Loading…
Loading…
Tender Value
₹3.0 Cr
EMD Value
₹3.0 L
Closing Date
23 Mar 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
WORKS
14 conditions · 3 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees, N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet. ( Click here to download Format)
The tenderer must have successfully completed or substantially completed any one of the following categories of work(s) during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: (i) Three similar works each costing not less than the amount equal to 30% of advertised value of the tender, or (ii) Two similar works each costing not less than the amount equal to 40% of advertised value of the tender, o r (iii) One similar work costing not less than the amount equal to 60% of advertised value of the tender Similar nature of work is "Supply installation, testing & commissioning of any outdoor lighting work." (As per CEE/MLG/NFR's L/No.- EL/W/29/Tender/similar works/2281, dated- 28.09.2010)
Similar nature of work is "Supply installation, testing & commissioning of any outdoor lighting work." (As per CEE/MLG/NFR's L/No.- EL/W/29/Tender/similar works/2281, dated- 28.09.2010)
92 conditions · 11 needing a document upload
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
The tenderer is advised to study the tender document in www.ireps.gov.in portal carefully.
These Conditions of tender shall be read in conjunction with General Condition of Contract /2022 subject to modification, additions or supersession's by Special Condition of Contract and Specification if any.
General Condition of Contract and Specification for material and works of the N.F. Railway can be seen at the office of DRM(Electrical) KIR N.F.Railway.
Tenderer whose tender is accepted shall be required to appear at the office of DRM(Electrical) KIR N.F.Railway in person or if a firm or corporation a duly authorized representative shall so appear and execute an agreement in the form for carrying out the works according to the General and Special Condition of Contract and Specification 2022 for the work within seven days after notice to him that the contract documents are ready. Failure to do so shall constitute a breach of the agreement effected by the acceptance of the tender in which case of earnest money accompanying the tender shall stand forfeited without prejudice to any rights or remedies.
In the event any tenderer whose tender is accepted shall refuse to execute the contract agreement as herein before provided and or fail to commence the work within a reasonable time (to be determined by the Engineer) after notification of the acceptance of his tender the Railway may determine that such tender has abandoned the contract and there upon his tender and the acceptance thereof shall be null and void and the Railway shall be entitled to forfeit the Earnest Money as liquidated damages for such default without prejudice to any rights or remedies.
JOINT VENTURE will only be permitted in the tender value of Rs.10 (Ten) crore and above.
Contractor has also to submit execution programme within 15 days of issue of Acceptance letter or at the time of signing CA whichever is earlier.
All documents being submitted by the Tenderer(s) alongwith their offer shall have to be self attested by the Tenderer
The earnest Money and tender documents cost in respect of e- tendering will be accepted through net banking on payment gate way. The Bid Security shall be deposited either in cash through e payment gateway or submitted as Bank Guarantee bond from a scheduled commercial bank of India or as mentioned in tender documents. The Bank Guarantee bond shall be as per Annexure-VIA and shall be valid for a period of 90days beyond the bid validity period.
Fixed Deposit Receipt (FDR) will not be accepted as EMD for tender invited on IREPS (e-tender portal). (Authority Railway Boards Letter No. 2014/CE- 1/WP/5 of 01.09.16
The earnest Money deposited by the Contractor with his tender will be retained by the Railways as part of Security for the due and faithful fulfillment of the contract by the contractor. The balance to make up the security deposit, the rate of recovery should be @ 10 Percent of the bill amount till the full security Deposit of 5 Percent of the contract value is recovered.
Every tenderer shall state in the tender his postal address fully and clearly. Any communication sent in time to the tenderer by post at the said address shall be deemed to have reached the tender duly and in time. Important documents shall be sent by Registered post.
The tenderer shall deposit their earnest money with the Tender for the due performance with the stipulation to keep the offer open till such date as specified in the Tender under the condition of Tender The earnest money shall be 2 Percent of the Tender face value in the name of FA and CAO/N. F. Railway/MLG as indicated in the Tender notice. The earnest Money shall be rounded to the nearest Rs.100/-
It may be noted that submission of complete and accurate information is the responsibility of the tenderer. The Tender Inviting Authority reserves the right to verify, in any manner at its sole discretion, the accuracy of the information furnished by the Tenderer and if it is revealed that the Tenderer had submitted incorrect information to derive undue benefits, his Tender may be summarily rejected on these grounds
The value of PG to be submitted by the contractor will not change for variation upto 25 Percent (either increase or decrease). In case during the course of execution, value of the contract increases by more than 25 Percent of the original contract value, an additional Performance Guarantee amounting to 5 Percent (five percent) for the excess value over the original contract value shall be deposited by the contractor.
The Performance Guarantee (PG) shall be released after physical completion of the work based on Completion Certificate? issued by the competent authority stating that the contractor has completed the work in all respects satisfactorily. The Security Deposit shall, however, be release only after expiry of the maintenance period and after passing the final bill based on No Claim Certificate? from the contractor.
Eligibility criteria for works tender in respect of Employment/Partnership etc. of Retired Railway Employees :-
(a) Should a tenderer (i) be a retired Engineer of the gazetted rank or any other gazetted officer working before his retirement, whether in the executive or administrative capacity or whether holding a pensionable post or not, in the Engineering or any other department of any of the railways owned and administered by the President of India for the time being, OR (ii) being partnership firm / joint venture (JV) / registered society / registered trust etc have as one of its partners/members a retired Engineer of the gazetted rank or any other gazetted officer working before his retirement, OR (iii) being an incorporated company have any such retired Engineer of the gazetted rank or any other gazetted officer working before his retirement as one of its directors AND in case where such Engineer or officer had not retired from government service at least 1 year prior to the date of submission of the tender THEN the tenderer will give full information as to the date of retirement of such Engineer or gazetted officer from the said service and as to whether permission for taking such contract, or if the Contractor be a partnership firm or an incorporated company, to become a partner or director as the case may be, has been obtained by the tenderer or the Engineer or officer, as the case may be from the President of India or any officer, duly authorized by him in this behalf, shall be clearly stated in writing at the time of submitting the tender.
b) In case, upon successful award of contract, should a tenderer depute for execution of the works under or to deal matters related with this contract, any retired Engineer of gazette rank or retired gazetted officer working before his retirement in the Engineering or any other department of any of the railways owned and administered by the President of India for the time being, and now in his employment, then the tenderer will ensure that retired Engineer or retired gazetted officer had retired from government service at least 1 year prior to the date of his employment with tenderer and in case he had retired from service within a year then he possesses the requisite permission from the President of India or any officer, duly authorized by him in this behalf, to get associated with the tenderer.
c ) Should a tenderer or Contractor being an individual, have member(s) of his family or in the case of partnership firm/ company / joint venture (JV) / registered society / registered trust etc. one or more of his partner(s)/shareholder(s) or member(s) of the family of partner(s)/shareholder(s) having share of more than 1%in the tendering entity employed in gazetted capacity in the Engineering or any other department of the railway, then the tenderer at the time of submission of tender, will inform the authority inviting tenders the details of such persons.
Note: -If information as required as per 17.1, 17.2, 17.3 above has not been furnished, contract is liable to be dealt in accordance with provision of clause 62 of the Standard General Condition of contract.
In these Conditions of tender the terms shall have the meaning assigned to them in the N.F.Railway Electrical Department. General Condition of Contract/2022 as amended from time to time hereinafter referred to as the General Condition of the Contract except where the context otherwise requires.
For those conditions for which standard formats have been given in the uploaded document titled-Formats for uploading of various format. The information should only be submitted in these standard formats
Rates are inclusive of all taxes/octroi, license fee, royalty charges etc. legally leviable by State, Central Govt. and/or any other local authority.
In addition to General condition of contract 2022 and Indian Railways Unified standard specification Works Materials Volume I II 2010, revised upto date, special condition attached shall also apply.
Sales tax/Business tax will be recovered as per extant instruction on the subject.
Earnest Money and Tender Document Cost: -All the tenderers / Contractors have to deposit full earnest money and tender document cost as stipulated in the tender document through net banking or payment get way. Note: The Bid Security shall be deposited either in cash through e payment gateway or submitted as Bank Guarantee bond from a scheduled commercial bank of India or as mentioned in tender documents. The Bank Guarantee bond shall be as per Annexure-VIA and shall be valid for a period of 90days beyond the bid validity period. In case, submission of Bid Security in the form of Bank Guarantee, following shall be ensured: (i) A scanned copy of the Bank Guarantee shall be uploaded on e-Procurement Portal (IREPS) while applying to the tender. (ii) The original Bank Guarantee should be delivered in person to the official nominated as indicated in the tender document within 5 working days of deadline of submission of bids. (iii) Non submission of scanned copy of Bank Guarantee with the bid on e-tendering portal (IREPS) and/or non submission of original Bank Guarantee within the specified period shall lead to summary rejection of bid. (iv) The Tender Security shall remain valid for a period of 90 days beyond the validity period for the Tender. (v) The details of the BG, physically submitted should match with the details available in the scanned copy and the data entered during bid submission time, failing which the bid will be rejected (vi) The Bank Guarantee shall be placed in an envelope, which shall be sealed. The envelope shall clearly bear the identification "Bid for the ***** Project" and shall clearly indicate the name and address of the Bidder. In addition, the Bid Due Date should be indicated on the right hand top corner of the envelope. (vii) The envelope shall be addressed to the officer and address as mentioned in the tender document. (viii) If the envelope is not sealed and marked as instructed above, the Authority assumes no responsibility for the misplacement or premature opening of the contents of the Bid submitted and consequent losses, if any, suffered by the Bidder.
Deposit Receipts, Pay Orders, Demand Drafts and Guarantee Bonds. These forms of Performance Guarantee could be either of the State Bank of India or of any of the Nationalized Banks.
Eligibility criteria for works tender in respect of partnership firms:-
In case the tenderer is a partnership firms , the experience, solvency and turn over shall be in the name and style of the firm only.
If the tenderer is a partnership firm, all the partners shall be jointly and severally liable for successful completion of the work and no request for change on the certification of the firm shall be entertained.
During the currency of the contract, no partner of the firm shall be permitted to withdraw from partnership business and in such and event it shall be treated as breach of trust and abandonment of the contract.
Any Conditional offer will be summarily rejected.
For Standard Financial criteria and Standard Technical criteria - Tenderers are required to submitted authenticated certificate along with the tenders from officers of government or semi- government/public sector undertakings under whom the work has been executed indicating there in the name of work executed, value of works/payment details and period during which completed. Such certificates should have signature and seal of the concerned officer. In the absence of such certificate the tender may not be considered.
All tenderers are expected to submit full credentials with their tender to establish their capacity to undertake and successfully complete the tender work.
The Tenderers should ensure that the information given in this part of the tender clearly establishes his capacity to successfully execute the tender work. It may be noted that the Tender Inviting Authority does not have any obligation to seek clarification on the information furnished or the information furnished is incomplete/inadequate to establish the tenderers capacity, the tender is likely to be rejected on these grounds. No plea made by the tenderer on this account by submitting additional information, etc. shall be entertained by the Tender Inviting Authority.
The successful bidder shall have to submit a Performance Guarantee (PG) within 21 (Twenty one) days from the date of issue of Letter of Acceptance (LOA). Extension of time for submission of PG beyond 21 (Twenty one) days and upto 60 days from the date of issue of LOA may be given by the Authority who is competent to sign the contract agreement. However, a penal interest of 12% per annum shall be charged for the delay beyond 21(Twenty one) days, i.e. from 22ndday after the date of issue of LOA. Further, if the 60thday happens to be a declared holiday in the concerned office of the Railway, submission of PG can be accepted on the next working day. In all other cases, if the Contractor fails to submit the requisite PG even after 60 days from the date of issue of LOA, the contract is liable to be terminated. In case contract is terminated railway shall be entitled to forfeit Bid Security and other dues payable to the contractor against that particular contract, subject to maximum of PG amount. In case a tenderer has not submitted Bid Security on the strength of their registration as a Startup recognized by Department of Industrial Policy and Promotion (DIPP) under Ministry of Commerce and Industry, DIPP shall be informed to this effect. The failed Contractor shall be debarred from participating in re-tender for that work.
The successful bidder shall submit the Performance Guarantee (PG) in any of the following forms, amounting to 5% of the original contract value:- (i) A deposit of Cash; (ii) Irrevocable Bank Guarantee; (iii) Government Securities including State Loan Bonds at 5% below the market value; (iv) Pay Orders and Demand Drafts tendered by any Scheduled Commercial Bank of India; (v) Guarantee Bonds executed or Deposits Receipts tendered by any Scheduled Commercial Bank of India; (vi) Deposit in the Post Office Saving Bank; (vii) Deposit in the National Savings Certificates; (viii) Twelve years National Defence Certificates; (ix) Ten years Defence Deposits; (x) National Defence Bonds and (xi) Unit Trust Certificates at 5% below market value or at the face value whichever is less. Also, FDR in favour of FA & CAO / N. F. Railway / Maligaon (free from any encumbrance) may be accepted.
The Performance Guarantee shall be submitted by the successful bidder after the Letter of Acceptance (LOA) has been issued, but before signing of the contract agreement. This P.G. shall be initially valid upto the stipulated date of completion plus 60 days beyond that. In case, the time for completion of work gets extended, the Contractor shall get the validity of P.G. extended to cover such extended time for completion of work plus 60 days.
The value of PG to be submitted by the Contractor is based on original contract value and shall not change due to subsequent variation(s) in the original contract value.
The Performance Guarantee (PG) shall be released after physical completion of the work based on 'Completion Certificate' issued by the competent authority stating that the Contractor has completed the work in all respects satisfactorily. The Security Deposit shall, however, be release only after expiry of the maintenance period and after passing the final bill based on No Claim Certificate from the contractor
Whenever the contract is rescinded, the Performance Guarantee already submitted for the contract shall be encashed.
No post tender correspondence will be done with participant tenderer(s) for submission of document for the deficiencies noted during the scrutiny of tender/offer. Offer of tenderer(s) will be strictly decided on the basis of the downloaded documents like credential, earnest money and tender cost etc.as found uploaded by the tenderer(s) with there respective offer. Hence tenderer shall not be asked to submit any additional document after opening of tender. In case of submission of incomplete document by tenderer, tender offer will be rejected and tender committee can mave to next valid tenderer as per document submitted
Amrit Bharat Station Scheme:- Improvement of Facade Lighting, Outdoor Lighting in Circulating Area, Parking Area & Other Ancillary Work at TKG, HDB & JPG in KIR Div.
11_2026
11_2026
Open
Works - General
6 Months
Katihar, Bihar
₹0
₹3.0 L
23 Mar 2026
28 Feb 2026
9 Mar 2026
168 items across 3 schedules · ₹3,01,20,321 total
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| 1 | Supply of LED LINEAR LIGHT 12-18 W. | Set | 40.00 | 7,841 | 3,13,640 |
| 2 | Supply of Main Controller. | Set | 1.00 | 1,48,666 | 1,48,666 |
| 3 | Supply of Sub Controller. | Set | 3.00 | 84,952 | 2,54,856 |
| 4 | Supply of RGBW LED Linear Light min 36 W. | Set | 30.00 | 8,305 | 2,49,150 |
| 5 | Supply of RGBW LED Linear Light min 24 W. | Set | 20.00 | 8,043 | 1,60,860 |
| 6 | Supply of RGBW LED Linear Light min 48 W. | Set | 40.00 | 18,925 | 7,57,000 |
| 7 | Supply of RGBW LED Linear Light min 100 W. | Set | 20.00 | 30,510 | 6,10,200 |
| 8 | Supply of Led Driver Power min 200 W. | Set | 30.00 | 4,758 | 1,42,740 |
| 9 | Supply of RGBW LED Spot Light min 18 W. | Set | 10.00 | 6,374 | 63,740 |
| 10 | Supply of RGBW LED Spot Light min 36 W. | Set | 40.00 | 13,680 | 5,47,200 |
| 11 | Supply of RGBW LED Spot Light min 72 W. | Set | 10.00 | 14,485 | 1,44,850 |
| 12 | Supply of RGBW LED Spot Light min 100 W. | Set | 10.00 | 21,324 | 2,13,240 |
| 13 | Supply of RGBW LED Strip Light min 14.4 W/meter. | Set | 100.00 | 1,272 | 1,27,200 |
| 14 | Supply of DMX Decoder for LED Strip input voltage 24 V DC. | Set | 6.00 | 2,897 | 17,382 |
| 15 | Supply of Aluminum Extrusion for LED Strip. | Metre | 50.00 | 161 | 8,050 |
| 16 | Supply of 8 Channel Opto Isolated DMX Signal Amplifier and Splitter. | Set | 1.00 | 26,562 | 26,562 |
| 17 | Supply of Digital Lighting Console with min. 1024 DMX Channels. | Set | 1.00 | 72,071 | 72,071 |
| 18 | Supply & laying of PVC Copper Cable 3 C x 1.5 Sq.mm. | Metre | 600.00 | 70 | 42,000 |
| 19 | Supply & laying of 5 Core Shielded DMX Signal Cable for DMX Network. | Metre | 800.00 | 138 | 1,10,400 |
| 20 | Supply of Waterproof Power Connectors for Light Fixture. | Numbers | 100.00 | 1,030 | 1,03,000 |
| 21 | Supply of Waterproof DMX Connectors for Light Fixture. | Numbers | 100.00 | 1,238 | 1,23,800 |
| 22 | Installation, Testing and Commissioning of the System and Fixing of LED RGBW Fitting at Site Location with Supply of MS Clamp, Fastener, Nut Bolt Screw etc. as per Site Requirement and Entire Programming and Free Demonstration of the System. (From SN 1 to 21) | Set | 1.00 | 1,30,151 | 1,30,151 |
| 23 | Supply, fixing, testing & commissioning of rigid PVC conduit pipe of 32 mm dia, Medium mechanical strength. The pipe should be fixed with ramp/FOB shed structure at regular interval with clamps as per instruction of Engineer Incharge at Site. | Metre | 200.00 | 56 | 11,200 |
| 24 | Supply, fixing, testing & commissioning of rigid PVC conduit pipe of 25 mm dia, Medium mechanical strength. The pipe should be fixed with with clamps as per instruction of Engineer Incharge at Site. | Metre | 300.00 | 26 | 7,800 |
| 25 | Supply, fixing, testing & commissioning of rigid PVC conduit pipe of 20 mm dia, Medium mechanical strength. The pipe should be fixed with with clamps as per instruction of Engineer Incharge at Site. | Metre | 500.00 | 12 | 6,000 |
| 26 | Supply, installation, testing and commissioning of drop down Led decorative light warm white Cast iron based pole of height 3 meter with 45 watt capacity double arm bracket mild steel grooved pipe pole made out of cast iron base 390 mm base dia, Top 83mm OD above the ground level primer coated and painted with polyurethane paint with die cast aluminum embellishments, joints/ column's section etc. The bottom column shall be integral connection box having mounting arrangement of One No. MCB, 4 Way heavy duty connector cover the same etc. as required with medium Led Hanging light made out of spun aluminium housing, minimum 4500 lumens with maximum system wattage 45 watt Led Mounting on aluminum die casted heat sink with power Led, minimum efficacy 100 Lumen per watt with external driver CCT 5700, CRI > 70, PF>0.90, Operating Voltage 220-240V AC Painted with PU Paint as matching of above Pole complete. The LED driver access should be from top for easy maintenance LEDs should be provided with non-yellowing modular secondary lens optics. LED used shall be SMD type, Life of fixture 50000 hrs, THD< 10%, and Operating Temperature Range 0 deg C to + 50 deg C, IP66. Built in Surge Protection of SKV & external surge protection of 10 kV. LED Driver should be of Constant current driver to have built-in surge, open & short circuit protection, Over Voltage Protection @ 300V+5V, Double Phase Protection (up to 48 hrs.) and as per requirement and direction of Railway site engineer in-charge. | Numbers | 20.00 | 52,751 | 10,55,020 |
| 27 | Supply, erection, testing & commissioning of 16 mt long High Mast Tower with 8 nos. x 250 watt LED luminaries in symmetrical arrangement complete with all accessories (Double drum winch, SS wire rope, integral power tool motor, head frame, junction box, foundation bolt, LED aviation light, Fedder pillar with single dial timer & raising lowering mechanism etc.) including shallow foundation with M20 grade concrete etc. as per instruction of Engineer Incharge at Site. | Set | 1.00 | 7,40,228 | 7,40,228 |
| 28 | Supply, installation, testing & commissioning of 250 watt LED flood light luminaires complete with pressure die cast aluminium housing, IP 66, Luminous efficacy >=100 lm/watt with heat sink feature, surge protection etc including wire connection as per instruction of Engineer incharge at site. | Numbers | 12.00 | 25,228 | 3,02,736 |
| 29 | Supply, fixing, testing, commissioning of 15 W LED Bollard light IP 66 complete as per IS & IE rules and as per instruction of Engineer Incharge at Site. | Numbers | 30.00 | 8,096 | 2,42,880 |
| 30 | Supply, fixing and connection of LED ARCHITECTURE Linear Profile Light Min 40W/meter as per instruction of Engineer incharge at site. | Metre | 200.00 | 1,911 | 3,82,200 |
| 31 | Supply, fixing and installation of Solar Tree min 1 KW with charging facility and sitting arrangement as per instruction of Engineer incharge at site. | Set | 2.00 | 2,22,999 | 4,45,998 |
| 32 | Supply, installation, testing & commissioning of Power One' make 3 KVA true online UPS system, 1 Phase input & 1 Phase output with Exide / Amara Raja make SMF batteries of 12V, 150 AH x 8 Nos. (Total: 14400 VAH) to provide 4-6 Hrs. backup along with suitable Battery Rack & battery interlink as per instruction of Engineer Incharge at Site. | Set | 3.00 | 2,29,608 | 6,88,824 |
| 33 | Supply, installation, commissioning & testing of LED indication name board (Length of board will be as per proportion of letter so that all the 4 side of the board will have extra space) with channel letters with 3.75 ft. in lenght with suitable widen and 4 mm projection size which inside ACP board (Brand- ALUDECOR, category- AL 33 series exterior & thikness-3 mm) with acrylic face on front and having Sumsung 5630 LED's (Shape- Lens type, operating voltage- 12 V DC, carring current-80 mA, power Dissipation- 0.96 watt, working hours-50000, case material-ABS ,protection-IP68) inside for illumination letters in English, Hindi, Bengali or regional language complete with all materials including provision of erection structure made of MS angle/channel/flat duly painted with aluminium paint over a coat of red oxide primer with CC foundation (1:3:6) of cement, sand and stone chips as required at site and as per instruction of Egnineer incharge at site. | Square Foot | 100.00 | 1,772 | 1,77,200 |
| 34 | Supply, installation, testing & commissioning of modular power unit complete with 32 Amp mini MCB DP "C" series 3kA , 25 amps starter, 25 Amp Socket and 25 Amp plug to be mounted on 6 module GI box, 6 module combined plate concealed on wall and wiring by 6 sq mm, Single Core FR-LSH PVC Insulated Industrial Grade Copper Conductor (Unsheathed) Flexible Cables, 1100 Volts with earth coninuity wire by 1 sq mm copper cable Conforming to IS: 694 to be drawn through Rigid PVC conduit pipe not less than 20 mm dia as per instruction of Engineer incharge at site. | Numbers | 4.00 | 1,193 | 4,772 |
| 35 | Supply, installation, testing & commissioning of Inverter Split Air Conditioners 1.5 Ton, (BEE star rating-5 star, Coil material-Copper, Echo- friendly refrigerant, Nominal cooling capacity in Ton / (kcal/hr)-1.5 Ton / 4500 kcal/hr) with all accessories as per OEM suitable for operation on 230V AC ,single phase, 50 Hz as per instruction of Engineer incharge at site. Re- mending work should be done after installation of RAC. (with 1 pair outdoor wall stand) | Numbers | 4.00 | 54,091 | 2,16,364 |
| 36 | Horizontal machine boring of 300 mm dia hole across track/Road/High drain etc. at a depth of 1.0 mtr below of ground level with suitable boring instruments & neessary arrangement and as per technical procedure. | Metre | 100.00 | 2,538 | 2,53,800 |
| 37 | Supply, laying, commissioning & testing of HDPE pipe 110 mm dia PN-6 grade conforming IS 4984/1995 or latest to to be laid partly along t h e pole with suitable fixing arrangement by MS clamp made of MS flat of size 50x6 mm and suitable size nut , bolt, washer as per instruction of Engineer incharge at site. | Metre | 100.00 | 383 | 38,300 |
| 38 | Supply, laying, commissioning & testing of HDPE Pipe 75 mm dia PN-6 grade to be laid partly along the pole /underground with suitable fixing arrangement by MS clamp made of MS flat of size 50x6 mm and suitable size nut, bolt, washer and required bend, joints as per instruction of Engineer incharge at site. | Metre | 600.00 | 278 | 1,66,800 |
| 39 | Supply, fixing, testing & commissioning of IP 66/67 thermoplastic cable junction box / loop box of size (210 x 310 x 116) mm with knockouts & 04 nos terminals as per instruction of Engineer incharge at site. | Numbers | 15.00 | 5,291 | 79,365 |
| 40 | Supply, erection, testing & commissioning of maintenance free earthing arrangement (Chemical Earthing with low impedance ,corrosion resistant & long life). Earth electrode is made up of high tensile low carbon steel circular rods bonded with copper on outer surface and interconnection of earth electrode with suitable size copper strip. The earth electrode shall be of minimum 17.0 mm diameter and 3.66 meter length as per instruction of Engineer Incharge at Site. | Numbers | 10.00 | 15,928 | 1,59,280 |
| 41 | Supply & Erection of earth by 50 mm dia 3 Mtrs. long (3.6 mm thickness) GI pipe, 32x6 mm GI strip- 5 Mtrs, GI nuts, bolts including masonry materials for earthing pit, salt, charcoal, soldered end terminal etc. and construction of earth pit covered with RCC cover slab12.7 mm thickness and watering pipe as per Drg. No.- PCEE/ELG/DRG/2024/1 Date:- 30.09.2024 and as per instruction of Engineer Incharge at site. | Numbers | 8.00 | 4,349 | 34,792 |
| 42 | Supply, installation and testing of Astro (Analog) time switch with 3 pole 63 amp contractor and suitable thermoplastic box and fitted on mounting plate/DIN rail as per instruction of Engineer Incharge at Site. | Set | 6.00 | 9,777 | 58,662 |
| 43 | (a) Supply, installation, testing & commissioning of 4 way VTPN MCCB DB (MCCB+12 modules) with IP 43 grade protection, metal door with wire sets, busbar, earth bar, blanking plates, cable ties etc with supply and fixing of following MCCB/MCB as per instruction of Engineer incharge at site. | Set | 4.00 | 12,330 | 49,320 |
| 44 | (b) MCCB FP 100 amps, 25 kA, Ics= 100% Icu | Numbers | 4.00 | 8,219 | 32,876 |
| 45 | (c) MCB SP 6-32 amps, 1 module, 10 kA, C- curve Conforms to IS/IEC 60898 - 1:2002 | Numbers | 48.00 | 245 | 11,760 |
| 46 | (a) Supply, fabrication, erection, testing, commissioning & painting of floor mounted powder coated cubicle panel board (Modular look) of suitable size (neither big nor small) ), outdoor type with double door made of suitable size MS/GI angle 50 x 50 x 6 mm, MS/GI flat 50 x 6 mm, 14 SWG MS sheet/Powder coated CRCA sheet with provision of weather proof,rust proof,dust proof, water proof having internal rubber gasket with supply and fixing of following ACB/MCCB/Bus bar/Meter etc. (Connections to be made by copper strips, glands should be provided at cable entry and exit, components should be compartmentalized, Each compartment will be provided with the door and pad locking arrangement. The compartment illumination lamp with door operated switch shall be provided for each compartment. Panel board drawing approval must be obtained with clear indication of make of items of components):- | Set | 1.00 | 32,916 | 32,916 |
| 47 | (b) MCCB FP 200 amps, 25 kA, Ics=100% Icu | Numbers | 1.00 | 15,354 | 15,354 |
| 48 | (c) MCCB FP 125 amps, 36 kA, Ics=100% Icu | Numbers | 4.00 | 7,919 | 31,676 |
| 49 | (d) MCCB FP 63 amps, 25 kA, Ics=100% Icu | Numbers | 8.00 | 7,272 | 58,176 |
| 50 | (e) MCCB FP 32 amps, 25 kA, Ics=100% Icu | Numbers | 16.00 | 5,865 | 93,840 |
| 51 | (f) Copper bus bar 200 amps made of electrolytic grade copper consisting of 4 bars ( 3 Ph and Neutral ) ( Bus bar should have insulation cover) | Set | 1.00 | 1,222 | 1,222 |
| 52 | (g) Digital voltmeter (0-500) amps and Digital ammeter (0-500) amps with s/switch and CTs | Set | 1.00 | 5,581 | 5,581 |
| 53 | (h) Supply, Fixing & Testing of LED multifunction meter, Accuracy Class 1.0, Input voltage measurement range 50-550 VAC (P-P), Aux supply 90-300VAC/DC for measuring of V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Interrupts, THD, neutral current etc parameters alongwith supply & fixing of 3 nos. suitable CTc. | Set | 1.00 | 10,470 | 10,470 |
| 54 | (i) LED Indication Lamp RYB | Set | 1.00 | 237 | 237 |
| 55 | Laying, commissioning & testing of HT/LT XLPE/PVC cable of different sizes partly along the pole and partly through ground in cable trench by excavation of ground below 1.5 mt from ground level with suitable fixing arrangement by MS clamp of size 50x6 mm and suitable size nut, bolt. Loading, Unloading & Carrying of cable to actual work site by contractor's own arrangement. (Aluminium Crimping Socket should be provided for each Cable Termination). (Cable will be supplied by Railway) | Metre | 3340.00 | 55 | 1,83,700 |
| 56 | Excavation of cable trench (0.3 x 1.5) mtr below ground level for laying of cable & refilling the soil after digging the earth as per instruction of Engineer incharge at site. Cable should be laid on bedding of height 75 mm sand at the bottom of trench, and covering it with additional sand of height 75 mm and thereafter protecing it by mean of bricks before refilling the soil as per IS 1255. | Metre | 500.00 | 148 | 74,000 |
| Schedule total | ₹1,00,40,107 | ||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
NITFacadeLightingTKGHDBJPG.pdf Tender Paper
ATTACHMENT
GCC 2022 with ACS
ATTACHMENT
GCCApril-2022PDFwithallcorrectionSlips.pdf
ATTACHMENT
NITFacadeLightingTKGHDBJPG.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .