EXECUTIVE ENGINEER
PMU POWER HOUSE
Work of Installing 160 kVA Transformer at Kuratoor and Installation of CTC RMU at Eswaravilasom Road (Nazzera) add on SSE type RMU at Cotton hill No.1 under Electrical section Poojappura 2. Interlinking Maru
2026_KSEB_866843_2
KSEBL/PMU-TVM/08/2026-27/dt 29.08.2026
Open Tender
Electrical Works
Percentage
PMU, POWERHOUSE
Please refer Tender documents.
6 documents required · 6 mandatory
₹5,900
₹50,000
26 Sept 2026
26 Sept 2026
17 Oct 2026
26 Sept 2026
14 Oct 2026
26 Sept 2026
26 Sept 2026 - 14 Oct 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Additional rate for excavation of one Earth Pit (2.5m depth) in Hard Laterite. | 4 | No | 1,737.55 | ₹6,950.2 |
| 2 | Doing straight joint on HT XLPE UG cables of sizes beyond 3x185 sqmm and upto and including 3x300 sq mm using the cable jointing kit supplied departmentally as per specification after providing proper traffic signalling and caution board fencing etc. wherever necessary, including charges for cable jointer and other sundries etc. as per the direction of departmental officers at site. | 3 | No | 3,229.41 | ₹9,688.23 |
| 3 | Transporting Transformers by hired vehicle to a distance upto 5km and carrying upto 2 numbers of 63/100/160/250kVA Transformers / Ring Main Units excluding loading& unloading charges. | 4 | Trip | 3,142.26 | ₹12,569.04 |
| 4 | Excavation of cable trench of appropriate size ( normally 1.2m deep and 0.35m /0.5m wide for single/double run) in all classes of soil including breaking clods, watering, ramming and sectioning of soil bank etc. and back filling the soil after cable laying and consolidating the soil in layers of 75cm (excluding laying of cable). | 1,090 | m | 318.86 | ₹3,47,557.4 |
| 5 | Laying HT XLPE UG cable of sizes beyond 3x185 sq mm and upto and including 3x300 sqmm including conveying cable from Sub Regional Store/stacking place to work site and laying it carefully using cable rollers, taking through stone ware/G.I.pipes at road crossing/culverts/bridges etc. whereever necessary, providing identification tags at 5m intervals, filling the space around the cable with riddled soil and covering the top with bricks, providing cable route markers at 100m intervals, inclusive of cost of all materials (other than cost of GI/HDPE pipe & UG Cable), labour and transport including crane charges excluding excavation and backfilling. | 1,060 | m | 481.95 | ₹5,10,867 |
| 6 | Additional rate for excavating trench on tarred/concrete surface of specified size. | 1,090 | m | 271.82 | ₹2,96,283.8 |
| 7 | Cost of construction of foundation, base plates, fixing anchor bots, loading & unloading, handling, erection, allignment and allied works for the installation of Data Aquisition compatible Extensible type Ring Main Units with terminal protector boots & extension modules, actuators for remote operatios, communicable FPIs, CTs, PTs & relay contacts for SCADA, giving power & control wiring and connections, providing terminal protector, interconnecting RMU bus bar and control cables, providing metered LT supply from nearest LT pole, providing earth leads, cable mounting & terminations, giving connections after ascertaing proper phase sequence, providing location name & warning boards, burying cables & refilling, conducting all precommissioning tests as required, complete, except cost of conveyance. RMUs with two nos load break switches & one VCB | 2 | No | 56,355.23 | ₹1,12,710.46 |
| 8 | Cost of construction of foundation, base plates, fixing anchor bots, loading & unloading, handling, erection, allignment and allied works for the installation of Data Aquisition compatible Extensible type Ring Main Units with terminal protector boots & extension modules, actuators for remote operatios, communicable FPIs, CTs, PTs & relay contacts for SCADA, giving power & control wiring and connections, providing terminal protector, interconnecting RMU bus bar and control cables, providing metered LT supply from nearest LT pole, providing earth leads, cable mounting & terminations, giving connections after ascertaing proper phase sequence, providing location name & warning boards, burying cables & refilling, conducting all precommissioning tests as required, complete, except cost of conveyance. Additional rate for RMUs with one additional Load Break switch / VCB | 1 | No | 14,202.5 | ₹14,202.5 |
| 9 | Coupling of Busbars | 2 | Set | 3,171.91 | ₹6,343.82 |
| 10 | Cutting Channel/Cross Arm/Angle Iron into two pieces. | 8 | No | 62.73 | ₹501.84 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
PART1.pdf
Tender Documents • 0.47 MB
PartII.pdf
Tender Documents • 0.48 MB
BIDFORMANDBIDAGREEMENT1.pdf
Tender Documents • 0.17 MB
BOQ_1481710.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .