Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹2.0 L
EMD Value
₹10,100
Closing Date
30 Jan 2026, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
DEPUTY EXECUTIVE ENGINEER, CAPITAL PROJECT ELECTRICAL SUB DN NO 23, GANDHINAGAR
Routine Maintenance of HT,LT panel and transformer at Water Pumping Station Sector-5 & Staff Training College Sector-17 Gandhinagar. [3rd ATTEMPT]
267800
17/04 OF 2025/2026
Open
Electrical
Works
Gandhinagar
8 documents required · 8 mandatory
₹600
Dy. Executive Engineer, Capital Project Electrical Sub Division No 23, Gandhinagar.
₹10,100
21 Jan 2026
21 Jan 2026
21 Jan 2026
30 Jan 2026
21 Jan 2026
Routine Maintenance of HT,LT panel and transformer at Water Pumping Station Sector-5 & Staff Training College Sector-17
Gandhinagar. [3rd ATTEMPT]
Fund Head : 2059 P.W. M&R - SR
Sr. No. Item No. Particulars. Qty. Rate Amount
Signature of Contractor Deputy.Executive.Engineer Executive Engineer
C.P.Electrical. Sub Div-23 C.P Electrical R & B Division
Gandhinagar Gandhinagar.
Name of Work Routine Maintenance of HT,LT panel and transformer at Water Pumping Station Sector-5 & Staff Training College Sector-17
Gandhinagar. [3rd ATTEMPT]
Estimated Quantity Item Description Unit Amount in Rs.
No. in Figure In Word
Carryout routine maintenance, servicing and testing of
Amps. H.T. OCB / VCB in accordance with I.S. 10119-1962
part I-to-IV with below defined scope: (1) Cleaning of
dust,spider web ,foreign particles. Etc . (2) Removal of old
Rupees Two Thousand
grease with new grease for various parts.(3) Cleaning of
1 9 Job. various parts with CRC.(4) Check the tightness of all 2354.31 Three Hundred Fifty Four & Job.
Paise Thirty One only
hardware (5)Checking of Spring Charging, Closing & Tripping
mechanism (11) Measurement of IRV (12) Measuring of
closing/tripping time by time testing kit (13) Measuring contact
resistance by CRM kit.
Carry out routine maintenance and servicing and testing up to
6300 Amp L.T. ACB with below defined scope: (1) Cleaning
of dust,spider web ,foreign particles. Etc . (2) Removal of old
grease with new grease for various parts.(3) Cleaning of
Rupees One Thousand
various parts with CRC.(4) Check the tightness of all
2 8 Job. hardware (5)Checking of Spring Charging, Closing & Tripping 1836.18 Eight Hundred Thirty Six & Job.
Paise Eighteen only
mechanism (11) Measurement of IRV (12) Measuring of
closing/tripping time by time testing kit (13) Measuring contact
resistance by CRM kit.(14) Release testing by OEM
recommended testing kit.
Carryout routine maintenance and servicing of L.T. cubical
panel board having approximately 15 to 22 Nos. of switches
Rupees Two Thousand
cleaning and servicing the contacts with CRC, tighting the
3 4 Job. connections of incoming and outgoing cables. and hacking 2140.19 One Hundred Forty & Paise Job.
the operating mechanism for smooth functioning of switches.
and putting them in smooth working order.
Routine maintenance of Transformer in operating covering
Insulation Resistance oil breakdown strength, reconditioning Rupees Two Thousand
4 4 Job. /replacement of silica gel, cleaning of transformer & topping 2568.43 Five Hundred Sixty Eight & Job.
up to of oil if required .(Oil will be provided departmentally or Paise Forty Three only
at extra cost.)
Carrying out the testing of earth fault and overload relay by
Rupees Two Thousand
authorized person ,on L.T. side. by removing the fault of
5 4 Job. relay by checking the trip devices, control wiring and putting 2140.19 One Hundred Forty & Paise Job.
the same in working order with test report
Rupees Two Thousand
Testing and calibration of relay series coils of H.T.O.C.B
6 9 Job. through primary Injection up to 3000 AMP (3 coils sets) 2140.19 One Hundred Forty & Paise Job.
Rupees Four Hundred
Testing of transformer oil by calibrated instrument for
7 8 Job. dielectric breakdown strength with test report 428.24 Twenty Eight & Paise Job.
Twenty Four only
Per Earth Pit Measurement of earthing resistance by loop test with Rupees Four Hundred
authorized test report after isolating & cleaning joint. Per Earth
8 14 428.24 Twenty Eight & Paise
Twenty Four only
Replacing the breather of the Transformer of following Rupees One Thousand
9 3 Nos. capacity. (B) 500 KVA/750 KVA/1000 /1250 KVA 1712.96 Seven Hundred Twelve & Nos.
Paise Ninety Six only
Transformer oil having good resistance to high electrical
stress, high di-electric strength (50KV) low viscosity, low pour Rupees Ninety & Paise
10 1000 Ltr. point, high flash point and excellent thermal properties for 90.90 Ninety only
efficient heat transfer and cooling as per I.S.335 -1972.
Filtration of transformer oil as per I.S. for removal of moisture,
carbon. slurry etc.by means of circulating oil through vacuum
Rupees Eight & Paise Eight
11 1630 Ltr. pump from heating elements and filters to with stand the 8.08 only
breaking strength of the oil above 40KV beyond one minute
tested in oil testing Kit. (A) on site.
RUPEES IN WORDS :
I/We am/are willing to carry out the work at(No above rates allowed) ____________% below ___________________________________
__________________percent (Should be written in figures and words) below the tendered rates mentioned above.
Amount of my/our tender works out as under :
Put to Tender Rs. 201,165.74 Put to Tender Rs.
(Please strike out whichever is not applicable)
1 I/We hereby declare that I/We have visited the site, fully exquisite myself/ourselves with the local situation regarding materials and other factors pertaining to the work before
submitting this tender.
2 I/we hereby declare that I/We carefully studied the conditions of specifications and other tender documents of this work and agree to execute the same accordingly.
3 A tender with any overwriting in percentage (should both in word and figures) rejected out right.
4 Insertions and/or corrections in the percentage quoted ( both in word and figures) resulting into increase in the value of the work shall be rejected outright unless it is
authenticated by the office opening the tender at the time of opening of tender.
5 Dismental Material Amount will be deducted from Bill
Signature of Contractor Deputy .Executive.Engineer. Executive Engineer
C.P.Electrical Sub Division-23 C.P Electrical R & B Division
Gandhinagar Gandhinagar.
Name of Work :- Routine Maintenance of HT,LT panel and transformer at Water
Pumping Station Sector-5 & Staff Training College Sector-17
Gandhinagar. [3rd ATTEMPT]
I / We am / are willing to carry out the work @…………………………………………
………………...% ( should be written in figures and words ) Below / Above the Tenderd
Rates mentioned above My / Our tender works out as under:-
(A) Total Tendered Amount Rs. ……………………….
(B) Rebate on above tender amount ( if any ) Rs. ……………………….
(C) Net Tendered Amount ( A - B ) Rs. ……………………….
Please strike out whichever is not Applicable.
1. I/ We hereby declare that, I / We have visited the site and fully acquainted my self
2. I / We hereby declare that, I / We have carefully studied conditions of contract,
Signature of Contractor Deputy Executive Engineer
C.P Electrical R & B Sub Dn
Executive Engineer
C.P Electrical R & B division
LIST OF DISMENTAL MATERIALS
Routine Maintenance of HT,LT panel and transformer at Water Pumping Station Sector-5 & Staff Training
Name of Work :-
College Sector-17 Gandhinagar. [3rd ATTEMPT]
Sr.No. Quantity Description Of Item DM Amount Per Amount
Cost of old & u/s breather of Transformer (B) 500 KVA/750
Total Cost of Dismental Materials Rs.
Say Round total Dismental Materials Rs.
Signature of Contractor Deputy Executive Engineer Executive.Engineer.
C.P Electrical R & B Sub Dn 23 C.P.Electrical R & B Division
Gandhinagar. Gandhinagar
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
G S T LTR.pdf
GR.pdf
NOTICE NO. 17 2025 2026.pdf
PQ.pdf
SBD Document.pdf
SCHEDULE A B C AND DM.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .