Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.8 CrAccepted-AOC 108 3 CHANDAR NAGAR DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | ₹6.8 Cr | L1 | Accepted-AOC AOC |
| 2 | L2₹7.5 Cr+₹71.7 L (10.6%)Rejected-Finance | ₹7.5 Cr+₹71.7 L (10.6%) | L2 | Rejected-Finance Highest Rate Quoted by bidder |
| 3 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Others-FDR not submitted by the tenderer, hence his online technical bid has been rejected. |
Tender Value
₹7.5 Cr
EMD Value
₹15.0 L
Closing Date
12 Aug 2024, 5:00 pmClosed
General Manager (Garhwal)
Office of Chief General Manager, Construction Wing, Uttarakhand Peyjal Nigam, Kamla Nagar(Opp. ONGC Hospital), Dehradun
Remaining works of Existing Swimming Pool at Indira Gandhi International Sports Stadium, Golapar, Haldwani (Uttarakhand)
2024_MDPEY_70188_2
832/Nivida(Garh) (Elect) D.Dun/04 Dt. 20/02/2024
Open Tender
Civil Works
Item Rate
120 days
Golapar, Haldwani (Uttarakhand)
Please refer tender document
3 documents required · 3 mandatory
₹11,800
PM,Const.Unit(Elect.),UKPJN, Dehradun
₹15.0 L
Dehradun
26 May 2025
26 Jul 2024
14 Aug 2024
27 Jul 2024
12 Aug 2024
30 Jul 2024
29 Jul 2024
Amount
Excavation work by mechanical means (Hydraulic excavator) / manual means in foundation trenches , including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soils as directed, within a lead of 50 m. :
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering.
P/L cement concrete excluding the cost of centering and shuttering - All work up to plinth level : 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
P/L cement concrete excluding the cost of centering and shuttering - All work up to plinth level : 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 40 mm nominal size)
P/L reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement : 1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size)
Centering and shuttering including strutting, propping etc. and removal of form for : Foundations, footings, bases of columns, etc. for mass concrete
Reinforcement for R.C.C. Work Using T.M.T. Bars
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position all complete.
G.I. chain link fabric fencing with G.I. wire of dia 4 mm
12mm thick C.P. in C.M. 1 : 6 ( 1 cement : 6 fine sand )
Applying priming coat on steel work.
Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade
Painting Steel work with Deluxe Multi Surface Paint to give an even shade.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Upto 35 sq. mm
Above 95 sq. mm and upto 185 sq. mm
Above 185 sq. mm and upto 400 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ x 185 Sq.mm. (57mm).
3½ x 400 Sq.mm. (70mm).
4X 25 Sq. mm. (28 mm) (For pumps etc)
4X 35 sqmm (32 mm) (For pumps etc)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm G.I earhting strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
(DG SET) 1 Nos. 625KVA
Providing, Installing, Testing and Commissioning of'Silent Type' Diesel Generating set having Prime Power Rating of 625 KVA, 415 volts, 50 Hz at 1500 RPM, 0.8 lagging power factor , three phase system & for 0.85 Load Factor with standard control panel andcopper control cable from DG to AMF Panel and consisting of the followings: a) Diesel Engine: Diesel engine 4 Stroke Water Cooled, electric start, of suitable BHP at 1500 RPM suitable for above output of alternator at 40 Degree C, 50%RH & at 1000 Meter MSL and conforming to BS 5514,BS 649, IS 10000, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories.
b) Engine mounted Instrument Panel fitted with and having digital display for following: i) Start-stop switch with key ii) Water temperature indication iii) Lubrication oil pressure indication iv) Battery charging indication v) RPM indication vi) Over speed indication vii) Low lub. Oil trip indication viii) Engine Hours indication
c) Alternator: Synchronous alternator rated at 500 KVA, 415 volts at 1500 RPM, three phase 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C,50% RH & at 1000 Meter MSL. The alternator shall be having SPDP enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to IS: 4722/BS 2613 suitable for tropical conditions and with c1ass-F/H insulation.
d) Base Frame & Foundation: Both the engine and alternator shall be mounted on suitable base frame made of M.S Channel with necessary reinforcement which shall be installed on suitable cement concrete foundation and vibration isolation arrangement as per recommendations of manufacturer.
acoustic enclosure with self contained hoses and other allied accessories as per specifications or as per OEM/OEA along with one number extra having suitable capacity as required .Extra Minimum 2000 Liters suitable for 12 hours continuous operation fabricated out of 3 mm thick M.S. sheet complete with all standard accessories and fuel piping between fuel tank and diesel engine with MS . class 'C' pipes of suitable dia. Complete with valves, level indications & accessories recommendation,
f) Exhaust System: Residential exhaust silencer .
g) Starting System: 24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with 180 AH Maintenance free battery as required or as per OEM/OEA .
h) Acoustic and weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per CPWD specification and norms of CPCB-II sound proofing done with help of high quality rock wool is further covered with fiberglass sheet and perforated powder coated sheet or as per OEM Standard design
(DG SET) 1 Nos. 625 KVA
Supplying and fixing additional exhaust gas piping of 250 mm Welded black MS, C class pipe conforming to IS : 3589 cut to required lengths and installed with necessary bends and clamps, anti- vibration mountings, insulation of exhaust system with Rockwool, 50 mm thick wire mesh & aluminum cladding, below etc., as required as per specifications.(The item shall be measured on linear basis per each run of exhaust piping from outlet of silencer to end of exhaust piping)
Main Essential Panel for Swimming Pool (Indoor Type)
Incoming 1 :- 1 Nos.(1No. from DG Set of 625KVA)
1000Amps. each four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS : 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Cable on incoming side and busbar connection at outgoing side, complete with following for each ACB with accessories - 1 Nos.
Outgoing ACB feeders consisting of
1No. Multifunction meter Neptune/ Equl with RS 485 communication port for communication with required set of CT's.
1 Set. Phase indicating lamps suitable for 230 V AC fittings with back up hrc fuse/MCB.
1Set. Breaker ON/OFF/TRIP/'Spring Charged', indicating lamps.
1No. T-N-C breaker control switch . (Trip/Neutral/Close)
Bus Coupler (1) :- 1 Nos.
1No. 1000A. four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS : 13947- 2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Busbar connection on incoming and outgoing side, complete with following accessories for ACB -
Motor wound spring closing mechanism - 1 No.
1 Set. of Breaker ON/OFF/'Spring Charged', indicating lamps.
1Nos. T-N-C breaker control switch . (Trip/Neutral/Close)
Control MCB 2A
Incoming 2 :- 1 Nos.(from DG Set of 500KVA)
800Amps. each four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS: 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Cable on incoming side and busbar connection at outgoing side, complete with following for each ACB with accessories - 1 Nos.
Motor wound spring closing mechanism - 1No.
1No. Multifunction meter Neptune/ Equl with RS 485 communication port for communication with required set of CT's.
1 Set. of phase indicating lamps, Breaker ON/OFF/'Spring Charged', indicating lamps.
1No. T-N-C breaker control switch . (Trip/Neutral/Close)
Control MCB 2A
Bus Coupler (2) :- 1 Nos.
1No. 1600Amps. four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS : 13947- 2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Busbar connection on incoming and outgoing side, complete with following accessories for ACB -
Motor wound spring closing mechanism - 1 No.
1 Set. of Breaker ON/OFF/'Spring Charged', indicating lamps.
1Nos. T-N-C breaker control switch . (Trip/Neutral/Close)
Control MCB 2A
Incoming 3 :- 1 Nos. (from Future 1000KVA Transformer)
1600Amps. each four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS: 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Cable on incoming side and busbar connection at outgoing side, complete with following for each ACB with accessories - 1 Nos.
Motor wound spring closing mechanism - 1Nos.
Microprocessor release PR122 (EMI & EMC Certified) for over current, earth fault & short circuit protection - 1Nos.
1Nos. Multifunction meter Neptune-M9 Plus / Equl of EM6400 with RS 485 communication port for communication with required set of CT's.
1Nos. Phase indicating lamps suitable for 230 V AC fittings with back up hrc fuse/MCB
1Nos. Breaker ON/OFF/TRIP/'Spring Charged', indicating lamps
1Nos. T-N-C breaker control switch . (Trip/Neutral/Close)
1Nos. Undervoltage, Overvoltage for persisted voltage of 105-180% & 20- 95% of rated voltage.
Bus Bars
1600/1000Amps FP Aluminium bus bars shall be colour coded and insulated by heat shrinkable sleaves & clip on shrouds for joints.
Necessory Interlocking arrangement with PLC having Auto Load Management and Auto Mains Failure Feature shall be provided by the Panel Manufacturer.
Outgoing
1000Amps. FP EDO with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, MDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS : 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for Busbar connection on incoming and cable termination of outgoing side, complete with following for each ACB with accessories - 1 Nos. (For Competition Pool Panel)
800Amps. FP EDO with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, MDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS: 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for Busbar connection on incoming and cable termination of outgoing side, complete with following for each ACB with accessories - 1 Nos. (For Diving Pool Panel)
2 Nos. 250 amp 4P MCCB with Thermal Magnetic based release for O/C & S/C Release, Breaking Capacity 36KA, Ics=100%Icu. (1 Nos. for Practice pool Panel & 1 Nos. Spare)
Outgoing MCCB feeders consisting of
4Nos. Breaker ON/OFF, indicating lamps.
Main Essential Panel for Swimming Pool (Indoor Type) , as described above
Competition Pool Panel (Indoor Type)
Incoming 1 :- 1 Nos.
1000Amps. four pole with 100% neutral horizontal drawout type air circuit breaker of fault breaking capacity 50 KA (Ics = Icu = Icw for 1 sec. at 415 V ), Microprocessor release (EMI & EMC Certified) for over current, earth fault & short circuit protection, impulse voltage (Ui) 1000 V, EDO operated, fitted with interlocked door, automatic safety shutters, mechanical ON/OFF, 4 NO + 4 NC auxiliary contacts, service/test/ isolated position indicators and frame earthing contact, confirming to IS : 13947-2, 1993 as amended up to date complete. The ACB shall have suitable arrangement for termination of Cable on incoming side and busbar connection at outgoing side, complete with following for ACB with accessories - 1 Nos.
1No. Multifunction meter Neptune/ Equl with RS 485 communication port for communication with required set of CT's.
1 Set. Phase indicating lamps suitable for 230 V AC fittings with back up hrc fuse/MCB.
1Set. Breaker ON/OFF/TRIP/'Spring Charged', indicating lamps.
1No. T-N-C breaker control switch . (Trip/Neutral/Close)
Bus Bars
1250Amps TPN Aluminium bus bars shall be colour coded and insulated by heat shrinkable sleaves & clip on shrouds for joints.
Outgoing
9 Nos. 160 amp 4P MCCB with Thermal Magnetic based release for O/C & S/C Release, Breaking Capacity 36KA, Ics=100%Icu. (7 Nos. 46.3KWPumps + 2 Nos.Spare)
9 Set Breaker ON/OFF, indicating lamps for each Outgoing.
Supplying of one No. XLPE insulated, PVC Sheathed, armoured aluminium conductor power cable of 1.1KV grade of following size in the ground
3½ x 185 Sq. mm.(For Panels)
3½ x 400 Sq.mm.(For DG Set, transformer and panels)
4X 35 sqmm (For pumps etc)
4X 25 sqmm (For pumps etc)
Pump and Pool cover for Competetion Pool - Water Volume 2700 m3
Supply, Installation, Testing and Commissioning of Outdoor Heat Exchange Pump Unit for heating and cooling swimming pool from an outdoor air temprature upto -7°C . Extremly Silent, made in metal with Titanium Heat Excahngers, Flowswitch, Defrost by Cycle Inversion (4 Way Valve), Water PumpControl and Electronic controller with LCD panel. Output 210 kW, Input - 46.3 kW.with 4 Nos of Rotary compressors , Vertical exhaust fan direction . Input/ Output water connections of 110mm dia PVC Type with water flow of 40m3/hour/50m3/hour Maximum capacity of pool temprature shall be 32°C, Optimised as per standard
Providing and fixing of thermal pool cover blue deluxe, bubble type, 400-500 micron complete etc cover to 50x 25 mtr as required & as per direction of Engineer-in-charge
Providig and fixing of SS 316 roller shaft with wheel support capable to handle 50 mtr long rolls in aluminium telescopic 5 - 6.6 m complete etc as required & as per direction of Engineer-in-charge
Plumbing for Complete System
Supply, Laying and Fixing of PVC U type Pipes with their respective fittings i.e. elbow , tee, sockets etc of various sizes. All includes. Suction Water Pressure Header - 2 Nos. Delivery Water Pressure Heder - 2 Nos. Bypass Pipelines from Main Delivery Line to Suction Pressure Header of suitable sizes Pipe from Suction Pressure Header to Each Heat pumps of suitable sizes -7 Nos Pipes from Heat pump to Delivery Pressure Header of suitable sizes - 7 Nos Bypass Pipelines from Delivery Pressure Header to Main Delivery Line to Pool. All Including high pressure Flow Control Valves , Flanges, Butteryfly Valves etc complete as required.
Operation & routine maintenance of 7 x 210 KW Heat pump including electrical panel and piping to interconnect the heat pumps to water filteration plant installed near swimming pool at Indira Gandhi International Sports Stadium, Golapar, Haldwani by deputing minimum staff as following complete etc. as required on all days i/c Sunday & holidays (after handover the scheme)
Skilled Staff - 1 No.
Unskilled Staff - 1 No
Katsons Technologies Private Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .