Assistant Engineer (E) EMSD-II, South East, PWD, G
Assistant Engineer (E) EMSD-II, South East, PWD, Giri Nagar Kalkaji New Delhi.
SH Serviceing of substation Equipment and replacement of defective Parts etc.
2026_PWD_297409_1
91/EE(E)/AE(E)-II/EMD South East/PWD/2026-27
Open Tender
Electrical Works
Percentage
60 days
At Site
Please refer Tender documents.
9 documents required · 9 mandatory
₹0
₹9,645
Yes
1 Sept 2026
21 Aug 2026
29 Aug 2026
21 Aug 2026
29 Aug 2026
21 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Servicing of 630Amps, 3 Phase, 11 KV, HT VCB, complete with removal from HT panel, opening the required parts for servicing, checking, cleaning, testing & rectification of defects, oiling, greasing of moving gear assembly and arc contacts with CR-2 spray and cadmium solution i/c re-assembling, re-installation in HT panel, re-commissioning etc as reqd. | 3 | Nos. | 8,142 | ₹24,426 |
| 2 | Testing and calibration of IDMT relay set having 2 Nos. O/L and one No. earth fault relay installed in the existing HT panel by secondary injection method, cleaning the contacts, resetting with required accuracy complete checking & setting of control wiring i/c refixing of the relay unit etc complete as reqd. | 1 | Nos. | 1,696 | ₹1,696 |
| 3 | Supplying, Fixing, Testing and Commissioning of IDMT relay set having 2 Nos. O/L and one No. earth fault relay installed in the existing HT panel by secondary injection method, cleaning the contacts, resetting with required accuracy complete checking & setting of control wiring i/c refixing of the relay unit etc complete as reqd. | 2 | Nos. | 26,370 | ₹52,740 |
| 4 | Serviceing and cleaning of LT panel, AMF panel, emergency panel, capacitor panel i/c MCCB, busbar, cable termination complete etc as reqd. | 1 | Jobs. | 5,428 | ₹5,428 |
| 5 | Supplying and fixing insulator in existing VCB/HT panel and connect properly to VCB etc complete as reqd. | 3 | Nos. | 1,568 | ₹4,704 |
| 6 | Supplying and fixing vacuum interrupter in existing VCB/HT panel and connect properly to VCB etc complete as reqd. | 3 | Sets. | 53,452 | ₹1,60,356 |
| 7 | SITC of power-Pack 12/24volt (DC Power supply Unit) in existing HT Panel complete etc as required. | 1 | No. | 11,118 | ₹11,118 |
| 8 | Supplying Installation Testing and Commissioing indication lamp complete as reqd. | 5 | Nos. | 157 | ₹785 |
| 9 | Dehydration and filtration of Transformer oil to bring the die- electric strength upto 50KV/min & submission of test reports before and after dehyderation of oil as recommended as reqd. | 300 | Ltrs. | 13 | ₹3,900 |
| 10 | Supplying & refilling of silica gel in the existing silica gel enclosures of ONAN type transformers complete, testing etc as required. | 1 | Kgs. | 648 | ₹648 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 5.65 MB
BOQ_396179.xls
BOQ • 0.36 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .