Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹48.0 LAccepted-AOC 1 C NEPAL BHATTACHARJEE STREET KALIGHAT KOLKATA 700026 | KOLKATA | KOLKATA | WEST BENGAL | 700026 | L1 | Accepted-AOC L1 | |
| 2 | L2₹50.0 L+₹2.1 L (4.33%)Rejected-Finance 13 11 MOTILAL GUPTA ROAD KOLKATA 700 008 | KOLKATA | KOLKATA | WEST BENGAL | 700008 | L2 | Rejected-Finance L2 | |
| 3 | L3₹53.8 L+₹5.9 L (12.2%)Rejected-Finance MOSAT HARIPUR RD VILL P O HARIPUR DIST HOOGHLY PIN 712701 | HARIPUR | HOOGHLY | WEST BENGAL | 712701 | L3 | Rejected-Finance L3 | |
| 4 | Rejected-Technical 17 23 K P ROY LANE KOLKATA 700 031 | KOLKATA | KOLKATA | WEST BENGAL | 700031 | - | Rejected-Technical Insufficient valid Documents in shortfall stage |
Tender Value
Refer Docs
EMD Value
₹95,972
Closing Date
8 Jul 2025, 3:00 pmClosed
Room No. 108, Purta Bhawan, Salt Lake
Room No. 108, Purta Bhawan, Salt Lake
Temporary Electrical Installation work including hiring of DG sets for utility and broadcasting in connection with the upcoming 134th Durand Cup Tournament 2025 to be held at Vivekananda Yuba Bharati Krirangan Salt Lake
2025_WBPWD_866439_1
WBPWD/EE/BED/e-NIQ-33/2025-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
3 days
Vivekananda Yuba Bharati Krirangan
Please refer Tender documents.
5 documents required · 5 mandatory
₹95,972
22 Jul 2025
19 Jun 2025
10 Jul 2025
24 Jun 2025
8 Jul 2025
24 Jun 2025
Amount
Supply & Providing on hire basis 415V 750 kVA 3 phase 50 Hz silent type DG set of suitable generator of reputed make including providing of 1.1 kv grade of 3 Run, 4/3.5 core 240 sqmm AL/A cable or equivalent of similar current carrying capacity cable (maximum length-250 mtr in each run) (From DG set to LT panel) with 4 nos proper earthing for neutral & body and dismantling the same after completion of event, including proper socketing, gland etc with suitable interconnection and provide sufficient manpower with tools & tackles for maintenance & operation arrangement for each DG set and the installation round the clock.
(01 nos DG set X 11 days) (10 match days for Utility service on match day and 01 day for testing)
Supply & Providing on hire basis 415V 500 kVA 3 phase 50 Hz silent type DG set of suitable generator of reputed make including providing of 1.1 kv grade of 2 Run, 4/3.5 core 240 sqmm AL/A cable or equivalent of similar current carrying capacity cable (maximum length-250 mtr in each run) (From DG set to LT panel) with 4 nos proper earthing for neutral & body and dismantling the same after completion of event, including proper socketing, gland etc with suitable interconnection and provide sufficient manpower with tools & tackles for maintenance & operation arrangement for each DG set and the installation round the clock.
(03 nos DG set X 11 days) (10 match days for Utility service on match day and 01 day for testing)
Supply & Providing on hire basis 415V 62.5 kVA 3 phase 50 Hz silent type DG set/equivalent capacity of suitable generator of reputed make including proving of 1.1 kv grade of 4 core 50 sqmm AL/A cable (maximum length-250 mtr in each run) (From hiring DG to changeover, existing panel to changeover, change over to distribution panel), 4 nos10' GI Pipe earthing for neutral & Body using 50 sq. mm. Single core copper cable & dismantle the same after completion of event, including proper socketing, gland etc with suitable interconnection as per GS and provide sufficient manpower with tools & tackles for maintenance & operation arrangement of the installation around the clock.
(01 nos DG set X 20 days) ( for dedicated power back up of Broadcasting on match day & before match day)
S & providing of Diesel oil for dedicated DG sets 1. S & providing of Diesel oil for dedicated power back up of Utility. ( 01 no 750 kVA DG set) (75% load) ( 126 ltr/h) 2. S & providing of Diesel oil for dedicated power back up of Utility . (3 nos 500kVA DG set) (80% load) ( 80 ltr/h) 3. S & providing of Diesel oil for dedicated for light tower. (4 nos 500kVA DG set) (90% load) ( 100 ltr/h) (for Exiting DGs) 4. S & providing of Diesel oil for dedicated power back up of Broadcasting. (01 no 62.5 kVA DG set) ( 20 ltr/h )
Transportation & storage and pouring handling of Diesel oil.
Supply & Providing of hire basis 415 V 4 Pole 125 A Onload Change Over Switch. (1no X 20 days)
Providing on hire basis following main switches/MCB/porcelain fuse base distribution system/200A four bar busbar chamber etc. on a suitable iron frame including providing suitable interconnection wiring with socketing and 2 nos 50 mm dia 10 feet long earthing arrangements including interconnection. Dismantling at the end of program Elect. Comprising of the following acessories i) 415 V 4 Pole 125A MCCB with all acessories . ii) 415 v 200A TPN busbar chamber with 4 (four) bar. iii) 16 A MCB distribution system - 10 Nos. iv) 32 A TPN MCB distribution system - 3 Nos. v) Suitable covering arrangements for weather protection (1no X 20 days)
Supply and installation on hire basic 800 Amp ATS panel for supply the electrical power with in 30 sec during power failure (4 nos X 20 days)
Supply and fixing of 6/16 A combination power consisting 3 nos each board with 5 mtr extension cable at Boardcast Room. (30 no X 20 days)
Supply & installation on Hire basis 30w LED Bulb with Holder (15 nos x 10 days) at Sequirity Checking Area (DFMD).
Supply & installation on Hire basis 2 core 6sq. mm. Al. Cable ( 800 mtr x 10 days)
Providing on hire basis outdoor type 3pin 6A Plug scoket with necessary interconnection wire 1.5 sq. mm. cupper wire for DFMD and Other areas. (60 nos x 10 days)
Supply & installation on Hire basis 200 w LED Flood Light Fittings for different Cutouts (50 nos x 10 days)
Supply & installation on Hire 2 x 2.5 sq mm + 1 x 1.5 sq. mm. Cu. Wire for lighting arrengment. (600 Mtr x 10 days)
Supply and installation 16 A DP MCB with suitable enclosure on hire basis.(08 nos x 10 days)
Supply and installation of pedestal fan with suitable enclosure on hire basis.(30 nos x 10 days)
Note:- 1. Rate should be quoted inclusive of all taxes and duties including GST, 2. Original diesel filter is to be changed in each D.G. sets before each match, keeping sufficient time in hand, 3. Fuel is to be stored in the fuel tank of D.G. sets once at a time before starting of the game (before at least 5 hours) considering the match duration including extra time. Further addition of fuel will not be allowed during the playing time. 4. Fuel Log must be updated on daily basis.
S. K. CHATTERJEE ELECTRICALS PVT LTD (BID ID -6683041)
GHANASHYAM ELECTRIC STORES (BID ID -6684232)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .