Head ESD
Post Mohkampur Dist Dehradun
Installation of ducting system and VRF and TFA system
2021_CSIR_98135_1
IIP/ESD/2/10/2021
Open Tender
Electrical Works
Item Rate
120 days
CSIR-IIP
Please refer Tender documents.
12 documents required · 12 mandatory
₹590
Director
₹51,900
Yes
23 Dec 2021
14 Dec 2021
21 Dec 2021
14 Dec 2021
20 Dec 2021
14 Dec 2021
Amount
REFRIGERANT PIPING (WITH INSULATION) (Rajco/Mexflow/Indigo) Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system,complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
31.8 mm dia (OD) (Hard drawn) with tube thickness 1.62 mm with 19 mm thick insulation
19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
GI Ducting (Ductofab/Zeco/Waves) Supply, installation, balancing and commissioning of fabricated at site GI sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes,hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
24 G (Thickness 0.63 MM)
22 G (Thickness 0.80 MM)
Air Distribution System (Systemair/Mapro/Servex/Cynor)
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
SITC of Nitrile Duct Insulation 19mm (Armaflex/Supreme/K-flex)
Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class "O") insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.
Cabling (Skytone/Polycab/KEI)
3 C X 2.5 Sq.mm with PVC conduit
4 C X 6 sq. mm + 2 X 6 sq. mm earth wire with PVC cinduit
Electrical Isolators (L&T/ABB/SIEMENS)
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, suitable for AHU & Tube axial fan, complete with connections, testing and commissioning etc. as required.
SITC of VARIABLE REFRIGERANT FLOW SYSTEM (Mitsubishi/Toshiba/Carrier/O-General/Voltas/Hitachi) Outdoor Unit - 38 HP (Heating & Cooling) (14HP+24HP) Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required.
The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5
SITC of Indoor Units (Edgetech/Zeco/Humid-in/Waves
DX TFA 7500 CFM SP-50mmwg/23 TR
TFA Kit
Drain Pipe (40mm dia)with 6mm Insulation (Supreme/Prince/Hindware)
Drain pipe (40mm dia)
Cabling (Skytone/Polycab/KEI)
4 C X 25 Sq.mm
Electrical Isolators (L&T/ABB/SIEMENS)
160 Amps suitable with outdoor unit ampere rating, complete with connections, testing and commissioning etc
VENTILATION EQUIPMENTS (Greenheck/Airflow/Flaktwood) SITC of Tube Axial type fan with F class insulation along with necessary accessories required. DB level not to exceed 75 @ 3 mtrs under room condition. Efficiency ≥ 65 %. Flow Direction of flow shall be impeller to motor.
Air Qty - 7500 CFM ; Static Pressure = 30 mm Wg
AIR PURIFICATION SYSTEM (Intelligreen/Aerisa/Bentaxna) Supply, Installation, Testing and commissioning of comprehensive Air Purification system in the specified areas where AHU/VRV/ Cassette /Hi-wall / Ductable units etc are installed , so as to improve Indoor air quality by using combination of Needle point , Tube Type & Carbon Brush Type Bi-polar Ionization technology, which produces a natural Bio Climate rich in positive and negative ions. The Needle Point and Carbon Brush type Bipolar Ionizers should not have any consumables and should have a life of 10 years. Project design should meet standard ASHRAE 62.1 IAQ Procedure for energy saving. System should kill microorganism and pathogens, remove Odour, VOC and reduce dust particle /particulate matter / PM2.5 /PM 10. The product should be UL / Intertek listed. Product should have minimal or negligible pressure drop & low power consumptions. Product should have UL 867 and UL 2998 certification (for zero ozone emission). The Product shall have been Tested on COVID-19 Surrogate for its efficacy.
Air Purification System as Above mentioned (7000 Series / 200 series
Utility Services
IRANI TRADERS
UNIQUE ENGINEERS PVT. LTD.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .