-4 (O-4)
Schedule-B-6 Construction of Sewage Pumping Station (O-3)
Schedule-B-7 Construction of Sewage Pumping Station (O-4)
Schedule-B-8 Providing and Laying of Rising Main
Schedule-B-9 Construction of Inspection Chambers
Schedule-B-10 Construction of House Connections
Total of Schedule-B
Schedule-C-1 02-Years of Operation & Maintanance For Drainage Network System
Total of Schedule-C
Total of Schedule-B + Schedule-C
Providing & Laying Gravity Sewerage Network
Item Rate Amount
Description Qty Unit
1 Excavation for pipe line trenches for water supply, sewerage line, 4,521.00 Cum 102.35
manhole etc. all with shoring and struting if required as per required
gradient and line including safety provisions using site rails and
stacking excavated stuff including up to all required
lead cleaning the site etc. complete for all lifts and strata as
In all sorts of soil and soft murrum
1.1 In hard murrum, boulders incl. macadam road. 9,042.00 Cum 155.25
1.2 In soft rock and/or masonry in CM or L M or Lime Concrete 13,562.00 Cum 187.45
1.3 In hard rock and / or in C. C. 1:2:4 or RCC with blasting, breaking, 18,083.00 Cum 427.80
chiseling, or by chiseling/breaking only.
In hard rock and / or in C. C. 1:2:4 or RCC with blasting, breaking,
chiseling, or by chiseling/breaking only.
1.5 3.0 mt to 4.5 mt depth 5,555.00 Cum 456.55
In hard rock and / or in C. C. 1:2:4 or RCC with blasting, breaking,
chiseling, or by chiseling/breaking only.
1.6 4.5 mt to 6.00 mt depth 448.00 Cum 465.75
In hard rock and / or in C. C. 1:2:4 or RCC with blasting, breaking,
chiseling, or by chiseling/breaking only.
2 Excavation in bituminous road as per required gradient and line 873.30 Cum 288.65
including safety provisions using site rails and stacking excavated
stuff including up to all required lead cleaning the site etc. complete
for all lifts as specified.
3 Providing bedding incl. ramming, watering, levelling, consolidating 596.00 Cum 378.35
etc. Complete as per standard and instruction of engineer incharge.
As above with required quality Sand brought from outside inclduing
4 Providing and casting in situ C.C. in grade M-20 (proportions as per 87.00 Cum 6,348.00
mix design or as per table9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap metal of size 6 mm to 20 mm
for RCC work, including scaffolding centering,
formwork, needle vibrated consolidation, curing complete up to
meter depth or height (excluding cost of reinforcement and neat
finishing) with centering and shuttering/deshuttering etc. complete
for structure other than water retaining (Below G.L)
Footing for column or foundation (with form work)
Item Rate Amount
Description Qty Unit
5 Providing and supplying ISI Standard R.C.C. pipes(of Sulphate 11,405.00 Rmt. 417.00
Resisting Cement) in standard lengths of following class and
diameter suitable for either collar joints or rubber ring joints
including all taxes, insurance, transportation, freight charges, octroi,
inspection charges, loading, unloading, conveyance to departmental
stores, stacking etc.
should be supplied with each full length plain ended RCC pipe, cost
included in rates below.
Note: One rubber ring should be supplied with each full length
socketed pipe, cost included in rates below.
Class NP3 Test Pressure 0.7kg/sq.cm
5.2 Class IRS/NP4 2,248.00 Rmt. 757.00
6 Lowering, laying & jointing R.C.C pipes in C.M. 1:1.5 for following 11,405.00 Rmt. 89.96
diameters in proper position, grade and alignment at level as
directed by Engineer-in-charge including conveyance from store to
site of work, labour, giving hydraulic testing as per ISI code.
7 Providing and constructing Sewer manholes, scraper manholes and 178.00 No. 14,005.85
unit house connection chamber, as per the type design in brick
masonry in C. M. 1:5 and inside and outside 20mm thick plastering
in C. M. 1:3 necessary 100 mm coping with reinforcement in
R.C.C.M. 200 fixing C. I. steps and fixing manhole frame and covers
(But excluding supply of manhole frame and covers) over manholes
and house connection chambers and fixing Manhole covers (but
excluding supplying of manhole covers) over scraper manhole etc.
complete, providing and fixing safety chain wherever necessary as
per the stipulations in the type design complete as per latest
(excl. excavation).
Manhole type "A" Circular type having inside diameter of 1200 mm
for depth upto 1.5 m depth (for 150 mm to 500 mm dia sewer)
Manhole type "A" as above but upto 1.0 M depth.
7.1 Extra depth beyond 1.0 M but upto 1.5 M depth for "A" type 110.00 Rmt. 7,622.20
7.2 Manhole type "B" circular type having inside diameter of minimum 274.00 No. 24,283.40
1500 mm and for depth from 1.5 M to 4.0 M (for 150 mm to
Manhole type "B" as above but upto 1.5 M depth.
7.3 Extra depth beyond 1.5 M but upto 4.0 M depth for type "B" 559.00 Rmt. 14,159.95
Item Rate Amount
Description Qty Unit
7.4 Manhole type "C" circular type having inside diameter of minimum 22.00 No. 60,844.20
1500 mm and for depth beyond 4.0 m to 6.0 m (for 150 mm to
1800 mm dia sewers)
Manhole type "C" as above but upto 4.0 M depth.
7.5 Extra depth beyond 4.0 M and up to 6.0 M depth for type "C" 41.00 Rmt. 21,603.90
8 RCC precast M.H. Frame & Cover Manufacture, supply & Delivery at 474.00 No. 1,121.00
store or at site of work precast RCC M.200 Frame & cover suitable to
drainage M.H. and as per type design & Drawing including cost of
reinforcement M.S.Angles or Flat, curing mold work etc.
Heavy Duty Frame Suitable for 50 cm Opening of MH
8.1 Heavy Duty Cover Suitable for 50 cm Opening of MH 474.00 No. 1,173.00
9 Refilling the pipeline trenches including ramming, watering, 67,402.00 Cum 25.30
consolidating disposal of surplus stuff as directed within a radius of
10 Making connection to the ex. M.H. in running sewer incl. Dewatering 6.00 No. 1,500.00
and other required machinery etc. of following dia pipes at any
convenient time. All damaged work shall be well repaired as per
instructions.etc. complete.
11 Providing, laying, spreading and compacting graded stone aggregate 728.00 cum 1,252.81
to wet mix macadam specification including premixing the Material
with water at OMC in mechanical mix plant carriage of mixed
Material by tipper to site, laying in uniform layers with grader in sub-
base / base course on well prepared surface and compacting with
vibratory roller to achieve the desired density as per MoRTH Clause
12 Construction of 200 mm thick un-reinforced, dowel jointed, plain 13,587.00 Sq.m 1,634.00
cement concrete pavement with M - 35 grade of concrete including
provision of contraction, expansion, construction and longitudinal
joints, joint filler,sealant primer, joint sealant, , dowel bar, tie rod,
admixtures as approved, finishing to lines and grades as per drawing
as per MoRTH clause 602 over a 200 mm thick WMM with necessary
excavation/ loosening and recompacting ground as per respective
MoRTH specification and as directed by engineerin charge
13 Providing and erecting C. I. and MS ventilating columns 15 cms. dia. 14.00 No. 38,911.40
with C.I. ornamental cap and Min 6.00 Mtr. Height (Height may be
varying as per site) base fixed firmly with necessary foundation with
one coat of red lead oxide paint and one coat of any approved
colour with 15 cms, dia.10 Mt.in length with 0.35mt*0.35mt* M100
Encasing, stoneware or R.C.C. pipe connection with M.H. including
excavation and jointing as required etc. complete. as per drawing.
For 6 Mtr. Height (6 Mt MS pipe)
13.1 For 12 Mtr. Height (2 M CI and 10 M MS) 15.00 No. 47,414.50
Item Rate Amount
Description Qty Unit
14 Dewatering by pumping set of required capacity including 10,150.00 HP/hr 21.07
temporary platform carting pumping at site and fixing the same in
position including all accessories, and fuel and labour etc. complete.
Pump set of Capacity
Electro-Mechanical and Instrumentation Work for SPS -01
Item Rate Amount
Description Qty Unit
1 MECHANICAL WORKS 2 Set 3,95,886.00
NON-CLOG SEWAGE SUBMERSIBLE PUMP MOTOR SET:
Supply, Installation (in Existing sump/wet well), Testing and Commissioning (SITC) of Submersible NC Pump-
Motor set suitable for sewage application with semi-open or enclosed or suitable type Impeller & wear
Rings in CF8M with CI FG 260 Casing & casing cover, SS 410 shaft & with motor suitable for 3-Phase, 415 V,
50 Hz., AC induction Air filled dry type submersible motor of mini. rating as specified having max. 1500 RPM
sync. speed, insulation Class 'F' With temp. rise limited to class B and IP-68 protection.
The scope shall include all required accessories viz. automatic coupling device, SS-304 heavy duty & of
suitable size double guide pipes of length to suit the sump height with required supports, SS-304 or suitable
stainless steel grade Chain with shackles (shall be with dual hook / shackles of 100 mm or suitable higher
size at app. every 1.5m C-C distance) & of length as per sump height + min. 3m, Submersible Power &
control cable (copper flexible & stranded type conductor of reqd. cores & size for each pump motor set) &
length of sump height + min. 10 m long each run with necessary electrical termination connection at
junction box / starter panel and Pre Cast RCC foundation blocks for auto coupling & delivery bend, PMU
etc. complete as per IS and Specification and also including in scope any other parts / accessories / fittings
required to complete the work in all respects & satisfactory operation of pump set.
Pump Capacity: 115 m /hr (Pump Type-1) (1W + 1S),
Max. RPM: 1500 &
Motor Rating: Minimum 18.5 kW (or higher as recommended by pump manufacturer),
Over all Minimum Acceptable Efficiency at Duty Point: 52%.
2 Item description as above and suitable for following duty parameters complete in all respect. 2 Set 4,84,957.00
Pump Capacity: 170 m3/hr (Pump Type-2)
Max. RPM: 1500 &
Motor Rating: Minimum 22 kW (or higher as recommended by pump manufacturer),
Over all Minimum Acceptable Efficiency at Duty Point: 57.00%.
3 VALVES: 2 Nos. 6,520.75
SITC of CI/ DI Double Flanged, Manually Operated Sluice Valve confirming to IS 14846, PN 1.0 of following
sizes with SS 304 seat rings and SS spindle with hot dipped galvanised hardwares, bolts, nuts & washers etc.
as per IS and Specification & complete the work in all respects.
Size: 150 mm NB (on delivery of each type-1 pumpsets)
4 --- Item description as above --- 2 Nos. 10,666.30
Size: 200 mm NB (on delivery of each type-2 pumpsets)
5 --- Item description as above --- 1 Nos. 17,007.90
Size : 250 mm NB (on common header)
6 SITC of Non slam, flanged, CI/DI Single Door type Non Return Valve conforming to IS 5312 (Part-1), PN 1.0, 2 Nos. 8,699.75
having DI/CI body and door, CF8M seat rings alongwith all necessary hardwares as per specifications and
complete in all respect.
Size: 150 mm NB (on delivery of each type-1 pumpsets)
7 --- Item description as above --- 2 Nos. 16,782.30
Size: 200 mm NB (on delivery of each type-2 pumpsets)
8 SITC of Flange ends Expansion Bellow (PN 1.0) as per EJMA standards and as per specs. and complete in all 4 Nos. 4,656.00
Size : 150 mm NB X 300 mm L (on delivery (Vertical and horizontal) of each pump type-1 pumpsets)
9 --- Item description as above --- 4 Nos. 6,216.00
Size : 200 mm NB X 300 mm L (on delivery (Vertical and horizontal) of each pump type-2 pumpsets)
10 --- Item description as above --- 1 Nos. 7,745.00
Size : 250 mm NB X 300 mm L (On Common Header near MSV)
11 MS PIPES & SPECIALS 20 Rmt 1,492.00
Supply, Gas cutting of pipe, Fabrication of reducer & expander, welding, Installation, testing and
commissioning of MS pipe, Specials, reducer, expander, bend for Y-Joint with header, etc. conforming to IS
3589 flanges confirming to IS 6392-PN-1.0, fabricated from MS. plate with necessary supports & anchoring.
Pipe fabricated from MS plate. (Excluding supply of flange) and complete in all respect.
Size : 168.3 mm OD x min. 4.5 mm Thk
12 --- Item description as above --- 20 Rmt 2,585.40
Size : 219.1 mm OD x min. 6.3 mm Thk
Item Rate Amount
Description Qty Unit
13 --- Item description as above --- 25 Rmt 3,232.01
Size : 273 mm OD x min. 6.3 mm Thk
14 Supply, Welding, Installation, Testing & Commissioning of MS flat machined faced flanges confirming to IS 8 Nos. 1,357.00
6392 & drilled as per IS-1538 with drilling off centre bolt holes and flange thickness as per PN 1.0 including
cutting & welding.
Size : 150 mm NB (Drilled)
15 --- Item description as above --- 8 Nos. 1,886.00
Size : 200 mm NB (Drilled)
16 --- Item description as above --- 5 Nos. 2,472.50
Size : 250 mm NB (Drilled)
17 --- Item description as above --- 1 Nos. 2,840.50
Size : 250 mm NB (Drilled Blind)
18 Flanged Joints of Pipes, Fittings and Specials: 4 Nos. 702.65
Supply, Installation, Making of Flanged DI /CI / GI / MS Pipes, Fittings and Specials Joints with all jointing
materials, rubber packing, nut bolts, labour etc.for complete connection.
Size : 150 mm dia.
19 --- Item description as above --- 4 Nos. 962.55
Size : 200 mm dia.
20 --- Item description as above --- 3 Nos. 1,158.05
Size : 250 mm dia.
21 MONORAIL EOT WITH ELECTRIC CHAIN HOIST 1 Set 2,28,220.00
SITC of Electrically Operated Chain Hoist & Electrically operated Trolley, suitable to operate on Mono Rail
Girder having motorised motion in vertical lifting & cross travel, manufactured as per IS:6547-1972-Class-II
& IS-3177- Class-II, complete with electrically operated chain hoist & Electically operated geared trolley,
brake, chain-gear, motors, safety device, pendant push button, starter panel, cables from motor to starter
panel and all other required accessories like limit switches, panel, power supply system (Fastoon cable
type), fasteners, epoxy painting, etc. tested for over load as per IS complete as per specifications and
complete in all respect.
Capacity : Min. 1.0 Ton. (At Ex. Pump House)
Lift : 10.00 m as mini. or as per site req.
Bay Length : 8.0 m min. or as per site req.
(w/o MONORAIL GIRDER & MS supporting structure)
22 Providing, Supply of Structure Steel at site of work with freight, loading, unloading carting, etc. including all 500 kg. 64.84
taxes and duties complete such as joints, channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates,
Chequered plates (min. 7 mm thickness) for cable trench etc. required for support structure of all Electro-
mechanical equipment, piping, etc. for support on floor / wall / beam / brackets etc. as per tender and IS.
23 Labour Charges for lowering, laying, Fixing with fabrication various size section of MS such as joints, 500 kg. 13.07
channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered plates, for cable trench etc
Complete with two coats of red oxide and two coats of approved colour shade of epoxy paint as per
relevant IS and as per specification.
TOTAL OF MECHANICAL WORK WITHOUT GST
24 ELECTRICAL WORK 1 Set 38,951.13
TPN MCCB (For LT Service Obtaining Requirement)
SITC of 250A TPN microprocessor MCCB, LSIG (50kA) with inbuilt O/L, S/C & E/F protection with Extended
rotary handle, Terminal spreader, Auxiliary change over & Trip contact, with Outdoor Enclosure with
canopy 2mm thick , Single/double door & Wall mounted/ stand mounted as per site requirement (with
incoming & outgoing cable entry at bottom )with Cable end boxes with RYB indicating lamp, Digital
voltmeter, VSS,ON,OFF & Trip indicating lamp etc as per Power supply company requirements & location.
Including all civil works for fixing of panel on wall.
(Wall mounted at Location as per PSC req.)
Item Rate Amount
Description Qty Unit
25 MEDIUM VOLTAGE PANEL BOARD (PMCC /APFC) 1 Set 6,94,000.00
SITC of PMCC Panel (50kA), compartmentalized, floor / Stand mounted as per site condition and
requirement with required modification / rectofication works as required, operating height maximum
1800/1900 mm, Extensible on both ends, suitable for Manual & Auto operation -Local & through
PLC/SCADA operation as per site conditions complete in all respects as per Tender SLD / Specification / IS
and including following as minimum:
(1) One no. Incoming feeder FP 250A Microprocessor MCCB (50kA), LSIG, with inbuilt O/C, S/C, & E/F
protection for I/c with Digital Voltmeter, Voltmeter selector switch, Digital Ammeter, Ammeter selector
switch, Power Factor Meter, MFM with RS-485 of Class-0.5, Indicating lamps R,Y,B,On,off,Trip, 3nos.
250A/5A, Cl.-0.5 metering CT, CL 0.5 CT for APFC relay etc. Constant voltage/control voltage transformer
1500VA, 415V/230V AC, with tapping +/-5% in steps of 2.5%, 32A DP MCB complete in all respects. (2) 250A
TPN Main Aluminium busbars. (main busbars size with current density 0.8A/Sq.mm)
(3) 22 KW STAR -DELTA STARTER FEEDER (SUBM.): 2 NOS
22 KW or higher as per pump manufacturer recommendation Star-delta starter with 100A TPN Thermal
magnetic MCCB with Adjustable O/L & Adjustable S/C protection, 95A AC3 duty contactors (3 nos.), O/L
Relay, star-delta timer, Ammeter with ASS, Resin Cast CT Cl: 0.5(3 nos.),SPP,PMU, A/M, L/R switch, ON, OFF,
TRIP Indication & Start, E-Stop & Reset pushbutton etc. for S/D starter. complete in all respects.
25 (4) 18.5 KW STAR -DELTA STARTER FEEDER (SUBM.): 2 NOS
18.5 KW or higher as per pump manufacturer recommendation Star-delta starter with 80A TPN Thermal
magnetic MCCB with Adjustable O/L & Adjustable S/C protection, 80A AC3 duty contactors (3 nos.), O/L
Relay, star-delta timer, Ammeter with ASS, Resin Cast CT Cl: 0.5(3 nos.),SPP, PMU, A/M, L/R switch, ON,
OFF, TRIP Indication & Start, E-Stop & Reset pushbutton etc. for S/D starter. complete in all respects.
(5) 63A TPN TM MCCB FEEDER : 1 No. ( for Spare)
Each feeder comprising of 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
(6) 32A TPN TM MCCB FEEDER : 4 Nos. (1 no. EOT with ECH at Pump house, 1 no. spare)
Each feeder comprising of 32A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
(7) 63A TPN TM MCCB FEEDER FOR ALL MCB FEEDERS: 1 set:
Incomer: 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
7.1) 3 nos. 32A 'C' curve 4P MCB feeders (for 1 no. Ind LDB & 2 nos. spare feeders)
7.2) 1 no. 32A 'C' curve 4P MCB with Time switch,32A contactor 4P,ON lamp feeders (for Outdoor LDB)
25 (8) APFC separate cubical compartment (minimum 35 KVAr) having 1 no. 100A TPN Thermal magnetic
MCCB 50KA with adjustable overload and adjustable short circuit, 8 step APFC relay with RS 485, 1 no.
A/5A, Cl.-1.0 CT for Ammeter, Digital Ammeter, ASS, 2 nos. 10 kVAR capacitor with 32A TPN D curve MCB,3
nos. 5 kVAR capacitor with 16A TPN D curve MCB with capacitor Duty Contractor, A/M switch, On delay
timer, Push Buttons etc. Complete in all respects as per Specification, IS & SLD.
(9) Multiplication relay as required for dry run protection of pumps.
NOTE: 1). All MCCB shall be 50KA, Ics = 100% Icu, inbuilt protection with adj O/L and Adj.S/c (LSIG for MP
MCCB),Extended rotary handle, Terminal spreader, Auxiliary Change over contact and trip contact as
required.2) All MFM, ACB, Soft Starter,Temp.Scanner etc shall be with inbuilt RS
26 ICP Cubical a part of PMCC Panel as below: 1 Nos. 40,000.00
ICP cubicle compartment as a part of PMCC (as per SLD) panel with required input / output for field
instruments interfacing at terminal strip& comprising of
(a) Door mounted 1 no. Process indicator with 8 nos. relay output for start pump at high level and stop at
low level for Level transmitter ,UPS power ON Indication, etc.)
(b) Required separate isolation switches (DP MCB only) for incoming 230 V AC power mains from UPS &
outgoing power feed to 1 no. Process indicator , 1 Nos. Multiplication Relay (1 no. 1 input + 4 Output) for
Dry run protection of Pump at low-low level ,etc.
(c) Offline type UPS of suitable rating (min. 250 VA with 15-20 min. backup time ) mounted within cubicle
on main incoming power line with required isolation device (DP MCB) & outgoing feed to power supply
(d) Any other as required to complete the work and meet the tender requirement/specification.
Item Rate Amount
Description Qty Unit
27 SITC of Lighting Distribution Board (LDB) as under: 2 Nos. 7,497.69
SITC of 3 Phase 4 Wire 4P, double door Prewired LDB each for Indoor Lighting & Outdoor Lighting Suitable
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB (9 nos.) & 16A SP MCB (9 nos.)
28 SITC of stand / wall mounting type MS Junction Box, minimum 2.5mm thick, with detachable cable gland 4 Nos. 1,906.78
plate of 3mm thick, duly powder coated, with earthing terminals, steel structure stand for mounting of JB,
etc. for Jointing/Termination suitable for 1.1 kV Submersible Flexible Copper Power cable with Aluminium/
Copper armoured power cable from PMCC . Scope shall include providing suitable rating AL busbars,
Support insulators, Crimping type lugs,nuts,bolts,washers etc. complete in all respects as instructed by
E.I.C. Drawing shall be got approved before SITC of the same. Lugs of cables shall not be connected
directly. (Structure steel for Stand shall be measured separately)
JB of minimum Size: 300mm x 300mm x 100mm or higher as required. or higher as required (for Pump)
29 SITC of stand / wall mounting type MS Junction Box, minimum 2.5mm thick, with detachable cable gland 4 Nos. 1,906.78
plate of 3mm thick, duly powder coated, with earthing terminals, steel structure stand for mounting of JB,
etc. for Joining/Termination suitable for 1.1 kV Submersible Flexible Control Cables of Submersible pump
with control cable from PMCC. Scope shall include providing Terminal connectors for connecting control
cable, copper lugs, etc. complete in all respects as instructed by E.I.C. 20% additional/spare Terminal
connector shall be provided. Drawing shall be got approved before SITC of the same. SMC/FRP/Bakelite
separator shall be provided between Power cable section & Control cable section. Lugs of cables shall not
be connected directly (Structure steel for Stand shall be measured separately).
JB of minimum Size: 300mm x 300mm x 100mm or higher as required. or higher as required (for Pump)
30 SITC of LCS pushbutton station ON & OFF (E-stop) set complete with Enclosure, necessary mounting/ 4 Nos. 2,008.47
fixing arrangement on wall / pipe support etc. to be installed near motors for remote operation, etc. as per
IS and specifications. (including structural steel) (For Pump)
31 LOW VOLTAGE (LT) CABLES 25 Mtr. 783.00
Supply, laying, testing and commissioning of 1.1 kV, A2XFY(X)/2XWY(X) XLPE insulated (IS 7098) AL / Cu
stranded conductor, Extruded innersheath cables as per specification & IS.
The cable when laid outside the building shall be laid underground in trench with brick & sand
protection/in DWC pipes as per specified method and shall be laid in prepared trench/ on cable tray when
laid inside the building.
SITC of 3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
32 SITC 3C x 6 sq. mm. A2XWY Cable (2 runs for PMCC to 2 nos. 18.5 kW Subm. pump Junction box, 2 runs for 160 Mtr. 104.12
PMCC to 2 nos. 22 kW Subm. pump Junction box)
33 SITC 4C x 6 sq. mm. A2XFY(X) Cable (For 1 no. Indoor LDB, Outdoor LDB) 50 Mtr. 123.12
34 SITC 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable (For 1 no. TPN MCCB for EOT with ECH at Pump House, 4 nos. 200 Mtr. 267.10
pump PMU & for 4 nos. street light)
35 5C x 2.5 sq.mm. 2XWY(X)Cable (for LCS) 80 Mtr. 220.00
36 SITC 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (APFC sensing C.T) 20 Mtr. 175.10
37 SITC Single core 95sq. mm. PVC insulated circular unsheathed copper conductor flexible Cable (For Power 20 Mtr. 867.12
supply Metering Panel to I/c MCCB Unit)
38 CABLE END TERMINATION AND CONNECTION: 2 Nos. 840.00
SITC of Double compression Ni-Plated brass cable glands and crimping type Bimetallic lugs / sockets with
necessary tools and equipments as specified in specifications and IS. The glands and lugs / sockets shall be
suitable for cable size and type mentioned below & as per specifications.
1) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common
2) The job also includes, if necessary, supply & fixing of extension busbar of same material on MCCB or
panel board terminal / connector to connect more than one no. of parallel cables or to connect higher
size cable to lower size unit. The job also includes earthing the glands and armour of the cable with
common earth bar or flexible copper mesh.(Cable termination qty. shall be as per site requirement)
3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
39 3C x 6 sq. mm. A2XWY Cable (2 runs for PMCC to 2 nos. 18.5 kW Subm. pump Junction box, 2 runs for 16 Nos. 110.00
PMCC to 2 nos. 22 kW Subm. pump Junction box)
40 4C x 6 sq. mm. A2XFY(X) Cable (For 1 no. Indoor LDB, Outdoor LDB) 4 Nos. 111.00
41 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable (For 1 no. TPN MCCB for EOT with ECH at Pump House, 4 nos. pump 18 Nos. 65.15
PMU & for 4 nos. street light)
Item Rate Amount
Description Qty Unit
42 5C x 2.5 sq.mm. 2XWY(X)Cable (for LCS) 8 Nos. 180.00
43 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (APFC sensing C.T) 2 Nos. 49.13
44 Single core 95sq. mm. PVC insulated circular unsheathed copper conductor flexible Cable (For Power 10 Nos. 47.11
supply Metering Panel to I/c MCCB Unit)
45 CABLE TRAY 30 Mtr. 388.00
SITC of G.I. (hot dip galvanised )Ladder type medium duty (2mm thick) Cable Tray with necessary bends,
tees, reducers, covers and clamps for fixing. All material shall be Hot dip galvanised as per Specification.
And including all accessories.
300 x 75 mm - Ladder type
46 150 x 50 mm - Ladder type 70 Mtr. 336.00
47 Supply, laying and erection of 75 mm ID approved make Double Walled Corrugated pipes (DWC) of 50 Mtr. 161.15
polyethelene (confirming to IS-14930 II) with necessary connecting accessoies of same material at required
depth for laying of cable below ground / road surface for enclosing cable and back filling the same to make
ground as per original. (LT cable etc)
48 Cable Trench, Laying & Installation of Cable: Making cable trench in soft soil of suitable width of 90cms 70 Mtr. 46.46
deep for laying cable, Sand cushioning and brick protection on sides and on top all over the run and back
filling the same and making the surface as normal ground as per IS & Specification. (For laying of LT cable
49 Cable Protection/ Covering in Trench: Cable Covering with second class bricks or cement tiles laid cover 20 Mtr. 133.31
the cable (top) & also on both side with sand bedding/cusioning of 75mm.& covering of 150mm Layer of
sand above cable (16 bricks per meter.) as per IS & Tender Drg/ Specification. (For HT/LT cable
protection) complete in all respects as instructed by EIC.
50 CHEMICAL EARTHING SYSTEM 4 Set 7,028.82
SITC of Maintenance free chemical earthing with earthpit of minimum bore size dia. 225mm Safe Earthing
Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987 /Tech spec. made of corrosion free Hot
dip Galvanised (min 150 Microns) Pipes having Outer pipe dia of 76 mm , Inner corrosion free Hot dip
galvanised (80 to 100 micron) pipe dia of 26 mm with copper flat strip type connection terminal 14mm
dia with constant ohmic value surrounded by highly conductive corrosion resistant chemical compound
with high charge dissipation suitable for electrical installation & 3Mtr. length of Pipe with two nos. 25Kg.
bag of Back filling compound. (2 nos. for PMCC panel & 2nos. for all elect. Equipments)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
51 SITC of 50mm(w) x 8mm(T) etc. sizes as required, HOT dip galvanized GI Strip including supply & fixing 184 Kg. 77.17
using GI spacers, saddles when laid inside the building and inclusive of excavation & refilling of earth when
laid outside the building & interconnection with earth pit & all electro-mechanical equipments.
(50X6 G.I Strip wt.2.3 kg/m, 2.3x80Mt.=184kg.)
52 Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes as required, HOT dip galvanized GI Strip 12 Kg. 77.17
including supply & fixing using GI spacers, saddles when laid inside the building and inclusive of excavation
& refilling of earth when laid outside the building & interconnection with earth pit & all electro-mechanical
equipments. (25X3 G.I Strip, 0.6 Kg/m, 0.6x60Mt.=12Kg.)
53 SITC of HOT Dip Galvanized iron strip wire 8 SWG (For LDB,LCS, etc.) 10 Kg. 77.17
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 100Mt.=10.3 Kg.)
54 INTERNAL WIRING 40 Mtr. 78.06
SITC of Mains & outlet points wiring with 1.1 kV grade FRLS PVC insulated ISI marked flexible stranded
copper conductor wires with medium class min. 25mm. dia. Electrical grade PVC pipe and accessories to be
erected concealed in / to be run on surface / wall / ceiling with following sizes as mentioned below. The
unit rate wirings shall be with connector, PVC junction box, wires, holder, ceiling rose, angle holder, switch,
sockets, switch board, brass chromium / cadmium plated machine screws, phase and neutral wires, green
Earth continuity wires etc. as required to complete wiring from LDB panel to the final outlet termination
points. The wiring shall be as per IS:732, IS:4648 and as per tender specification / IS.
(a) SITC of Mains wiring with 3 wire 1.5 sq.mm.
55 same as above, but (b) SITC of Mains wiring with 3 wire 2.5 sq.mm as per tender specification & IS. 40 Mtr. 96.06
56 same as above, but (c) SITC of Mains wiring with 4 wire 1.5 sq.mm as per tender specification & IS. 50 Mtr. 86.06
57 same as above, but (d) SITC of Mains wiring with 4 wire 2.5 sq.mm as per tender specification & IS. 50 Mtr. 119.06
Item Rate Amount
Description Qty Unit
58 SITC of Point wiring for Light / fan / Bell / Primary Point with 2nos. 1.5 sq. mm & earth wire of 1.5 sq. mm 11 Nos. 326.59
(green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multistrand copper wires , pipe to be
erected concealed in flushed on wall / ceiling, complete with 6A Tissino Type ISI marked flush type switch /
bell push & accessories erected on metal / PVC Box covered with 3 mm thick PC (Polycarbonate) / Acrylic
sheet with necessary lamp holder / ceiling Rose / H. D. connector as directed with medium class Rigid PVC
pipe & accessories.
59 SITC of 6A independent Plug with 2nos. 1.5 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) 2 Nos. 288.50
both are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand copper wires with medium class Rigid
PVC pipe and accessories to be erected on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and
tissino type switch erected with earth continuity connection erected on Metal / PVC box covered with
mm thick PC(Polycarbonet) / Acrylic sheet.
60 SITC of 6/16A independent Plug with 2nos. 4 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) 2 Nos. 1,005.00
both are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand copper wires with medium class Rigid
PVC pipe and accessories to be erected on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and
tissino type switch erected with earth continuity connection erected on Metal / PVC box covered with
mm thick PC(Polycarbonet) / Acrylic sheet. (1 no. LT Room, 1 no. Pump House)
61 SITC of One 300/380 mm dia. Ex fan 16A independent Plug point near Ex. Fan with 2nos. 4 sq.mm Cu. 2 Nos. 1,005.00
Mains size wiring & earthwire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC pipe and accessories to be erected on wall / ceiling,
complete with ISI marked 3Pin socket and tissino type switch erected with earth continuity connection
erected on Metal / PVC box covered with 3 mm thick PC(Polycarbonet) / Acrylic sheet. Plug point shall be
62 SITC of 380mm sweep 1400 R.P.M exhaust fan, capacitor type, having double ball bearing, M.S.blades, 2 Nos. 3,052.47
mounting frame, forearms, suitable to operate on 230V,50 HZ AC supply conforming to IS: 2312.Fan shall
be painted with epoxy grey colour controlled by one 6 A flush type switch on board and 6A plug point near
63 SITC of Single Phase 20A 3 Pin Metal clad Industrial Type Socket with plug top and 20A SPMCB, suitable 2 Nos. 820.00
for flush mounting, in 16 SWG MS box of suitable size and covered with 3 mm thick electrical grade hylam
sheet or equivalent ISI marked Electrical grade Bakelite sheet and earthing with 2.5 sq.mm insulated
copper wire run inside the conduit including interconnections etc. complete as required.
(1 no. LT Room, 1 no. Pump House)
64 SITC of Sheets steel powder coated weather proof enclosure with One no. 32A, 415V 4P MCB for Motor & 1 Nos. 765.39
Inductive load (C Curve) having 10 KA breaking capacity & confirms to IS: 8828. (1 no. for EOT with ECH at
65 1200mm sweep ceiling fan, capacitor type, having double ball bearing 450mm down rod, canopies, shackle, 1 Set 1,581.51
rubber bush, blades, electronic speed regulator, suitable to operate on 230V,50Hz AC supply conforming to
IS: 374/1979.Fan shall be painted with white colour.(1 no. LT Room, 1 no. at P.H)
66 LED LIGHT FIXTURES & LIGHTING: 4 Nos. 293.26
SITC of Indoor wall mounting 20Watt or up to 25% higher wattage LED 4 feet Tube Light indoor fittings with
LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall
be made of thick sheet Steel conforming to IS: 513/CRCA polyester powder coated and high U.V. &
corrosion resistance with diffuser and/or Polycarbonate optics with company mark/name
120 to 300 V,Power Factor more than 0.9, THD < 20 %,
CCT 4000 K to 6500K, Uniformity ratio >0.7,
Luminaries efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80 Certificates)
Tube Light with integral / non-integral driver, Surge-4KV,IP-20, 4 feet, Cat-III
67 Item description as above SITC of 7 watts LED Lamps integral type,cool white with PC diffuser suitable for 1 Nos. 111.00
B22 LAMP holder (1 no. LT Room)
Item Rate Amount
Description Qty Unit
68 SITC of 40W LED Surface / Wall mounted LED Flood Light fittings with High power White LEDs wattage of 2 Nos. 5,144.28
1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High
pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium
with diffuser and Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Indoor use: (at Pump House)
69 SITC of 'B' class galvanised iron pipe 32 mm outside dia 45 cms long duly welded on 20 cms x 20 cms x 3 6 Nos. 553.86
mm thick M.S. base plate, erected on wall or corner for mounting luminaries with necessary hardware
materials duly painted for wall mounting indoor flood light fixtures on Wall of Buildings & post top lantern.
70 EXTERNAL LIGHTING (Flood LIGHT): 4 Nos. 6,029.70
SITC of 70W LED Wall mounted LED Flood Light fittings with High power White LEDs wattage of 1Watt and
above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die
cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser
and Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Outdoor use: (for area lighting)
71 EXTERNAL LIGHTING (STREET LIGHT): 4 Nos. 10,719.13
SITC of Street Light Pole, steel tubular swaged type, 7.5 meter long with single arm & M.S.base plate with
pipe cap and over hung 1.5 m long having dia to suit the socket of 240V LED street light fixtures. Street light
pole unit rate shall be with (i) IP 65 SMC box of size 20 x 15 x 15 cms. with MCB & terminal strip inside the
box with hinged/sliding door (ii) 50mm dia, B class GI pipe bracket min.1.5mtr long for Incoming &
outgoing cable (iii)MS Cable Clamp of 25 x 3mm (iv)SITC of 1.5 Mtr.single Arm bracket of medium duty MS
pipe of 4.2 cms. Out side dia complete with suitable sleeve tubing 45 cms. long of required size of pole top
etc. and having spread of 1.5.mtr. length with 110 deg.(v) Complete painted with one coat of Red oxide /
PU base primer and two coats of Aluminium / PU paint for Pole,Arm, pipe etc.
72 SITC of 70W LED Street light fittings with High power White LEDs wattage of 1Watt and above assembled 4 Nos. 5,918.70
on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum
housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
Street Light (IP-65), Surge -4KV, 70 watt Cat-III
73 SITC of M-20 / 1:2:4 cement concrete foundation for Street light pole & 70 % PCC from bottom including 4 Nos. 1,282.12
excavation for the pole of size 60 x 60 x 120 cms. Deep in below ground level with plinth of 45 cms x
cms(or 45 cms dia x 45 cms) high upper ground level with necessary curing and finishing in approved
74 SAFETY ACCESSORIES 1 Nos. 8,586.26
SITC of following safety accessories complete with necessary fixing brackets, other accessories and tools
etc. as required to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher of 6.5kg capacity with necessary clamps made
from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall complete.
(For 1 no. for LT Room)
75 Supplying of standard first AID box with antiseptic cream, medicine for use on wounds due burn, crepe 1 Nos. 297.00
bandage, guage bandage, medicated ready to use bandage (Band-aid) adhesive tape for medicinal user,
scissors, antiseptic solution (Savlon or similar) etc. (All above contents shall be of standard makes)
(For 1 no. For LT Room)
76 Supply & fixing of printed instruction (First Aid) Chart both in English and Gujarati and duly framed with 1 Nos. 129.06
front glasses, for treatment of person suffering from electric shock. (For 1 no. For LT Room)
Item Rate Amount
Description Qty Unit
77 Supply and fixing of 20 W fluorescent lamp operated emergency light with maintenance free battery for 1 Nos. 2,670.00
3 hours operation during mains power failure.
(For 1 no. LT Room)
78 Supply and laying of Synthetic Insulating Mat of Class - A of min. thickness 2mm as per IS:15652 and with 3 Sq.mtr. 1,017.00
good electrical insulation property for 1.1KV/3.3KV as per site requirement. (For LT Panel)
TOTAL OF ELECTRICAL WORKS WITHOUT GST
79 PRESSURE MEASURING SYSTEM 4 Nos. 5,413.00
Supply, installation, testing & commissioning of Diaphragm Type pressure guage having 150 mm dial with
necessary fittings/accessories in SS
(manifold valve, nipples etc.) complete in all respects and as per specs.
Range : 0 - 4 Kg/cm2 (at each pump discharge line)
80 LEVEL MEASURING SYSTEM FOR SUMP 1 Nos. 59,436.00
Supply, installation, testing and commissioning of Ultrasonic type Level Transmitter with remote type
transmitter with 10meter cable between Sensor and Transmitter along with all required accessories,
Weather proof enclosure for transmitter for outdoor application, mounting stand, etc. complete in all
respects as per specification and having following measurement ranges for liquid (Water) application:
Meas. Range: upto 10 m (at sump )
81 Supply, installation, testing and commissioning of Float type Level Switch along with 10 mtr. Cable and WP 1 Nos. 12,802.00
Junction Box (at sump for dry run protection of pumps through relay multiplication in PLC), etc., complete
in all respects and as per specification.
Meas. Range: upto 10 m (at sump )
82 ELECTRO MAGNETIC FLOWMETER MAINS OPERATED 1 Nos. 1,17,201.00
Supply, installation, testing and commissioning of Full Bore Electromagnetic flow meter comprising of IP-68
Sensor , IP-66 remote type transmitter with 20 m cable between sensor and transmitter along with all
mounting accessories, Weather proof enclosure for transmitter, hardware, mounting stand, etc.
as per specification and to complete the work in all respect as per site condition necessary connection with
pipe and shall have following size.
Meter Size: 250 mm (At Pump common Header )
Pipe Size : 250 mm
83 INSTRUMENT CABLE & ACCESSORIES 50 Mtr. 203.00
'Supply, Laying, Installation, Connection, Termination, Testing & Commissioning of Instrument Cables as per
The unit rate shall include
a)Supply, loading & unloading of the cable at site from store.
b)Shifitng of cable from site store to place of installation.
c)Fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely.
d)Excavation, back filling and levelling of ground alongwith laying of fine sand, protection bricks and other
necessary civil material for laying cables outside the building.
f)Testing and submission of sketches & reports of all the cables laid.
84 SIGNAL CABLE 50 Mtr. 176.00
85 CABLE END TERMINATION AND CONNECTION : 4 Nos. 224.00
'Supply, fixing, connection, testing and commissioning of double compression brass cable glands and
crimping type Bimetalic lugs / sockets with necessary tools and equipments as specified in specifications
and IS complete in all respects. The glands and lugs / sockets shall be suitable for cable size and type
mentioned above. The job also includes earthing the glands and armour of the cable with common earth
bar or flexible copper mesh as applicable.
86 SIGNAL CABLE 6 Nos. 224.00
TOTAL OF INSTRUMENTATION WORK WITHOUT GST
Electro-Mechanical and Instrumentation Work for MPS
Item Rate Amount
Description Qty Unit
1 MECHANICAL WORKS 2 Set 3,95,886.00
NON-CLOG SEWAGE SUBMERSIBLE PUMP MOTOR SET:
Supply, Installation (in Existing sump/wet well), Testing and Commissioning (SITC) of Submersible NC Pump-
Motor set suitable for sewage application with semi-open or enclosed or suitable type Impeller & wear Rings in
CF8M with CI FG 260 Casing & casing cover, SS 410 shaft & with motor suitable for 3-Phase, 415 V, 50 Hz., AC
induction Air filled dry type submersible motor of mini. rating as specified having max. 1500 RPM sync. speed,
insulation Class 'F' With temp. rise limited to class B and IP-68 protection.
The scope shall include all required accessories viz. automatic coupling device, SS-304 heavy duty & of suitable
size double guide pipes of length to suit the sump height with required supports, SS-304 or suitable stainless
steel grade Chain with shackles (shall be with dual hook / shackles of 150 mm or suitable higher size at app.
every 1.5m C-C distance) & of length as per sump height + min. 3m, Submersible Power & control cable (copper
flexible & stranded type conductor of reqd. cores & size for each pump motor set) & length of sump height +
min. 10 m long each run with necessary electrical termination connection at junction box / starter panel and
Pre Cast RCC foundation blocks for auto coupling & delivery bend, PMU etc. complete as per IS and
Specification and also including in scope any other parts / accessories / fittings required to complete the work
in all respects & satisfactory operation of pump set.
Pump Capacity: 160 m3/hr (Pump Type-1) (1W + 2S),
Max. RPM: 1500 &
Motor Rating: Minimum 18.5 kW (or higher as recommended by pump manufacturer),
Over all Minimum Acceptable Efficiency at Duty Point: 56.5%.
2 Item description as above and suitable for following duty parameters complete in all respect. 2 Set 6,67,927.00
Pump Capacity: 230 m3/hr (Pump Type-2)
Max. RPM: 1500 &
Motor Rating: Minimum 30 kW (or higher as recommended by pump manufacturer),
Over all Minimum Acceptable Efficiency at Duty Point: 61.00%.
3 VALVES: 2 Nos. 10,666.30
SITC of CI/ DI Double Flanged, Manually operated Sluice Valve confirming to IS 14846, PN 1.0 of following
sizes with SS 304 seat rings and SS spindle with hot dipped galvanised hardwares, bolts, nuts & washers etc. as
per IS and Specification & complete the work in all respects.
Size: 200 mm NB (on delivery of each type-1 pumpsets)
4 --- Item description as above --- 2 Nos. 10,666.30
Size: 200 mm NB (on delivery of each type-2 pumpsets)
5 --- Item description as above --- 1 Nos. 21,696.15
Size : 300 mm NB (on common header)
6 SITC of Non slam, flanged, CI/DI Single Door type Non Return Valve conforming to IS 5312 (Part-1), PN 1.0, 2 Nos. 16,782.30
having DI/CI body and door, CF8M seat rings alongwith all necessary hardwares as per specifications and
complete in all respect.
Size: 200 mm NB (on delivery of each type-1 pumpsets)
7 --- Item description as above --- 2 Nos. 16,782.30
Size: 200 mm NB (on delivery of each type-2 pumpsets)
8 SITC of Flange ends Expansion Bellow (PN 1.0) as per EJMA standards and as per specs. and complete in all 4 Nos. 6,216.00
Size : 200 mm NB X 300 mm L (on delivery (Vertical and horizontal) of each pump type-1 pumpsets)
9 --- Item description as above --- 4 Nos. 6,216.00
Size : 200 mm NB X 300 mm L (on delivery (Vertical and horizontal) of each pump type-2 pumpsets)
10 --- Item description as above --- 1 Nos. 10,200.00
Size : 300 mm NB X 300 mm L (On Common Header near MSV)
11 MS PIPES & SPECIALS 40 Mtr. 2,585.40
Supply, Gas cutting of pipe, Fabrication of reducer & expander, welding, Installation, testing and commissioning
of MS pipe, Specials, reducer, expander, bend for Y-Joint with header, etc. conforming to IS 3589 flanges
confirming to IS 6392-PN-1.0, fabricated from MS. plate with necessary supports & anchoring. Pipe fabricated
from MS plate. (Excluding supply of flange) and complete in all respect.
Size : 219.1 mm OD x min. 6.3 mm Thk
Item Rate Amount
Description Qty Unit
12 --- Item description as above --- 25 Mtr. 4,533.66
Size : 323.9 mm OD x min. 7.1 mm Thk
13 Supply, Welding, Installation, Testing & Commissioning of MS flat machined faced flanges confirming to IS 16 Nos. 1,886.00
6392 & drilled as per IS-1538 with drilling off centre bolt holes and flange thickness as per PN 1.0 including
cutting & welding.
Size : 200 mm NB (Drilled)
14 --- Item description as above --- 8 Nos. 2,898.00
Size : 300 mm NB (Drilled)
15 --- Item description as above --- 1 Nos. 3,553.50
Size : 300 mm NB (Drilled Blind)
16 Flanged Joints of Pipes, Fittings and Specials: 12 Nos. 962.55
Supply, Installation, Making of Flanged DI /CI / GI / MS Pipes, Fittings and Specials Joints with all jointing
materials, rubber packing, nut bolts, labour etc.for complete connection.
Size : 200 mm dia.
17 --- Item description as above --- 4 Nos. 1,406.45
Size : 300 mm dia.
18 MONORAIL EOT WITH ELECTRIC CHAIN HOIST 1 Set 2,28,220.00
SITC of Electrically Operated Chain Hoist & Electrically operated Trolley, suitable to operate on Mono Rail
Girder having motorised motion in vertical lifting & cross travel, manufactured as per IS:6547-1972-Class-II &
IS-3177- Class-II, complete with electrically operated chain hoist & Electically operated geared trolley, brake,
chain-gear, motors, safety device, pendant push button, starter panel, cables from motor to starter panel and
all other required accessories like limit switches, panel, power supply system (Fastoon cable type), fasteners,
epoxy painting, etc. tested for over load as per IS complete as per specifications and complete in all respect.
Capacity : Min. 1.0 Ton. (At Ex. Pump House)
Lift : 10.00 m as mini. or as per site req.
Bay Length : 8.0 m min. or as per site req.
(w/o MONORAIL GIRDER & MS supporting structure)
19 Providing, Supply of Structure Steel at site of work with freight, loading, unloading carting, etc. including all 500 kg. 64.84
taxes and duties complete such as joints, channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates,
Chequered plates (min. 7 mm thickness) for cable trench etc. required for support structure of all Electro-
mechanical equipment, piping, etc. for support on floor / wall / beam / brackets etc. as per tender and IS.
20 Labour Charges for lowering, laying, Fixing with fabrication various size section of MS such as joints, channels, 500 kg. 13.07
angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered plates, for cable trench etc Complete with two
coats of red oxide and two coats of approved colour shade of epoxy paint as per relevant IS and as per
TOTAL OF MECHANICAL WORK WITHOUT GST
21 ELECTRICAL WORK 1 Set 38,951.13
TPN MCCB (For LT Service Obtaining Requirement)
SITC of 250A TPN microprocessor MCCB, LSIG (50kA) with inbuilt O/L, S/C & E/F protection with Extended
rotary handle, Terminal spreader, Auxiliary change over & Trip contact, with Outdoor Enclosure with canopy
2mm thick , Single/double door & Wall mounted/ stand mounted as per site requirement (with incoming &
outgoing cable entry at bottom )with Cable end boxes with RYB indicating lamp, Digital voltmeter, VSS,ON,OFF
& Trip indicating lamp etc as per Power supply company requirements & location. Including all civil works for
fixing of panel on wall.
(Wall mounted at Location as per PSC req.)
Item Rate Amount
Description Qty Unit
22 MEDIUM VOLTAGE PANEL BOARD (PMCC /APFC) 1 Set 7,86,000.00
SITC of PMCC Panel (50kA), compartmentalized, floor / Stand mounted as per site condition and requirement
with required modification / rectofication works as required, operating height maximum 1800/1900 mm,
Extensible on both ends, suitable for Manual & Auto operation -Local & through PLC/SCADA operation as per
site conditions complete in all respects as per Tender SLD / Specification / IS and including following as
(1) One no. Incoming feeder FP 250A Microprocessor MCCB (50kA), LSIG, with inbuilt O/C, S/C, & E/F
protection for I/c with Digital Voltmeter, Voltmeter selector switch, Digital Ammeter, Ammeter selector
switch, Power Factor Meter, MFM with RS-485 of Class-0.5, Indicating lamps R,Y,B,On,off,Trip, 3nos. 250A/5A,
Cl.-0.5 metering CT, CL 0.5 CT for APFC relay etc. Constant voltage/control voltage transformer 1500VA,
415V/230V AC, with tapping +/-5% in steps of 2.5%, 32A DP MCB complete in all respects.
(2) 250A TPN Main Aluminium busbars. (main busbars size with current density 0.8A/Sq.mm)
(3) 30 KW STAR -DELTA STARTER FEEDER (SUBM.): 2 NOS
30 KW or higher as per pump manufacturer recommendation Star-delta starter with 125A TPN Thermal
magnetic MCCB with Adjustable O/L & Adjustable S/C protection, 95A AC3 duty contactors (3 Nos), O/L Relay,
star-delta timer, MFM with RS-485, Resin Cast CT Cl: 0.5, MPR with RS-485, CBCT, SPP, PMU, A/M, L/R switch,
ON, OFF, TRIP Indication & Start, E-Stop & Reset pushbutton etc. for S/D starter. complete in all respects.
22 (4) 18.5 KW STAR -DELTA STARTER FEEDER (SUBM.): 2 NOS
18.5 KW or higher as per pump manufacturer recommendation Star-delta starter with 80A TPN Thermal
magnetic MCCB with Adjustable O/L & Adjustable S/C protection, 80A AC3 duty contactors (3 nos.), O/L Relay,
star-delta timer, Ammeter with ASS, Resin Cast CT Cl: 0.5(3 nos.),SPP, PMU, A/M, L/R switch, ON, OFF, TRIP
Indication & Start, E-Stop & Reset pushbutton etc. for S/D starter. complete in all respects.
(5) 63A TPN TM MCCB FEEDER : 1 No. ( for Spare)
Each feeder comprising of 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
(6) 32A TPN TM MCCB FEEDER : 4 Nos. (1 no. EOT with ECH at Pump house, 1 no. spare)
Each feeder comprising of 32A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
(7) 63A TPN TM MCCB FEEDER FOR ALL MCB FEEDERS: 1 set:
Incomer: 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
7.1) 3 nos. 32A 'C' curve 4P MCB feeders (for 1 no. Ind LDB & 2 nos. spare feeders)
7.2) 1 no. 32A 'C' curve 4P MCB with Time switch,32A contactor 4P,ON lamp feeders (for Outdoor LDB)
22 (8) APFC separate cubical compartment (minimum 40 KVAr) having 1 no. 100A TPN Thermal magnetic MCCB
50KA with adjustable overload and adjustable short circuit, 8 step APFC relay with RS 485, 1 no. 100 A/5A, Cl.-
1.0 CT for Ammeter, Digital Ammeter, ASS, 3 nos. 10 kVAR capacitor with 32A TPN D curve MCB,2 nos. 5 kVAR
capacitor with 16A TPN D curve MCB with capacitor Duty Contractor, A/M switch, On delay timer, Push
Buttons etc. Complete in all respects as per Specification, IS & SLD.
(9) Multiplication relay as required for dry run protection of pumps.
NOTE: 1). All MCCB shall be 50KA, Ics = 100% Icu, inbuilt protection with adj O/L and Adj.S/c (LSIG for MP
MCCB),Extended rotary handle, Terminal spreader, Auxiliary Change over contact and trip contact as
required.2) All MFM, ACB, Soft Starter,Temp.Scanner etc shall be with inbuilt RS
23 ICP Cubical a part of PMCC Panel as below: 1 Nos. 40,000.00
ICP cubicle compartment as a part of PMCC (as per SLD) panel with required input / output for field
instruments interfacing at terminal strip& comprising of
(a) Door mounted 1 no. Process indicator with 8 nos. relay output for start pump at high level and stop at low
level for Level transmitter ,UPS power ON Indication, etc.)
(b) Required separate isolation switches (DP MCB only) for incoming 230 V AC power mains from UPS &
outgoing power feed to 1 no. Process indicator , 1 Nos. Multiplication Relay (1 no. 1 input + 4 Output) for Dry
run protection of Pump at low-low level ,etc.
(c) Offline type UPS of suitable rating (min. 250 VA with 15-20 min. backup time ) mounted within cubicle on
main incoming power line with required isolation device (DP MCB) & outgoing feed to power supply
(d) Any other as required to complete the work and meet the tender requirement/specification.
24 SITC of Lighting Distribution Board (LDB) as under: 2 Nos. 7,497.69
SITC of 3 Phase 4 Wire 4P, double door Prewired LDB each for Indoor Lighting & Outdoor Lighting Suitable to
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB (9 nos.) & 16A SP MCB (9 nos.)
Item Rate Amount
Description Qty Unit
25 SITC of stand / wall mounting type MS Junction Box, minimum 2.5mm thick, with detachable cable gland plate 4 Nos. 1,906.78
of 3mm thick, duly powder coated, with earthing terminals, steel structure stand for mounting of JB, etc. for
Jointing/Termination suitable for 1.1 kV Submersible Flexible Copper Power cable with Aluminium/ Copper
armoured power cable from PMCC . Scope shall include providing suitable rating AL busbars, Support
insulators, Crimping type lugs,nuts,bolts,washers etc. complete in all respects as instructed by E.I.C. Drawing
shall be got approved before SITC of the same. Lugs of cables shall not be connected directly. (Structure steel
for Stand shall be measured separately)
JB of minimum Size: 300mm x 300mm x 100mm or higher as required. or higher as required (for Pump)
26 SITC of stand / wall mounting type MS Junction Box, minimum 2.5mm thick, with detachable cable gland plate 4 Nos. 1,906.78
of 3mm thick, duly powder coated, with earthing terminals, steel structure stand for mounting of JB, etc. for
Joining/Termination suitable for 1.1 kV Submersible Flexible Control Cables of Submersible pump with control
cable from PMCC. Scope shall include providing Terminal connectors for connecting control cable, copper lugs,
etc. complete in all respects as instructed by E.I.C. 20% additional/spare Terminal connector shall be provided.
Drawing shall be got approved before SITC of the same. SMC/FRP/Bakelite separator shall be provided
between Power cable section & Control cable section. Lugs of cables shall not be connected directly (Structure
steel for Stand shall be measured separately).
JB of minimum Size: 300mm x 300mm x 100mm or higher as required. or higher as required (for Pump)
27 SITC of LCS pushbutton station ON & OFF (E-stop) set complete with Enclosure, necessary mounting/ fixing 4 Nos. 2,008.47
arrangement on wall / pipe support etc. to be installed near motors for remote operation, etc. as per IS and
specifications. (including structural steel) (For Pump)
28 LOW VOLTAGE (LT) CABLES 25 Mtr. 783.00
Supply, laying, testing and commissioning of 1.1 kV, A2XFY(X)/2XWY(X) XLPE insulated (IS 7098) AL / Cu
stranded conductor, Extruded innersheath cables as per specification & IS.
The cable when laid outside the building shall be laid underground in trench with brick & sand protection/in
DWC pipes as per specified method and shall be laid in prepared trench/ on cable tray when laid inside the
SITC of 3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
29 3C x 10 sq. mm. A2XFY Cable (2 runs for PMCC to 2 nos. 30 kW Subm. pump Junction box) 80 Mtr. 128.12
30 SITC 3C x 6 sq. mm. A2XWY Cable (2 runs for PMCC to 2 nos. 18.5 kW Subm. pump Junction box) 80 Mtr. 104.12
31 SITC 4C x 6 sq. mm. A2XFY(X) Cable (For 1 no. Indoor LDB, Outdoor LDB) 50 Mtr. 123.12
32 SITC 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable (For 1 no. TPN MCCB for EOT with ECH at Pump House, 4 nos. pump 200 Mtr. 267.12
PMU & for 4 nos. street light)
33 5C x 2.5 sq.mm. 2XWY(X)Cable (for LCS) 80 Mtr. 220.00
34 SITC 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (APFC sensing C.T) 20 Mtr. 175.10
35 SITC Single core 95sq. mm. PVC insulated circular unsheathed copper conductor flexible Cable (For Power 20 Mtr. 867.12
supply Metering Panel to I/c MCCB Unit)
36 CABLE END TERMINATION AND CONNECTION: 2 Nos. 840.00
SITC of Double compression Ni-Plated brass cable glands and crimping type Bimetallic lugs / sockets with
necessary tools and equipments as specified in specifications and IS. The glands and lugs / sockets shall be
suitable for cable size and type mentioned below & as per specifications.
1) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common earth
2) The job also includes, if necessary, supply & fixing of extension busbar of same material on MCCB or panel
board terminal / connector to connect more than one no. of parallel cables or to connect higher size cable to
lower size unit. The job also includes earthing the glands and armour of the cable with common earth bar or
flexible copper mesh.(Cable termination qty. shall be as per site requirement)
3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
37 3C x 10 sq. mm. A2XFY Cable (2 runs for PMCC to 2 nos. 30 kW Subm. pump Junction box) 8 Nos. 126.00
38 3C x 6 sq. mm. A2XWY Cable (2 runs for PMCC to 2 nos. 18.5 kW Subm. pump Junction box, 2 runs for PMCC to 16 Nos. 110.00
2 nos. 22 kW Subm. pump Junction box)
39 4C x 6 sq. mm. A2XFY(X) Cable (For 1 no. Indoor LDB, Outdoor LDB) 4 Nos. 111.00
40 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable (For 1 no. TPN MCCB for EOT with ECH at Pump House, 4 nos. pump 18 Nos. 65.15
PMU & for 4 nos. street light)
41 5C x 2.5 sq.mm. 2XWY(X)Cable (for LCS) 8 Nos. 180.00
42 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (APFC sensing C.T) 2 Nos. 49.13
43 Single core 95sq. mm. PVC insulated circular unsheathed copper conductor flexible Cable (For Power supply 10 Nos. 47.11
Metering Panel to I/c MCCB Unit)
Item Rate Amount
Description Qty Unit
44 CABLE TRAY 30 Mtr. 388.00
SITC of G.I. (hot dip galvanised )Ladder type medium duty (2mm thick) Cable Tray with necessary bends, tees,
reducers, covers and clamps for fixing. All material shall be Hot dip galvanised as per Specification. And
including all accessories.
300 x 75 mm - Ladder type
45 150 x 50 mm - Ladder type 70 Mtr. 336.00
46 Supply, laying and erection of 75 mm ID approved make Double Walled Corrugated pipes (DWC) of 50 Mtr. 161.15
polyethelene (confirming to IS-14930 II) with necessary connecting accessoies of same material at required
depth for laying of cable below ground / road surface for enclosing cable and back filling the same to make
ground as per original. (LT cable etc)
47 Cable Trench, Laying & Installation of Cable: Making cable trench in soft soil of suitable width of 90cms deep 70 Mtr. 46.46
for laying cable, Sand cushioning and brick protection on sides and on top all over the run and back filling
the same and making the surface as normal ground as per IS & Specification. (For laying of LT cable in ground)
48 Cable Protection/ Covering in Trench: Cable Covering with second class bricks or cement tiles laid cover the 20 Mtr. 133.31
cable (top) & also on both side with sand bedding/cusioning of 75mm.& covering of 150mm Layer of sand
above cable (16 bricks per meter.) as per IS & Tender Drg/ Specification. (For HT/LT cable protection)
complete in all respects as instructed by EIC.
49 CHEMICAL EARTHING SYSTEM 4 Set 7,028.82
SITC of Maintenance free chemical earthing with earthpit of minimum bore size dia. 225mm Safe Earthing
Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987 /Tech spec. made of corrosion free Hot dip
Galvanised (min 150 Microns) Pipes having Outer pipe dia of 76 mm , Inner corrosion free Hot dip galvanised
(80 to 100 micron) pipe dia of 26 mm with copper flat strip type connection terminal 14mm dia with constant
ohmic value surrounded by highly conductive corrosion resistant chemical compound with high charge
dissipation suitable for electrical installation & 3Mtr. length of Pipe with two nos. 25Kg. bag of Back filling
compound. (2 nos. for PMCC panel & 2nos. for all elect. Equipments)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
50 SITC of 50mm(w) x 8mm(T) etc. sizes as required, HOT dip galvanized GI Strip including supply & fixing using GI 184 Kg. 77.17
spacers, saddles when laid inside the building and inclusive of excavation & refilling of earth when laid outside
the building & interconnection with earth pit & all electro-mechanical equipments.
(50X6 G.I Strip wt.2.3 kg/m, 2.3x80Mt.=184kg.)
51 Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes as required, HOT dip galvanized GI Strip including 36 Kg. 77.17
supply & fixing using GI spacers, saddles when laid inside the building and inclusive of excavation & refilling of
earth when laid outside the building & interconnection with earth pit & all electro-mechanical equipments.
(25X3 G.I Strip, 0.6 Kg/m, 0.6x60Mt.=36Kg.)
52 SITC of HOT Dip Galvanized iron strip wire 8 SWG (For LDB,LCS, etc.) 10 Kg. 77.17
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 100Mt.=10.3 Kg.)
53 INTERNAL WIRING 40 Mtr. 78.06
SITC of Mains & outlet points wiring with 1.1 kV grade FRLS PVC insulated ISI marked flexible stranded copper
conductor wires with medium class min. 25mm. dia. Electrical grade PVC pipe and accessories to be erected
concealed in / to be run on surface / wall / ceiling with following sizes as mentioned below. The unit rate
wirings shall be with connector, PVC junction box, wires, holder, ceiling rose, angle holder, switch, sockets,
switch board, brass chromium / cadmium plated machine screws, phase and neutral wires, green Earth
continuity wires etc. as required to complete wiring from LDB panel to the final outlet termination points. The
wiring shall be as per IS:732, IS:4648 and as per tender specification / IS.
(a) SITC of Mains wiring with 3 wire 1.5 sq.mm.
54 same as above, but (b) SITC of Mains wiring with 3 wire 2.5 sq.mm as per tender specification & IS. 40 Mtr. 96.06
55 same as above, but (c) SITC of Mains wiring with 4 wire 1.5 sq.mm as per tender specification & IS. 50 Mtr. 86.06
56 same as above, but (d) SITC of Mains wiring with 4 wire 2.5 sq.mm as per tender specification & IS. 50 Mtr. 119.06
57 SITC of Point wiring for Light / fan / Bell / Primary Point with 2nos. 1.5 sq. mm & earth wire of 1.5 sq. mm 11 Nos. 326.59
(green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multistrand copper wires , pipe to be erected
concealed in flushed on wall / ceiling, complete with 6A Tissino Type ISI marked flush type switch / bell push &
accessories erected on metal / PVC Box covered with 3 mm thick PC (Polycarbonate) / Acrylic sheet with
necessary lamp holder / ceiling Rose / H. D. connector as directed with medium class Rigid PVC pipe &
Item Rate Amount
Description Qty Unit
58 SITC of 6A independent Plug with 2nos. 1.5 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) both 2 Nos. 288.50
are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand copper wires with medium class Rigid PVC pipe
and accessories to be erected on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and tissino type
switch erected with earth continuity connection erected on Metal / PVC box covered with 3 mm thick
PC(Polycarbonet) / Acrylic sheet.
59 SITC of 6/16A independent Plug with 2nos. 4 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) 2 Nos. 1,005.00
both are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand copper wires with medium class Rigid PVC
pipe and accessories to be erected on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and tissino type
switch erected with earth continuity connection erected on Metal / PVC box covered with 3 mm thick
PC(Polycarbonet) / Acrylic sheet. (1 no. LT Room, 1 no. Pump House)
60 SITC of One 300/380 mm dia. Ex fan 16A independent Plug point near Ex. Fan with 2nos. 4 sq.mm Cu. Mains 2 Nos. 1,005.00
size wiring & earthwire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC pipe and accessories to be erected on wall / ceiling,
complete with ISI marked 3Pin socket and tissino type switch erected with earth continuity connection erected
on Metal / PVC box covered with 3 mm thick PC(Polycarbonet) / Acrylic sheet. Plug point shall be near Ex.Fan.
61 SITC of 380mm sweep 1400 R.P.M exhaust fan, capacitor type, having double ball bearing, M.S.blades, 2 Nos. 3,052.47
mounting frame, forearms, suitable to operate on 230V,50 HZ AC supply conforming to IS: 2312.Fan shall be
painted with epoxy grey colour controlled by one 6 A flush type switch on board and 6A plug point near Ex. fan.
62 SITC of Single Phase 20A 3 Pin Metal clad Industrial Type Socket with plug top and 20A SPMCB, suitable for 2 Nos. 820.00
flush mounting, in 16 SWG MS box of suitable size and covered with 3 mm thick electrical grade hylam sheet or
equivalent ISI marked Electrical grade Bakelite sheet and earthing with 2.5 sq.mm insulated copper wire run
inside the conduit including interconnections etc. complete as required.
(1 no. LT Room, 1 no. Pump House)
63 SITC of Sheets steel powder coated weather proof enclosure with One no. 32A, 415V 4P MCB for Motor & 1 Nos. 765.39
Inductive load (C Curve) having 10 KA breaking capacity & confirms to IS: 8828. (1 no. for EOT with ECH at P.H)
64 1200mm sweep ceiling fan, capacitor type, having double ball bearing 450mm down rod, canopies, shackle, 1 Set 1,581.51
rubber bush, blades, electronic speed regulator, suitable to operate on 230V,50Hz AC supply conforming to IS:
374/1979.Fan shall be painted with white colour.(1 no. LT Room, 1 no. at P.H)
65 LED LIGHT FIXTURES & LIGHTING: 4 Nos. 293.26
SITC of Indoor wall mounting 20Watt or up to 25% higher wattage LED 4 feet Tube Light indoor fittings with
LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall be
made of thick sheet Steel conforming to IS: 513/CRCA polyester powder coated and high U.V. & corrosion
resistance with diffuser and/or Polycarbonate optics with company mark/name
120 to 300 V,Power Factor more than 0.9, THD < 20 %,
CCT 4000 K to 6500K, Uniformity ratio >0.7,
Luminaries efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80 Certificates)
Tube Light with integral / non-integral driver, Surge-4KV,IP-20, 4 feet, Cat-III
66 Item description as above SITC of 7 watts LED Lamps integral type,cool white with PC diffuser suitable for B22 1 Nos. 111.00
LAMP holder (1 no. LT Room)
67 SITC of 40W LED Surface / Wall mounted LED Flood Light fittings with High power White LEDs wattage of 2 Nos. 5,144.28
1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure
die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser
and Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Indoor use: (at Pump House)
68 SITC of 'B' class galvanised iron pipe 32 mm outside dia 45 cms long duly welded on 20 cms x 20 cms x 3 mm 6 Nos. 553.86
thick M.S. base plate, erected on wall or corner for mounting luminaries with necessary hardware materials
duly painted for wall mounting indoor flood light fixtures on Wall of Buildings & post top lantern.
Item Rate Amount
Description Qty Unit
69 EXTERNAL LIGHTING (Flood LIGHT): 4 Nos. 6,029.70
SITC of 70W LED Wall mounted LED Flood Light fittings with High power White LEDs wattage of 1Watt and
above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast
aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Outdoor use: (for area lighting)
70 EXTERNAL LIGHTING (STREET LIGHT): 4 Nos. 10,619.32
SITC of Street Light Pole, steel tubular swaged type, 7.5 meter long with single arm & M.S.base plate with pipe
cap and over hung 1.5 m long having dia to suit the socket of 240V LED street light fixtures. Street light pole
unit rate shall be with (i) IP 65 SMC box of size 20 x 15 x 15 cms. with MCB & terminal strip inside the box
with hinged/sliding door (ii) 50mm dia, B class GI pipe bracket min.1.5mtr long for Incoming & outgoing cable
(iii)MS Cable Clamp of 25 x 3mm (iv)SITC of 1.5 Mtr.single Arm bracket of medium duty MS pipe of 4.2 cms.
Out side dia complete with suitable sleeve tubing 45 cms. long of required size of pole top etc. and having
spread of 1.5.mtr. length with 110 deg.(v) Complete painted with one coat of Red oxide / PU base primer and
two coats of Aluminium / PU paint for Pole,Arm, pipe etc.
71 SITC of 70W LED Street light fittings with High power White LEDs wattage of 1Watt and above assembled on 4 Nos. 5,918.70
single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum housing with
smooth finish powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/ lenses
with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
Street Light (IP-65), Surge -4KV, 70 watt Cat-III
72 SITC of M-20 / 1:2:4 cement concrete foundation for Street light pole & 70 % PCC from bottom including 4 Nos. 1,282.12
excavation for the pole of size 60 x 60 x 120 cms. Deep in below ground level with plinth of 45 cms x 45 cms(or
45 cms dia x 45 cms) high upper ground level with necessary curing and finishing in approved manner.
73 SAFETY ACCESSORIES 1 Nos. 8,586.26
SITC of following safety accessories complete with necessary fixing brackets, other accessories and tools etc. as
required to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher of 6.5kg capacity with necessary clamps made from
x 6 mm M.S. Flat with nut & bolts grouted in wall complete.
(For 1 no. for LT Room)
74 Supplying of standard first AID box with antiseptic cream, medicine for use on wounds due burn, crepe 1 Nos. 297.00
bandage, guage bandage, medicated ready to use bandage (Band-aid) adhesive tape for medicinal user,
scissors, antiseptic solution (Savlon or similar) etc. (All above contents shall be of standard makes)
(For 1 no. For LT Room)
75 Supply & fixing of printed instruction (First Aid) Chart both in English and Gujarati and duly framed with front 1 Nos. 129.06
glasses, for treatment of person suffering from electric shock. (For 1 no. For LT Room)
76 Supply and fixing of 20 W fluorescent lamp operated emergency light with maintenance free battery for 3 1 Nos. 2,670.00
hours operation during mains power failure.
(For 1 no. LT Room)
77 Supply and laying of Synthetic Insulating Mat of Class - A of min. thickness 2mm as per IS:15652 and with 3 Sq.mtr 1,017.00
good electrical insulation property for 1.1KV/3.3KV as per site requirement. (For LT Panel) .
TOTAL OF ELECTRICAL WORKS WITHOUT GST
78 PRESSURE MEASURING SYSTEM 4 Nos. 5,413.00
Supply, installation, testing & commissioning of Diaphragm Type pressure guage having 150 mm dial with
necessary fittings/accessories in SS
(manifold valve, nipples etc.) complete in all respects and as per specs.
Range : 0 - 4 Kg/cm2 (at each pump discharge line)
Item Rate Amount
Description Qty Unit
79 LEVEL MEASURING SYSTEM FOR SUMP 1 Nos. 59,436.00
Supply, installation, testing and commissioning of Ultrasonic type Level Transmitter with remote type
transmitter with 10meter cable between Sensor and Transmitter along with all required accessories, Weather
proof enclosure for transmitter for outdoor application, mounting stand , etc. complete in all respects as per
specification and having following measurement ranges for liquid (Water) application:
Meas. Range: upto 10 m (at sump )
80 Supply, installation, testing and commissioning of Float type Level Switch along with 10 mtr. Cable and WP 1 Nos. 12,802.00
Junction Box (at sump for dry run protection of pumps through relay multiplication in PLC), etc., complete in
all respects and as per specification.
Meas. Range: upto 10 m (at sump )
81 ELECTRO MAGNETIC FLOWMETER MAINS OPERATED Supply, installation, testing and 1 Nos. 1,34,422.00
commissioning of Full Bore Electromagnetic flow meter comprising of IP-68 Sensor , IP-66 remote type
transmitter with 20 m cable between sensor and transmitter along with all mounting accessories, Weather
proof enclosure for transmitter, hardware, mounting stand, etc.
as per specification and to complete the work in all respect as per site condition necessary connection with
pipe and shall have following size.
Meter Size: 300 mm (At Pump common Header )
Pipe Size : 300 mm
82 INSTRUMENT CABLE & ACCESSORIES 50 Mtr. 203.00
'Supply, Laying, Installation, Connection, Termination, Testing & Commissioning of Instrument Cables as per
The unit rate shall include
a)Supply, loading & unloading of the cable at site from store.
b)Shifitng of cable from site store to place of installation.
c)Fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely.
d)Excavation, back filling and levelling of ground alongwith laying of fine sand, protection bricks and other
necessary civil material for laying cables outside the building.
f)Testing and submission of sketches & reports of all the cables laid.
83 SIGNAL CABLE 50 Mtr. 176.00
84 CABLE END TERMINATION AND CONNECTION : 4 Nos. 224.00
'Supply, fixing, connection, testing and commissioning of double compression brass cable glands and crimping
type Bimetalic lugs / sockets with necessary tools and equipments as specified in specifications and IS
complete in all respects. The glands and lugs / sockets shall be suitable for cable size and type mentioned
above. The job also includes earthing the glands and armour of the cable with common earth bar or flexible
copper mesh as applicable.
85 SIGNAL CABLE 6 Nos. 224.00
TOTAL OF INSTRUMENTATION WORK WITHOUT GST
Electro-Mechanical and Instrumentation Work for PS-3 (O-3)
Item Rate Amount
Description Qty Unit
1 MECHANICAL WORK 2 Set 2,07,662
SUBMERSIBLE NONCLOG PUMP SET
Supply, Installation, Testing and Commissioning (SITC) of Submersible NC Pump-Motor set suitable for
sewage application with semi-open or enclosed or suitable type Impeller & wear Rings in CF8M with CI FG
260 Casing & casing cover, SS 410 shaft & with motor suitable for 3-Phase, 415 V, 50 Hz., AC induction Air
filled dry type submersible motor of mini. rating as specified having max. 1500 RPM sync. speed, insulation
Class 'F' With temp. rise limited to class B and IP-68 protection.
The scope shall include all required accessories viz. automatic coupling device, SS-304 heavy duty & of
suitable size double guide pipes of length to suit the sump height with required supports, SS-304 or
suitable stainless steel grade Chain with shackles (shall be with dual hook / shackles of 100 mm or suitable
higher size at app. every 1.5m C-C distance) & of length as per sump height + min. 3m, Submersible Power
& control cable (copper flexible & stranded type conductor of reqd. cores & size for each pump motor set)
& length of sump height + min. 5 m long each run with necessary electrical termination connection at
junction box / starter panel and RCC foundation blocks for auto coupling & delivery bend, PMU etc.
complete as per IS, Tender Drawings and Specification and also including in scope any other parts /
accessories / fittings required to complete the work in all respects & satisfactory operation of pump set.
Pump Capacity: 50 m3 / hr.,
Motor Rating: min. 7.5 kW (or higher rating as reco. by pump manufacturer)
Over all Efficiency at Duty- min. 39%
2 VALVES: 2 Nos. 4,067.85
SITC of CI/ DI Double Flanged, Manually operated Sluice Valve confirming to IS 14846, PN 1.0 of following
sizes with SS 304 seat rings and SS spindle with hot dipped galvanised hardwares, bolts, nuts & washers
etc. as per IS and Specification & complete the work in all respects.
Size: 100 mm NB (on delivery of each pumpsets)
3 --- Item description as above --- 1 Nos. 4,067.85
Size : 100 mm NB (on common header)
4 SITC of Non slam, flanged, CI/DI Single Door type Non Return Valve conforming to IS 5312 (Part-1), PN 1.0, 2 Nos. 5,852.85
having DI/CI body and door, CF8M seat rings alongwith all necessary hardwares as per specifications and
complete in all respect.
Size: 100 mm NB (on delivery of each pumpsets)
5 DI PIPES 450 kg 155.00
SITC of Double Flanged DI Pipes confirming to IS 8329-2000, class K9 with connections complete for
delivery and header lines and as per specifications. The scope also includes connection with main
header/rising main.
Size: 80 mm to 300 mm
6 DI FITTINGS 250 kg 155.00
SITC with sution, delivery / header, testing and commissioning of Flanged DI Fittings and Specials like
deg. Bend, Drilled / Blind Flanges, Reducer / enlarger, TEE, etc. as required to complete the piping and
connection of pumps with header/rising main conforming to IS
Size : 80 to 300 mm dia
7 Flanged Joints of Pipes, Fittings and Specials: 20 Nos. 548.55
Supply, Installation, Making of Flanged CI / DI / MS Pipes, Fittings and Specials Joints with all jointing
materials, rubber packing, nut bolts, labour etc.for complete connection.
Size: 100 mm dia
Item Rate Amount
Description Qty Unit
8 Manual Mesh Screen with Screening Collecting Trough/ Box 1 Nos. 1,59,760
SITC of Manual Mesh Screen having following size, made of SS 304 material having round bars of size 9 mm
dia. with clear bar opening as specified here below, suitably welded in outer frame of equal Leg SS angle of
size 50 mm x 50 mm x 6 mm thick or higher, with intermediate support at required locations, complete as
per specs. & shall also including followings:
The screen shall be with SS perforated Screening Material Collection Box/Trough at bottom end of screen
having size as specified, fabricated from 3 mm thk. SS sheet, screen shall be suitable to lower in MCP
guide channel, complete of following size with SS lifting chain and as per specifications with all necessary
hardware, SS nuts, bolts & washers, sacrificial Brass lugs on sides, min. two lifting lugs/hooks & SS lifting
chain having intermediate link/chain of 300 mm dia. or suitable higher size at every 1.5 m distance with
shackle, etc. complete in all respects and provided with 1 set of cleaning rake with each screen complete as
per specification and complete in all respect.
Screen Size: 500 mm (W-or actual channel width as per site) x 600 mm (H)
Screening Box/Trough size: 450 mm (W-or suit actual screen width as per site) x 150 mm (H) x 200 mm (D)
Opening: 50 mm x 50 mm sq. opening.
(w/o Guide channel & MS supporting structure)
(Note: Screen suitable for 600 mm width or to suit site requirement.)
9 MONORAIL EOT WITH ELECTRIC CHAIN HOIST 1 Set 2,28,220.00
SITC of Electrically Operated Chain Hoist & Electrically operated Trolley, suitable to operate on Mono Rail
Girder having motorised motion in vertical lifting & cross travel, manufactured as per IS:6547-1972-Class-II
& IS-3177- Class-II, complete with electrically operated chain hoist & Electically operated geared trolley,
brake, chain-gear, motors, safety device, pendant push button, starter panel, cables from motor to starter
panel and all other required accessories like limit switches, panel, power supply system (Fastoon cable
type), fasteners, epoxy painting, etc. tested for over load as per IS complete as per specifications and
complete in all respect.
Capacity : Min. 1.0 Ton. (At Pump House)
Lift : 5-10 m as mini. or as per site req.
Bay Length : 2-5 m min. or as per site req.
(w/o MONORAIL GIRDER & MS supporting structure)
Note: (1) Minimum as specified capacity or higher as per requirement such that ECH capacity is min.1.25
times of the pump/motor OR single heaviest component to be lifted within pump house.
10 Item description as above and of following size complete, 1 Set 2,28,220.00
Capacity : 1.0 Ton. Min. (For Manual Screen)
Lift : 5-10 m as mini. or as per site req.
Bay Length : 2-5 m min. or as per site req.
Note: (1) Minimum as specified capacity or higher as per requirement such that ECH capacity is min.1.25
times single heaviest component to be lifted.
11 SITC of Manually operated C.I. Thimble mounted Sluice Gate conforming to AWWA C 501 or IS : 13349 - 1 Nos. 1,80,040
1992 Class - 1 with rising spindle, single faced, wall thimble mounted, handwheel, flush bottom closing,
flange back frame, head stock, Spindle with supports brackets having length as specified or to suit site
condition, suitable for seating as well as unseating water head, complete in all respect.
Size : 250 mm X 250 mm - approx. 5.70 m spindle length (At Inlet Pipe)
12 Providing, Supply of Structure Steel at site of work with freight, loading, unloading carting, etc. including all 500 kg 64.84
taxes and duties complete such as joints, channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates,
Chequered plates (below 10mm thickness) for cable trench etc. required for support structure of all Electro-
mechanical equipment, piping, etc. for support on floor / wall / beam / brackets etc. as per tender and IS.
13 Labour Charges for lowering, laying, Fixing with fabrication various size section of MS such as joints, 500 kg 13.07
channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered plates, for cable trench etc
Complete with two coats of red oxide and two coats of approved colour shade of epoxy paint as per
relevant IS and as per specification.
TOTAL OF MECHANICAL WORK WITHOUT GST
Item Rate Amount
Description Qty Unit
14 ELECTRICAL WORK 1 Set 38,951.13
TPN MCCB (For LT Service Obtaining Requirement)
SITC of 250A TPN microprocessor MCCB, LSIG (50kA) with inbuilt O/L, S/C & E/F protection with Extended
rotary handle, Terminal spreader, Auxiliary change over & Trip contact, with Outdoor Enclosure with
canopy 2mm thick , Single/double door & Wall mounted/ stand mounted as per site requirement (with
incoming & outgoing cable entry at bottom )with Cable end boxes with RYB indicating lamp, Digital
voltmeter, VSS,ON,OFF & Trip indicating lamp etc as per Power supply company requirements & location.
Including all civil works for fixing of panel on wall.
(Wall mounted at Location as per PSC req.)
15 MEDIUM VOLTAGE PANEL BOARD (PMCC /APFC) 1 Set 4,94,200.00
SITC of PMCC Panel (50kA), compartmentalized, Stand mounted, operating height maximum 1800/1900
mm, Extensible on both ends, suitable for Manual & Auto operation -Local & through PLC/SCADA operation
as per site conditions complete in all respects as per Tender SLD / Specification / IS and including following
(1) One no. Incoming feeder FP 250A Microprocessor MCCB (50kA), LSIG, with inbuilt O/C, S/C, & E/F
protection for I/c with Digital Voltmeter, Voltmeter selector switch, Digital Ammeter, Ammeter selector
switch, Power Factor Meter, MFM with RS-485 of Class-0.5, Indicating lamps R,Y,B,On,off,Trip, 3nos.
250A/5A, Cl.-0.5 metering CT, CL 0.5 CT for APFC relay etc. Constant voltage/control voltage transformer
1500VA, 415V/230V AC, with tapping +/-5% in steps of 2.5%, 32A DP MCB complete in all respects.
(2) 250A TPN Main Aluminium busbars. (main busbars size with current density 0.8A/Sq.mm)
(3) 7.5 KW STAR-DELTA STARTER FEEDER (SUBM.): 2 NOS
7.5 KW or higher as per pump manufacturer recommendation Star-delta starter with 40A TPN Thermal
magnetic MCCB with Adjustable O/L & Adjustable S/C protection, 50A AC3 duty contactors (3 nos.), O/L
Relay, star-delta timer, Ammeter, Resin Cast CT Cl: 1.0,SPP, PMU, A/M, L/R switch, ON, OFF, TRIP
Indication & Start, E-Stop & Reset pushbutton etc. for S/D starter. complete in all respects.
(4) 63A TPN TM MCCB FEEDER : 1 No. (for Spare)
Each feeder comprising of 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
15 (5) 32A TPN TM MCCB FEEDER : 4 Nos. (1 no. EOT with ECH at PH, 1 no. EOT with ECH at screen, 2 nos.
Each feeder comprising of 32A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
(6) 63A TPN TM MCCB FEEDER FOR ALL MCB FEEDERS: 1 set:
Incomer: 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
a) 3 nos. 32A 'C' curve 4P MCB feeders (for 1 no. Ind LDB, & 2 nos. spare feeders)
B) 1 no. 32A 'C' curve 4P MCB with Time switch,32A contactor 4P,ON lamp feeders (for Outdoor LDB)
(7) APFC separate cubical compartment (minimum 10 KVAr) having 1 no. 32A TPN Thermal magnetic
MCCB 50KA with adjustable overload and adjustable short circuit, 8step APFC relay with RS 485, 1 no.
A/5A, Cl.-1.0 CT for Ammeter, Digital Ammeter, ASS, 1 no. 1 kVAR capacitor with 16A TPN D curve MCB,
nos. 2 kVAR capacitor with 16A TPN D curve MCB, 1 no. 5 kVAR capacitor with 16A TPN D curve MCB with
capacitor Duty Contractor, A/M switch, On delay timer, Push Buttons etc. Complete in all respects as per
Specification, IS & SLD.
(8) Multiplication relay as required for dry run protection of pumps.
NOTE: 1). All MCCB shall be 50KA, Ics = 100% Icu, inbuilt protection with adj O/L and Adj.S/c (LSIG for MP
MCCB),Extended rotary handle, Terminal spreader, Auxiliary Change over contact and trip contact as
required.2) All MFM, ACB, Soft Starter,Temp.Scanner etc shall be with inbuilt RS
Item Rate Amount
Description Qty Unit
16 ICP Cubical a part of PMCC Panel as below: 1 Nos. 40,000
ICP cubicle compartment as a part of PMCC (as per SLD) panel with required input / output for field
instruments interfacing at terminal strip& comprising of
(a) Door mounted 1 no. Process indicator with 4 nos. relay output for start pump at high level and stop at
low level for Level transmitter ,UPS power ON Indication, etc.)
(b) Required separate isolation switches (DP MCB only) for incoming 230 V AC power mains from UPS &
outgoing power feed to 1 no. Process indicator , 1 Nos. Multiplication Relay (1 no. 1 input + 2 Output) for
Dry run protection of Pump at low-low level ,etc.
(c) Offline type UPS of suitable rating (min. 250 VA with 15-20 min. backup time ) mounted within cubicle
on main incoming power line with required isolation device (DP MCB) & outgoing feed to power supply of
(d) Any other as required to complete the work and meet the tender requirement/specification.
17 SITC of Lighting Distribution Board (LDB) as under: 2 Nos. 7,497.69
SITC of 3 Phase 4 Wire 4P, double door Prewired LDB each for Indoor Lighting & Outdoor Lighting Suitable
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB (9 nos.) & 16A SP MCB (9 nos.)
18 SITC of stand / wall mounting type MS Junction Box, minimum 2.5mm thick, with detachable cable gland 2 Nos. 1,906.78
plate of 3mm thick, duly powder coated, with earthing terminals, steel structure stand for mounting of JB,
etc. for Jointing/Termination suitable for 1.1 kV Submersible Flexible Copper Power cable with Aluminium/
Copper armoured power cable from PMCC . Scope shall include providing suitable rating AL busbars,
Support insulators, Crimping type lugs,nuts,bolts,washers etc. complete in all respects as instructed by
E.I.C. Drawing shall be got approved before SITC of the same. Lugs of cables shall not be connected
directly. (Structure steel for Stand shall be measured separately)
JB of minimum Size: 300mm x 300mm x 100mm or higher as required. or higher as required (for Pump)
19 SITC of stand / wall mounting type MS Junction Box, minimum 2.5mm thick, with detachable cable gland 2 Nos. 1,906.78
plate of 3mm thick, duly powder coated, with earthing terminals, steel structure stand for mounting of JB,
etc. for Jointing/Termination suitable for 1.1 kV Submersible Flexible Copper control cable with Aluminium/
Copper armoured power cable from PMCC . Scope shall include providing suitable rating AL busbars,
Support insulators, Crimping type lugs,nuts,bolts,washers etc. complete in all respects as instructed by
E.I.C. Drawing shall be got approved before SITC of the same. Lugs of cables shall not be connected
directly. (Structure steel for Stand shall be measured separately)
JB of minimum Size: 300mm x 300mm x 100mm or higher as required. or higher as required (for Pump)
20 LOW VOLTAGE (LT) CABLES 25 Mtr. 783.00
Supply, laying, testing and commissioning of 1.1 kV, A2XFY(X)/2XWY(X) XLPE insulated (IS 7098) AL / Cu
stranded conductor, Extruded innersheath cables as per specification & IS.
The cable when laid outside the building shall be laid underground in trench with brick & sand
protection/in DWC pipes as per specified method and shall be laid in prepared trench/ on cable tray when
laid inside the building.
SITC of 3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
21 3C x 2.5 sq. mm. 2XWY Cable (2 runs for PMCC to 2 nos. 7.5 kW Subm. pump Junction box) 80 Mtr. 211.10
22 4C x 6 sq. mm. A2XFY(X) Cable (For 1 no. Indoor LDB, Outdoor LDB) 50 Mtr. 78.00
23 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable (For 1 no. TPN MCB for EOT with ECH at Pump House,1 no. ECH at 200 Mtr. 81.00
Screen, 2 nos. pump PMU & for 4 nos. street light)
24 5C x 2.5 sq.mm. 2XWY(X)Cable (for LCS) 40 Mtr. 220.00
25 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (APFC sensing C.T) 20 Mtr. 175.10
26 Single core 95sq. mm. PVC insulated circular unsheathed copper conductor flexible Cable (For Power 20 Mtr. 867.12
supply Metering Panel to I/c MCCB Unit)
Item Rate Amount
Description Qty Unit
27 CABLE END TERMINATION AND CONNECTION: 2 Nos. 838.00
SITC of Double compression Ni-Plated brass cable glands and crimping type Bimetallic lugs / sockets with
necessary tools and equipments as specified in specifications and IS. The glands and lugs / sockets shall be
suitable for cable size and type mentioned below & as per specifications.
1) Earthing the glands and armouring with earthing clamp and jumper and also connecting to common
2) The job also includes, if necessary, supply & fixing of extension busbar of same material on MCCB or
panel board terminal / connector to connect more than one no. of parallel cables or to connect higher
size cable to lower size unit. The job also includes earthing the glands and armour of the cable with
common earth bar or flexible copper mesh.(Cable termination qty. shall be as per site requirement)
3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
28 3C x 2.5 sq. mm. 2XWY Cable (2 runs for PMCC to 2 nos. 7.5 kW Subm. pump Junction box) 8 Nos. 110.00
29 4C x 6 sq. mm. A2XFY(X) Cable (For 1 no. Indoor LDB, Outdoor LDB) 4 Nos. 111.00
30 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable (For 1 no. EOT with ECH at Pump House,1 no. EOT with ECH at 16 Nos. 65.15
Screen, 2 nos. pump PMU & for 4 nos. street light)
31 5C x 2.5 sq.mm. 2XWY(X)Cable (for LCS) 4 Nos. 180.00
32 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (APFC sensing C.T) 2 Nos. 49.13
33 Single core 95sq. mm. PVC insulated circular unsheathed copper conductor flexible Cable (For Power 10 Nos. 47.11
supply Metering Panel to I/c MCCB Unit)
34 CABLE TRAY 30 Mtr. 388.00
SITC of G.I. (hot dip galvanised )Ladder type medium duty (2mm thick) Cable Tray with necessary bends,
tees, reducers, covers and clamps for fixing. All material shall be Hot dip galvanised as per Specification.
And including all accessories.
300 x 75 mm - Ladder type
35 150 x 50 mm - Ladder type 70 Mtr. 336.00
36 Supply, laying and erection of 75 mm ID approved make Double Walled Corrugated pipes (DWC) of 50 Mtr. 161.15
polyethelene (confirming to IS-14930 II) with necessary connecting accessoies of same material at required
depth for laying of cable below ground / road surface for enclosing cable and back filling the same to make
ground as per original. (LT cable etc)
37 Cable Trench, Laying & Installation of Cable: Making cable trench in soft soil of suitable width of 90cms 70 Mtr. 46.46
deep for laying cable, Sand cushioning and brick protection on sides and on top all over the run and back
filling the same and making the surface as normal ground as per IS & Specification. (For laying of LT cable
38 Cable Protection/ Covering in Trench: Cable Covering with second class bricks or cement tiles laid cover 20 Mtr. 133.31
the cable (top) & also on both side with sand bedding/cusioning of 75mm.& covering of 150mm Layer of
sand above cable (16 bricks per meter.) as per IS & Tender Drg/ Specification. (For HT/LT cable
protection) complete in all respects as instructed by EIC.
39 CHEMICAL EARTHING SYSTEM 4 Set 7,028.82
SITC of Maintenance free chemical earthing with earthpit of minimum bore size dia. 225mm Safe Earthing
Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987 /Tech spec. made of corrosion free Hot
dip Galvanised (min 150 Microns) Pipes having Outer pipe dia of 76 mm , Inner corrosion free Hot dip
galvanised (80 to 100 micron) pipe dia of 26 mm with copper flat strip type connection terminal 14mm
dia with constant ohmic value surrounded by highly conductive corrosion resistant chemical compound
with high charge dissipation suitable for electrical installation & 3Mtr. length of Pipe with two nos. 25Kg.
bag of Back filling compound. (2 nos. for PMCC panel & all elect. Equipments)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
40 SITC of 50mm(w) x 8mm(T) etc. sizes as required, HOT dip galvanized GI Strip including supply & fixing 184 kg 77.17
using GI spacers, saddles when laid inside the building and inclusive of excavation & refilling of earth when
laid outside the building & interconnection with earth pit & all electro-mechanical equipments.
(50X6 G.I Strip wt.2.3 kg/m, 2.3x80Mt.=230kg.)
41 Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes as required, HOT dip galvanized GI Strip 36 kg 77.17
including supply & fixing using GI spacers, saddles when laid inside the building and inclusive of excavation
& refilling of earth when laid outside the building & interconnection with earth pit & all electro-mechanical
equipments. (25X3 G.I Strip, 0.6 Kg/m, 0.6x60Mt.=36Kg.)
42 SITC of HOT Dip Galvanized iron strip wire 8 SWG (For LDB,LCS, etc.) 10 kg 77.17
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 100Mt.=10.3 Kg.)
Item Rate Amount
Description Qty Unit
43 INTERNAL WIRING 40 Mtr. 78.06
SITC of Mains & outlet points wiring with 1.1 kV grade FRLS PVC insulated ISI marked flexible stranded
copper conductor wires with medium class min. 25mm. dia. Electrical grade PVC pipe and accessories to be
erected concealed in / to be run on surface / wall / ceiling with following sizes as mentioned below. The
unit rate wirings shall be with connector, PVC junction box, wires, holder, ceiling rose, angle holder, switch,
sockets, switch board, brass chromium / cadmium plated machine screws, phase and neutral wires, green
Earth continuity wires etc. as required to complete wiring from LDB panel to the final outlet termination
points. The wiring shall be as per IS:732, IS:4648 and as per tender specification / IS.
(a) SITC of Mains wiring with 3 wire 1.5 sq.mm.
44 Same as per above, but (b) SITC of Mains wiring with 3 wire 2.5 sq.mm as per tender specification & IS. 40 Mtr. 96.06
45 Same as per above, but (c) SITC of Mains wiring with 4 wire 1.5 sq.mm as per tender specification & IS. 50 Mtr. 86.06
46 Same as per above, but (d) SITC of Mains wiring with 4 wire 2.5 sq.mm as per tender specification & IS. 50 Mtr. 119.06
47 SITC of Point wiring for Light / fan / Bell / Primary Point with 2nos. 1.5 sq. mm & earth wire of 1.5 sq. mm 11 Nos. 326.59
(green) both are of ISI marked 1.1 kv grade FRLS PVC insulated multistrand copper wires , pipe to be
erected concealed in flushed on wall / ceiling, complete with 6A Tissino Type ISI marked flush type switch /
bell push & accessories erected on metal / PVC Box covered with 3 mm thick PC (Polycarbonate) / Acrylic
sheet with necessary lamp holder / ceiling Rose / H. D. connector as directed with medium class Rigid PVC
pipe & accessories.
48 SITC of 6A independent Plug with 2nos. 1.5 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) 2 Nos. 288.50
both are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand copper wires with medium class Rigid
PVC pipe and accessories to be erected on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and
tissino type switch erected with earth continuity connection erected on Metal / PVC box covered with
mm thick PC(Polycarbonet) / Acrylic sheet.
49 SITC of 6/16A independent Plug with 2nos. 4 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) 2 Nos. 1,005.00
both are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand copper wires with medium class Rigid
PVC pipe and accessories to be erected on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and
tissino type switch erected with earth continuity connection erected on Metal / PVC box covered with
mm thick PC(Polycarbonet) / Acrylic sheet. (1 no. LT Room, 1 no. Pump House)
50 SITC of One 300/380 mm dia. Ex fan 16A independent Plug point near Ex. Fan with 2nos. 4 sq.mm Cu. 2 Nos. 1,005.00
Mains size wiring & earthwire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC pipe and accessories to be erected on wall / ceiling,
complete with ISI marked 3Pin socket and tissino type switch erected with earth continuity connection
erected on Metal / PVC box covered with 3 mm thick PC(Polycarbonet) / Acrylic sheet. Plug point shall be
(2 nos. LT room, 2 nos. P.H)
51 SITC of 380mm sweep 1400 R.P.M exhaust fan, capacitor type, having double ball bearing, M.S.blades, 2 Nos. 3,052.47
mounting frame, forearms, suitable to operate on 230V,50 HZ AC supply conforming to IS: 2312.Fan shall
be painted with epoxy grey colour controlled by one 6 A flush type switch on board and 6A plug point near
Ex. fan. (2 nos. LT room, 2 nos. P.H)
52 SITC of Single Phase 20A 3 Pin Metal clad Industrial Type Socket with plug top and 20A SPMCB, suitable 2 Nos. 820.00
for flush mounting, in 16 SWG MS box of suitable size and covered with 3 mm thick electrical grade hylam
sheet or equivalent ISI marked Electrical grade Bakelite sheet and earthing with 2.5 sq.mm insulated
copper wire run inside the conduit including interconnections etc. complete as required.
(1 no. LT Room, 1 no. Pump House)
53 SITC of Sheets steel powder coated weather proof enclosure with One no. 32A, 415V 4P MCB for Motor & 2 Nos. 765.39
Inductive load (C Curve) having 10 KA breaking capacity & confirms to IS: 8828. (1 no. for EOT with ECH at
P.H.,1 no. ECH for Screen)
54 1200mm sweep ceiling fan, capacitor type, having double ball bearing 450mm down rod, canopies, 1 Set 1,581.51
shackle, rubber bush, blades, electronic speed regulator, suitable to operate on 230V,50Hz AC supply
conforming to IS: 374/1979.Fan shall be painted with white colour.(1 no. LT Room)
Item Rate Amount
Description Qty Unit
55 LED LIGHT FIXTURES & LIGHTING: 4 Nos. 293.26
SITC of Indoor wall mounting 20Watt or up to 25% higher wattage LED 4 feet Tube Light indoor fittings with
LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB, with housing used as a heat sink shall
be made of thick sheet Steel conforming to IS: 513/CRCA polyester powder coated and high U.V. &
corrosion resistance with diffuser and/or Polycarbonate optics with company mark/name
120 to 300 V,Power Factor more than 0.9, THD < 20 %,
CCT 4000 K to 6500K, Uniformity ratio >0.7,
Luminaries efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80 Certificates)
Tube Light with integral / non-integral driver, Surge-4KV,IP-20, 4 feet, Cat-III
56 Item description as above SITC of 7 watts LED Lamps integral type,cool white with PC diffuser suitable for 1 Nos. 111.00
B22 LAMP holder (1 no. LT Room)
57 SITC of 40W LED Surface / Wall mounted LED Flood Light fittings with High power White LEDs wattage of 2 Nos. 5,144.28
1Watt and above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High
pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium
with diffuser and Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Indoor use: (at Pump House)
58 SITC of 'B' class galvanised iron pipe 32 mm outside dia 45 cms long duly welded on 20 cms x 20 cms x 3 6 Nos. 553.86
mm thick M.S. base plate, erected on wall or corner for mounting luminaries with necessary hardware
materials duly painted for wall mounting indoor flood light fixtures on Wall of Buildings & post top lantern.
59 EXTERNAL LIGHTING (Flood LIGHT): 4 Nos. 6,029.70
SITC of 70W LED Wall mounted LED Flood Light fittings with High power White LEDs wattage of 1Watt and
above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die
cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser
and Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Outdoor use: (4 nos. for area lighting)
60 SITC of 40watt, Cat-III Post Top Lantern LED fitting comprises of 650 MM TOP Diameter, 120 degree beam 2 Nos. 4,986.28
angle with 3 Nos. Supporting Ribs and with 0.5mt. G.I. fitting pipe (for Gate light)
61 EXTERNAL LIGHTING (STREET LIGHT): 4 Nos. 10,619.32
SITC of Street Light Pole, steel tubular swaged type, 7.5 meter long with single arm & M.S.base plate with
pipe cap and over hung 1.5 m long having dia to suit the socket of 240V LED street light fixtures. Street light
pole unit rate shall be with (i) IP 65 SMC box of size 20 x 15 x 15 cms. with MCB & terminal strip inside the
box with hinged/sliding door (ii) 50mm dia, B class GI pipe bracket min.1.5mtr long for Incoming &
outgoing cable (iii)MS Cable Clamp of 25 x 3mm (iv)SITC of 1.5 Mtr.single Arm bracket of medium duty MS
pipe of 4.2 cms. Out side dia complete with suitable sleeve tubing 45 cms. long of required size of pole top
etc. and having spread of 1.5.mtr. length with 110 deg.(v) Complete painted with one coat of Red oxide /
PU base primer and two coats of Aluminium / PU paint for Pole,Arm, pipe etc.
62 SITC of 70W LED Street light fittings with High power White LEDs wattage of 1Watt and above assembled 4 Nos. 5,918.70
on single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminum
housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency > 85 %.
( Each fittings required LM-79 & LM-80 certificates)
Street Light (IP-65), Surge -4KV, 70 watt Cat-III
Item Rate Amount
Description Qty Unit
63 SITC of M-20 / 1:2:4 cement concrete foundation for Street light pole & 70 % PCC from bottom including 4 Nos. 1,282.12
excavation for the pole of size 60 x 60 x 120 cms. Deep in below ground level with plinth of 45 cms x
cms(or 45 cms dia x 45 cms) high upper ground level with necessary curing and finishing in approved
64 SAFETY ACCESSORIES 1 Nos. 8,586.26
SITC of following safety accessories complete with necessary fixing brackets, other accessories and tools
etc. as required to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher of 6.5kg capacity with necessary clamps made
from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall complete.
(For 1 no. for LT Room)
65 Supplying of standard first AID box with antiseptic cream, medicine for use on wounds due burn, crepe 1 Nos. 297.00
bandage, guage bandage, medicated ready to use bandage (Band-aid) adhesive tape for medicinal user,
scissors, antiseptic solution (Savlon or similar) etc. (All above contents shall be of standard makes)
(For 1 no. For LT Room)
66 Supply & fixing of printed instruction (First Aid) Chart both in English and Gujarati and duly framed with 1 Nos. 129.06
front glasses, for treatment of person suffering from electric shock. (For 1 no. For LT Room)
67 Supply and fixing of 20 W fluorescent lamp operated emergency light with maintenance free battery for 1 Nos. 2,670.00
3 hours operation during mains power failure.
(For 1 no. LT Room)
68 Supply and laying of Synthetic Insulating Mat of Class - A of min. thickness 2mm as per IS:15652 and with 3 Sq.mtr. 1,017.00
good electrical insulation property for 1.1KV/3.3KV as per site requirement. (For LT Panel)
TOTAL OF ELECTRICAL WORKS WITHOUT GST
69 PRESSURE MEASURING SYSTEM 2 Nos. 5,413.00
Supply, installation, testing & commissioning of Diaphragm Type pressure guage having 150 mm dial with
necessary fittings/accessories in SS
(manifold valve, nipples etc.) complete in all respects and as per specs.
Range : 0 - 2.5 Kg/cm2 (at each pump discharge line)
70 LEVEL MEASURING SYSTEM FOR SUMP 1 Nos. 59,436
Supply, installation, testing and commissioning of Ultrasonic type Level Transmitter with remote type
transmitter with 10meter cable between Sensor and Transmitter along with all required accessories,
Weather proof enclosure for transmitter for outdoor application, mounting stand , etc. complete in all
respects as per specification and having following measurement ranges for liquid (Water) application:
Meas. Range: upto 10 m (at sump )
71 Supply, installation, testing and commissioning of Float type Level Switch along with 10 mtr. Cable and WP 1 Nos. 12,802
Junction Box (at sump for dry run protection of pumps through relay multiplication in PLC), etc., complete
in all respects and as per specification.
Meas. Range: upto 10 m (at sump )
72 ELECTRO MAGNETIC FLOWMETER MAINS OPERATED Supply, installation, testing and 1 Nos. 65,837
commissioning of Full Bore Electromagnetic flow meter comprising of IP-68 Sensor , IP-66 remote type
transmitter with 20 m cable between sensor and transmitter along with all mounting accessories,
Weather proof enclosure for transmitter, hardware, mounting stand, etc.
as per specification and to complete the work in all respect as per site condition necessary connection with
pipe and shall have following size.
Meter Size: 100 mm (At Pump common Header )
Pipe Size : 100 mm
73 INSTRUMENT CABLE & ACCESSORIES 50 Mtr. 203.00
'Supply, Laying, Installation, Connection, Termination, Testing & Commissioning of Instrument Cables as
The unit rate shall include
a)Supply, loading & unloading of the cable at site from store.
b)Shifitng of cable from site store to place of installation.
c)Fixing of cable clamps, brackets, supports, route markers etc. where ever required to fix the cables safely.
d)Excavation, back filling and levelling of ground alongwith laying of fine sand, protection bricks and other
necessary civil material for laying cables outside the building.
f)Testing and submission of sketches & reports of all the cables laid.
Item Rate Amount
Description Qty Unit
74 SIGNAL CABLE 50 Mtr. 176.00
75 CABLE END TERMINATION AND CONNECTION : 4 Nos. 224.00
'Supply, fixing, connection, testing and commissioning of double compression brass cable glands and
crimping type Bimetalic lugs / sockets with necessary tools and equipments as specified in specifications
and IS complete in all respects. The glands and lugs / sockets shall be suitable for cable size and type
mentioned above. The job also includes earthing the glands and armour of the cable with common earth
bar or flexible copper mesh as applicable.
76 SIGNAL CABLE 6 Nos. 224.00
TOTAL OF INSTRUMENTATION WORK WITHOUT GST
Electro-Mechanical and Instrumentation Work for PS-4 (O-4)
Item Rate Amount
Description Qty Unit
1 MECHANICAL WORK 2 Set 1,63,319
SUBMERSIBLE NONCLOG PUMP SET
Supply, Installation, Testing and Commissioning (SITC) of Submersible NC Pump-Motor
set suitable for sewage application with semi-open or enclosed or suitable type
Impeller & wear Rings in CF8M with CI FG 260 Casing & casing cover, SS 410 shaft &
with motor suitable for 3-Phase, 415 V, 50 Hz., AC induction Air filled dry type
submersible motor of mini. rating as specified having max. 1500 RPM sync. speed,
insulation Class 'F' With temp. rise limited to class B and IP-68 protection.
The scope shall include all required accessories viz. automatic coupling device, SS-304
heavy duty & of suitable size double guide pipes of length to suit the sump height with
required supports, SS-304 or suitable stainless steel grade Chain with shackles (shall be
with dual hook / shackles of 100 mm or suitable higher size at app. every 1.5m C-C
distance) & of length as per sump height + min. 3m, Submersible Power & control cable
(copper flexible & stranded type conductor of reqd. cores & size for each pump motor
set) & length of sump height + min. 5 m long each run with necessary electrical
termination connection at junction box / starter panel and RCC foundation blocks for
auto coupling & delivery bend, PMU etc. complete as per IS, Tender Drawings and
Specification and also including in scope any other parts / accessories / fittings required
to complete the work in all respects & satisfactory operation of pump set.
Pump Capacity: 25 m3 / hr.,
Motor Rating: min. 3.7 kW (or higher rating as reco. by pump manufacturer)
Over all Efficiency at Duty- min. 30%
2 VALVES: 3 Nos. 3,112.00
SITC of CI/ DI Double Flanged, Sluice Valve confirming to IS 14846, PN 1.0 of following
sizes with SS 304 seat rings and SS spindle with hot dipped galvanised hardwares, bolts,
nuts & washers etc. as per IS and Specification & complete the work in all respects.
Size: 80 mm NB (on delivery of each pumpsets & common header)
3 SITC of Non slam, flanged, CI/DI Single Door type Non Return Valve conforming to IS 2 Nos. 4,406.00
5312 (Part-1), PN 1.0, having DI/CI body and door, CF8M seat rings alongwith all
necessary hardwares as per specifications and complete in all respect.
Size: 80 mm NB (on delivery of each pumpsets)
4 DI PIPES 350 kg 155.00
SITC of Double Flanged DI Pipes confirming to IS 8329-2000, class K9 with connections
complete for delivery and header lines and as per specifications. The scope also
includes connection with main header/rising main.
Size: 80 mm to 300 mm
5 DI FITTINGS 200 kg 155.00
SITC with sution, delivery / header, testing and commissioning of Flanged DI Fittings
and Specials like 90 deg. Bend, Drilled / Blind Flanges, Reducer / enlarger, TEE, etc. as
required to complete the piping and connection of pumps with header/rising main
conforming to IS
Size : 80 to 300 mm dia
Item Rate Amount
Description Qty Unit
6 Flanged Joints of Pipes, Fittings and Specials: 20 Nos. 499.10
Supply, Installation, Making of Flanged CI / DI / MS Pipes, Fittings and Specials Joints
with all jointing materials, rubber packing, nut bolts, labour etc.for complete
Size: 80 mm dia
7 Manual Mesh Screen with Screening Collecting Trough/ Box 1 Nos. 1,59,760
SITC of Manual Mesh Screen having following size, made of SS 304 material having
round bars of size 9 mm dia. with clear bar opening as specified here below, suitably
welded in outer frame of equal Leg SS angle of size 50 mm x 50 mm x 6 mm thick or
higher, with intermediate support at required locations, complete as per specs. & shall
also including followings:
The screen shall be with SS perforated Screening Material Collection Box/Trough at
bottom end of screen having size as specified, fabricated from 3 mm thk. SS sheet,
screen shall be suitable to lower in MCP 100 guide channel, complete of following size
with SS lifting chain and as per specifications with all necessary hardware, SS nuts, bolts
& washers, sacrificial Brass lugs on sides, min. two lifting lugs/hooks & SS lifting chain
having intermediate link/chain of 300 mm dia. or suitable higher size at every 1.5 m
distance with shackle, etc. complete in all respects and provided with 1 set of cleaning
rake with each screen complete as per specification and complete in all respect.
Screen Size: 500 mm (W-or actual channel width as per site) x 600 mm (H)
Screening Box/Trough size: 450 mm (W-or suit actual screen width as per site) x
Opening: 50 mm x 50 mm sq. opening.
(w/o Guide channel & MS supporting structure)
(Note: Screen suitable for 600 mm width or to suit site requirement.)
8 MONORAIL EOT WITH ELECTRIC CHAIN HOIST 1 Set 2,28,220
SITC of Electrically Operated Chain Hoist & Electrically operated Trolley, suitable to
operate on Mono Rail Girder having motorised motion in vertical lifting & cross travel,
manufactured as per IS:6547-1972-Class-II & IS-3177- Class-II, complete with
electrically operated chain hoist & Electically operated geared trolley, brake, chain-gear,
motors, safety device, pendant push button, starter panel, cables from motor to starter
panel and all other required accessories like limit switches, panel, power supply system
(Fastoon cable type), fasteners, epoxy painting, etc. tested for over load as per IS
complete as per specifications and complete in all respect.
Capacity : Min. 1.0 Ton. (At Pump House)
Lift : 7-10 m as mini. or as per site req.
Bay Length : 3-5 m min. or as per site req.
(w/o MONORAIL GIRDER & MS supporting structure)
Note: (1) Minimum as specified capacity or higher as per requirement such that ECH
capacity is min.1.25 times of the pump/motor OR single heaviest component to be
lifted within pump house.
9 Item description as above and of following size complete, 1 Set 2,28,220
Capacity : 1.0 Ton. Min. (For Manual Screen)
Lift : 7-10 m as mini. or as per site req.
Bay Length : 3-5 m min. or as per site req.
Note: (1) Minimum as specified capacity or higher as per requirement such that ECH
capacity is min.1.25 times single heaviest component to be lifted.
Item Rate Amount
Description Qty Unit
10 SITC of Manually operated C.I. Thimble mounted Sluice Gate conforming to AWWA C 1 Nos. 1,64,830
501 or IS : 13349 - 1992 Class - 1 with rising spindle, single faced, wall thimble mounted,
handwheel, flush bottom closing, flange back frame, head stock, Spindle with supports
brackets having length as specified or to suit site condition, suitable for seating as well
as unseating water head, complete in all respect.
Size : 200 mm X 200 mm - approx. 5.00 m spindle length (At Inlet Pipe)
11 Providing, Supply of Structure Steel at site of work with freight, loading, unloading 500 kg 64.84
carting, etc. including all taxes and duties complete such as joints, channels, angles, Iron
Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered plates (below 10mm thickness) for
cable trench etc. required for support structure of all Electro-mechanical equipment,
piping, etc. for support on floor / wall / beam / brackets etc. as per tender and IS.
12 Labour Charges for lowering, laying, Fixing with fabrication various size section of MS 500 kg 13.07
such as joints, channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered
plates, for cable trench etc Complete with two coats of red oxide and two coats of
approved colour shade of epoxy paint as per relevant IS and as per specification.
TOTAL OF MECHANICAL WORK WITHOUT GST
13 ELECTRICAL WORK 1 Set 38,951.13
TPN MCCB (For LT Service Obtaining Requirement)
SITC of 250A TPN microprocessor MCCB, LSIG (50kA) with inbuilt O/L, S/C & E/F
protection with Extended rotary handle, Terminal spreader, Auxiliary change over &
Trip contact, with Outdoor Enclosure with canopy 2mm thick , Single/double door &
Wall mounted/ stand mounted as per site requirement (with incoming & outgoing
cable entry at bottom )with Cable end boxes with RYB indicating lamp, Digital
voltmeter, VSS,ON,OFF & Trip indicating lamp etc as per Power supply company
requirements & location. Including all civil works for fixing of panel on wall.
(Wall mounted at Location as per PSC req.)
14 MEDIUM VOLTAGE PANEL BOARD (PMCC /APFC) 1 Set 4,73,000.00
SITC of PMCC Panel (50kA), compartmentalized, Stand mounted, operating height
maximum 1800/1900 mm, Extensible on both ends, suitable for Manual & Auto
operation -Local & through PLC/SCADA operation as per site conditions complete in all
respects as per Tender SLD / Specification / IS and including following as minimum:
(1) One no. Incoming feeder FP 250A Microprocessor MCCB (50kA), LSIG, with inbuilt
O/C, S/C, & E/F protection for I/c with Digital Voltmeter, Voltmeter selector switch,
Digital Ammeter, Ammeter selector switch, Power Factor Meter, MFM with RS-485 of
Class-0.5, Indicating lamps R,Y,B,On,off,Trip, 3nos. 250A/5A, Cl.-0.5 metering CT, CL
CT for APFC relay etc. Constant voltage/control voltage transformer 1500VA,
415V/230V AC, with tapping +/-5% in steps of 2.5%, 32A DP MCB complete in all
(2) 250A TPN Main Aluminium busbars. (main busbars size with current density
(3) 3.7 KW DOL STARTER FEEDER (SUBM.): 2 NOS
Each starter comprising of 9-13A TPN MPCB with adjustable overload & adjustable
short circuit, 25A contactor, Digital Ammeter, 32A/1A, Cl.-1.0, 2.5VA CT, PMU, Start, E-
Stop, Reset push Button, A/M, L/R switch, ON, OFF, trip Indications etc.
(4) 63A TPN TM MCCB FEEDER : 1 No. (for Spare)
Each feeder comprising of 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp
Item Rate Amount
Description Qty Unit
14 (5) 32A TPN TM MCCB FEEDER : 4 Nos. (1 no. EOT with ECH at PH, 1 no. EOT with ECH
at screen, 2 nos. spare)
Each feeder comprising of 32A TPN Thermal Magnetic (TM) MCCB, with indicating lamp
(6) 63A TPN TM MCCB FEEDER FOR ALL MCB FEEDERS: 1 set:
Incomer: 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
a) 3 nos. 32A 'C' curve 4P MCB feeders (for 1 no. Ind LDB & 2 nos. spare feeders)
B) 1 no. 32A 'C' curve 4P MCB with Time switch,32A contactor 4P,ON lamp feeders (for
(7) APFC separate cubical compartment (minimum 10 KVAr) having 1 no. 32A TPN
Thermal magnetic MCCB 50KA with adjustable overload and adjustable short circuit,
8step APFC relay with RS 485, 1 no. 32 A/5A, Cl.-1.0 CT for Ammeter, Digital Ammeter,
ASS, 1 no. 1 kVAR capacitor with 16A TPN D curve MCB, 2 nos. 2 kVAR capacitor with
16A TPN D curve MCB, 1 no. 5 kVAR capacitor with 16A TPN D curve MCB with capacitor
Duty Contractor, A/M switch, On delay timer, Push Buttons etc. Complete in all respects
as per Specification, IS & SLD.
(8) Multiplication relay as required for dry run protection of pumps.
NOTE: 1). All MCCB shall be 50KA, Ics = 100% Icu, inbuilt protection with adj O/L and
Adj.S/c (LSIG for MP MCCB),Extended rotary handle, Terminal spreader, Auxiliary
Change over contact and trip contact as required.2) All MFM, ACB, Soft
Starter,Temp.Scanner etc shall be with inbuilt RS
15 ICP Cubical a part of PMCC Panel as below: 1 Nos. 40,000
ICP cubicle compartment as a part of PMCC (as per SLD) panel with required input /
output for field instruments interfacing at terminal strip& comprising of
(a) Door mounted 1 no. Process indicator with 4 nos. relay output for start pump at
high level and stop at low level for Level transmitter ,UPS power ON Indication, etc.)
(b) Required separate isolation switches (DP MCB only) for incoming 230 V AC power
mains from UPS & outgoing power feed to 1 no. Process indicator , 1 Nos.
Multiplication Relay (1 no. 1 input + 2 Output) for Dry run protection of Pump at low-
low level ,etc.
(c) Offline type UPS of suitable rating (min. 250 VA with 15-20 min. backup time )
mounted within cubicle on main incoming power line with required isolation device (DP
MCB) & outgoing feed to power supply of instruments.
(d) Any other as required to complete the work and meet the tender
requirement/specification.
16 SITC of Lighting Distribution Board (LDB) as under: 2 Nos. 7,497.69
SITC of 3 Phase 4 Wire 4P, double door Prewired LDB each for Indoor Lighting &
Outdoor Lighting Suitable to house :
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB (9 nos.) & 16A SP MCB (9 nos.)
Item Rate Amount
Description Qty Unit
17 SITC of stand / wall mounting type MS Junction Box, minimum 2.5mm thick, with 2 Nos. 1,906.78
detachable cable gland plate of 3mm thick, duly powder coated, with earthing
terminals, steel structure stand for mounting of JB, etc. for Jointing/Termination
suitable for 1.1 kV Submersible Flexible Copper Power & control cable with Aluminium/
Copper armoured power cable from PMCC . Scope shall include providing suitable
rating AL busbars, Support insulators, Crimping type lugs,nuts,bolts,washers etc.
complete in all respects as instructed by E.I.C. Drawing shall be got approved before
SITC of the same. Lugs of cables shall not be connected directly. (Structure steel for
Stand shall be measured separately)
JB of minimum Size: 300mm x 300mm x 100mm or higher as required. or higher as
required (for Pump)
18 LOW VOLTAGE (LT) CABLES 25 Mtr. 783.00
Supply, laying, testing and commissioning of 1.1 kV, A2XFY(X)/2XWY(X) XLPE insulated
(IS 7098) AL / Cu stranded conductor, Extruded innersheath cables as per specification
The cable when laid outside the building shall be laid underground in trench with brick
& sand protection/in DWC pipes as per specified method and shall be laid in prepared
trench/ on cable tray when laid inside the building.
SITC of 3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
19 3C x 2.5 sq. mm. 2XWY Cable (1 runs for PMCC to 2 nos. 3.7 kW Subm. pump Junction 80 Mtr. 211.10
20 4C x 6 sq. mm. A2XFY(X) Cable (For 1 no. Indoor LDB, Outdoor LDB) 50 Mtr. 78.00
21 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable (For 1 no. TPN MCB for EOT with ECH at Pump 220 Mtr. 81.00
House,1 no. ECH at Screen, 2 nos. pump PMU & for 4 nos. street light)
22 5C x 2.5 sq.mm. 2XWY(X)Cable (for LCS) 40 Mtr. 220.00
23 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (APFC sensing C.T) 20 Mtr. 175.10
24 Single core 95sq. mm. PVC insulated circular unsheathed copper conductor flexible 20 Mtr. 867.12
Cable (For Power supply Metering Panel to I/c MCCB Unit)
25 CABLE END TERMINATION AND CONNECTION: 2 Nos. 838.00
SITC of Double compression Ni-Plated brass cable glands and crimping type Bimetallic
lugs / sockets with necessary tools and equipments as specified in specifications and IS.
The glands and lugs / sockets shall be suitable for cable size and type mentioned
below & as per specifications.
1) Earthing the glands and armouring with earthing clamp and jumper and also
connecting to common earth bar.
2) The job also includes, if necessary, supply & fixing of extension busbar of same
material on MCCB or panel board terminal / connector to connect more than one no.
of parallel cables or to connect higher size cable to lower size unit. The job also includes
earthing the glands and armour of the cable with common earth bar or flexible copper
mesh.(Cable termination qty. shall be as per site requirement)
3.5C x 240 sq. mm. A2XFY(X) Cable (1 run for MCCB to PMCC panel)
26 3C x 2.5 sq. mm. 2XWY Cable (1 runs for PMCC to 2 nos. 3.7 kW Subm. pump Junction 4 Nos. 110.00
27 4C x 6 sq. mm. A2XFY(X) Cable (For 1 no. Indoor LDB, Outdoor LDB) 4 Nos. 111.00
28 4C x 2.5 sq. mm. 2XWY/2XFY(X) Cable (For 1 no. EOT with ECH at Pump House,1 no. EOT 16 Nos. 65.15
with ECH at Screen, 2 nos. pump PMU & for 4 nos. street light)
29 5C x 2.5 sq.mm. 2XWY(X)Cable (for LCS) 4 Nos. 180.00
30 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (APFC sensing C.T) 2 Nos. 49.13
31 Single core 95sq. mm. PVC insulated circular unsheathed copper conductor flexible 10 Nos. 47.11
Cable (For Power supply Metering Panel to I/c MCCB Unit)
Item Rate Amount
Description Qty Unit
32 CABLE TRAY 30 Mtr. 388.00
SITC of G.I. (hot dip galvanised )Ladder type medium duty (2mm thick) Cable Tray with
necessary bends, tees, reducers, covers and clamps for fixing. All material shall be Hot
dip galvanised as per Specification. And including all accessories.
300 x 75 mm - Ladder type
33 150 x 50 mm - Ladder type 70 Mtr. 336.00
34 Supply, laying and erection of 75 mm ID approved make Double Walled Corrugated 50 Mtr. 161.15
pipes (DWC) of polyethelene (confirming to IS-14930 II) with necessary connecting
accessoies of same material at required depth for laying of cable below ground / road
surface for enclosing cable and back filling the same to make ground as per original. (LT
35 Cable Trench, Laying & Installation of Cable: Making cable trench in soft soil of suitable 70 Mtr. 46.46
width of 90cms deep for laying cable, Sand cushioning and brick protection on sides
and on top all over the run and back filling the same and making the surface as normal
ground as per IS & Specification. (For laying of LT cable in ground)
36 Cable Protection/ Covering in Trench: Cable Covering with second class bricks or 20 Mtr. 133.31
cement tiles laid cover the cable (top) & also on both side with sand bedding/cusioning
of 75mm.& covering of 150mm Layer of sand above cable (16 bricks per meter.) as per
IS & Tender Drg/ Specification. (For HT/LT cable protection) complete in all respects as
instructed by EIC.
37 EARTHING SYSTEM 4 Set 7,028.82
SITC of Maintenance free chemical earthing with earthpit of minimum bore size dia.
225mm Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987
/Tech spec. made of corrosion free Hot dip Galvanised (min 150 Microns) Pipes having
Outer pipe dia of 76 mm , Inner corrosion free Hot dip galvanised (80 to 100 micron)
pipe dia of 26 mm with copper flat strip type connection terminal 14mm dia with
constant ohmic value surrounded by highly conductive corrosion resistant chemical
compound with high charge dissipation suitable for electrical installation & 3Mtr.
length of Pipe with two nos. 25Kg. bag of Back filling compound. (2 nos. for PMCC panel
& all elect. Equipments)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
38 SITC of 50mm(w) x 8mm(T) etc. sizes as required, HOT dip galvanized GI Strip including 184 kg 77.17
supply & fixing using GI spacers, saddles when laid inside the building and inclusive of
excavation & refilling of earth when laid outside the building & interconnection with
earth pit & all electro-mechanical equipments.
(50X6 G.I Strip wt.2.3 kg/m, 2.3x80Mt.=230kg.)
39 Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes as required, HOT dip 36 kg 77.17
galvanized GI Strip including supply & fixing using GI spacers, saddles when laid inside
the building and inclusive of excavation & refilling of earth when laid outside the
building & interconnection with earth pit & all electro-mechanical equipments. (25X3
G.I Strip, 0.6 Kg/m, 0.6x60Mt.=36Kg.)
40 SITC of HOT Dip Galvanized iron strip wire 8 SWG (For LDB,LCS, etc.) 10 kg 77.17
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 100Mt.=10.3 Kg.)
Item Rate Amount
Description Qty Unit
41 INTERNAL WIRING 40 Mtr. 78.06
SITC of Mains & outlet points wiring with 1.1 kV grade FRLS PVC insulated ISI marked
flexible stranded copper conductor wires with medium class min. 25mm. dia. Electrical
grade PVC pipe and accessories to be erected concealed in / to be run on surface / wall
/ ceiling with following sizes as mentioned below. The unit rate wirings shall be with
connector, PVC junction box, wires, holder, ceiling rose, angle holder, switch, sockets,
switch board, brass chromium / cadmium plated machine screws, phase and neutral
wires, green Earth continuity wires etc. as required to complete wiring from LDB panel
to the final outlet termination points. The wiring shall be as per IS:732, IS:4648 and
as per tender specification / IS.
(a) SITC of Mains wiring with 3 wire 1.5 sq.mm.
42 Same as per above, but (b) SITC of Mains wiring with 3 wire 2.5 sq.mm as per tender 40 Mtr. 96.06
specification & IS.
43 Same as per above, but (c) SITC of Mains wiring with 4 wire 1.5 sq.mm as per tender 50 Mtr. 86.06
specification & IS.
44 Same as per above, but (d) SITC of Mains wiring with 4 wire 2.5 sq.mm as per tender 50 Mtr. 119.06
specification & IS.
45 SITC of Point wiring for Light / fan / Bell / Primary Point with 2nos. 1.5 sq. mm & earth 11 Nos. 326.59
wire of 1.5 sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC insulated
multistrand copper wires , pipe to be erected concealed in flushed on wall / ceiling,
complete with 6A Tissino Type ISI marked flush type switch / bell push & accessories
erected on metal / PVC Box covered with 3 mm thick PC (Polycarbonate) / Acrylic sheet
with necessary lamp holder / ceiling Rose / H. D. connector as directed with medium
class Rigid PVC pipe & accessories.
46 SITC of 6A independent Plug with 2nos. 1.5 sq.mm Cu. Mains size wiring & earthwire of 2 Nos. 288.50
1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand
copper wires with medium class Rigid PVC pipe and accessories to be erected on wall /
ceiling, complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with
earth continuity connection erected on Metal / PVC box covered with 3 mm thick
PC(Polycarbonet) / Acrylic sheet.
47 SITC of 6/16A independent Plug with 2nos. 4 sq.mm Cu. Mains size wiring & earthwire 2 Nos. 1,005.00
of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC pipe and accessories to be
erected on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and tissino type
switch erected with earth continuity connection erected on Metal / PVC box covered
with 3 mm thick PC(Polycarbonet) / Acrylic sheet. (1 no. LT Room, 1 no. Pump House)
48 SITC of One 300/380 mm dia. Ex fan 16A independent Plug point near Ex. Fan with 2nos. 2 Nos. 1,005.00
4 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) both are of ISI marked
1.1 KV grade FRLS PVC insulated multistrand copper wires with medium class Rigid PVC
pipe and accessories to be erected on wall / ceiling, complete with ISI marked 3Pin
socket and tissino type switch erected with earth continuity connection erected on
Metal / PVC box covered with 3 mm thick PC(Polycarbonet) / Acrylic sheet. Plug point
shall be near Ex.Fan.
(2 nos. LT room, 2 nos. P.H)
49 SITC of 380mm sweep 1400 R.P.M exhaust fan, capacitor type, having double ball 2 Nos. 3,052.47
bearing, M.S.blades, mounting frame, forearms, suitable to operate on 230V,50 HZ AC
supply conforming to IS: 2312.Fan shall be painted with epoxy grey colour controlled by
one 6 A flush type switch on board and 6A plug point near Ex. fan. (2 nos. LT room,
Item Rate Amount
Description Qty Unit
50 SITC of Single Phase 20A 3 Pin Metal clad Industrial Type Socket with plug top and 20A 2 Nos. 820.00
SPMCB, suitable for flush mounting, in 16 SWG MS box of suitable size and covered
with 3 mm thick electrical grade hylam sheet or equivalent ISI marked Electrical grade
Bakelite sheet and earthing with 2.5 sq.mm insulated copper wire run inside the
conduit including interconnections etc. complete as required.
(1 no. LT Room, 1 no. Pump House)
51 SITC of Sheets steel powder coated weather proof enclosure with One no. 32A, 415V 2 Nos. 765.39
4P MCB for Motor & Inductive load (C Curve) having 10 KA breaking capacity & confirms
to IS: 8828. (1 no. for EOT with ECH at P.H.,1 no. EOT with ECH for Screen)
52 1200mm sweep ceiling fan, capacitor type, having double ball bearing 450mm down 1 Set 1,581.51
rod, canopies, shackle, rubber bush, blades, electronic speed regulator, suitable to
operate on 230V,50Hz AC supply conforming to IS: 374/1979.Fan shall be painted with
white colour.(1 no. LT Room, 1 no. at P.H)
53 LED LIGHT FIXTURES & LIGHTING: 4 Nos. 293.26
SITC of Indoor wall mounting 20Watt or up to 25% higher wattage LED 4 feet Tube Light
indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single MCPCB,
with housing used as a heat sink shall be made of thick sheet Steel conforming to IS:
513/CRCA polyester powder coated and high U.V. & corrosion resistance with diffuser
and/or Polycarbonate optics with company mark/name
120 to 300 V,Power Factor more than 0.9, THD < 20 %,
CCT 4000 K to 6500K, Uniformity ratio >0.7,
Luminaries efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80 Certificates)
Tube Light with integral / non-integral driver, Surge-4KV,IP-20, 4 feet, Cat-III
54 Item description as above SITC of 7 watts LED Lamps integral type,cool white with PC 1 Nos. 111.00
diffuser suitable for B22 LAMP holder (1 no. LT Room)
55 SITC of 40W LED Surface / Wall mounted LED Flood Light fittings with High power 2 Nos. 5,144.28
White LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High pressure die cast aluminum housing with
smooth finish powder coated and heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency >
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Indoor use: (at Pump House)
56 SITC of 'B' class galvanised iron pipe 32 mm outside dia 45 cms long duly welded on 20 6 Nos. 553.86
cms x 20 cms x 3 mm thick M.S. base plate, erected on wall or corner for mounting
luminaries with necessary hardware materials duly painted for wall mounting indoor
flood light fixtures on Wall of Buildings & post top lantern.
Item Rate Amount
Description Qty Unit
57 EXTERNAL LIGHTING (Flood LIGHT): 4 Nos. 6,029.70
SITC of 70W LED Wall mounted LED Flood Light fittings with High power White LEDs
wattage of 1Watt and above assembled on single MCPCB, efficiency more than
lm/w and corrosion free High pressure die cast aluminum housing with smooth finish
powder coated and heat sink extruded aluminium with diffuser and Polycarbonate
optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency >
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Outdoor use: (4 nos. for area lighting)
58 SITC of 40watt, Cat-III Post Top Lantern LED fitting comprises of 650 MM TOP 2 Nos. 4,986.28
Diameter, 120 degree beam angle with 3 Nos. Supporting Ribs and with 0.5mt. G.I.
fitting pipe (for Gate light)
59 EXTERNAL LIGHTING (STREET LIGHT): 4 Nos. 10,619.32
SITC of Street Light Pole, steel tubular swaged type, 7.5 meter long with single arm &
M.S.base plate with pipe cap and over hung 1.5 m long having dia to suit the socket of
240V LED street light fixtures. Street light pole unit rate shall be with (i) IP 65 SMC box
of size 20 x 15 x 15 cms. with MCB & terminal strip inside the box with hinged/sliding
door (ii) 50mm dia, B class GI pipe bracket min.1.5mtr long for Incoming & outgoing
cable (iii)MS Cable Clamp of 25 x 3mm (iv)SITC of 1.5 Mtr.single Arm bracket of
medium duty MS pipe of 4.2 cms. Out side dia complete with suitable sleeve tubing
cms. long of required size of pole top etc. and having spread of 1.5.mtr. length with
deg.(v) Complete painted with one coat of Red oxide / PU base primer and two coats of
Aluminium / PU paint for Pole,Arm, pipe etc.
60 SITC of 70W LED Street light fittings with High power White LEDs wattage of 1Watt and 4 Nos. 5,918.70
above assembled on single MCPCB, efficiency more than 130 lm/w and corrosion free
High pressure die cast aluminum housing with smooth finish powder coated and heat
sink extruded aluminium with diffuser and Polycarbonate optics/ lenses with company
mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency >
( Each fittings required LM-79 & LM-80 certificates)
Street Light (IP-65), Surge -4KV, 70 watt Cat-III
61 SITC of M-20 / 1:2:4 cement concrete foundation for Street light pole & 70 % PCC from 4 Nos. 1,282.12
bottom including excavation for the pole of size 60 x 60 x 120 cms. Deep in below
ground level with plinth of 45 cms x 45 cms(or 45 cms dia x 45 cms) high upper ground
level with necessary curing and finishing in approved manner.
62 SAFETY ACCESSORIES 1 Nos. 8,586.26
SITC of following safety accessories complete with necessary fixing brackets, other
accessories and tools etc. as required to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher of 6.5kg capacity with
necessary clamps made from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall
(For 1 no. for LT Room)
Item Rate Amount
Description Qty Unit
63 Supplying of standard first AID box with antiseptic cream, medicine for use on wounds 1 Nos. 297.00
due burn, crepe bandage, guage bandage, medicated ready to use bandage (Band-aid)
adhesive tape for medicinal user, scissors, antiseptic solution (Savlon or similar) etc. (All
above contents shall be of standard makes)
(For 1 no. For LT Room)
64 Supply & fixing of printed instruction (First Aid) Chart both in English and Gujarati and 1 Nos. 129.06
duly framed with front glasses, for treatment of person suffering from electric shock.
(For 1 no. For LT Room)
65 Supply and fixing of 20 W fluorescent lamp operated emergency light with 1 Nos. 2,670.00
maintenance free battery for 3 hours operation during mains power failure.
(For 1 no. LT Room)
66 Supply and laying of Synthetic Insulating Mat of Class - A of min. thickness 2mm as per 3 Sq.mt 1,017.00
IS:15652 and with good electrical insulation property for 1.1KV/3.3KV as per site r.
requirement. (For LT Panel)
TOTAL OF ELECTRICAL WORKS WITHOUT GST
67 PRESSURE MEASURING SYSTEM 2 Nos. 5,413.00
Supply, installation, testing & commissioning of Diaphragm Type pressure guage having
150 mm dial with necessary fittings/accessories in SS
(manifold valve, nipples etc.) complete in all respects and as per specs.
Range : 0 - 1.6 Kg/cm2 (at each pump discharge line)
68 LEVEL MEASURING SYSTEM FOR SUMP 1 Nos. 59,436
Supply, installation, testing and commissioning of Ultrasonic type Level Transmitter
with remote type transmitter with 10meter cable between Sensor and Transmitter
along with all required accessories, Weather proof enclosure for transmitter for
outdoor application, mounting stand , etc. complete in all respects as per specification
and having following measurement ranges for liquid (Water) application:
Meas. Range: upto 10 m (at sump )
69 Supply, installation, testing and commissioning of Float type Level Switch along with 1 Nos. 12,802
10 mtr. Cable and WP Junction Box (at sump for dry run protection of pumps through
relay multiplication in PLC), etc., complete in all respects and as per specification.
Meas. Range: upto 10 m (at sump )
70 ELECTRO MAGNETIC FLOWMETER MAINS OPERATED Supply, 1 Nos. 61,837
installation, testing and commissioning of Full Bore Electromagnetic flow meter
comprising of IP-68 Sensor , IP-66 remote type transmitter with 20 m cable between
sensor and transmitter along with all mounting accessories, Weather proof enclosure
for transmitter, hardware, mounting stand, etc.
as per specification and to complete the work in all respect as per site condition
necessary connection with pipe and shall have following size.
Meter Size: 80 mm (At Pump common Header )
Pipe Size : 80 mm
Item Rate Amount
Description Qty Unit
71 INSTRUMENT CABLE & ACCESSORIES 50 Mtr. 203.00
'Supply, Laying, Installation, Connection, Termination, Testing & Commissioning of
Instrument Cables as per specs.
The unit rate shall include
a)Supply, loading & unloading of the cable at site from store.
b)Shifitng of cable from site store to place of installation.
c)Fixing of cable clamps, brackets, supports, route markers etc. where ever required to
fix the cables safely.
d)Excavation, back filling and levelling of ground alongwith laying of fine sand,
protection bricks and other necessary civil material for laying cables outside the
f)Testing and submission of sketches & reports of all the cables laid.
72 SIGNAL CABLE 50 Mtr. 176.00
73 CABLE END TERMINATION AND CONNECTION : 4 Nos. 224.00
'Supply, fixing, connection, testing and commissioning of double compression brass
cable glands and crimping type Bimetalic lugs / sockets with necessary tools and
equipments as specified in specifications and IS complete in all respects. The glands
and lugs / sockets shall be suitable for cable size and type mentioned above. The job
also includes earthing the glands and armour of the cable with common earth bar or
flexible copper mesh as applicable.
74 SIGNAL CABLE 6 Nos. 224.00
TOTAL OF INSTRUMENTATION WORK WITHOUT GST
Construction of Sewage Pumping Station (O-3)
Item Rate Amount
Description Qty. Unit
1 Excavation for well/pumping station including removing and spreading the excavated 122.00 Cum 313.95
stuffs directed with all lead.
0.0 m to 1.5 m depth
In hard rock with blasting and chiselling or by chiselling/Breaking only for finishing.
In hard rock with blasting and chiselling or by chiselling/Breaking only for finishing.
In hard rock with blasting and chiselling or by chiselling/Breaking only for finishing.
In hard rock with blasting and chiselling or by chiselling/Breaking only for finishing.
2 Refilling the pipeline trenches incl. ramming, watering, consolidating desposal of surplus 140.00 Cum 25.30
stuff as directed within a radius of 3 km. Refilling as directed.
3 Providing and casting in situ C.C. in grade M-15 (approx. corresp. to prop. 1:2:4) 15.00 Cum 5641.90
(proportions as per mix design or as per Table 9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work,
including scaffolding centering, form work, needle vibrated consolidation, curing
comp. up to 6 meter depth or height (excluding cost of reinforcement and neat finishing)
with centering and shuttering/deshuttering etc. comp. for structure for other than water
Footing for column or foundation (with form work)
4 Providing and casting in situ C.C. in grade M-15 (approx. corresp. to prop. 1:2:4) 5.00 Cum 5441.80
(proportions as per mix design or as per Table 9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work,
including scaffolding centering, form work, needle vibrated consolidation, curing
comp. up to 6 meter depth or height (excluding cost of reinforcement and neat finishing)
with centering and shuttering/deshuttering etc. comp. for structure for other than water
Footing (Without form work)
5 Providing and laying one layer of bitumen craft paper conforming to IS:1398 of approved 28.00 Smt 13.00
make and quality
6 Providing and cast in situ C.C. in grade M-30 proportions of ingredients as per mix design 22.00 Cum 9444.95
by weigh batching using granite, quartzite trap metal of size 12 mm to 20 mm and or
mm to 12 mm including scaffolding centering formwork, needle vibrated consolidation,
curing and hydraulic testing etc. complete (excluding cost of reinforcement) with
centering and shuttering/deshuttering etc. comp. up to 6 meter height /depth Av. G.L.for
all water retaining structures.
Flat bottom slab/floor slab/slab with shuttering
6.1 Vertical Wall Above 25 cm 50.00 Cum 9295.45
6.2 Beams 2.00 Cum 9758.90
6.3 Staircase 1.00 Cum 9654.25
Item Rate Amount
Description Qty. Unit
7 Providing and cast in situ C.C. in grade M-25 proportions of ingredients as per mix design 2.00 Cum 10574.25
by weigh batching using granite, quartzite trap metal of size 12 mm to 20 mm and or
mm to 12 mm including scaffolding centering formwork, needle vibrated consolidation,
curing and hydraulic testing etc. complete (excluding cost of reinforcement) with
centering and shuttering/deshuttering etc. comp. up to 6 meter height /depth Av. G.L.for
all water retaining structures.
8 Providing and casting in situ C.C. in grade M-20 (proportions as per mix design or as per 1.00 Cum 6348.00
table9 of IS456 2000 in masses by weigh batching ) using granite, quartzite trap metal of
size 6 mm to 20 mm for RCC work, including scaffolding centering, formwork, needle
vibrated consolidation, curing complete up to 6 meter depth or height (excluding cost of
reinforcement and neat finishing) with centering and shuttering/deshuttering etc.
complete for structure other than water retaining (Below G.L)
9 Supplying cutting, bending, binding and placing in position steel as per plan and design 9.00 MT 89129.60
and as per ISS 2502 including cost of steel and binding wire for reservoirs/structures only
including lift up to 6 meter height or depth below G.L. for all diameters.
Do – deformed (TMT) bars confirming to relevant IS Fe – 500 grade for all diameters.
10 Grouting with 1:3 cement mortar for anchor bolt pockets machine bases, pipe sleeves, 2.00 Cum 3628.63
pocket holes etc. including roughening and cleaning of concrete surfaces curing etc.
11 Supplying, cleaning, cutting, bending, welding, 'fabricating, erecting structural steel in 300.00 Kg 99.00
position irrespective of locations and levels as per drawing including handling and
transport etc. complete including applying two coats of primer red oxide and two coats of
approved quality of paint over it etc. complete as directed for gentry girder, platform,
stairs, chequered plate for cable trench etc.
12 Providing and fixing MS grating with 8 mm thick 50 mm wide flat at 50 mm c/c to form 4.00 Smt 12590.00
grid pattern as specified and wherever directed including two coats of approved quality
oil paint with one coat of primer red oxide etc. complete.
13 Providing and applying 20 mm thick inside OPC cement plaster with water proofing agent 76.00 Smt 303.00
on inside of sump consisting of 12 mm thick backing coat of CM 1:3 (1 cement : 3 sand)
and 8 mm thick finishing coat of CM 1:1 (1 cement : 1 sand) etc. complete including
necessary curing, scaffolding required if any etc. complete.
14 'Providing and applying 15 mm thick cement plaster in single coat on brick work with 10.00 Smt 246.05
floating coat of net cement slurry for interior plastering of pumphouse and outside
plastering of sump upto finished even and smooth in Cement motar 1 : 3 (1 cement :
sand) including racking out joint curing, scaffolding required if any, with necessary
cement finishing etc. complete as directed. (In pump house).
15 Providing and applying 20 mm thick sand faced cement plaster at outside RCC / brick on 7.00 Smt 342.41
work upto height 10 mtr. above ground level consisting of 12 mm thick backing coat of C.
M. 1:3 (1 cement : 3 sand) and 8 mm thick finishing coat of C. M. 1:1 (1 cement : 1 sand)
16 Providing and laying 40 mm thick cement concrete flooring in 1:2:4 (1 cement : 2 coarse 5.00 Smt 307.19
sand : 4 graded stone aggregate 20 mm nominal size) including water proofing compound
finishing with a floating of neat cement etc. complete laid in one layer finished including
necessary curing with sulphate resistant cement.
Item Rate Amount
Description Qty. Unit
17 Providing 100 mm x 100 mm size vata in cement concrete (1:2:4) including water proofing 12.00 Rmt 41.00
compounds, smooth finish, curing, etc. complete for the internal side of the SPS.
18 Providing, Cement vata (10 cm. X 10. cm. size) quarter round in cement motar 1:1 22.00 Rmt 24.28
including neat cement finishing, watering etc. complete
19 Brick work using common burnt clay building bricks having crushing strength not less 12.00 Cum 4214.33
than 35 kg./Sq.Cm. in foundation and plinth in Cement Mortar 1:6 (1- Cement : 6 -fine
sand)(B) Conventional
20 Providing and applying epoxy paint of approved make to concrete surface for RCC 76.00 Smt 103.50
structure including cleaning the surface by scrapping and air blowers to the satisfaction of
Engineer-in -charge necessary scaffolding etc. complete with all leads and lifts and giving
satisfactory hydraulic test for water tightness as per IS codes. For new surface-Two coats
21 Distempering in 3 coats with oil bound distemper of approved brand and manufacture 10.00 Smt 106.92
and of required shade on wall surface to give an even shade over and including a primer
coat with distemper primer of approved brand, thoroughly brushing the surface free
from mortar dropping and other foreign material and also inclusive of preparing the
surface even and smooth etc. complete,
22 Applying two coats of Birla(white cement based) or Asian (acryliclapy putty) or equivalent 10.00 Smt 40.59
& two coats of primer of approved brand and manufacture on new wall surface to give an
even shade including thoroughly brushing the surface free from mortar dropping and
other foreign matte rand sand papered smooth.
23 Wall painting (two coats) with plastic emulsion paint of approved brand and manufacture 7.00 Smt 82.85
of undercoated wall surface to give an even shade including thoroughly brushing the
surface free from mortar dropings and other foreign matter and sand papered smooth.
24 Providing and fixing 40mm dia. GI pipe medium weight quality as openable type with 4.00 Rmt 1433.00
angle iron support at 1.5 m c/c using 75 x 75 x 10 mm angles, 1 m long with three rows of
pipes as railing including necessary painting with two coats of approved quality oil paint
over one coat of approved primer including necessary welding, bolting required, if any.
25 Providing and fixing 50 cm wide M.S. Ladder fabricated from M.S. Flats 10 mm x 75 mm 7.00 Rmt 3392.50
with 20 mm dia steel bar steps in double rows, @ 30 em C/C. The include stays of
mm x 50 mm flats fixed at 3 meter C/C wtih welding anchoring and 3 coats
anticorrosive paint. (M.S. ladder (without safty cage))
26 Providing and fixing water tight construction or expansion joints 150 mm. dia. Wide thin 88.00 Rmt 379.50
27 Providing and fixing plastic moulded reinforced steps with 10 mm TOR steel bar with 40.00 No. 87.00
plastic polyproclene (P.P.) material (vergin) etc. complete.
28 Dewatering by pumping set of required capacity including temporary platform carting 500.00 HP/hr 21.07
pumping at site and fixing the same in position including all accessories, and fuel and
labour etc. complete.
Construction of Sewage Pumping Station (O-4)
Item Rate Amount
Description Qty. Unit
1 Excavation for well/pumping station including removing and spreading the excavated 73.00 Cum 313.95
stuffs directed with all lead.
0.0 m to 1.5 m depth
In hard rock with blasting and chiselling or by chiselling/Breaking only for finishing.
In hard rock with blasting and chiselling or by chiselling/Breaking only for finishing.
1.3 4.5 m to 6.0 m depth 1.00 Cum 813.05
In hard rock with blasting and chiselling or by chiselling/Breaking only for finishing.
2 Refilling the pipeline trenches incl. ramming, watering, consolidating desposal of surplus 70.00 Cum 25.30
stuff as directed within a radius of 3 km. Refilling as directed.
3 Providing and casting in situ C.C. in grade M-15 (approx. corresp. to prop. 1:2:4) 14.00 Cum 5641.90
(proportions as per mix design or as per Table 9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work,
including scaffolding centering, form work, needle vibrated consolidation, curing
comp. up to 6 meter depth or height (excluding cost of reinforcement and neat
finishing) with centering and shuttering/deshuttering etc. comp. for structure for other
than water retaining.
Footing for column or foundation (with form work)
4 Providing and casting in situ C.C. in grade M-15 (approx. corresp. to prop. 1:2:4) 5.00 Cum 5441.80
(proportions as per mix design or as per Table 9 of IS456 2000 in masses by weigh
batching ) using granite, quartzite trap metal of size 6 mm to 20 mm for RCC work,
including scaffolding centering, form work, needle vibrated consolidation, curing
comp. up to 6 meter depth or height (excluding cost of reinforcement and neat
finishing) with centering and shuttering/deshuttering etc. comp. for structure for other
than water retaining.
Footing (Without form work)
5 Providing and laying one layer of bitumen craft paper conforming to IS:1398 of 22.00 Smt 13.00
approved make and quality
6 Providing and cast in situ C.C. in grade M-30 proportions of ingredients as per mix 12.00 Cum 9444.95
design by weigh batching using granite, quartzite trap metal of size 12 mm to 20 mm
and or 6 mm to 12 mm including scaffolding centering formwork, needle vibrated
consolidation, curing and hydraulic testing etc. complete (excluding cost of
reinforcement) with centering and shuttering/deshuttering etc. comp. up to 6 meter
height /depth Av. G.L.for all water retaining structures.
Flat bottom slab/floor slab/slab with shuttering
6.1 Vertical Wall Above 25 cm 30.00 Cum 9295.45
6.2 Beams 2.00 Cum 9758.90
6.3 Staircase 1.00 Cum 9654.25
Item Rate Amount
Description Qty. Unit
7 Providing and cast in situ C.C. in grade M-25 proportions of ingredients as per mix 2.00 Cum 10574.25
design by weigh batching using granite, quartzite trap metal of size 12 mm to 20 mm
and or 6 mm to 12 mm including scaffolding centering formwork, needle vibrated
consolidation, curing and hydraulic testing etc. complete (excluding cost of
reinforcement) with centering and shuttering/deshuttering etc. comp. up to 6 meter
height /depth Av. G.L.for all water retaining structures.
8 Providing and casting in situ C.C. in grade M-20 (proportions as per mix design or as per 1.00 Cum 6348.00
table9 of IS456 2000 in masses by weigh batching ) using granite, quartzite trap metal of
size 6 mm to 20 mm for RCC work, including scaffolding centering, formwork, needle
vibrated consolidation, curing complete up to 6 meter depth or height (excluding cost of
reinforcement and neat finishing) with centering and shuttering/deshuttering etc.
complete for structure other than water retaining (Below G.L)
9 Supplying cutting, bending, binding and placing in position steel as per plan and design 5.00 MT 89129.60
and as per ISS 2502 including cost of steel and binding wire for reservoirs/structures
only including lift up to 6 meter height or depth below G.L. for all diameters.
Do – deformed (TMT) bars confirming to relevant IS Fe – 500 grade for all diameters.
10 Grouting with 1:3 cement mortar for anchor bolt pockets machine bases, pipe sleeves, 2.00 Cum 3628.63
pocket holes etc. including roughening and cleaning of concrete surfaces curing etc.
11 Supplying, cleaning, cutting, bending, welding, 'fabricating, erecting structural steel in 300.00 Kg 99.00
position irrespective of locations and levels as per drawing including handling and
transport etc. complete including applying two coats of primer red oxide and two coats
of approved quality of paint over it etc. complete as directed for gentry girder, platform,
stairs, chequered plate for cable trench etc.
12 Providing and fixing MS grating with 8 mm thick 50 mm wide flat at 50 mm c/c to form 4.00 Smt 12590.00
grid pattern as specified and wherever directed including two coats of approved quality
oil paint with one coat of primer red oxide etc. complete.
13 Providing and applying 20 mm thick inside OPC cement plaster with water proofing 50.00 Smt 303.00
agent on inside of sump consisting of 12 mm thick backing coat of CM 1:3 (1 cement :
sand) and 8 mm thick finishing coat of CM 1:1 (1 cement : 1 sand) etc. complete
including necessary curing, scaffolding required if any etc. complete.
14 'Providing and applying 15 mm thick cement plaster in single coat on brick work with 10.00 Smt 246.05
floating coat of net cement slurry for interior plastering of pumphouse and outside
plastering of sump upto finished even and smooth in Cement motar 1 : 3 (1 cement :
sand) including racking out joint curing, scaffolding required if any, with necessary
cement finishing etc. complete as directed. (In pump house).
15 Providing and applying 20 mm thick sand faced cement plaster at outside RCC / brick on 7.00 Smt 342.41
work upto height 10 mtr. above ground level consisting of 12 mm thick backing coat of
C. M. 1:3 (1 cement : 3 sand) and 8 mm thick finishing coat of C. M. 1:1 (1 cement :
sand) etc. complete
16 Providing and laying 40 mm thick cement concrete flooring in 1:2:4 (1 cement : 2 coarse 5.00 Smt 307.19
sand : 4 graded stone aggregate 20 mm nominal size) including water proofing
compound finishing with a floating of neat cement etc. complete laid in one layer
finished including necessary curing with sulphate resistant cement.
Item Rate Amount
Description Qty. Unit
17 Providing 100 mm x 100 mm size vata in cement concrete (1:2:4) including water 12.00 Rmt 41.00
proofing compounds, smooth finish, curing, etc. complete for the internal side of the
18 Providing, Cement vata (10 cm. X 10. cm. size) quarter round in cement motar 1:1 20.00 Rmt 24.28
including neat cement finishing, watering etc. complete
19 Brick work using common burnt clay building bricks having crushing strength not less 12.00 Cum 4214.33
than 35 kg./Sq.Cm. in foundation and plinth in Cement Mortar 1:6 (1-Cement : 6 -fine
sand) (B) Conventional
20 Providing and applying epoxy paint of approved make to concrete surface for RCC 50.00 Smt 103.50
structure including cleaning the surface by scrapping and air blowers to the satisfaction
of Engineer-in -charge necessary scaffolding etc. complete with all leads and lifts and
giving satisfactory hydraulic test for water tightness as per IS codes. For new surface-
21 Distempering in 3 coats with oil bound distemper of approved brand and manufacture 10.00 Smt 106.92
and of required shade on wall surface to give an even shade over and including a primer
coat with distemper primer of approved brand, thoroughly brushing the surface free
from mortar dropping and other foreign material and also inclusive of preparing the
surface even and smooth etc. complete,
22 Applying two coats of Birla(white cement based) or Asian (acryliclapy putty) or 10.00 Smt 40.59
equivalent & two coats of primer of approved brand and manufacture on new wall
surface to give an even shade including thoroughly brushing the surface free from
mortar dropping and other foreign matte rand sand papered smooth.
23 Wall painting (two coats) with plastic emulsion paint of approved brand and 7.00 Smt 82.85
manufacture of undercoated wall surface to give an even shade including thoroughly
brushing the surface free from mortar dropings and other foreign matter and sand
papered smooth.
24 Providing and fixing 40mm dia. GI pipe medium weight quality as openable type with 4.00 Rmt 1433.00
angle iron support at 1.5 m c/c using 75 x 75 x 10 mm angles, 1 m long with three rows
of pipes as railing including necessary painting with two coats of approved quality oil
paint over one coat of approved primer including necessary welding, bolting required, if
25 Providing and fixing 50 cm wide M.S. Ladder fabricated from M.S. Flats 10 mm x 75 mm 5.00 Rmt 3392.50
with 20 mm dia steel bar steps in double rows, @ 30 cm C/C. The include stays of
mm x 50 mm flats fixed at 3 meter C/C with welding anchoring and 3 coats anticorrosive
paint.. (M.S. ladder (without safty cage))
26 Providing and fixing water tight construction or expansion joints 150 mm. dia. Wide thin 62.00 Rmt 379.50
27 Providing and fixing plastic moulded reinforced steps with 10 mm TOR steel bar with 30.00 No. 87.00
plastic polyproclene (P.P.) material (vergin) etc. complete.
28 Dewatering by pumping set of required capacity including temporary platform carting 500.00 HP/hr 21.07
pumping at site and fixing the same in position including all accessories, and fuel and
labour etc. complete.
Providing and Laying of Rising Main
Item Rate Amount
Description Qty Unit
1 Excavation for pipe line trenches for water supply, sewerage line, manhole etc. 4181.80 Cum 102.35
all with shoring and struting if required as per required gradient and line
including safety provisions using site rails and stacking excavated stuff
including up to all required lead cleaning the site etc. complete for all lifts and
strata as specified.
0 to 1.5 Mtr Depth
In all sorts of soil and soft murrum
2 Excavation in bituminous road as per required gradient and line including 568.2 Cum 288.65
safety provisions using site rails and stacking excavated stuff including up to all
lead cleaning the site etc. complete for all lifts as specified.
3 Providing and supplying D. I. K-9 grade pipes for following nominal bore 2280.00 Rmt 1655.00
diameter with internal cement mortar lining including all taxes,
insurance,transportation, freight charges, octroi,inspection charges, loading,
unloading, conveyance to departmental stores, stacking etc.complete. (IS 8329-
For sewerage project cement mortor lining shall be with sulphate resistance
4 Lowering, laying and jointing C. I. S & S Spun pipes suitable for Tyton joints / 2280.00 Rmt 87.40
Mortar lined D. I. Pipes of various classes with CI / MS specials of following
diameters in proper position, grade and alignment as directed by Engineer-in-
charge including hydraulic testing etc. comp.
5 Manufacture, Supply & Delivery of Ductile Iron Flange socket spigot bends, 2108.00 kg 148.00
tees, reducers or any other specials as per BS-EN-545/1995 Class-A series K12
suitable for use with D.I. Pipes manufactured as per IS:8329/1994delivery of
specials is to be made to store or site of works any where in Gujarat including
all taxes, loading, unloading, carting, stacking, insurance, inspection charges,
octroi etc. complete.
With external bitumen & zinc coating & internal cement mortar lining.
Socket & Spigot Type
80 to 300 mm Dia
6 Providing and casting in situ C.C. in grade M-20 (proportions as per mix design 18.00 Cum 6348.00
or as per table9 of IS456 2000 in masses by weigh batching ) using granite,
quartzite trap metal of size 6 mm to 20 mm for RCC work, including scaffolding
centering, formwork, needle vibrated consolidation, curing complete up to
meter depth or height (excluding cost of reinforcement and neat finishing)
with centering and shuttering/deshuttering etc. complete for structure other
than water retaining (Below G.L)
Footing for column or foundation (with form work) (For Thrust block &
Item Rate Amount
Description Qty Unit
7 Supplying cutting, bending, binding and placing in position steel as per plan 1.00 MT 89129.60
and design and as per ISS 2502 including cost of steel and binding wire for
reservoirs/structures only including lift up to 6 meter height or depth below
G.L. for all diameters
Do – deformed (TMT) bars confirming to relevant IS Fe – 500 grade for all
8 Refilling the pipeline trenches including ramming, watering, consolidating 4676.00 Cum 25.30
disposal of surplus stuff as directed within a radius of 3 Km. Refilling as
9 Providing and supplying ISI mark CI D/F Sluice Valves as per IS:14846 (Latest 2.00 No. 5848.00
Edition) of following class and diameter including all taxes, insurance,
transportation, freight charges, octroi, inspection charges, loading, unloading,
conveyance to departmental stores, stacking etc. complete.
PN-1 With hand wheel /cap operated (PD type short body)
9.1 Lowering, laying and jointing in position following C. I. / D/F Reflux valves, 2.00 No. 672.75
Butterfly valves, Sluice valves and Air valves including cost of all labour,
jointing material, including nut bolts and giving satisfactory hydraulic testing,
10 Providing and supplying ISI mark CI D/F Scour Valves as per IS: 14846 (Latest 2.00 No. 3563.00
Edition) of following class and diameter including all taxes, insurance,
transportation, freight charges, octroi, inspection charges, loading, unloading,
conveyance to departmental stores, stacking etc. complete.
PN-1 With hand wheel /cap operated (PD type short body)
10.1 Lowering, laying & jointing in position following CI D/F Scour Valves including 2.00 No. 504.85
cost of all labour, jointing material, including nut bolts & giving satisfactory
hydraulic testing, etc. complete.
11 Providing and supplying C. I. Temper proof Air valves with SS 304 Float gun 4.00 No. 11221.00
metal- nozzle of approved make & quality of following class and diameter
including all taxes, insurance, transportation, freight charges, octroi,
inspection charges, loading, unloading, conveyance to
departmental stores, stacking etc. complete.
With Isolating Sluice Valve PN
11.1 Lowering, laying & jointing in position following CI D/F Scour Valves including 4.00 No. 435.85
cost of all labour, jointing material, including nut bolts & giving satisfactory
hydraulic testing, etc. complete.
Air Valve Double Ball Flanged
Item Rate Amount
Description Qty Unit
12 Construction of 200 mm thick un-reinforced, dowel jointed, plain cement 2440.00 Sq.m 1634.00
concrete pavement with M - 35 grade of concrete including provision of
contraction, expansion, construction and longitudinal joints, joint filler,sealant
primer, joint sealant, , dowel bar, tie rod, admixtures as approved, finishing to
lines and grades as per drawing as per MoRTH clause 602 over a 200 mm thick
WMM with necessary excavation/ loosening and recompacting ground as per
respective MoRTH specification and as directed by engineerin charge
13 Construction of valves chambers in brick or bela stone masonry, locally 8.00 No. 8898.70
available in C. M. 1:6. Foundation concrete 150 mm thick in C. C. 1:4:8 of trap
metal size 25 mm to 40 mm thick, inside cement plaster in C. M. 1:3 and
cement pointing outside in C. M. 1:3 and top cover of precast RCC slab
mm thick (with key hole in two parts, each with handles or MS Bar etc.
complete as given size) Upto 1 Mt. depth from G. L. to pipe invert level incl.
complete civil works but excl. cost of excavation and refilling, with cast in situ
RCC slab in one single piece with fixing of CI-MH Frame and cover (excl. cost of
CI-MH Frame and cover) with 23 mm thick brick masonry wall in C.M.1:6
Size of 0.9 m x 0.9 m and 1.0 m deep
With precast slab in two parts 15 mm
13.1 For 1 m. extra depth 4.00 Rmt 5150.85
14 Drilling of Horizontal bore hole for water main pipeline under the Railway / 20.00 Rmt 2148.00
Road tracks in all strata with required length including fixing of M.S.(or as
specified by Railway / Road authority) casing pipe of suitable size and
Thickness. Rate includes the cost of Drilling of bore hole , Casing pipe &
welding pushing etc complete but excluding the cost of water main, valves and
other items. Entire work should be as per Approved Drawing and as per
instruction of Railway / Road authority for Following diameter of Bore hole. for
Horizontal Drilling-250:& MS Casing Pipe-200 thick:5
Construction of Inspection Chambers
Item Rate Amount
Description Qty Unit
1 Providing and supplying of Class SN8 Structured Wall polyethelene Piping systems (Pipe with 17000.00 Rmt 208.00
online/offline coupler and elastomeric sealing ring) with non-smooth External Annular
Corrugated and Smooth Internal Surfaces (Double Wall) for non-pressure underground
Sewerage & Drainage application as per EN:13476-3 including all local and central taxes,
transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to
the departmental stores etc. complete.(ID Dia) 100 mm Dia
2 Excavation for pipeline trenches for sewerage line, manhole etc. all with shoring and strutting if 7900.02 Cum. 102.35
required as per required gradient and line including safety provisions using site rails and
stacking excavated stuff including up to all required lead Cleaning the site etc. complete for lifts
and strata as specified.
In all sorts of soil and soft murrum
3 Providing and laying cement concrete 1:5:10 (1- Cement : 5-Coarse sand : 10- hand broken 558.35 Cum. 2606.92
stone aggregates 40 mm nominal size) and curing complete excluding cost of formwork in (A)
Foundation and Plinth
4 Brick work using common burnt clay building bricks having crushing strength not less than 35 672.13 Cum. 4245.09
kg./Sq.Cm. in foundation and plinth in Cement Mortar 1:5. (1- Cement : 5 -fine sand) (B)
5 Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or half brick 2218.50 Sqmt 195.42
walls for interior plastering up to floor two level and finished even and smooth in (i) Cement
mortar 1:3 (1-cement:3-sand)
5.1 Extra over above itmes for finishing with a floating coat of neat cement slurry. 2218.50 Sqmt 50.62
6 Refilling the Pipeline Trenches incl. Ramming, watering, consolidating and deposal of surplus 6183.85 Cum. 25.30
stuff as directed within a radius of 3 KM. Refilling as directed.
7 Providing and laying cement concrete work 1:2:4 (1- Cement : 2- Coarse sand : 4- graded stone 472.12 Cum. 4189.91
aggregates 20 mm nominal size) and curing complete excluding cost of formwork and
reinforcement for reinforced concrete work in (B) Slabs, landing, shelves, Balconies, Lintels,
Beams, Girders and Cantilever up to floor two level.
8 Providing formwork of ordinary timber planking so as to give a rough finish including centring 3114.40 Sqmt 205.45
shuttering strutting and propping etc. height of propping and centring below supporting floor to
ceiling not exceeding 4 M. and removal of the same for in situ reinforced concrete and plain
concrete work in. (H) (1) Sides and soffits of Beams Beam Haunching's cantilevers Girders
Bressummers and Lintels not exceeding 1 M. in Depth.
9 Providing and laying cement concrete work 1:2:4 (1- Cement : 2- Coarse sand : 4- graded stone 82.69 Cum. 4094.10
aggregates 20 mm nominal size) and curing complete excluding cost of formwork and
reinforcement for reinforced concrete work in (A) Foundations, footings, Base or columns and
Mass concrete For Benching
10 Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior 953.70 Sqmt 145.65
plastering up to floor two level and finished even and smooth in (I Cement mortar 1:3 (1-
cement:3- sand) above beaching
11 RCC precast M.H. Frame & Cover Manufacture, supply & Delivery at store or at site of work 1700.00 Nos. 813.00
precast RCC M.200 Frame & cover suitable to drainage M.H. and as per type design & Drawing
including cost of reinforcement M.S. Angles or Flat, curing mold work etc.
House Connection Chamber Light duty
Item Rate Amount
Description Qty Unit
12 Lowering, laying and jointing of class SN 8 structured wall ( External Annular Corrugated & 17000.00 Rmt 24.15
Smooth Internal surface) Polyethylene Piping and fittings with the help of coupler ( on line / off
line ) attached with one end of pipes, sliding over the elastomeric sealing rubber ring placed on
the specified valley of the corrugation at the spigot end, lowering the same into the trench at all
level, laying on the lower bedding (constructed at bottom of trenches) at prescribed
gradient,depth & alignment ,testing the water tightness of the joints, ensuring the continuity
tests of specified pipe segments etc. complete as per drawing,specifications & detailed
engineering, including carriage of pipes & fittings from site stacks to the place of laying etc. as
per direction of Engineer-in-charge.
Construction of House Connections
Item Rate Amount
Description Qty Unit
1 Providing and supplying of Class SN8 Structured Wall polyethelene Piping systems (Pipe with 34000.00 Rmt 208.00
online/offline coupler and elastomeric sealing ring) with non-smooth External Annular Corrugated and
Smooth Internal Surfaces (Double Wall) for non-pressure underground Sewerage & Drainage
application as per EN:13476-3 including all local and central taxes, transportation, freight charges,
octroi, inspection charges, loading, unloading, conveyance to the departmental stores etc. complete.(ID
Dia) 100 mm Dia
2 Excavation for pipeline trenches for sewerage line, manhole etc. all with shoring and strutting if 14287.62 Cum 102.35
required as per required gradient and line including safety provisions using site rails and stacking
excavated stuff including up to all required lead Cleaning the site etc. complete for lifts and strata as
In all sorts of soil and soft murrum
3 Providing and laying cement concrete 1:5:10 (1- Cement : 5-Coarse sand : 10- hand broken stone 573.04 Cum 2606.92
aggregates 40 mm nominal size) and curing complete excluding cost of formwork in (A) Foundation and
4 Brick work using common burnt clay building bricks having crushing strength not less than 35 746.03 Cum 4245.09
kg./Sq.Cm. in foundation and plinth in Cement Mortar 1:5. (1- Cement : 5 -fine sand)
(B) Conventional
5 Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or half brick walls 1836.00 Sqmt 195.42
for interior plastering up to floor two level and finished even and smooth in
(i) Cement mortar 1:3 (1-cement:3-sand)
5.1 Extra over above items for finishing with a floating coat of neat cement slurry. 1836.00 Sqmt 50.62
6 Refilling the Pipeline Trenches incl. Ramming, watering, consolidating and deposal of surplus stuff as 12549.05 Cum 25.30
directed within a radius of 3 KM. Refilling as directed.
7 Providing and laying cement concrete work 1:2:4 (1- Cement : 2- Coarse sand : 4- graded stone 392.77 Cum 4189.91
aggregates 20 mm nominal size) and curing complete excluding cost of formwork and reinforcement
for reinforced concrete work in (B) Slabs, landing, shelves, Balconies , Lintels, Beams, Girders and
Cantilever up to floor two level.
8 Providing formwork of ordinary timber planking so as to give a rough finish including centring 3583.60 Sqmt 205.45
shuttering strutting and propping etc. height of propping and centring below supporting floor to ceiling
not exceeding 4 M. and removal of the same for in situ reinforced concrete and plain concrete work in.
(H) (1) Sides and soffits of Beams Beam Haunching's cantilevers Girders Bressummers and Lintels not
exceeding 1 M. in Depth.
9 Providing and laying cement concrete work 1:2:4 (1- Cement : 2- Coarse sand : 4- graded stone 102.30 Cum 4094.10
aggregates 20 mm nominal size) and curing complete excluding cost of formwork and reinforcement
for reinforced concrete work in (A) Foundations, footings, Base or columns and Mass concrete For
10 Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior plastering up to 336.60 Sqmt 145.65
floor two level and finished even and smooth in (I Cement mortar 1:3 (1-cement:3- sand) above
11 RCC precast M.H. Frame & Cover Manufacture, supply & Delivery at store or at site of work precast RCC 3400.00 Nos. 813.00
M.200 Frame & cover suitable to drainage M.H. and as per type design & Drawing including cost of
reinforcement M.S. Angles or Flat, curing Mold work etc.
House Connection Chamber light duty
12 Lowering, laying and jointing of class SN 8 structured wall ( External Annular Corrugated & Smooth 34000.00 Rmt 24.15
Internal surface) Polyethylene Piping and fittings with the help of coupler ( on line / off line ) attached
with one end of pipes, sliding over the elastomeric sealing rubber ring placed on the specified valley of
the corrugation at the spigot end, lowering the same into the trench at all level, laying on the lower
bedding (constructed at bottom of trenches) at prescribed gradient,depth & alignment ,testing the
water tightness of the joints, ensuring the continuity tests of specified pipe segments etc. complete as
per drawing,specifications & detailed engineering, including carriage of pipes & fittings from site stacks
to the place of laying etc. as per direction of Engineer-in-charge.
02-Years of Operation & Maintanance For Drainage Network System
ITEM QTY. UNIT RATE (RS.) AMOUNT (Rs)
Comprehensive Operation and Maintenance of the various components of Under ground Drainage scheme
undertaken in this tender mainly sewer collecting network, pumping station, Rising Main pipeline, pumping
machinery & Electrical works & other works as a whole including 1) Breakdown Maintenance or Emergency
Maintenance, 2) Day to day Maintenance, 3) Preventive or Periodic Maintenance, 4) Major Maintenance (or Special
repairs and replacement including Training to O & M staff of Municipality. The rate shall also include all
consumables and deployment of Manpower but excluding electric power (The electrical bill for power shall be paid
by the municipality) . The O & M work shall be carried out as per detailed specifications in the tender & maintaining
the record for the same. - For 1st year O&M
Comprehensive Operation and Maintenance of the various components of Under ground Drainage scheme
undertaken in this tender mainly sewer collecting network, pumping station, Rising Main pipeline, pumping
machinery & Electrical works & other works as a whole including 1) Breakdown Maintenance or Emergency
Maintenance, 2) Day to day Maintenance, 3) Preventive or Periodic Maintenance, 4) Major Maintenance (or Special
repairs and replacement including Training to O & M staff of Municipality. The rate shall also include all
consumables and deployment of Manpower but excluding electric power (The electrical bill for power shall be paid
by the municipality) . The O & M work shall be carried out as per detailed specifications in the tender & maintaining
the record for the same. - For 2nd year O&M
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01_Vol-I-A_Technical_Bid_Chorwad_UGD-II.pdf
02_Vol-I-B_GCC_Chorwad_UGD-II.pdf
03_Vol-II-Part-A_Extent_of_Works_Chorwad_UGD-II.pdf
05_Vol-II_Part-C_Gen_Tech_Spec_Civil_R_and_B.pdf
06_Vol-II_Part-D_Gen_Tech_Spec_Electrical-Part-1.pdf
07_Vol-II_Part-E_Gen_Tech_Spec_Electrical-Part-2.pdf
08_Vol-II_Part-F_Technical_Data_Sheet_Chorwad_UGD-II.pdf
09_Vol-III_Price_Bid_Chorwad_UGD-II.pdf
10_Vol-III_Price_Bid_Schedule-B_Chorwad_UGD-II.pdf
11_Vol-IV_Bid_Drawing_Chorwad_UGD-II.pdf
12_Vol-V_Cond_of_Cont_for_O_and M_UGD_Chorwad_UGD-II.pdf
13_DMO_2941_01-Apr-2026_744.pdf
14_Price_Variation_Paripatra_16-03-2023.pdf
15_GR_DOC_1.pdf
16_GR_DOC_2.pdf
04_Vol-II-Part-B_Tech_Spec_Civil_Elect-Mech_Chorwad_UGD-II.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .