| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.6 LAccepted-AOC LAXMI BAZAER TEHSIL JOGINDERNAGAR DISTT MANDI HP | MANDI | HIMACHAL PRADESH | 175001 | L1 | Accepted-AOC As per negotiation | |
| 2 | L2₹16.2 L+₹20,451 (1.28%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹19.1 L+₹3.1 L (19.3%)Rejected-Finance | L3 | Rejected-Finance Other than lowest | |
| 4 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | |
| 5 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹16.1 L
EMD Value
₹32,000
Closing Date
7 Sept 2020, 5:00 pmClosed
Executive Engineer
Executive Engineer Jal Shakti Division Mandi Tarna Hill
Supply and installation of Centrifugal Pumping Machinery with allied accessories and Rising Main
2020_HPIPH_40235_1
7373-7422
Open Tender
Pumps/Motors
Item Rate
120 days
Marathu Janed Mandi
Please refer Tender documents.
9 documents required · 9 mandatory
₹400
Yes
EE Mandi
₹32,000
Yes
16 Jan 2021
1 Sept 2020
8 Sept 2020
1 Sept 2020
7 Sept 2020
1 Sept 2020
Amount
Providing and installation of horizontal spindle,horizontal/redial split casing/end suction(Back-pull out arrangements) single/double/multi stage centrifugal pump or combination of pumps, In series/parallel of recommended make such as Mather and Platt/KSB/ Beacon Weir/Kirlosker/BE/Jyoti as per BIS 1520-1980 with upto date ammendments, read with IS:9137-1978 or latest edition suitable for lifting water for under mentioned characterestics with bronze,impellers/priming funnels,casing ring and shaft sleeves of bronze,shaft of steel grade 4508 FN8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel base plate (base plate to be from the manufacturer of the pumping unit only) to slip ring/ squirrel cage screen protected drip proof induction motor /motors of standard make such as Kirlosker/BHEL /Crompton /NGEF /GEC/Siemens/Jyoti /ABB and suitable for operation on 400(+/-)10% volts,50 cycles /second.3 phase AC electric supply. The power of electric motor/motors should be at +10% in excess of the maximum power required by the pump/pumps in the operation range of (+) 10% and (-)15% of the duty poiint head. The motor/motors as per ISI:325:1978 with upto date ammendments read with IS 900:1972. It should include cost of bearing nuts , bolts and painting etc. and should meet the following requirements: .
Providing ICTP main switch with HRC fuses of Kilburn/ L&T/Siemens/Standard/ Havells make and having capacity 30% extra of the operational rating as per IS: 4064-1978 with up to date amendments , immediately after the power meter of the HPSEBL.
Providing MS sheet steel fabricated floor mounted closed(almirah type) switch board including angle iron post of suitable height and size ISA 40x4r0x6 duly painted with steel sheet of 16 gauge comprising and capable of mounting the following accessories within all internal connections. All the accessories should be suitable for the proposed pumping machinery at item No.1 above and to the entire satisfaction of HPSEB authorities. The same shall have to be replaced with out extra cost if recommended by HPSEB authorities
a) OCB/MCCB of MEI/Havels/ standard make and of suitable capacity for offered motor on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage released as per relevent IS code with upto date ammendments
b) Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per IS:2516:1977 with upto date ammendments of suitable range which should have control box, operation, handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the ciruit breaking for cover current protection. The circuit should be equipped with magnet thermal release with metallic tap etc, it should also be fitted with earth fault for tripping of breaker on occurnce of earth fault on off breaker load side end.
c) The voltage monitor relay of AE/MEI/L&T / Havells make three phase with all protection and usual indicator and electric siren against single phasing,low voltage,high voltage, reverse phasing, over loading and phase voltage difference as per IS:3482(latest edition)
e) Digital Power factor meter of standard make AE/L&T/IMP/Havells as per relevant IS code with upto dateammendments
f) Digital Frequencey meter of standard makeAE/L&T/IMP/Havells as per relvant IS code with uptodate ammendments
g) Bus bar chamber having three copper bars of suitable rating for full length equal to the width of the board for three live phases and suitable for inducted current, one copper bar of half the rating of full length for neutral phase as per IS 8084-1976 and IS:11353-1985 read with BIS 5578-1985 with upto date ammendments
h) ICTP switches with HRC fuses unit of Kilbur/L&T/siemens/stands/Havells make and of suitable capacity as per IS:4064:1978 with upto date ammendments
i) Three phase indicator lamps complete with toggle switches for individual motors as per IS:3452:(P-I & II) with upto date ammendments
k) Capacitor of Mechnical/ BHEL/GEC make as per 15:2834:1986 with upto date ammendments , to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rting according to H.P.offered including cables as per relevant ISI code (of siemens/clocter.IEC make )from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per Is:4064:1978 with upto date ammendments
l) Providing suitable oil immersed starter delta/direct on line/auto transformer/. starter rotor starter of MEI/.Kilburn/Jyoti /L&T/Siemens make as per IS:8544:1979 with upto date ammendments for squirrel cage/slip ring motor mounted on panel board with magnetic type over-load release and dashpot, time lag, under voltage release with or without initial oil filling as the case may be with single phae preventor as per IS:1248( P-V) 1983 with upto date ammendments
m) Providng Digital hour run meter of recommended make and suitable capacity as per IS:722(latest edition.)
n) Providing antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337:1971.
Providing double flanged CI sluice valve PN1 of Leader/BHEL/Kirlosker/GLEd/Kilburn Fourses / Kartar make and equal to dia of suction pipe and cpable of withstanding the normal seat pressure as per IS:780:1984 with upto date ammendments
Providng double flanged cast steel sluice valves ASA-300 of leader/BHEL Kirlosker/Kilburn GLED/fourses make and one step higher then delivery line of pump and capable of withstanding the normal seat pressure and as per BIS standards with upto date ammdnements
Providing double flanged swing type cast steel reflux valve, ASA-300 of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses make and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments)
Providing double flanged cast steel reflux valves class ASA-300 of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES make and of 100 mm dia having bye pass arrangements for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date ammendments.
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head The size of the various components to be as under: a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe
c) Common header : One dia higher then delivery of pump x 100 mm dia and will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor .(a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
2nd stage Providing and installing horizontal spindle,horizontal/redial split casing/end suction(Back-pull out arrangements) single/double/multi stage centrifugal pump or combination of pumps, In series/parallel of recommended make such as Mather and Platt/KSB/ Beacon Weir/Kirlosker/BE/Jyoti as per BIS 1520-1980 with upto date ammendments, read with IS:9137-1978 or latest edition suitable for lifting water for under mentioned characterestics with bronze,impellers/priming funnels,casing ring and shaft sleeves of bronze,shaft of steel grade 4508 FN8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel base plate (base plate to be from the manufacturer of the pumping unit only) to slip ring/ squirrel cage screen protected drip proof induction motor /motors of standard make such as Kirlosker/BHEL /Crompton /NGEF /GEC/Siemens/Jyoti /ABB and suitable for operation on 400(+/-)10% volts,50 cycles /second.3 phase AC electric supply. The power of electric motor/motors should be at +10% in excess of the maximum power required by the pump/pumps in the operation range of (+) 10% and (-)15% of the duty poiint head. The motor/motors as per ISI:325:1978 with upto date ammendments read with IS 900:1972. It should include cost of bearing nuts , bolts and painting etc. and should meet the following requirements: .
Providing ICTP main switch with HRC fuses of Kilburn/ L&T/Siemens/Standard/ Havells make and having capacity 30% extra of the operational rating as per IS: 4064-1978 with up to date amendments , immediately after the power meter of the HPSEBL.
Providing MS sheet steel fabricated floor mounted closed(almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6 duly painted with steel sheet of 16 gauge comprising and capable of mounting the following accessories within all internal connections. All the accessories should be suitable for the proposed pumping machinery at item No.1 above and to the entire satisfaction of HPSEB authorities. The same shall have to be replaced with out extra cost if recommended by HPSEB authorities
a) OCB/MCCB of MEI/Havels/ standard make and of suitable capacity for offered motor on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage released as per relevent IS code with upto date ammendments
b) Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per IS:2516:1977 with upto date ammendments of suitable range which should have control box, operation, handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the ciruit breaking for cover current protection. The circuit should be equipped with magnet thermal release with metallic tap etc, it should also be fitted with earth fault for tripping of breaker on occurnce of earth fault on off breaker load side end.
c) The voltage monitor relay of AE/MEI/L&T / Havells make three phase with all protection and usual indicator and electric siren against single phasing,low voltage,high voltage, reverse phasing, over loading and phase voltage difference as per IS:3482(latest edition)
e) Digital Power factor meter of standard make AE/L&T/IMP/Havells as per relevant IS code with upto dateammendments
f) Digital Frequencey meter of standard makeAE/L&T/IMP/Havells as per relvant IS code with uptodate ammendments
g) Bus bar chamber having three copper bars of suitable rating for full length equal to the width of the board for three live phases and suitable for inducted current, one copper bar of half the rating of full length for neutral phase as per IS 8084-1976 and IS:11353-1985 read with BIS 5578-1985 with upto date ammendments
h) ICTP switches with HRC fuses unit of Kilbur/L&T/siemens/stands/Havells make and of suitable capacity as per IS:4064:1978 with upto date ammendments
i) Three phase indicator lamps complete with toggle switches for individual motors as per IS:3452:(P-I & II) with upto date ammendments
k) Capacitor of Mechnical/ BHEL/GEC make as per 15:2834:1986 with upto date ammendments , to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rting according to H.P.offered including cables as per relevant ISI code (of siemens/clocter.IEC make )from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per Is:4064:1978 with upto date ammendments
l) Providing suitable oil immersed starter delta/direct on line/auto transformer/. starter rotor starter of MEI/.Kilburn/Jyoti /L&T/Siemens make as per IS:8544:1979 with upto date ammendments for squirrel cage/slip ring motor mounted on panel board with magnetic type over-load release and dashpot, time lag, under voltage release with or without initial oil filling as the case may be with single phae preventor as per IS:1248( P-V) 1983 with upto date ammendments
m) Providng Digital hour run meter of recommended make and suitable capacity as per IS:722(latest edition.)
n) Providing antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337:1971.
Providing double flanged CI sluice valve PN1 of Leader/BHEL/Kirlosker/GLEd/Kilburn Fourses / Kartar make and equal to dia of suction pipe and cpable of withstanding the normal seat pressure as per IS:780:1984 with upto date ammendments
Providng double flanged cast steel sluice valves ASA-300 of leader/BHEL Kirlosker/Kilburn GLED/fourses make and one step higher then delivery line of pump and capable of withstanding the normal seat pressure and as per BIS standards with upto date ammdnements.
Providing double flanged swing type cast steel reflux valve, ASA-300 of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses make and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments)
Providing double flanged cast steel reflux valves class ASA-300 of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES make and of 80 mm dia having bye pass arrangements for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date ammendments.
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under: a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe
c) Common header : One dia higher then delivery of pump x 80 mm dia and will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor. (a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Excavation in foundation, trenches ( for pipes & pits) upto all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing and pumping out water, blasting soft/ hard rock or chiselling soft/hard rock where blasting is prohibited in all lifts including trimming and dressing of sides, leveling of beds to correct grade i/c shoring /strutting , planking, timbering & dewatering wherever required, stacking the useable & unuseable material /soil separately & after laying jointing & testing of pipes, returning the useable soil in trenches in 15 cm layers including consolidating of such deposited layer by ramming & watering & then disposing of all surplus excavated soil /unusable material as directed with in all leads & lifts including restoration of un-metalled /metalled surfaces to its original condition & including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respects with in all leads & lifts as per directions of Engineer-in-Charge.
Laying,jointing and testing in trenches GMS tube pipe of following dia meters conforming to BIS :1239(Part-1),of following grade and having wall thickness as spacified below with plain end and dia meters capable of withstanding required test pressure in rendom length of 4 to 7 mtrs ,including spacials,short peices ,bends ,reducers ,tees etc.made from parent tube ,providing and welding of MS flsanges detail as below the MSflanges shall conform to BIS 6392-1971((with latest up to date amendments )duly welded in two layers (two inner and two outer)with pipes and both ends as per relevent BIS standers along with nuts and bolts of required sizes 3 mm thick compressed asbestos fiber/synthetic rubber gasket conformming to relevent BIS standerds .The laying of pipe will include all oprations such as cutting welding jointiong providing and fixing of MS flanges febrication of bends ,tees etc.including lowering and laying in excavated tranches to ensure frequired level including flushing cleaning and hydraulic testing complete in all respect to the satisfaction of Engineer -in-Charge .The fabriction bends shall have three or four cuts having its radious not less than five five times of dia of pipes.The pipes shall be factory galvanized (zinc coating both inside and outside )as per relevent IS standards .The welding electrods shall be as per IS 814 of Advani oerlikon/L & T or ISI marked make .The rates also inbcludes entire carrige of matirial flushing clkeaning and hydraulic testing complete to the best satisfaction & direction of Enginee-in -Charge with in all leads and lifts (Earth work in tranches will be measured saparately. First stage 100mm dia -GMS pipe 4.50 mm thoickness with Ft-28 (Medium class)
100mm dia -GMS pipe 4.50 mm thoickness with Ft-17 (Medium class)
100mm dia -GMS pipe 4.50 mm thoickness with Ft-5 (Medium class)
Second stage:- 80 mm dia -GMS pipe 4.50 mm thoickness with Ft-17 (Medium class)
Laying jointing and testing (by way of circumferences butt welded joints by electrical arc welding) and testing of GMS pipe of following dia mtr confirming to BIS 1239 (part 1) of following grade and having wall thickness as specified bellow with plane end and capable of withstanding required test pressure in random length of 4 to 7 mtrs. including special, short pieces bends reducers ,Tees etc. The laying of pipe will include all operators such as cutting ,welding ,jointing Providing and fixing MS flanges fabrications of bends ,tees etc including lowering and laying in excavated tranches to ensure required level including flushing cleaning and hydraulic testing complete in all respect to the satisfaction of Engineer-in Charge .The fabricated bend s shall have three or four cuts having its radios not less then 5 times the dia of pipe .The balding electrodes shell be as per IS 814 of Advani oerlikon /LNT or ISI marked make.The rates also included entire carriage of material, flushing, cleaning and hydraulic testing complete to the best satisfaction and direction of the Engineer-In-Charge with in all leads and lifts(earth work in tranches will be measured and paid for separately) First stage:- 100mm dia -GMS pipe 4.50 mm thoickness with (Medium class)
100mm dia -GMS pipe 4.50 mm thoickness with (Medium class)
100mm dia -GMS pipe 4.50 mm thoickness with (Medium class)
Second stage 80 mm dia -GMS pipe 4.50 mm thoickness with (Medium class)
SB Trading company
competent associates
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .