Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 20 2169 PALLURTH PO ERNAKULUM KERALA 682006 | ERNAKULAM | KERALA | 682006 | Admitted-Finance |
| 2 | Admitted-Finance MUKALATH VALAYANCHIRANGARA PO PERUMBAVOOR ERNAKULAM KOCHI 683556 | PERUMBAVOOR | ERNAKULAM | KERALA | 683556 | Admitted-Finance |
| 3 | Admitted-Finance MATTILIPARAMBIL HOUSE SAHODHARAN AYYAPPAN ROAD EROOR WEST PO THIRUPUNITHURA 682306 | THIRUPUNITHURA | ERNAKULAM | KERALA | 682306 | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹46 L
EMD Value
₹92,000
Closing Date
6 Jan 2022, 6:00 pmClosed
Shri SK Choudhary IDSE EE GE NW Kochi
GE NW Kochi Katraibagh Naval Base Post Pin 682004
COMPREHENSIVE MAINTENANCE TO INTERNAL WIRING, ELECTRICAL FITTINGS FIXTURES FANS GEYSERS FIRE FIGHTING INSTALLATIONS AND SOLAR WATER HEATING SYSTEM AT SATELLITE AREA KOCHI UNDER GE NW KOCHI
2021_MES_494078_1
8497_NW
Open Tender
Electrical and Maintenance Works
Works
Kochi
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE NW Kochi
₹92,000
Yes
11 Jan 2022
11 Dec 2021
8 Jan 2022
12 Dec 2021
6 Jan 2022
25 Dec 2021
12 Dec 2021 - 30 Dec 2021
Amount
Taking down copper/aluminium point wiring (light, fan, bell, socket or power etc.) complete with all accessories like switches, sockets, regulators, ceiling roses, light fittings etc. for taking credit and making good disturbed surfaces, applying distemper / Emulsions matching to the existing colour / quality of walls / floors / ceiling etc all as specified.
M&L Point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits) with 1.5 sqmm nominal cross sectional area, copper conductor unsheathed FRLS cable 1100 Volts grade ISI marked with valid CML No. single core multistranded cable in and including medium grade concealed PVC conduit not less than 20mm dia and accessories ISI marked with valid CML No. (IS-9573-1983 for conduits and IS: 3419: 1976 for conduit accessories) and including 2 mm thick MS sheet/ pressed steel sunken boxes (earth dolly) duly painted with two coats of anti corrosive paint / aluminium paint over a coat of red oxide primer internally and two coats of black bituminous paints over a coat of red oxide primer externally covered with 3 mm thick plastic laminated sheet cover for fixing of switches sockets and fan regulators etc including 1.5 Sqmm nominal cross sectional area PVC insulated copper conductor unsheathed FRLS cable single core multistranded cable as earth continuity wire for one light point controlled by one switch, complete all as specified and as directed.
All as per item No 2 here-in-before but for One ceiling / exhaust fan point controlled by one switch
All as per item No 2 here-in-before but for One 3 pin socket outlet, 5 Amps controlled by one switch in same board with other switches
All as per item No 2 here-in-before but for One 3 pin socket outlet, 5Amps controlled by one switch independent
All as per item No 2 here-in-before but for One bell point controlled by one bell push on same board or independent
All as per item No.2 above but for One 3 pin socket outlet, 15Amps controlled by one switch independent with 2.5 sqmm cable and 2.5Sqmm cable as earth wire on independent board
S&F switch piano flush type, 5A, AC, 240V, one way ISI Marked complete all as specified and as directed.
S&F Bell Push, Flush type, 5A, AC, 240V, ISI Marked complete all as specified and as directed.
S&F socket piano flush type, 5A, 5pin, AC, 240V ISI Marked complete all as specified and as directed.
S&F socket piano flush type, 15A, 6pin, AC, 240V ISI Marked complete all as specified and as directed.
S&F Power Unit suitable for AC/Geyser, 20A, 3pin, AC, 240V ISI Marked incl PVC Surface Box complete all as specified and as directed.
S&F Electronic 5 Step Fan Regulator, 240V, AC, ISI Marked complete all as specified and as directed.
S&F in repairs switch piano flush type, 5A, AC, 240V, one way ISI Marked all complete all as specified and as directed.
S&F in repairs switch piano flush type,15A, AC, 240V, one way ISI Marked complete all as specified and as directed.
S&F in repairs Bell Push, Flush type, 5A, AC, 240V, ISI Marked complete all as specified and as directed.
S&F in repairs socket piano flush type, 5A, 5pin, AC, 240V ISI Marked complete all as specified and as directed.
S&F in repairs socket piano flush type, 15A, 6pin, AC, 240V ISI Marked complete all as specified and as directed.
S&F in repairs Power Unit suitable for AC / Geyser, 20A, 3pin, AC, 240V ISI Marked incl PVC Surface Box complete all as specified and as directed.
S&F in repairs Electronic Step type/ switch type Fan Regulator, 240V, AC, ISI Marked complete all as specified and as directed.
S&F in repairs Ceiling rose surface Bakelite 65x50mm, 3 terminals, AC, 240V, ISI Marked complete all as specified and as directed..
S&F in repairs Call Bell, AC, 240V, SP, ISI Marked complete all as specified and as directed.
S&F in repairs lamp holder, PVC / Polycarbonate type with back plate suitable for batten fittings, AC, 240V, Pin type, ISI marked complete all as specified and as directed.
S&F in repairs switch socket combination 2 in 1, 5 amps flush type suitable for 2/4 screws as per site requirement complete all as specified and as directed.
S&F in repairs switch socket combination 2 in 1 3 pin, 5/15 amps flush type suitable for 2/4 screws as per site requirement complete all as specified and as directed.
S&F in repairs Modular Switch, 1 module, 6A, AC, 240V, one way ISI Marked complete all as specified and as directed.
S&F in repairs Modular Switch, 1 module, 16A, AC, 240V, one way ISI Marked complete all as specified and as directed.
S&F in repairs Modular Bell Push, 1 module, 6A, AC, 240V, ISI Marked complete all as specified and as directed.
S&F in repairs Modular Step Fan Regulator, 2 module, 120W, AC, 240V, ISI Marked complete all as specified and as directed.
S&F in repairs Modular Socket, 2 module, 6A, 2/3 pin combined, AC, 240V, ISI Marked complete all as specified and as directed.
S&F in repairs Modular Socket, 2 module, 6A / 16A, 2/3 pin combined, AC, 240V, ISI Marked complete all as specified and as directed.
M&L in repair sub main wiring on wall/ceiling with 2 runs of 4sqmm single core PVC cable as per IS 694-1990(third revision) insulated unsheathed multistranded copper conductor FRLSH cable 1100 Volts grade drawn through and including fire resistant PVC casing & capping / PVC conduit with all accessories such as Tees, elbows, junction box etc.as required of not less than 20 mm dia and 1 run of 4 Sqmm single core PVC insulated unsheathed 1100 Volts grade, multistranded copper conductor FRLSH cable as earth continuity conductor and connecting to existing earth dolly with suitable size thimble and making good the disturbed surface to match with the existing complete all as specified and as directed. Note : 3 runs of 4 Sqmm cable and one run of PVC casing and capping / PVC conduit with accessories shall be measured as one unit.
M&L in repair sub main wiring on wall/ceiling with 2 runs of 6Sqmm single core PVC cable as per IS 694-1990(third revision) insulated unsheathed multistranded copper conductor FRLSH cable 1100 Volts grade drawn through and including fire resistant PVC casing & capping / PVC conduit with all accessories such as Tees, elbows, junction box etc.as required of not less than 20 mm dia and 1 run of 6 Sqmm single core PVC insulated unsheathed 1100 Volts grade, multistranded copper conductor FRLSH cable as earth continuity conductor and connecting to existing earth dolly with suitable size thimble and making good the disturbed surface to match with the existing complete all as specified and as directed. Note : 3 runs of 6 Sqmm cable and one run of PVC casing and capping / PVC conduit with accessories shall be measured as one unit.
M&L In repair sub main wiring on wall/ceiling with 4 runs of 6 Sqmm single core PVC cable as per IS 694-1990(third revision) insulated unsheathed multistranded copper conductor FRLSH cable 1100 Volts grade drawn through and including PVC casing & capping / PVC conduit with all accessories such as Tees, elbows, junction box etc.as required of not less than 20 mm dia and 1 run of 6 Sqmm single core PVC insulated unsheathed 1100 Volts grade, multistranded copper conductor FRLSH cable as earth continuity conductor and connecting to existing earth dolly with suitable size thimble and making good the disturbed surface to match with the existing complete all as specified and as directed. Note : 5 runs of 6 Sqmm cable and one run of PVC casing and capping / PVC conduit with accessories shall be measured as one unit.
M&L in repairs (sub main wiring with) XLPE insulated, armoured heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, cross-sectional area 10 sqmm 4 core including all fixing arrangement etc complete all as specified and as directed.
Taking down existing sub main LT cable of any type and refixing the same as directed with clamps, saddles, screws etc complete all as specified and as directed.
S&F in repair Acrylic / Fibre Enclosure, SPN DB, 240V, AC, 2 way, double door with 200Amps rated busbar ISI Marked complete all as specified and as directed.
All as per item no.37 above but 4 way with 200Amps rated busbar complete all as specified and as directed. .
All as per item no.37 above but 8 way with 200Amps rated busbar complete all as specified and as directed.
All as per item no.37 above but TPN DB, vertical mounting, 415V, 4 way with 200Amps rated busbar, double door complete all as specified and as directed.
S&F in repair MCB SP 6 to 32 A, AC, 240V, 10KA, ISI Marked complete all as specified and as directed.
S&F in repair Isolator DP, 40A, AC, 240V, 10KA, ISI Marked complete all as specified and as directed.
S&F in repair Isolator 4P, 63A, AC, 415V, 10KA ISI Marked complete all as specified and as directed.
S&F in repair RCCB / ELCB, double pole, AC, 40A, 30mA, 240V ISI Marked a complete all as specified and as directed.
S&F in repair RCCB / ELCB, 4P, AC, 63A, 30mA, 415V ISI Marked complete all as specified and as directed.
S&F in repairs Regal Batten 1x22W for LED tube lights, both side connection type complete all as specified and as directed. Make:- Havells Cat Part No. Regal batten 8UPT001X22WSSBSWH / Crompton Cat Part No. IGP131LT8-16 / Philips Cat Part No. TMC501P1XTLED22WP3241 or equivalent model of other approved manufacturers from the list.
S&F in repairs for LED Mirror light fitting 8 watt with connected accessories complete all as specified & directed. Make:- Crompton Cat No. LDL-10-WW or Polycab Cat Part No. LD00103040 / Luker Cat Part No. LTSM10 or equivalent model of other approved manufacturers from the list.
S&F in repairs LED tube rod 1 x 20 Watt, both side connection complete all as specified & directed. Make:- Havells Cat Part No. Crystal 1213T8DSTL20W LED 865 GLASS / Crompton Cat Part No. LG-T8-20-865-2 / Philips Cat Part No. Essential LED tube 1200mm 20W865T865T81ND-1 or equivalent model of other approved manufacturers from the list.
S&F in repairs LED tube rod 1 x 20 Watt, single side connection complete all as specified & directed. Make:- Havells Cat Part No. PHOTONULTRA+1213T8SSTL20W LED865SPC / Crompton Cat Part No. LG-T8-20-865-2 / Philips Cat Part No. Essential LED tube 1200mm 20W865T865T81ND-1 or equivalent model of other approved manufacturers from the list.
S&F in repairs 1x15 Watt LED down lighter square / round in shape, surface mounted type and connecting to the existing electrical system complete all as specified & directed. Make:- Luker Cat Part no. LCL 15NR or equivalent model of other approved manufacturers from the list.
S&F in repairs existing holder, 12w LED Bulb with B22 base, clear acrylic diffuser, Self declaring R No, power factor .90, 100 lumens light output complete all as specified & directed.
S&F in repairs existing holder, 5w LED Bulb with B22 base, clear acrylic diffuser, Self declaring R No, power factor .90, 85 lumens light output complete all as specified & directed. .
M & L for rewinding of Ceiling Fan 1200mm Sweep of any make, any model, from a reputed workshop, removing the burnt winding, cleaning slots, re-winding the motor with super enamelled copper wire of size equivalent to the original winding including insulated packing materials, Varnishing, Drying etc, replacement of body screws, testing and commissioning on full load for 8 hrs continuous running all as directed for
All as per item No.53 here-in-before but for Ceiling Fan 1400mm Sweep
All as per item No.53 here-in-before but for Wall Fan 450mm Sweep
All as per item No.53 here-in-before but for Exhaust Fan 300mm Sweep
All as per item No.53 here-in-before but for Exhaust Fan 450mm Sweep
S&F in repairs, Condenser / Capacitor 2.5 mfd, 240V, AC, suitable for fans complete all as specified & directed.
S&F in repairs, Condenser / Capacitor 4.0 mfd, 240V, AC, suitable for fans complete all as specified & directed.
S&F in repairs Ball bearing made out of high carbon steel, equivalent to the original, suitable for any type, any make, any size fans complete all as specified & directed.
S&F in repairs Bush bearing, made out of brass alloy, equivalent to the original, suitable for any type, any make, any size, fan complete all as specified & directed.
S&F in repairs Nickel plated mild steel clamps, Nuts, Bolts, Washers and split pin suitable for ceiling fans any type, any make, any size complete all as specified & directed.
S&F in repairs down rod, suitably threaded and holed, made out of 15mmdia GI tubes, duly painted, 300mm long, suitable for ceiling fans any type, any make, any size all as directed of any length as per site requirement.
S&F in repairs Fan canopy with tightening screw/check nut, made out of PVC, suitable for ceiling fans any type, any make, any size complete complete all as specified & directed.
S&F in repairs Rubber reel insulator, suitable for ceiling fans any type, any make, any size complete all as specified & directed.
S&F in repairs Fan blades made out of 1.2mm thick Aluminium alloy and MS screws duly balanced & spray painted with White or Brown colour, Set of three, suitable for ceiling fans 1200mm Sweep of any type, any make complete all as specified & directed.
All as per item No.66 here-in-before but for 1400mm Sweep ceiling fan.
S&F in repairs Fan blades made out of Acrylic / PVC alloy and MS screws duly balance suitable for 450mm wall fans of any type, any make complete all as specified & directed.
S&F in repairs Fan blades made out of 1.2mm thick Aluminium alloy and MS screws duly balanced & spray painted with approved colour, suitable for Exhaust fans 300mm sweep of any type, any make complete all as specified & directed.
All as per item No.69 here-in-before but for 450mm Sweep Exhaust fan
S&F in repairs Split pin made out of Nickel plated mild steel with specified temper, suitable for ceiling fans of any type, any make with bolts of any size complete all as specified & directed.
S&F in repairs Bakelite body Nichrome connectors, 2 way with fixing screws of suitable size for ceiling fans of any type, any make complete all as specified & directed.
S&F Energy efficient ceiling fan of 1200mm sweep (5 star rated) 230 Volt 50 Hz including all electrical connection all as specified and as directed including taking down old one and deposited with MES store yard complete all as specified & directed. . Make:- Havells Cat Part No. ES-40 or Crompton Cat Part No. Maximus (5 star rated) or equivalent model of other approved manufacturers from the list.
S&F in repairs PVC body exhaust fan motor suitable for 250/300 mm sweep of any make as per site requirement complete all as specified & directed.
S&F in repairs exhaust fan motor suitable for metallic body exhaust fan of any make and type of 250 mm sweep complete all as specified & directed.
S&F in repairs motor for 400 mm wall fans any make complete all as specified & directed.
S&F in repair Exhaust fan 250mm sweep PVC body heavy duty, single phase 230 Volts, all as specified & directed. Make:- Havells Cat Part No. Ventil Air-DX white or Crompton Cat Part No. EXHD300-4-1 or equivalent model of other approved manufacturers from the list. Note :- Old fan shall be deposited to MES store yard.
S&F in repairs LED driver suitable for of 14 Watt mirror lamp all as specified and directed. Crompton Make:- LED lamp Cat Part No. LCL-14-CDL or equivalent model of other approved manufacturers from the list.
S&F in repairs Hylem sheet of 3 mm thick as per site requirement including cutting for accommodating existing switches, sockets, regulators etc.complete all as specified & directed.
S&F in repairs white cover plate with frame for modular switches of one module complete all as specified and directed complete all as specified & directed.
S&F in repairs white cover plate with frame for modular switches of two module complete all as specified and directed
S&F in repairs white cover plate with frame for modular switches of three module complete all as specified and directed
S&F in repairs white cover plate with frame for modular switches of four module complete all as specified and directed
S&F in repairs white cover plate with frame for modular switches of six module complete all as specified and directed
S&F in repairs Decorative wall light fixture made up of Polycarbonate, suitable for 9 W retrofit LED Lamp B22 base complete all as specified and as directed. Make:- Havells Cat Part No. LHDL06160099 or any approved make.
Dismantling and removing the existing Geysers 25 Litre of any type, any make, from various locations of satellite area for repair / painting / replacement of defective parts, pressure testing and refixing at it's original location, connecting complete all as specified and directed.
S&F in repairs Heating element, suitable for any type, any make geyser, 240V, AC, ISI Marked, with heat resistant rubber washer, for1.5 KW capacity, connecting complete all as specified and directed.
S&F in repairs Thermostat control unit suitable for any type, any make 25 Ltrs capacity geyser, 30-90 degree rating, 240V, AC, ISI Marked, connecting complete all as specified and directed.
S&F in repairs indicating lamp unit round / rectangular type, suitable for any type, any make geyser, standard quality, AC, 240V, Red or Green, connecting complete all as specified and directed.
S&F in repairs fusible plug made out of brass with internal or external threading suitable for any type, any make geyser of capacity 25 Ltrs complete all as specified and directed.
S&F in repairs Inner assembly made out of brass with chromium plating, with heat resistant rubber washer, suitable for any type, any make Geyser 25 Ltr capacity ISI marked, complete all as specified and directed.
S&F in repairs inner tank made out of cast copper alloy, ISI Marked, suitable for any type, any make geyser 25 Ltr capacity complete all as specified and directed.
S&F in repairs Metallic Outer cover including bottom and top cover duly painted suitable for any type, any make geyser 25 Ltr capacity complete all as directed .
M&L for repairs to any type, any make geyser 25 Ltr capacity metallic inner tank, arresting the leakage by welding, brazing etc, pressure testing after repairs, complete all as directed.
Taking down Heating element / Thermostat control unit / indicating lamp unit round / rectangular type
M&L for filling the glass wool between outer cover and inner tank of any type, any make geyser, 25 litres capacity, complete all as directed.
M&L for Preparing the surface of any type / any make geyser 25 Ltrs capacity by removing the existing painting by scraping, cleaning, filling the cavities and applying 2 coats of spray paint with synthetic enamel white paint over a coat of red oxide primer, including writing the MES Nos. all as directed.
M&L for Fabricate and fix, GI bottom cover / inspection plate, suitable for any type, any make geyser, 2 mm thick, split type, duly painted with 2 coats synthetic enamel paint over a coat of metallic primer to match with the existing colour all as directed.
M&L for replacement of bottom main terminal, synthetic gasket, fixing clamps suitable for any type, any make geyser, cleaning inner container/tank and assembly complete all as directed.
M&L for making hole in wall, Grouting 4Nos Rag Bolts of size 125mm long x 12mmm dia in PCC on wall including suitable nuts and washers for fixing / hanging geysers, complete all as directed.
S&F in repairs pressure / air release valve suitable for any type, any make geyser, made out of brass, 15mm bore, ISI marked, complete all as directed.
S&F in repairs non-return valve, made out of brass 15mm bore, ISI marked, complete all as directed.
S&F in repairs low density polyethylene pipe 16 mm dia (outer), 450mm long suitable for Hot water application complete with threaded brass union, teflon washers on both sides to suit 15 mm dia fittings complete all as directed.
Labour only for attending urgent nature of electrical complaints (within 3 hrs from intimation) like checking of existing electrical items for continuous electric supply including carrying out minor repairs such as checking of voltage calibration, checking of variation of R Y B phase in LT panel/DBs ,changing of MCBs, small pieces of wires including connections etc carrying out repairs such as tightening of loosen electric connections, nuts, bolts, screws of switches, sockets, switch boards, making joints and covering with PVC tape, minor repairs to ceiling fans / exhaust fans like repair of capacitors, cleaning and oiling etc. as required to make the electrical items/ appliances fully functional at Trangini apartment ,Fernson apartment, DERA enclave ,Varsha ,Varuna complex and Dawson Vihar from 5.00 PM to 9.00 AM on all working days all as specified and directed by Engineer-in-Charge. NOTE:- (i) The material and labour cost required for taking down existing fitting / fixture and fixing of new item shall be measured and paid separately under relevant item. Additional labour charge required for immediate attendance of complaint only shall be quoted under this item. (ii)The technician employed by the contractor shall available on all working days. The quoted rate shall inclusive of all labour, transportation of material and tools. (iii) The contractor shall display contact number of technicians in 'E' area at Naval Base to register users complaint. (iv) A penal recovery of Rs. 400/hour/complaint shall be effected on contractor beyond 3 hrs. A register shall be maintained by contractor duly countersigned by Concerned JE & AGE with time of occurrence of defect and time of rectification and submitted for claiming payment.. (v) Number of complaints may vary day to day and shall be on required basis. Contractor shall quote their rates accordingly including all aspects like labours ,tool, transportation etc.
All as per item No.104 here-in-before but for Sundays and Holidays / during lockdown periods etc (entire day).
Supply Installation Testing and Commissioning of Vertical Wall mounted storage type 25 litres Electric Water Heater (Geyser) with warranty/Guarantee as per OEM norms complete all as directed. Note:- Supply of accessories, modification/rectification of civil works such as plumbing, wiring etc if any required to install the Geyser shall be deemed to be inclided in the quoted rate.complete all as directed.
S&F in repairs Cadmium plated screws of various types and sizes for existing switch boards with washer as per sample all as specified and directed
M&L for Servicing of 'DOCTOR' make water cooler through authorised company representative including replacement of Primary, Secondary and Carbon Filters as and when required and keep the water cooler in serviceable condition for 12 months. Note:- The rate quoted shall be for keeping the water cooler in serviceable condition throughout the contract period ie for 12 months by providing servicing as required
M&L for servicing of split type Air conditioner (03 Nos) installed at Varsha Apartments through authorised service representative of the company and keep in serviceable condition for 12 months. Note:- The rate quoted shall be for keeping all the 03 split type Air conditioner in serviceable condition throughout the contract period ie for 12 months by providing servicing as required
M&L for checking of ceiling fan stability / tightness with fan hook for complete Satellite area as directed and make good, re-tightening of split pin / nut, bolt etc. all as per site requirement complete all as specified and as directed. Note:- (i) The cost of accessories like split pin, nuts, bolts, washers etc if any required shall be included in the quoted rate. The quoted rate shall inclusive of all labour and plants like ladder etc complete. (ii) The contractor shall maintain a register showing the location of fan duly signed by the users for the service carried out. This register shall be produced while claiming payment. (iii) The checking of fans shall be carried out once in 6 months.
M&L for Serviceability Check, Keeping the fire fighting system functional round the clock, Attending Fire Practices as per users requirements, necessary Repair / Maintenance / Servicing of machineries and fittings of Fire Fighting Systems complete with Electrical Panel Boards, Removal / Replacement of defective parts incl sundry items viz. grease, lubricants, cotton waste, small pieces of cable lugs etc. which are not covered under spares of this schedule for the following location:- A. MAP (Powar, Panigrahi & Chandrasekhar Apt) at Dharamveer Enclave) (a) 100 HP Electric Driven Fire Pump -1 No Powar/Panigrahi Apt (b) 92 HP Diesel Driven Fire Pump - 1 No Powar/Panigrahi Apt (c) 20 HP Electric Driven Jockey Pump - 1 No Powar/Panigrahi Apt (d)10 HP Electric Driven Terrace Pump sets - 3 Nos Powar/Panigrahi/Chandrasekhar Apt connected LT panel & pump panel B. Varsha Enclave (a) Electric driven fire pump 40 HP - 02 Nos (b) Electric driven Terrace pump 10 HP - 02 Nos (c) Connected LT panel and pump panel - 01 No
NOTE :- (i) The rate quoted by contractor shall deemed to be included for cleaning of the premises of installation, keep it neat and tidy in all the manners. (ii) All Tools & Plants or Transport required for carrying out daily maintenance and necessary stationary & documents (log books, test records etc.) for maintaining the records at each installation shall be arranged by the contractor and nothing extra will be admissible on this account. (iii) The contractor shall ensure full safety and functionability of the assets being maintained by him. Any casualty or injury sustained by the operators during the working hours at the premises of installations shall be sole liability of the contractor. No claim on this account shall be entertained by the Department. (iv) The quoted rates are deemed to be included for provision of communication facility for operators with JE / AGE / GE. (v) The contractor has to make own arrangements for testing the fire fighting system every month in presence of user rep and MES rep and produce the record for the same for verification.
S&F steel water tubing medium duty galvanised 100mm ISI marked with all fittings like elbow, tee, bend, socket, reducers, flange, taper, nut, bolt, gasket etc fixed on walls or floor or roof including fixing with clamps made out of suitable size of angle Iron and MS Flat on wall for Wet risers, Down comers etc. including painting with Signal Red synthetic enamel paint including taking down old items complete all as directed.
All as per Item No. 112 here-in-before but for 80 mm dia pipe.
Supply, Lay and Jointing in repairs, DI pipes 150mm bore with flanged ends centrifugally cast class 'K9' in any length laid in trenches, floors or fixed to wall all as directed.
Supply, Lay and Jointing in repairs, DI pipes 100mm bore with flanged ends centrifugally cast class 'K9' in any length laid in trenches, floors or fixed to wall all as directed.
Material and labour in repairs for DI fittings such as bends, tee, single branch, 'y' junctions, double branch, straight connecting pieces any type and angle/radius etc for flanged pipes up to 150mm bore all as directed.
S&F MS pipe 150 mm dia with welded joints and flanges with gaskets, nut, bolt washers of suitable size including 2 coats of red paint or a coat of primer complete all as specified and directed.
All as per Item No. 117 here-in-before but for 100 mm dia pipe
All as per Item No. 117 here-in-before but for 80 mm dia pipe
Supply, fix, test and commissioning of butterfly valve 150 mm dia PN 1.6, bronze / Gun metal seat, ISI marked complete with Nuts, Bolts, washers, 3mm thick insertion rubber gaskets conforming to IS 13095 complete all as specified and directed.
All as per Item No. 120 here-in-before but for 100 mm dia butterfly valve
S&F in repairs horizontal type double flanged Non Return Butterfly valve 150 mm dia, ISI Marked complete with bolts, nuts, washers, 3mm thick insertion rubber gaskets complete all as specified and directed.
All as per Item No. 122 here-in-before but for 100 mm dia Non Return Butterfly valve
All as per Item No. 122 here-in-before but for 80 mm dia Non Return Butterfly valve
S&F in repairs fabricated hose cabinet box mounted on wall, made out of 18 gauge MS Sheet of size 800X600x250mm with double door with 4 mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside with provn of lock & keys (two Nos) suitable for indoor use complete all as directed.
S&F in repairs fabricated hose cabinet made out of 18 gauge MS Sheet of size 800X600x250mm with double door with 4 mm thick glass and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside with provn of lock & keys (two Nos)suitable for outdoor use mounted on and including PCC 1:3:6 type C1 foundation of size 800x600x1000mm, complete all as directed.
S&F in repairs non-percolating type reinforced rubber cotton synthetic fibre circular woven jacketed fire delivery hose 63 mm dia treated against rot / mystex conforming to IS-636, 15 Mtr long with male and female SS coupling complete all as directed. Make:- Newage / Omex / Essel
S&F in repairs and connect to wet riser, first-aid hose reel swinging wall mounted type comprising rubber hose 19mm dia 30m long high pressure double braided bearing, PVC shut off nozzle and 25mm gunmetal inlet valve conforming to IS-884 complete all as directed. Make:- Newage / Mahavir
S&F in repairs landing valve (internal hydrant) Single headed SS conforming to IS, 63 mm female instantaneous outlet complete with PVC blank cap with chain and having suitable flanges for 100 mm dia wet riser complete all as directed. Make:- Newage/Omex/Essel
S&F in repairs Stainless steel branch pipe 63mm dia male instantaneous inlet, threaded outlet fitted with hexagonal based nozzle of 20mm dia heavy duty conforming to IS-903 complete all as directed. Make:- Newage/Omex/Essel
Supply, Fix, Connect and Testing in repairs, Fire brigade in let connection 4 way made out of gunmetal with flanged inlet and 63mm male instantaneous inlet with 150mm dia cast iron stand post including blank caps with chain, conforming to IS with flanged riser duck foot bend, 1m long 150mm dia short piece-1No, 150 mm dia Butter Fly Valve PN 16, bolts, nuts, washers and 3mm thick insertion rubber gaskets for flanged joints, painting with Signal Red synthetic enamel paint complete all as directed.
S&F in repairs, testing and Commissioning of Pressure switch Universal type 3 Kg/cm² to 9 Kg/cm². Make :- Danfoss / Indfoss
S&F in repairs Testing and Commissioning of Pressure Gauge, 4" dia, 0 - 14 Kgs rating complete all as directed. Make:- H guru
S&F in repairs Testing and Commissioning of Gun metal Air release valve 25mm dia complete all as directed. Make:- SKS / SB / Kartar
S&F in repairs Connect, Testing and Commissioning of IP:44 Intelligent Addressable loop power Manual Call Point (Dual Action) with inbuilt turbo Isolator suitable for flush or surface mounting and shall have test key feature without removing the glass complete as per site requirement and conforming to EN 54 / LPCB / VDS / FM. Make:- Model No. FDM223 (FDME223+FDMH293-R) of Siemens Cerberus or equivalent of Honeywell Essar / Bosch
Supply and installation, testing and commissioning in repairs Addressable fire alarm sounders / siren electronic type horizontal single stage continuous normal operation for at least 50 minutes with sound level 65 db to 120 db measured at 1.5 mtr with sound output variation of+ 5 db, 500 Mtrs range.
Supply, Fix, Connect, in repairs Testing and Commissioning of IP:40 Intelligent Addressable loop power Multi sensor (Heat and Smoke) Detector with inbuilt turbo isolator and integral response indicator with 360° viewing angle. Note:- Detector shall communicate 3 danger levels of differentiated alarm activation and height tolerance to Dust, Dirt, Temperature fluctuations and Air currents. Detector should have unique address for communication and assigned through panel including mounting base complete as per site requirement and conforming to EN 54 / LPCB / VDS / FM.
Dismantling and removing the motor of the mono block / coupled Pump set of capacity 10 HP 3 phase, AC, 415V from existing position, Shifting to authorized workshop for the repair work, removing the burnt winding, cleaning rotor / stator, re-winding the motor with super enamelled copper wire of size equivalent to the original winding including insulated packing materials, Varnishing, Drying etc and installing back to the original position, testing and commissioning on full load for 8 hrs continuous running complete all as specified & directed. Note:- The dismantling and refixing etc shall be carried out after Shut down of LT power supply to the equipment.
All as per Item No. 138 here-in-before but for motor of capacity 20 HP 3 phase, AC, 415V
All as per Item No. 138 here-in-before but for motor of capacity 100 HP 3 phase, AC, 415V
Dismantling and removing the mono block / Coupled pump set from the existing positing, opening the pump set, removing the unserviceable ball bearing from motor or pump side, supply and fix new ball bearing of suitable size (Make : SKF ) for pump set of capacity 10 HP 3 phase, AC, 415V, testing and commissioning on full load for 8 hrs continuous running, all as specified & directed.
All as per Item No. 141 here-in-before but for motor of capacity 20 HP 3 phase, AC, 415V
All as per Item No. 141 here-in-before but for motor of capacity 100 HP/ 92 BHP 3 phase, AC, 415V
Shut down LT power supply and Dismantling and removing the existing unserviceable motor starter from the panel board supply and fix new starter of the same capacity in the panel board including necessary connections testing and commissioning etc for the following capacities all as specified and directed.
DOL starter 3 phase, AC, 50Hz, 415Volts make L & T MN 16 DOL or equivalent suitable for pump of capacity up to 10 HP with relay range 9 to 15Amps
Fully Automatic star delta motor starter 3 phase, AC, 50Hz, 415Volts make L&T MN 25 FASD or equivalent suitable for pump set capacity up to 20 HP with relay range 14 to 23 Amps
Fully Automatic star delta motor starter 3 phase, AC, 50Hz, 415Volts make L&T MN 110 FASD or equivalent suitable for pump set capacity up to 100 HP with relay range 66 - 110 Amps
S&F in repair Single phase preventer suitable for 3phase pump sets of any capacity all as specified and directed. Make : L&T or Equivalent
S&F in repair 3 phase, 3 pole power contactor, 415V, suitable motor starters for 18 Amps AC3 rating all as specified and directed.
All as per Item No. 146 here-in-before but for 25 Amps
All as per Item No. 146 here-in-before but for 125 Amps
S&F in repair brass bush of the pump set of 10 HP pump capacity all as specified and directed.
S&F in repair brass bush of the pump set of 20 HP pump capacity all as specified and directed.
S&F in repair brass bush of the pump set of 100 HP/ 92 BHP 3 phase, AC, 415V pump capacity all as specified and directed.
S&F in repair Cast Iron foot valve Ball 150 mm dia heavy duty all as directed. Make: Normex
Preparing the surface by scrapping the old painting, removing the grease, oil, dirt etc and Spray painting with one coat of super enamelled anti corrosive paint of approved colour, over a coat of auto primer, for pump sets of 10 HP 3 phase capacity including painting of metallic base channel complete all as directed.
All as per Item No. 153 here-in-before but for pump of capacity 20 HP 3 phase
All as per Item No. 153 here-in-before but for pump of capacity 100 HP 3 phase
All as per Item No. 153 here-in-before but for pump of capacity 92 BHP 3 phase
Disconnect and remove burnt out No-Volt coil, Supply and fix No-Volt Coil suitable for 3 phase motor starters, AC, 415V, connecting, testing complete
M&L for Servicing /maintenance /repair of diesel engine driven pumping set of capacity 92 BHP removing of defective parts and replacing with new parts diesel pipe ,fuel line from pump to injectors, oil pipe 'o' rings ,gaskets, belt, radiator hose clip,battery leads with terminals including necessary nuts ,bolts and washer ,carbon brushes, coupling pad, replacement engine oil along with fuel filter, oil filter and air cleaner filter element as per existing make and type and filling of distilled water ,electrolyte ,mineral jelly for battery terminals ,cut out relay 24 volt/12 volt,including cleaning of fuel tank, engine oil pump etc. as directed. NOTE:- (a) Engine oil, radiator coolant etc. shall be measured and paid separately under relevant items as supply only. (b)The unit rate quoted shall be deemed to be inclusive of cost of labour for opening Gen set for replacement of defective parts and re-assembling the same after carrying out the repair as described. (c) The cost of minor parts which are not mentioned in item, but are essential for satisfactory functioning of the DG set shall be deemed to be included in the rate quoted for the item like nuts, bolts, washers, screws, cotton waste, cleaning materials etc. grease, lubricants etc.
Repair self starter of Diesel operated Pump set 12 V /24 V by transporting to local workshop, removing the starter, re-winding, with super enamelled copper winding wire of existing capacity, Varnishing, drying heating, refixing the starter including replacement of worn out bearing 01 No. greasing complete all as directed and refixing the same including testing for pump set of capacity 92 BHP
Material and labour for removing radiator from engine, cleaning and descaling the top / bottom tanks and fans repairing the fins/ leaking fins, refitting the same to engine, all as directed for diesel driven pump set of capacity 92 BHP
Supply only Coolant Castrol Radicool (Premixed) for radiator
Supply only engine oil 20 W 40. Make : Castrol/HP
Supply, fix, test and commissioning of Sluice valve PN 1.6, 150mm, ISI marked complete with Nuts, Bolts, washers, 3mm thick insertion rubber gaskets conforming to IS 13095 all as directed.
Supply and fix in repairs Hydrant valve adapter instantaneous outlet of landing valve S/S conforming to IS, 63 mm complete with PVC blank cap with chain complete all as directed.
Servicing and maintenance of complete solar water heater plant of cap 1000 LPD installed at multi story bldgs for carrying out minor leakage, cleaning of flat plate collector & sintex tank and make up tank incl dismantling inlet and outlet connection and refixing the same after cleaning for proper functioning to maintain proper water temperature, complete all as specified.
S&F as in repairs Hot water tank of cap 1000 ltr, Epoxy coated steel tank with n-sis technology, CFC-free PUF insulation, overnight temp drop less than 3°C, with protection against salt, deposition in inner tank incl fixing on same position & connecting of hot water & cold water system complete in all respect incl all fixing arrangement and testing for solar water heater complete all as specified and as directed by Engineer-in-Charge including complete cladding/ insulation of the tank with as per manufacturers instructions.
S&F in repair of rubber hose pipe 15mm dia between hot water tank & collector complete.
S&F in repair galvanized steel water tubing medium grade of 15mm bore with & including all fittings and fixed complete to walls and ceilings or laid in floors.
S&F in repair galvanized steel water tubing medium grade of 20mm bore with & including all fittings and fixed complete to walls and ceilings or laid in floors.
S&F CPVC pipes 25 mm outer dia SDR 13.5 and plain CPVC SDR 11 fittings complete on wall/ceiling or laying in floor/concealed complete all as specified and directed including taking down old pipe.
S&F float valve assembly made out of gun metal 20 mm complete all as specified and as directed.
S&F in repairs Gun-metal gate valve 15 mm bore, with iron wheel head, screwed both ends complete all as specified and as directed.
S&F in repairs Gun-metal gate valve 20 mm bore, with iron wheel head, screwed both ends complete all as specified and as directed.
S&F in repair Non return valve 15mm dia horizontal/vertical type complete all as specified and as directed by Engineer-in-Charge.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for laying pipe etc in soft or loose soil n exc 10 sqm on plan and n exc 1.5 m in depth and getting out complete all as specified and directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for laying pipe etc in hard/dense soil n exc 10 sqm on plan and n exc 1.5 m in depth and getting out complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and as directed.
Removing excavated material to a distance n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed.
Cutting existing road/hardstand of any type by using crow bar chisel up to a depth of 30cm and including excavation of remaining 30cm soft /loose soil for laying of pipes/UG cables etc and making good the surface by returning filling in layers nexc 25cm thick, watering, well ramming in layers and top layer using 150 mm thick PCC 1:2:4 over 150 mm thick hard core of broken bricks/stones complete all as specified and directed.
SREENARAYANA ENTERPRISES
ST ANTONY CONSTRUCTIONS
Oriental Constructions
Jack Electrolinks Private Limited
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .