Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.3 LAccepted-AOC 24 234 2 NEAR VYDHYUTHI BHAVAN KOTTAPPURAM ROAD PUNKUNNAM THRISSUR KERALA 680002 | THRISSUR | KERALA | 680002 | L1 | Accepted-AOC Lowest | |
| 2 | L2₹17.8 L+₹56,465 (3.27%)Rejected-Finance | L2 | Rejected-Finance Second lowest |
| Sl No | Description | Qty | Unit | MERKURY ELECTRICAL CORPORATION L1 | Biju E.M L2 |
|---|---|---|---|---|---|
| 1.00Electrical Work | |||||
| 1.00 | OD1898/2025-2026:Supply, installation, Programming, testing and commissioning of 80W Non integral Solar Floodlight System with 24 hours back up with dimming option.Floodlight Luminaire shall have min 13,000Lumens System output greater than 160 Lumens Per watt system efficiency, IP66, IK10 Protection, luminaire made of single piece Pressure Diecast aluminium Housing and individual lens for each LED embedded PC cover. Minimum 75,000 burning hours as per L70 and 500 hours Salt spray tested finish of Philips BVP483 series or equivalent. The Solar Panel shall be min. 200Wp Mono-Crystalline of 39V with excellent aging resistance and UV endurance to withstand harsh environment, environmentally sealed to IP67. The Batteries using in the system shall be Lithium Pherro Phospate type with 25.6 V 72 Ah with 1843 Wh Maintenance free having minimum 2000 cycles life.
The Charge controller using in the system shall be MPPT type Programmable and 4 step Dimmable via app with 93% efficiency and IP67 Connectors. Built in protection of Battery Reverse Polarity, Panel Reverse Polarity, Panel Reverse Current, Surge Protection at PV input, Battery over Voltage, Load short circuit and fuse protection in series for battery. Cleaning of solar panels must be done at least once in every 3 months during DLP period. The entire unit shall have an warranty of 5years. Preferred Make: PHILIPS/OSRAM/KESSLEC only | 8 | set | 1,58,198 ₹12,65,584 Lowest | 1,63,366 ₹13,06,928 |
| 1.00 | OD1899/2025-2026:Supply and installation of 8-meter Solar High mast with bottom min 310 mm and top 150 mm. Base Plate shall be min 25 mm thick and minimum 6 nos foundation bolts of size M24, 850mm long . The pole shall be provided with all accessories suitable for mounting above mentioned solar flood light in double lantern carriage. The mast shall be designed to for raising and lowering sing suitable load winch by manual operation. The mast shall be structurally designed to withstand 39 m/s wind speed. The entire unit shall have a warranty of 5years. Preferred make Philips / Utkarsh /Keselec only. | 2 | no | 1,90,939 ₹3,81,878 Lowest | 1,97,176 ₹3,94,352 |
| 1.00 | OD1851/2025-2026: Supply and installation of extra length of factory made foundation bolt of size M24 Galvanised MS bolt in RCC foundation with suitable stiffener piece etc. complete as required. | 24 | metre | 598 ₹14,352 Lowest | 617.4 ₹14,817.6 |
| 1.00 | OD1900/2025-2026:Supply and wiring with ISI marked, FRLS PVC, UV Protected insulated following size single core DC Copper conductor cables for interconnecting the control devices/ equipments including the wiring firm by suitable tie/ tie mounts/ PVC duct etc with sockets as required. 4.00 Sq.mm. | 160 | metre | 95 ₹15,200 Lowest | 98 ₹15,680 |
| 1.00 | OD1901/2025-2026:Supply and Fixing of high-quality bird and pigeon spikes (6/4/BS-18-1 64BS18) for using prevent birds from settling on solar panels. These spikes act as an effective deterrent, ensuring that birds do not nest or perch on the panels, which can cause damage, reduce efficiency, and lead to maintenance issues. Made from durable materials, the spikes are designed to withstand various weather conditions while ensuring the safety and cleanliness of your solar panel system. | 120 | no | 85 ₹10,200 Lowest | 88.2 ₹10,584 |
| 1.01 | 14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres. | 3 | cum | 379 ₹1,137 Lowest | 392 ₹1,176 |
| 1.01 | OD1850/2025-2026: Supply and installing RCC precast well steining of size 750mm dia and 300m height complete with all expense at site as required. | 8 | no | 930 ₹7,440 Lowest | 960.4 ₹7,683.2 |
| 1.01 | 14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement). | 1.49 | cum | 10,629 ₹15,837.21 Lowest | 10,976 ₹16,354.24 |
| 1.01 | 14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels | 3.6 | sqm | 399 ₹1,436.4 Lowest | 412.58 ₹1,485.29 |
Tender Value
₹18.2 L
EMD Value
₹45,533
Closing Date
12 Aug 2025, 3:00 pmClosed
The Executive Engineer Electrical HEED Harbour Eng
O/o The chief Engineer, Harbour Engineering Electrical Division, Kamaleswaram, TVPM
Expansion of Muthalapozhy Fishing Harbour _Supply Installation Testing and Commissioning of Two Numbers of Rectractable Type Solar Highmast Flood Light System at Muthalapozhy Fishing Harbour_General Electrical Work
2025_HED_780386_1
HED/CEHED/TR/501/2025_6_1_1/1
Open Tender
Electrical Works
Item Rate
60 days
MUTHALAPOZHY
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹45,533
20 Sept 2025
29 Jul 2025
14 Aug 2025
29 Jul 2025
12 Aug 2025
29 Jul 2025
Amount
Electrical Work
OD1898/2025-2026:Supply, installation, Programming, testing and commissioning of 80W Non integral Solar Floodlight System with 24 hours back up with dimming option.Floodlight Luminaire shall have min 13,000Lumens System output greater than 160 Lumens Per watt system efficiency, IP66, IK10 Protection, luminaire made of single piece Pressure Diecast aluminium Housing and individual lens for each LED embedded PC cover. Minimum 75,000 burning hours as per L70 and 500 hours Salt spray tested finish of Philips BVP483 series or equivalent. The Solar Panel shall be min. 200Wp Mono-Crystalline of 39V with excellent aging resistance and UV endurance to withstand harsh environment, environmentally sealed to IP67. The Batteries using in the system shall be Lithium Pherro Phospate type with 25.6 V 72 Ah with 1843 Wh Maintenance free having minimum 2000 cycles life. The Charge controller using in the system shall be MPPT type Programmable and 4 step Dimmable via app with 93% efficiency and IP67 Connectors. Built in protection of Battery Reverse Polarity, Panel Reverse Polarity, Panel Reverse Current, Surge Protection at PV input, Battery over Voltage, Load short circuit and fuse protection in series for battery. Cleaning of solar panels must be done at least once in every 3 months during DLP period. The entire unit shall have an warranty of 5years. Preferred Make: PHILIPS/OSRAM/KESSLEC only
OD1899/2025-2026:Supply and installation of 8-meter Solar High mast with bottom min 310 mm and top 150 mm. Base Plate shall be min 25 mm thick and minimum 6 nos foundation bolts of size M24, 850mm long . The pole shall be provided with all accessories suitable for mounting above mentioned solar flood light in double lantern carriage. The mast shall be designed to for raising and lowering sing suitable load winch by manual operation. The mast shall be structurally designed to withstand 39 m/s wind speed. The entire unit shall have a warranty of 5years. Preferred make Philips / Utkarsh /Keselec only.
OD1851/2025-2026: Supply and installation of extra length of factory made foundation bolt of size M24 Galvanised MS bolt in RCC foundation with suitable stiffener piece etc. complete as required.
OD1900/2025-2026:Supply and wiring with ISI marked, FRLS PVC, UV Protected insulated following size single core DC Copper conductor cables for interconnecting the control devices/ equipments including the wiring firm by suitable tie/ tie mounts/ PVC duct etc with sockets as required. 4.00 Sq.mm.
OD1901/2025-2026:Supply and Fixing of high-quality bird and pigeon spikes (6/4/BS-18-1 64BS18) for using prevent birds from settling on solar panels. These spikes act as an effective deterrent, ensuring that birds do not nest or perch on the panels, which can cause damage, reduce efficiency, and lead to maintenance issues. Made from durable materials, the spikes are designed to withstand various weather conditions while ensuring the safety and cleanliness of your solar panel system.
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
OD1850/2025-2026: Supply and installing RCC precast well steining of size 750mm dia and 300m height complete with all expense at site as required.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
CIVIL WORK
5.9.6:Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
5.22.1:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelMild steel and Medium Tensile steel bars
Biju E.M (BID ID -2278448)
Bidder Name
Biju E.M
MERKURY ELECTRICAL CORPORATION
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1279018.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .