Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.3 LAccepted-AOC SADARPARA PURULIA 723101 | PURULIA | PURULIA | WEST BENGAL | 723101 | L1 | Accepted-AOC L1 | |
| 2 | L2₹3.4 L+₹8,011.28 (2.41%)Rejected-Finance NAMOPARA PURULIA | PURULIA | PURULIA | WEST BENGAL | 723101 | L2 | Rejected-Finance L2 | |
| 3 | L3₹4.1 L+₹74,730.63 (22.5%)Rejected-Finance | L3 | Rejected-Finance L3 |
Tender Value
Refer Docs
EMD Value
₹6,660
Closing Date
27 Nov 2024, 10:00 amClosed
AE/PESD-I/PWD
O/O the AE/PESD-I/PWD ranchi road purulia
Repairing renovation of Electrical Installation works for sifting of air-Conditioning Machines at proposed office of the Medical Superintendent cum Vice Principal, Deben Mahata Government Medical College and Hospital Sadar Campus, Purulia
2024_WBPWD_770245_1
WBPWD/ AE/ PESD-I/ eNIQ-23/ 2024-2025
Open Tender
ELECTRICAL WORKS ORG
Item Rate
10 days
Purulia
Please refer Tender documents.
4 documents required · 4 mandatory
₹6,660
O/O the AE/PESD-I/PWD ranchi road purulia
24 Dec 2024
18 Nov 2024
29 Nov 2024
18 Nov 2024
27 Nov 2024
21 Nov 2024
20 Nov 2024
Amount
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy.fittings as required 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm)ECC [ E-14/1(a)(iii) ]
4 x 84/0.3 (6 sqmm) + 2 x 56/0.3 (4 sqmm) ECC [ E-14/1(b)(v) ]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment 4 Way [Make- Legrand, Enclosure (607715)/L & T/Siemens/ABB] [ D-10/14]
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. 63A FP [Make- Legrand/L & T/Siemens/ABB] [D-5/6]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection 6-32A SP [Make- Legrand] [D-6/7]
63A TP [Make-Legrand/Havells] [D-6/7]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-17/5(a)]
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections. [E-17/5(b]
Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-19/17]
Installation and Commissioning of hard/soft copper refrigerant piping, complete with fitting, elbows, bends, supporting arrangement on walls for Suction Line 5/8" OD with .7mm thick For 1.5 Tr 1.8/2.0 Conceale Split type AC(Make:Ryoku/Nippon)
Installation and Commissioning of hard/soft copper refrigerant piping, complete with fitting, elbows, bends, supporting arrangement on walls for Liquid Line 1/4" OD with .7mm thick For 1.5 Tr 1.8/2.0 Tr split type AC(Make:Ryoku/Nippon)
Supply & Fixing Pipe Insulation in 5/8" with 9mm nitrile rubber tube(Make:Accoroflex/Suprime)
Supply & Fixing Pipe Insulation in suction line 1/4"with 9mm nitrile rubber tube Suction Line (Make:Accoroflex/Suprime)
Drain water piping work out of 25mm dia PVC/HDPE harded pipes with Insulation, fitting,accessories, bends, elbows, tees, flanges, tappings, wall sleeves, hangers, supports, anchors.
Providing and laying electrical cabling 3 Core 2.5sq. mm. Communication Cable (Make:Finolex/KEI/Polycab)
Installation, testing & commissioning of the above-said 2.0/1.5 Ton split AC incl. Supply & fixing required Angle Iron Structure/MS bracket on wall & mending works as per direction of E.I.C.
Changes of Compressor Capacitor (50MFD) of Different Make AC Machine (Make-Universal/Sarada/JK)
Changes of ODU Fan's Capacitor (3MFD) of Different Make AC Machine (Make-Universal/Sarada/JK)
Changes of IDU Blower Capacitor (2.5/1.5MFD) of Different Make AC Machine (Make-Universal/Sarada/JK)
Charges of Refrigerant R22
Charges of Refrigerant R32
SITC of complete time switch for controlling of 1 no AC machine individually housed in SS double door phosphatised powder coated box with IP- 43 protection with electrical accessories & front door locking arrangement with all connection, a) 32A DP power contactor- 1 no, Make- L&T /Siemens /BCH /Schnider, b) Daily and weekly programmable basis digital time switch, min switching time 1 min, 25 ON/OFF programs, 6 yrs battery backup, settable DST & key pad lock features - 1 no, Make- L&T /Siemens /BCH /Schnider, c) 32A DP MCB (Breaking capacity 10 KA, 'C' characteristics) for power circuit-1 no. d) 3 A SP MCB (Breaking capacity 10KA ' C' series ) for control circuit- 1 no. The work should be completed with all fabrications, wiring with suitable guage wires of not less than 4 sq mm copper wire for power wiring & 1.5 sq mm for control circuit, with suitable heavy duty terminal blocks, terminations etc. complete as per direction of the EIC.
Add GST @18% On total from item no 1 to 20.
Add LWC @1% On total from item no 1 to 21.
COMBINE ENTERPRISES (BID ID -5774894)
DEB SHANKAR LAYEK (BID ID -5775728)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .