Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹2.1 LAccepted-AOC | 1 | Accepted-AOC L1 | |
| 2 | 2₹2.2 L+₹10,545.70 (5.00%)Rejected-AOC | 2 | Rejected-AOC L2 |
Tender Value
₹2.1 L
EMD Value
₹5,273
Closing Date
22 Jan 2025, 4:00 pmClosed
SHAINY VISWAMBARAN
Secretary Cheruvannur GP Cheruvannur
Annual plan Cheruvannur GP ProNo56/25 Poolakkul Rayarothkunnu DWSS Electrification and motor pump set installation General Electrical work
2025_DP_726145_1
5/AE/LIDEW/15/CNR/24-25
Open Tender
Electrical Works
Item Rate
270 days
LSGD SECTION CHERUVANNUR
Please refer Tender documents.
9 documents required · 9 mandatory
₹555
Yes
₹5,273
Yes
28 Feb 2025
14 Jan 2025
25 Jan 2025
14 Jan 2025
22 Jan 2025
14 Jan 2025
Amount
Electrification
90.14.1.2:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br> Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD81229/2024-2025:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipment s including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 1.50 sq mm single run with required sockets.
OD81230/2024-2025:Supply and providing Danger 415 V, 150 X 100 mm Enameled danger plates
OD81231/2024-2025:Supply and providing LED indicator lamp (Red, Green, Black, Yellow, Orange colours) in the existing panel board and giving connection
OD81232/2024-2025:Supply and providing LED indicator lamp (Blue colour) in the existing panel board and giving connection
90.14.24.19:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.4 KVAr, 3 phase, 440 V, delta connected, standard duty Metalised Poly Propylene Capacitor, Box Type, suitable for direct connection to motors.
2.1.1:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.32 Amp TP & N
2.1.2:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N
2.10.3:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
90.2.1.1:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point
90.2.1.6:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points
OD81328/2024-2025:Supply, Conveyance, Installation and testing of robust & reliable LED Bulk head with IP65 Protection and IK08 impact resistance suitable for wall mounting application including giving connection as required. (Make: Philips (Model: WT140W LED7S CW PSU S1 PC-9405) or any other equivalent make
90.6.6.3:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.4 sq mm
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
90.6.10.3:Supply and fixing of following sizes of light gauge PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required32 mm
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD81341/2024-2025:Supply and providing 2x25x3 mm G I strip as test joint on the existing watering pipe of earthing including bending and giving connections
OD81342/2024-2025:Supply and providing 25X3 mm GI strip
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD81344/2024-2025:Supply and providing 25x6mm brass nut and bolt etc. as required.
OD81351/2024-2025: Supply and fixing 50mm GM Non Return valve in the existing ASTM/GI pipe
OD246629/2024-2025:Supply, installation, testing and commissioning of 2 1/2" Cast Iron Non Return Valve in the existing PVC/ ASTM pipe
OD81352/2024-2025:Supply and fixing 50mm GM Ball valve in the existing ASTM pipe Zoloto make or equivalent
OD81353/2024-2025:Supply and providing suitable stranded Steel rope for hanging the 10HP submersible motor pump set
OD81354/2024-2025:Supply and fixing 50mm ASTM socket 80 Sch
OD81355/2024-2025:Supply, laying and fitting 50 mm 80 Sch ASTM pipe with suitable type solvent etc. as required at site,
OD81356/2024-2025:Supply and fixing 50mm 80Sch ASTM bend
OD81357/2024-2025:Supply and fixing 50mm 80 Sch ASTM Tee
OD81358/2024-2025:Supply and fixing 50mm 80 Sch ASTM Union
OD81359/2024-2025:Supply and fixing 50mm 80 Sch ASTM Threaded Adaptor Male
OD81360/2024-2025:Supply and fixing 50mm 80 Sch ASTM Threaded Adaptor Female
OD81361/2024-2025:Supply and fixing 63mm PVC pipe 6kgf/cm2
OD81362/2024-2025:Supply and fixing 63mm PVC threaded adaptor male
OD81363/2024-2025:Supply and fixing 50mm B class GI pipe as support for hanging submersible motor pump set in open well
OD81364/2024-2025:Supply and fixing clamp made with 50x6mm MS Flat for hanging delivery pipe of submersible motor pump set in existing GI pipe above the open well
OD81365/2024-2025:Supply and fixing 50mm (2") GI flange in the existing suction/delivery pipe line using required leak proofing materials etc. as required
OD81366/2024-2025:Supply and providing 20-63A offset staggered HRC fuse link
OD81367/2024-2025:Supply and providing 63A 2 way neutral link on existing meter board using suitable nut, bolt etc. as required.
OD81368/2024-2025:Supply and providing suitable Steel hook on the wall for binding GI wire of service.
OD81370/2024-2025:Supply and fixing 63A Bakelite fuse holder with necessary bolt and nuts etc. as required
OD81371/2024-2025:Supply & installation of dust and vermin proof, 3 Phase Sintex Meter Board( GS-MB- 6535) and to fix KSEB meters, fuse units, CT etc as required including fixing it on wall, making good the damages colour washing etc. as required.
OD246566/2024-2025:Supply and fixing pump controller suitable for 3 Phase 10 HP Open well submersible motor pump set complete with fully automatic star delta starter, single phasing preventer, ON OFF indication lamps, push buttons, volt meter and ammeter etc. in sheet steel enclosure duly wired in the existing panel board and giving connection etc. as required. LT LK make MU-G15 FASD or equivalent
OD246619/2024-2025:SITCof 3 phase 10HP vertical open well submersible pump set with head range 84 to 140 Mtr discharge 18000 LPH, in the existing open well using suitable tools and plants DECCAN make 10DGM /8 model or equivalent
SASINDRAN E (BID ID -2072501)
Bidder Name
SASINDRAN E
SASI T
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1154706.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .